LINCE 230V/110V/24V
USER’S AND INSTALLER’S MANUAL

v8.0
REV. 03/2018
00. CONTENT 01. SAFETY INSTRUCTIONS
INDEX STANDARDS TO FOLLOW
01. SAFETY INSTRUCTIONS ATTENTION:
STANDARDS TO FOLLOW 01B
02.PACKAGE
This product is certified in accordance with European Community
INSIDE PACKAGE 03A (EC) safety standards.
03. OPERATOR
CHANGE MOTOR DIRECTION 03B
MANUAL RELEASE 04B
This product complies with Directive 2011/65/EU of the European
TECHNICAL SPECIFICATIONS Parliament and of the Council, of 8 June 2011, on the restriction of
05A
the use of certain hazardous substances in electrical and electronic
04. INSTALLATION equipment.
INSTALLATION DIMENSIONS 05B
INSTALLATION STEPS 07A
INSTALLATION MAP 08
(Applicable in countries with recycling systems).
This marking on the product or literature indicates that the product
05. TROUBLESHOOTING
and electronic accessories (eg. Charger, USB cable, electronic material,
FINAL CONSUMERS INSTRUCTIONS 09 controls, etc.) should not be disposed of as other household waste at
INSTRUCTIONS FOR SPECIALIZED INSTALLERS 09 the end of its useful life. To avoid possible harm to the environment
06. COMPONENTS TEST or human health resulting from the uncontrolled disposal of waste,
230V/110V MOTOR separate these items from other types of waste and recycle them
10A
responsibly to promote the sustainable reuse of material resources.
24V MOTOR 10B
Home users should contact the dealer where they purchased this
07. MAINTENANCE product or the National Environment Agency for details on where and
MAINTENANCE 11A how they can take these items for environmentally safe recycling.
08. CONTROL BOARD MC2 Business users should contact their vendor and check the terms and
conditions of the purchase agreement. This product and its electronic
CONNECTIONS SCHEME 230V/110V 12
accessories should not be mixed with other commercial waste.
09. CONTROL BOARD MC11
CONNECTIONS SCHEME 24V 13
This marking indicates that the product and electronic accessories
(eg. charger, USB cable, electronic material, controls, etc.) are
susceptible to electric shock by direct or indirect contact with
electricity. Be cautious when handling the product and observe all
safety procedures in this manual.

2A 2B
EN EN
01. SAFETY INSTRUCTIONS 01. SAFETY INSTRUCTIONS
STANDARDS TO FOLLOW STANDARDS TO FOLLOW
• It is important for your safety that these instructions are followed. • Before installing, the installer must verify that the equipment to be automated is
• Keep these instructions in a safe place for future reference. in good mechanical condition, correctly balanced and opens and closes properly.
• The ELECTROCELOS S.A. is not responsible for the improper use of the product, • If the automation is to be installed at a level higher than 2,5 m above ground
or other use than that for which it was designed. level or other level of access, , should be followed the minimum safety and
• The ELECTROCELOS S.A. is not responsible if safety standards were not taken health requirements for the use of work equipment workers at work in Directive
into account when installing the equipment, or for any deformation that may 2009/104/EC of the European Parliament and of the Council of 16th September
occur. of 2009.
• The ELECTROCELOS S.A. is not responsible for insecurity and malfunction of the • In the case of the equipment where the automation will be installed, have
product when used with components that were not sold by the them. a pedestrian door, be aware that it must be closed when the automation is
• This product was designed and manufactured strictly for the use indicated in activated.
this manual. • After installation, make sure that the mechanism is properly adjusted and that
• This control board is not appropriate for inflammable or explosive environments. the protection system and any manual unlocker works correctly.
• Any other use not expressly indicated may damage the product and/or can • In order to protect the electrical cables against mechanical stress, you should
cause physical and property damages, and will void the warranty. use conduit for the electrical wires, essentially on the power cable.
• Do not make any changes to the automation components and/or their accessories. • When programming the control unit, pay particular attention to touching only
• Control board for indoor use with 24Vdc/110Vac/230Vac connection. the location intended for that purpose. Failure to do so may result in electric
• Keep remote controls away from children, to prevent the automated system shock.
from being activated involuntarily. • Replacement of the power cable in the automation can only be carried out by
• The customer shall not, under any circumstances, attempt to repair or tune the specialized technicians or by the manufacturer.
automatism. Must call qualified technician only.
• The installer must have certified professional knowledge at the level of
mechanical assemblies in doors and gates and control board programmation.
He should also be able to perform electrical connections in compliance with all
applicable regulations.
• The installer should inform the customer how to handle the product in an
emergency and provide him the manual.
• This device can be used by children 8 year old or older and persons whose
physical, sensory or mental capacities are reduced, or by persons without
experience or knowledge if they have received supervision or instructions on
the use of the device in a safe manner and understood the hazards involved.
Children should not play with the device. Cleaning and maintenance by the user
must not be carried out by unsupervised children.
• Automatism powered by very low safety voltage, with electronic board/control
board/control unit (only applicable to 24V motors).
• Before installing, the installer must verify that the temperature range indicated
on the automatism is appropriate to the location of the installation.

3A 3B
EN EN
02. PACKAGE 03. OPERATOR
INSIDE PACKAGE CHANGE MOTOR DIRECTION
In the package you will find the following components: The operator LINCE, is a product developed exclusively for the automatic opening of swing
gates.
01• 02 Swing operators LINCE
02• 01 Control Board Besides being pratical, safe and powerful, this product has a new function incorporated so
03• 02 transmitters that you can transform a motor to apply on right leaves to left leaves.
04• 02 Front supports This allows greater flexibility in the use of each operator.
05• 02 Rear supports
06• 02 Capacitors [only available with the 230V (8µF) and 110V(20µF) models]
07• 01 Photocells
08• 01 User’s manual
09• 02 Release keys

09•
Upper part Middle part
08•
04•
Lower part
01•
05• 06•
04
01
Motor disassembly and assembly process, in order to transform motor, must be done as
Electronic components the kit: follows:

03• 07•
02• 02

210mm

280mm 810mm 05 06
03 01 • Loosen the screws that secure the 02 • Remove Lower Part.
Lower Part to Middle Part.

4A 4B
EN EN
03. OPERATOR 03. OPERATOR
CHANGE MOTOR DIRECTION UNLOCK OPERATOR

07 08 12 13
03 • Loosen the screws of the Middle Part. 04 • Remove Middle Part. 01 • Remove the plastic cap from the rear Information engraved on the unlock shaft.
end. D=Unlock || B=Lock

09 10
14 15
05 • Rotate Upper Part 180°. 06 • Assemble operator by tightening all
components with the screws. 02 • Insert Release key on the unlock shaft. 03 • Rotate key 180 ° in the direction indicated
in the figure to unlock.

04 • Operator unlocked.

Note • To lock operator so it can work


automatically, must do it by turning the key
anticlockwise.

11
16
07 • Full transformed operator.

5A 5B
EN EN
03. OPERATOR 04. INSTALLATION
TECHNICAL SPECIFICATIONS VERTICAL INSTALLATION DIMENSIONS
LINCE300 LINCE400 LINCE600 The operator LINCE must be installed with a small inclination , to prevent water infiltration
through the extension arm.
230V 230Vac 50/60Hz 230Vac 50/60Hz 230Vac 50/60Hz
For this, the front support must be fixed to the gate with a height lower than the height of
• Power Supply 110V 110Vac 50/60Hz 110Vac 50/60Hz 110Vac 50/60Hz the rear support. See example below:
24V 24Vdc 24Vdc 24Vdc
230/110V 180W 180W 180W
• Power
24V 60W 60W 60W
230V 1,3A 1,3A 1,3A
• Current 110V 2,5A 2,5A 2,5A
24V 1A to 3A 1A to 3A 1A to 3A
230/110V 1400 RPM 1400 RPM 1400 RPM
• RPM A
24V 1600 RPM 1600 RPM 1600 RPM
• Noise level LpA <= 50 dB (A) LpA <= 50 dB (A) LpA <= 50 dB (A)
• Force 2300N 2300N 2300N
• Operating temperatures -25°C to 65°C -25°C to 65°C -25°C to 65°C
• Thermal protection 120°C 120°C 120°C
• Protection class IP54 IP54 IP54
230/110V 25% 25% 25%
• Working frequence
24V Intensive Intensive Intensive
• Opening time 8 sec. to 13 sec. 13 sec. to 18 sec. 20 sec. to 28 sec. B
A B
• Course 300mm 400mm 600mm
• Max leaf lenght 2500mm 3000mm 4000mm
230V 8µF 8µF 8µF
• Capacitor 18
110V 20µF 20µF 20µF
Dimension A • Vertical distance from the floor to the top of the rear support .
Dimension B • Vertical distance from the floor to the top of the front support.
LINCE 300 || 400 || 600 dimensions are the following:
A ? mm • Set dimension A (this can be any size of your choice).
B A-10mm • After you set dimension A, subtract 10mm to find dimensionB.

Example:
962mm || 1162mm || 1562mm • If the height of the rear bracket (dimension A)is set at 600 mm, then the height of the front
175mm bracket (dimension B) will be 590 mm (600mm-10mm).

It is very important that these dimensions are respected! Only this way can be assured
159mm the correct functioning and durability of the operators!
It is also very important to have a levelled ground/terrain!

647mm || 747mm || 947mm 104mm 17

6A 6B
EN EN
04. INSTALLATION 04. INSTALLATION
VERTICAL INSTALLATION DIMENSIONS HORIZONTAL INSTALLATION DIMENSIONS
On the Illustrated diagrams below and on the next page, are the horizontal dimensions for
the installation of the automated system. EXTERIOR OPENING

INTERIOR OPENING
Opening mechanical stopper

Opening
Axis of rotation of the motor,
(EXTERIOR) on the front bracket
direction

Axis of rotation of the gate Closing mechanical


stopper (EXTERIOR)
(center of the door hinge)

Axis of rotation of the gate


(center of the door hinge)
Y
W
Distance between the
Y
centers of the holes on the
Closing mechanical
X
supports from operator W stopper
Axis of rotation of the motor,
Axis of rotation of the motor,
on the rear support
Opening X
(INTERIOR) on the front support
direction
(INTERIOR) Axis of rotation of the motor, Distance between the centers of the
on the rear support holes on the supports from operator 20
Opening mechanical stopper
19 Opening angle X Y W

Opening angle X Y W
• LINCE300 95º 120 a 180 120 a 180 595 a 600

• LINCE300 95º 120 a 180 120 a 180 895 a 900 • LINCE400 95º 160 a 200 120 a 180 695 a 700

95º 120 a 180 120 a 180 1095 a 1100 • LINCE600 95º 160 a 300 120 a 280 900 a 905
• LINCE400
120º 160 a 180 120 a 140 1095 a 1100
Legend:
95º 120 a 350 120 a 200 1495 a 1500 Dimension X - Horizontal distance between hinge axis of the door and the rear axle of the motor.
• LINCE600 Dimension Y - Vertical distance between hinge axis of the door and the rear axle of the motor.
120º 200 a 280 120 a 200 1495 a 1500
Dimension W - Distance between axis of the motor brackets.

It is very important that these dimensions are respected! Only this way can be assured
the correct functioning and durability of the operators!

7A
6A 7B
6B
EN EN
04. INSTALLATION 04. INSTALLATION
INSTALLATION STEPS INSTALLATION STEPS
04 • Install operator on the supports
Pay attention to installation dimensions mentioned on pages 04B, 05A and 05B!
• The operator must be placed on both
supports the same time to avoid leaving
01 • Fixing rear support the operator suspended by only one of the
supports.
• The Rear support must be fixed to the
To make the task easier, you should unlock
pillar or wall using dimensions provided
the operator in order to be able to stretch/
in the preceding pages.
retract arm easily (see page 03B),to get
It can be fixed using screws with
the correct position for supports.
mechanical bushing or chemical welding
process, or one of your choice since it 24
provides an appropriate support.
05 • Test movement
21 • Install the pins removed earlier on each
place with a small amount of lubricant for
02 • Fixing front support less friction.
• Move the door manually to see if the door
• The Front support should be fixed to the opens and closes uniformly and correctly,
gate, respecting height dimensions and without any irregular friction during its
distance to the rear support. entire travel;
This may be fixed by using screws, welding This will ensure that operator is not
process, or to choose another long as it subjected to problems during operation.
provides a secure proper support. 25

06 • Connecting operator to control board


22 and configuring control devices.
• With the operator installed, connect it
03 • Remove caps and pins from motor to control board for system configuration
(see control board user manual).
• Before installing motor, remove caps Must also configure the desired control
and pins from motor. devices (transmitters, wall switch, etc.)
and other additional components such
• At the end of the installation, put back as antenna, warning light, key selector,
plastic covers for a better visual finish of among others.
the operator. 26

It is important to respect this installation order!


23 Otherwise, it is not possible to ensure correct installation and operators may not
work properly!

8A
7A 8B
7B
EN EN
04. INSTALLATION
INSTALLATION MAP
• CONTROL
• INTERIOR • EXTERIOR • MOTOR LINCE • EXTERIOR • KEY • WARNING • ANTENNA BOARD
PHOTOCELLS PHOTOCELLS PHOTOCELLS SELECTOR LAMP

• JUNCTION
BOX

LEGEND:
• Connection cables

27

It is important to use mechanical stoppers in the opening and closing position of the gate. It is important to use junction boxes for connections between motors, components and
If not respected, components of the automation may suffer efforts for which they were not control unit. All cables must enter and exit on the bottom of the junction and control
prepared, and as a result will be damaged. board box.

9
8
EN
05. TROUBLESHOOTING
FINAL CONSUMERS INSTRUCTIONS INSTRUCTIONS FOR SPECIALIZED INSTALLERS

Anomaly Procedure Behavior Procedure II Discovering the origin of the problem

•Make sure you 1 • Open control box and check board and test them by connecting problem is on the control board. remove them from installation
• Motor if it has 230V/110V/24V power directly to power supply in order to Pull it out and send it to our site and send to our MOTORLINE
have power in the
doesn't • Consult a qualified supply; find out if they have problems (see MOTORLINE technical services for technical services for diagnosis.
automation control • Still not working
work MOTORLINE technician. 2 • Check input fuses; page 09A/09B). diagnosis;
board and if it is
at all 3 • Disconnect motors from control 4 • If the motors work, the 5 • If the motors doesn’t work,
working properly.

• Is the gate • Consult an experienced


1 • Check all motion axis and associated motion systems related with gate and operators (pins, hinges, etc.) to find out what is the problem.
closed? gate expert
• Unlock motor
• Motor
and move gate
doesn’t 1 • Check capacitors, testing find out if they have problems (see diagnosis;
by hand to check
move but operator with new capacitors; page 09A/09B). 4 • If the motors doesn’t work,
for mechanical
makes noise • Gate moves • Consult a qualified 2 • If capacitors are not the problem, 3 • If the motors work, the problem remove them from installation
problems on the
gate. easily? MOTORLINE technician. disconnect motors from control is from control board. site and send to our MOTORLINE
board and test them by connecting Pull it out and send it to our technical services for diagnosis.
directly to power supply in order to MOTORLINE technical services for

All MOTORLINE control boards have LEDs that A) SECURITY SYSTEMS: B) START SYSTEMS:
1 • Check if there is any easily allow to conclude which devices are
• Unlock motor and with anomalies. 1 • Close with a shunt all safety systems on 1 • Disconnect all wires from START terminal
obstacle in front of the
move gate by hand All safety devices LEDs (DS) in normal the control board (check manual of the control input.
photocells;
to closed position. situations remain On. board in question). 2 • If the LED turned Off, try reconnecting one
2 • Check if any of the
• Motor Lock motor(s) All "START" circuits LEDs in normal situations If the automated system starts working device at a time until you find the defective
control devices (key
opens but again and turn off remain Off. normally check for the problematic device. device.
• Gate opened but selector, push button, video
doesn’t power supply for 5 2 • Remove one shunt at a time until you find
didn’t close again. intercom, etc.) of the gate
close seconds. Reconnect If LEDs devices are not all On, there is some the malfunction device .
are jammed and sending
it and send order to security systems malfunction (photocells, 3 • Replace it for a functional device and check NOTE:
permanent signal to control
open safety edges), etc. if the operator works correctly with all the n case procedures described in sections A) and
unit;
gate using If "START" circuits LEDs are turn On, there is a other devices. If you find another one defective, B) don’t result, remove control board and send
3 • Consult a qualified
transmitter. control device sending permanent signal. follow the same steps until you find all the to our technical services for diagnosis.
MOTORLINE technician.
problems.

• Encountered • Consult an experienced


1 • Check all motion axis and associated motion systems related with gate and operators (pins, hinges, etc.) to find out what is the problem.
problems? gate expert

1 • Check capacitors, testing with gate at full force during the NOTE: Setting force of the
• Unlock motor new capacitors; entire course, the problem is from controller should be sufficient to
• Motor 2 • If capacitors are not the problem, controller. Set force using trimmer make the gate open and close
and move gate
doesn’t disconnect motors from control on the board. Make a new working without stopping, but should
by hand to check
make board and test them by connecting time programming , giving suffient stop with a little effort from a
for mechanical
complete • Gate moves • Consult a qualified directly to power supply in order to time for opening and closing with person.
problems on the
route easily? MOTORLINE technician. find out if they are faulty; appropriate force (see manual of In case of safety systems failure,
gate.
3 • If the motors doesn’t work, the controller in question). the gate shall never cause
remove them from installation 5 • If this doesn’t work, remove physical damaged to obstacles
site and send to our MOTORLINE control unit and send it to (vehicles, people, etc.).
technical services for diagnosis. MOTORLINE technical services
4 • If motors work well and move services.

10
9
EN
06. COMPONENTS TEST 06. COMPONENTS TEST
230V/110V MOTOR 24V MOTOR
To detect if the malfunction is on the control board or on the motor is, sometimes, necessary To detect which are the components with problems in a 24V LINCE automatism instalation,
to perform tests with connection directly to a 110V/230V power supply. it's sometimes necessary to run a test directly to a external power supply (another 24V
For this, it is necessary to interpose a capacitor on the connection in order to the automatism battery).
to work (check the type of capacitor to be used in the product manual). The diagram below, The diagram below shows how to connect the motor to the battery.
shows how to make that connection and how to merge the different components wires.
NOTES:
NOTES: • To make these tests it isn't necessary to remove it from the location where it is installed,
• To perform the tests, there is no need to remove the automatism from the place it is installed, because in this way, you can understand of the automatism works properly directly
because in this way, it is possible to understand if the automatism can function properly connected to the external battery.
connected directly to the current. • Once you connect the wires to a battery 24V, the motor must work for one direction. To test
• You should use a new capacitor during this test to ensure that the problem does not lie on it. the opposite movement, change the position of the wires connected to the battery.

01 • Connect the power wires to the terminal, as shown below.


02 • Connect the automatism wires in the terminal, interposing a capacitor in the opening 24V Battery 24V Battery
and closing wires.
03 • Once these connections are completed, connect to a 110V/230V power outlet, depending AUTOMATISM
on the motor/control board in test.

Close Phase 1
Power Supply 1
Motor COM 1
COM
COM 2 3 Motor's wires
Open
Power Supply 2
Phase 2
Motor rotates Motor rotates in the
Ground Wire to one direction opposite direction
8μF (230V) / 20μF (110V) (eg: right) (eg: left)
Capacitor 24V Battery

1
All tests must be performed by qualified personnel due to serious danger associated
2 with the misuse of electrical systems!
2
AUTOMATISM

All tests must be performed by qualified personnel due to serious danger associated
with the misuse of electrical systems!

11A
10A 11B
10B
EN EN
07. MAINTENANCE 07. MAINTENANCE
MAINTENANCE MAINTENANCE

28 30
• Clean stainless steel arm • Check motor supports
• With a cloth soaked in lubricant spray, wipe any residue that accumulates on the operator’s •Make sure that supports remain well fixed on the pillars and gate to ensure proper functioning of
stainless steel arm. the equipment.
• Apply a small amount of spray lubricant on the arm and using a dry cloth remove the excess,
leaving a homogeneous layer of lubricant over the arm.
These maintenance measures must be applied every year in order to insure proper
functioning of the automated system.

29
• Lubricate pins
• Remove front and rear caps
• Place a small amount of lubricant on the holes that contains support pins.
• Install caps on the respective holders.

12A
11A 12B
11B
EN EN
08. CONTROL BOARD MC2
230/110V CONNECTIONS SCHEME
Antenna
INB.CMD.AP
T.MOT.PED

CODE PED

9 10 11 12
T.MOTOR
T.RIT.ANT
T. PAUSA

* For more

- Force +
CODE
informations,

PUL PED DS1 DS2

CONTACT

CONTACT
check the manual

DS2

COM NC

COM NC
Pedestrian of the photocells
Opening to be installed.

12V/24V

12V/24V
POWER

POWER
~ ~

~ ~
(1 leaf)

PED DS1
8
Exterior Interior

7
Photocells* Photocells*

6
Close the circuit

12V/24V

12V/24V
PUL

POWER

POWER
~ ~

~ ~
with bridge (shunt)

5
Complete when the

SERR.
4
Opening photocells circuit
Lock (2 leaves) is not being used!

3
(9∑8 - 9∑10)

V
1
Brown

9 10

AP COM CH
MOTORE 2
Blue Motor 2
Black
8

AP COM CH Black
7

MOTORE 1

Blue • Motor 1 starts opening before Motor 2


6

Brown • Motor 2 starts closing before Motor 1


5

• It must be applied an 8µ capacitor


in each motor, on the opening and
LAMP
4

110V

closing wires as explained above.


3

L N
2

110V

NOTE • If any one of the motors moves


in the wrong way, just switch the brown
1

Light Bulb and black cables of that motor to


PL

change the direction.


3

Earth wire
2

Earth wire
1

Motor 1 32

12
13
EN
09. CONTROL BOARD MC11
24V CONNECTIONS SCHEME

RX

10 11 12 13 14 15 16 17 18
Antenna
SENSITIVITY
VR1

FA2 FC2

FA2 FC2
(NC Contact) (NC Contact) (NC Contact) (NC Contact)

TIPO MOTORE

CONTACT

CONTACT

CONTACT

CONTACT
COM NC

COM NC

COM NC

COM NC
T. MOT. PED.
T. RIT. ANTE

CODE PED.

AUTO PGM
T. PAUSE

12V/24V

12V/24V

12V/24V

12V/24V
POWER

POWER

POWER

POWER
~ ~

~ ~

~ ~

~ ~
T. MOT.

CODE

BL DS FA1 FC1

BL DS FA1 FC1
SET
POWER/SPEED

Pushbutton Set of Set of Set of Set of


(NC Contact) photocells 1 photocells 2 photocells 3 photocells 4

SEL
VR1

12V/24V

12V/24V

12V/24V

12V/24V
POWER

POWER

POWER

POWER
~ ~

~ ~

~ ~

~ ~
9

L.SPIA PUL PED


PUL PUD

8
7

+12V-
6 12Vdc 3W Máx. NA NA
Complete (NA
5
Opening Contact) COMPONENTS DIAGRAM
CN2
4

Set of
SERR. +V
3

photocells
Electric lock 4
+ -
2

12/24Vdc
12W Máx.
1

Motor 2
10 11

MOT.2

Set of Set of
photocells photocells
2 3
MOT.1
9
FUSE

Motor 1 Motor 2
Flashing light Motor 1
12/20V BATT S.P. LAMP
+12V- + + -
7

12/24VDC
4W Máx.
6
CN1
5

Set of
4

photocells
+12V-
FUSE

1
3

Transformer:
230/12VAC
*1 When the photocells circuits are not being used, you must
2

230VAC

50/60Hz close them with a bridge (shunt) on the control board.


1

120W Máx. (9∑11 - 14∑12 - 14∑13 - 14∑15 - 14∑16)


31

13
14
EN