Higher positive pressure of say 0.1” wg (2.5 mm) shall mean higher velocity pressure of 1266 fpm
(~6.4 m/s). The amount of leakage for 2 square feet opening shall be 2532 CFM an increase of
40%. Higher the velocity pressure higher shall be the ex-filtration or the leakages.
Assuming an ASHARE design condition of 95°F DB/72°F WB (~35°C DB/22° C WB) and room
conditions of 72°F DB/60°F WB (~22°C DB/15.5°C WB, ~50% RH), the enthalpy difference is 9.5
This is not only the extra capital cost but also the recurring energy costs of nearly 6 kWh @ 1kWh
The room pressure should be limited to 0.03” to 0.05” (~0.75 to 1.25mm) as pressure above this