Professional Documents
Culture Documents
Form23 FIVE POLES Transformer
Form23 FIVE POLES Transformer
Transformer No. 01
T-01
Left Side
Pole Number kVA/Pole No. of SPAN kVA SPAN
P-1 17.246 2 34.492
P-2 18.208 1 18.208
P-3 19.825 1 19.825
Right Side
Pole Number kVA/Pole No. of SPAN kVA SPAN
P-4 15.524 1 15.524
P-5 20.644 2 41.288
Transformer No. 02
No. & Type of Maximum
Pole Number Number of SPAN kVA SPAN
Customers Demand
P-6 3B+2F+SL 19.292 2 38.584
P-7 B+C+2F+SL 13.269 1 13.269
P-8 3B+C+F+SL 20.85 1 20.85
P-9 A+C+3F+SL 17.246 1 17.246
P-10 C+D+3E+SL 15.286 2 30.572
T-02
Left Side
Pole Number kVA/Pole No. of SPAN kVA SPAN
P-6 19.292 2 38.584
P-7 13.269 1 13.269
P-8 20.85 1 20.85
Right Side
Pole Number kVA/Pole No. of SPAN kVA SPAN
P-9 17.246 1 17.246
P-10 15.286 2 30.572
For T - 01
Use 167 KVA, 34.5kV, 230V, 115V, grounded, 60 Hz distribution transformer with 5% impedance.
= 91.447 x 100%
167
= 54.76 %
The rating of the transformer shall be 167 KVA, 34.5kV, 230V, 115V, 60 Hz, single
phase distribution transformer with 5% impedance,the total expected load is
54.76 %, the
the rating of the fus 20 ampere fuse link. The maximum setting is
14.522 amps;
the L.A. shall be line type rated 27 kV.
For T - 01
Use 167 KVA, 34.5kV, 230V, 115V, grounded, 60 Hz distribution transformer with 5% impedanc
kVA SPAN
38.584
13.269 % Loading = Total Maximum Demand of Transformer
x 100%
20.85 KVA Rating of Transformer
17.246
30.572 = 85.943 x 100%
167
= 51.46 %
The rating of the transformer shall be 167 KVA, 34.5kV, 230V, 115V, 60 Hz, single
phase distribution transformer with 5% impedance,the total expected load is
51.46
the rating of the fus 20 ampere fuse link. The maximum setting is
14.522
the L.A. shall be line type rated 27 kV.
with 5% impedance.
0 Hz, single
nsformer with 5% impedance.
x 100%
in the primary.
impedance)