You are on page 1of 2

Condition Report of Deluge Valve Inspected during Month of August 2020

Deluge outlet Butterfly


Fire line inlet Butterfly

Pressure and pressure


Quick Open Ball Valve

control box operation


Trail Alarm Bell Valve
Deluge inlet Butterfly

Alarm Bell Ball Valve


Diaphram Chamber

drain water header


Emergency Manual
Control Ball Valve
Non Return Valve

Remote opration
Gauges codition
Reset Ball Valve
Pressure Switch
Solenoid Valve

heating coil
Valve

Valve

Valve
Equepment Auto Manual

Unit #1 Feed Water Pump A can't ok 2 N/A 2 2 2 3 2 2 2 2 2 2 2 2 3 CHK


Unit #1 Feed Water Pump B can't ok 2 N/A 2 2 2 3 2 2 2 2 2 2 2 2 3 CHK
Unit #1 Feed Water Pump C can't ok 2 N/A 2 2 2 3 2 2 2 2 2 2 2 2 3 CHK
Unit #1 Turbine Lubricating Oil Tank can't can't 3 N/A 2 2 3 3 3 3 3 3 3 3 2 2 3 N/A
Unit #1 Middle Layer Oil Pipe Line can't can't 3 N/A 2 2 3 3 3 3 3 3 3 3 2 2 3 N/A
Unit #1 Bottom Layer Oil Pipe Line can't can't 2 N/A 2 2 2 3 2 2 2 2 2 2 2 2 3 N/A
Unit #1 Generator Seal Oil Device can't ok 2 N/A 2 2 2 3 2 2 2 2 2 2 2 2 3 N/A
Unit #1 Outdoor Oil Storage Tank can't ok 2 N/A 2 2 2 3 2 2 2 2 2 2 2 2 3 N/A
Unit #1 Main Transformer can't ok 2 N/A 2 2 2 3 2 2 2 2 2 2 2 2 3 CHK
Unit #1 Auxillary Transformer can't ok 2 N/A 2 2 2 3 2 2 2 2 2 2 2 2 3 CHK
Startup Standby Transformer #1 can't ok 2 N/A 2 2 2 3 2 2 2 2 2 2 2 2 3 CHK

Unit#1 Coal Crusher#01 Oil system can't can't 3 N/A 2 2 3 3 3 3 3 3 3 3 2 2 3 N/A


Unit#1 Coal Crusher#02 Oil system can't can't 3 N/A 2 2 3 3 3 3 3 3 3 3 2 2 3 N/A
Unit#1 Coal Crusher#03 Oil system can't can't 3 N/A 2 2 3 3 3 3 3 3 3 3 2 2 3 N/A
Unit#1 Coal Crusher#04 Oil system can't can't 3 N/A 2 2 3 3 3 3 3 3 3 3 2 2 3 N/A
Unit#1 Coal Crusher#05 Oil system can't can't 3 N/A 2 2 3 3 3 3 3 3 3 3 2 2 3 N/A
Unit #1 Air Pre Heater A can't can't 2 N/A 2 2 2 3 2 2 2 2 2 2 2 2 3 CHK
Unit #1 Air Pre Heater B can't can't 2 N/A 2 2 2 3 2 2 2 2 2 2 2 2 3 CHK
Unit #1 Boiler Burner at Angle A can't can't 2 N/A 2 2 3 3 3 3 3 3 3 3 2 2 3 N/A
Unit #1 Boiler Burner at Angle B can't can't 2 N/A 2 2 3 3 3 3 3 3 3 3 2 2 3 N/A
Unit #1 Boiler Burner at Angle C can't can't 2 N/A 2 2 3 3 3 3 3 3 3 3 2 2 3 N/A
Unit #1 Boiler Burner at Angle D can't can't 2 N/A 2 2 3 3 3 3 3 3 3 3 2 2 3 N/A

Unit #2 Feed Water Pump A can't ok 2 N/A 2 2 2 3 2 2 2 2 2 2 2 2 3 N/A


Unit #2 Feed Water PumpB can't OK 2 N/A 2 2 2 3 2 2 2 2 2 2 2 2 3 CHK
Unit #2 Feed Water Pump C can't ok 2 N/A 2 2 2 3 2 2 2 2 2 2 2 2 3 N/A
Unit #2 Turbine Lubricating Oil Tank can't ok 2 N/A 2 2 2 3 2 2 2 2 2 2 2 2 3 N/A
Unit #2 Middle Layer Oil Pipe Line can't ok 2 N/A 2 2 2 3 2 2 2 2 2 2 2 2 3 N/A
Unit #2 Bottom Layer Oil Pipe Line can't ok 2 N/A 2 2 2 3 2 2 2 2 2 2 2 2 3 N/A
Unit #2 Generator Seal Oil Device can't ok 2 N/A 2 2 2 3 2 2 2 2 3 2 2 2 3 N/A
Unit #2 Outdoor Oil Storage Tank can't ok 2 N/A 2 2 2 3 2 2 2 2 2 2 2 2 3 N/A
Deluge outlet Butterfly
Fire line inlet Butterfly

Pressure and pressure


Quick Open Ball Valve

control box operation


Trail Alarm Bell Valve
Deluge inlet Butterfly

Alarm Bell Ball Valve


Diaphram Chamber

drain water header


Emergency Manual
Control Ball Valve
Non Return Valve

Remote opration
Gauges codition
Reset Ball Valve
Pressure Switch
Solenoid Valve

heating coil
Valve

Valve

Valve
Equepment Auto Manual

Unit #2 Main Transformer can't ok 2 N/A 2 2 2 3 2 2 2 2 2 2 2 2 3 N/A


Unit Auxillary Transformer #2 can't ok 2 N/A 2 2 2 3 2 2 2 2 2 2 2 2 3 N/A
Startup Standby Transformer #2 can't ok 2 N/A 2 2 2 3 2 2 2 2 2 2 2 2 3 N/A

Unit#2 Coal Crusher#01 Oil system can't can't 3 N/A 2 2 3 3 3 3 3 3 3 3 2 2 3 N/A


Unit#2 Coal Crusher#02 Oil system can't can't 3 N/A 2 2 3 3 3 3 3 3 3 3 2 2 3 N/A
Unit#2 Coal Crusher#03 Oil system can't can't 3 N/A 2 2 3 3 3 3 3 3 3 3 2 2 3 N/A
Unit#2 Coal Crusher#04 Oil system can't can't 3 N/A 2 2 3 3 3 3 3 3 3 3 2 2 3 N/A
Unit#2 Coal Crusher#05 Oil system can't can't 3 N/A 2 2 3 3 3 3 3 3 3 3 2 2 3 N/A
Unit #2 Air Pre Heater A can't can't 2 N/A 2 2 2 3 2 2 2 2 2 2 2 2 3 CHK
Unit #2 Air Pre Heater B can't can't 2 N/A 2 2 2 3 2 2 2 2 2 2 2 2 3 CHK
Unit #2 Boiler Burner at Angle A can't can't 2 N/A 2 2 3 3 3 3 3 3 3 3 2 2 3 N/A
Unit #2 Boiler Burner at Angle B can't can't 2 N/A 2 2 3 3 3 3 3 3 3 3 2 2 3 N/A
Unit #2 Boiler Burner at Angle C can't can't 2 N/A 2 2 2 3 2 2 2 2 2 2 2 2 3 CHK
Unit #2 Boiler Burner at Angle D can't can't 2 N/A 2 2 2 3 2 2 2 2 2 2 2 2 3 CHK

Note :
Need to repair due to corrosion effect
Need to repair due to corrosion effect,cable not connected
can operate need to repair
2
can check, need to repair
Water drain header is block,need to repair
can't operate & need to repair

damage & can't check, need to replace


can't remotely operate
3
damage & can't operate need to replace
can't operate & need to replace

CHK can't inspected