To cite this article: Wei Liu, Mingang Jin, Chun Chen & Qingyan Chen (2016) Optimization of
air supply location, size, and parameters in enclosed environments using a computational fluid
dynamics-based adjoint method, Journal of Building Performance Simulation, 9:2, 149-161, DOI:
10.1080/19401493.2015.1006525
Optimization of air supply location, size, and parameters in enclosed environments using a
computational fluid dynamics-based adjoint method
Wei Liua,b , Mingang Jinb , Chun Chenb and Qingyan Chena,b∗
a TianjinKey Lab of Indoor Air Environmental Quality Control, School of Environmental Science and Engineering, Tianjin University,
Tianjin 300072, People’s Republic of China; b School of Mechanical Engineering, Purdue University, West Lafayette, IN 47905, USA
(Received 5 June 2014; accepted 3 January 2015 )
Optimal design of an indoor environment based on specific design objectives requires a determination of thermo-fluid control
methods. The control methods include the air supply location, size, and parameters. This study used a computational fluid
dynamics- (CFD) based adjoint method to identify the optimal air supply location, size, and parameters. Through defining
the air distribution in a certain area (design domain) as a design objective in a two-dimensional, ventilated cavity, the adjoint
method can identify the air supply location, size, and parameters. However, the air supply location, size, and parameters
were not unique, which implied multiple solutions. By using any of the air supply location, size, and parameters identified
as boundary conditions for forward CFD simulations, the computed air distribution in the design domain was the same as
that used as a design objective. Thus, the computing costs did not depend on the number of design variables.
Keywords: shape optimization; adjoint method; inverse design
local optimal solutions. The adjoint method requires less design objectives and objective functions, refer to the study
computing load than the CFD-based GA method. Besides, by Zhou and Haghighat (2009).
a CFD-based adjoint method can be more accurate than the Step 2 The parameters in the objective functions (p, V,
POD technique as it directly solves the Navier–Stokes (NS) T) are calculated in our case by solving the NS equations,
equations with a suitable turbulence model using actual which are denoted by vector S = (S 1 , S 2 , S 3 , S 4 , S 5 ) = (0,
thermo-fluid boundary conditions. Liu and Chen (2014) 0, 0, 0, 0):
have validated this method for finding optimal thermo-
fluid boundary conditions in a two-dimensional cavity. S1 = −∇ · V, (1)
The results showed the capacity and high accuracy of this
(S2 , S3 , S4 ) = (V · ∇)V + ∇p − ∇ · (2νD(V))
T
method, but the number of design variables in our previous
study was limited. − γ g (T − Top ), (2)
With more design variables, the CFD-based adjoint S5 = ∇ · (VT) − ∇ · (κ∇T). (3)
method can achieve a better design for an indoor
environment. The current design method for an indoor Step 3 With an initialized ξ , the initial O(p, V, T) calcu-
environment (ASHRAE 2010) does not provide specific lated in step 2 is often not minimal. The CFD-based adjoint
instructions for determining the exact location of the air method determines the derivative of the objective function
supply diffuser or its size, which are very critical to over the design variables (dO/dξ ) in order to search for the
know in determining air distributions. The design vari- trend in varying ξ that can lead to a smaller O. Since O
ables in the CFD-based adjoint method could include air is a function of the V, T, and p but not ξ , the gradient
supply location and size. This paper describes our effort dO/dξ cannot be directly computed. Since ξ determines V,
in using the CFD-based adjoint method to determine air T, and p and further O, the adjoint method introduces a
supply location, size, and parameters through implement- Lagrangian multiplier (p a , Va , Ta ), which stands for adjoint
ing the method in open field operation and manipulation velocity, temperature, and pressure, respectively, to make
(OpenFOAM 2007). dO/dξ computable. The adjoint variables could be regarded
as purely mathematical terms, but they do have physical
significance. According to Giles and Pierce (2000), one
2. Method way of looking at them is that they give the influence of
In an enclosed environment, the air supply location, size, an arbitrary source term on the functional of interest (the
and parameters are critical in determining the air distribu- NS equations here). Then, this method uses an augmented
tions. Thus, our effort is to identify the proper air supply objective function as
location, size, and parameters for designing an indoor envi-
ronment. This investigation used the CFD-based adjoint L=O+ (pa , Va , Ta )S d. (4)
method for identifying the optimal air supply location, size,
and parameters. The corresponding numerical algorithm
used is also discussed. Since S = (0, 0, 0, 0, 0) in step 2, L actually equals
O in Equation (4). Therefore, finding ξ for minimizing O
becomes finding ξ for minimizing the augmented objec-
2.1. CFD-based adjoint method tive function L. Our effort is to calculate the gradient
dL/dξ instead of dO/dξ . Considering the variation of ξ , the
The CFD-based adjoint method uses the following pro- variation of L can be expressed as
cesses to identify the optimal design variable ξ , which rep-
resents air supply location (xin , y in ), size (hin ), and param- ∂L ∂L ∂L ∂L
eters (Vin , Tin ) in this study. It forms a vector or a 1 × 5 dL = dξ + dp + dV + dT. (5)
∂ξ ∂p ∂V ∂T
matrix ξ = (xin , y in , hin , Vin , Tin ) and any mathematical
operations involving ξ are matrix operations. To determine the gradient dL/dξ , the adjoint variables
Step 1 Establish the design objective in the occupied (p a , Va , Ta ) are chosen to satisfy
zone of a room and construct the corresponding objective
function O(p, V, T), which will be minimal with an optimal ∂L ∂L ∂L
ξ . Objective function is actually a mathematical explana- dp + dV + dT = 0. (6)
∂p ∂V ∂T
tion for the design objective. One can construct various
objective functions for a design objective. For example, Equation (6) would eliminate the contribution of dp,
the design objective can be the thermal comfort or air qual- dV, and dT in Equation (5), then dL/dξ = ∂L/∂ξ which is
ity in the occupied zone of a room. The objective function straightforward. Equation (6) has to be fulfilled for any (dp,
can be constructed to make predicted mean vote (PMV) dV, dT) that is entailed by dξ , which can be accomplished
or the age of the air very small with appropriate p, V, and by setting the three partial derivatives on the left-hand side
T distributions in the occupied zone. For more examples of at zero, respectively, which constructs three independent
Journal of Building Performance Simulation 151
where the outermost sum is over those elements E j that ∂S5 ∂S5,j
n
new air supply location and size were obtained in step In the experiment, the inlet air velocity was Vx = 0.57 m/s,
4 of Section 2.1, this study adopted the Gambit journal Vy = 0.0 m/s, and the inlet air temperature (Tin ) was 15 °C.
files (GAMBIT CFD Preprocessor 1998) to automatically The temperature of the walls (Twl ) was 15 °C, and that of
regenerate the corresponding mesh. the floor (Tfl ) was 35.5 °C to form a thermal plume. The
case used here is representative of airflows in enclosed
environments as it includes major flow characteristics in an
3. Results indoor environment, such as jets and thermal plumes. Fur-
This section reports the validation of the CFD-based thermore, it was not desirable to use very complex cases for
adjoint method with an attainable design objective and this investigation since those cases may have uncertainties.
the demonstration of its performance with an ideal design Instead, this simple two-dimensional case, but still with
objective. The first case used an example with known air complex flow features, was more desirable for validation.
supply location, size, and parameters and airflow fields The experiment by Blay, Mergui, and Niculae (1992)
from the experiment. By using the measured air velocity measured the air velocity and temperature on red dash
and temperature in the flow domain as the design objec- lines, as shown in Figure 1(a). Our inverse simulation thus
tive, the adjoint method was used to identify the air supply sets the measured air velocity and temperature as a design
location, size, and parameters. If the air supply location, objective for simplification. This is because any complex
size, and parameters calculated are the same as the known design objective in an enclosed environment such as PMV
ones, the adjoint method is thus validated. The second or the age of the air is based on flow and/or temperature
case started with desirable air velocity and temperature fields. Then, the objective function for this case can be
distributions in a design domain. The adjoint method was constructed as
employed to find the corresponding air supply location,
size, and parameters. Then, with the air supply location, O(ξ ) = α (V − V0 ) dθ + β (T − T0 )2 dθ ,
2
(21)
θ θ
size, and parameters found as the boundary conditions for
forward CFD simulations, the CFD results can be used to where α and β were chosen to adjust the relative impor-
verify if the air velocity and temperature distributions in tance of the two integrals and θ denotes the design domain
the design domain are the same as the desired ones. represented by the red dash lines in Figure 1(a). This
design objective was clearly attainable because it mea-
sured data from the experiment with the corresponding
3.1. Validation with an attainable design objective boundary conditions used. The boundary conditions were
The validation of the CFD-based adjoint method in the velocity Vx = 0.57 m/s and Vy = 0, temperature 15 °C,
first case used the inverse identification of air supply location y in /H = 0.991, and size hin = 0.018 m of the air
location, size, and parameters for a two-dimensional, non- supply and wall surface temperatures. Thus, the inverse
isothermal case with experimental data from Blay, Mer- simulation, if successful, must be able to find the boundary
gui, and Niculae (1992). In Figure 1(a), the dimensions conditions. Figure 1(b) shows the resolution of the mesh
of the flow domain were H × H = 1.04 × 1.04 m, the when the inlet was located at y in /H = 0.991. The mesh
inlet location was y in /H = 0.991 (y in is the y coordinate resolution at the inlet, outlet, and near wall region was
of the middle point of the inlet), the inlet height was finer because of the high gradient of velocity and temper-
hin = 18 mm, and the outlet height was hout = 24 mm. ature there. This principle was applied to regenerate the
(a) (b)
Figure 1. Sketch (a) and mesh (b) of the two-dimensional, non-isothermal case.
154 W. Liu et al.
Fixed boundary
Scenario Design variables Objective function conditions Initial conditions ψ ϕ M1 M2
1–1 y in Equation (21) with Vx,in = 0.57 m/s, y in /H = 0.5 10−2 10−2 7000 7000
α = 1, β = 1 Vy,in = 0 m/s,
Tin = 15 °C,
hin = 0.018 m,
Twl = 15 °C,
Tfl = 35.5 °C
1–2 y in , Vy,in , Tin Equation (21) with Q = 0.01026 m2 /s, y in /H = 0.5,
α = 1, β = 1 hin = 0.018 m, Vy,in = 0.2
Twl = 15 °C, m/s, Tin = 10 °C
Tfl = 35.5 °C
1–3 y in , Vx,in , Vy,in , Tin , hin Equation (21) with Q = 0.01026 m2 /s, y in /H = 0.5,
α = 1, β = 1 Twl = 15 °C, hin = 0.0342
Tfl = 35.5 °C m, Vx,in = 0.3 m/s,
Vy,in = 0.2 m/s,
Tin = 10 °C
(a) (b)
1000 Scenario 1-1 1
Scenario 1-2
Scenario 1-3
0.9
Objective function
100
0.8
y/H
0.7
10
Figure 2. (a) Objective function and (b) inlet location determined versus design cycles (number of updating the design variables).
mesh when the air supply location and size changed in the assumed the air supply parameters to be unknown. How-
calculation. ever, the airflow rate was constrained by
To inversely identify the air supply location, size, and
parameters, a number of design variables were added one (Vin · n)hin = Q, (22)
by one to test the robustness of the method:
where Q = 0.01026 m2 /s in this study. Scenario 1–3 fur-
ther assumed that the inlet size was a design variable.
• Scenario 1–1: Inverse identification of the air supply Table 1 summarizes the detailed thermo-fluid conditions
location. for the three scenarios.
• Scenario 1–2: Inverse identification of the air supply Figure 2(a) shows that all the inverse calculations
location and supply parameters. led the variation of objective function |Onew − Oold | to
• Scenario 1–3: Inverse identification of the air supply be smaller than 10–2 so the convergence criterion was
location, size, and supply parameters. achieved. The design cycle is the number of updating
design variables. Therefore, this method could inversely
identify the local optimal design variables. The con-
Scenario 1–1 used the air supply location as a vergence speed of the three scenarios was similar. The
design variable. The air supply size and parameters increase in design variables would not increase the com-
were fixed at hin = 0.018 m, Vx = 0.57 m/s, Vy = 0 m/s, putational effort, which is a strong feature of the adjoint
and Tin = 15 °C, respectively. Therefore, the optimal air method. Although all the calculations had similar values to
supply location should be y in /H = 0.991. Scenario 1–2 the design objective, the optimal air supply location, size,
Journal of Building Performance Simulation 155
(a) (b)
(c) (d)
Figure 3. Computed flow fields at (a) initial condition, (b) design cycle (number of updating the design variables) 16, (c) design cycle
17, and (d) design cycle 40 for Scenario 1–3.
and parameters obtained differed significantly, as shown in field at design cycle 40 for Scenario 1–3. The flow field
Figure 2(b). This was due to the different combinations significantly differed from that for the initial condition, as
of air supply location, size, and parameters, which could shown in Figure 3(a).
lead to similar air distributions at the design domain and When setting the air supply size as a design variable
indicated the existence of multiple local optima. in Scenario 1–3, the air supply velocity in the x direc-
The objective function for Scenario 1–3 had a sudden tion was also a design variable due to the requirement
jump at design cycle 16. The reason was that the flow fea- of a constrained air flow rate. The computed results by
ture at design cycle 17 had a sudden change, as shown this CFD-based adjoint method would provide the vari-
in Figure 3(c). As depicted in Figure 4, the temperature ations of the air supply size hin and air supply velocity
profiles changed a lot as well. The objective function for in the x direction Vx,in at the same time. When both of
Scenario 1–3 still had fluctuations after design cycle 20. them change, it is hard or impossible to maintain a con-
The reason was that the inlet was close to the upper wall stant air flow rate. Therefore, this study varied Vx,in to
and its location fluctuated. The fluctuation in the air sup- determine the air supply size hin using Equation (22). The
ply location (Figure 3(b)) did not change much the flow results in Figure 4 show that this treatment works well for
field, but did influence the heat transfer between the jet and the inverse identification of air supply size in an enclosed
the upper wall. In Figure 5, the velocity profiles of design environment.
cycles 20 and 21 did not change much, but the temperature The air supply location, size, and parameters obtained
profiles differed a lot. Figure 3(d) shows the optimal flow by the CFD-based adjoint method were then used as inputs
156 W. Liu et al.
1 1
0.8 0.8
0.6 0.6
y [m]
y [m]
0.4 0.4
0.2 0.2
0 0
-0.4 -0.2 0 0.2 0.4 13 15 17 19 21 23 25
Vx [m/s] T [°C] x/H = 0.5
Figure 4. Comparison of the velocity and temperature profiles determined by the adjoint method and the design objective at x/H = 0.5
for Scenario 1–3.
1 1
0.8 0.8
Design objective
Scenario 1-1
Scenario 1-2
0.6 0.6 Scenario 1-3
y [m]
y [m]
0.4 0.4
0.2 0.2 H
0 0 Tfl
-0.4 -0.2 0 0.2 0.4 15 17 19 21 23 25
Vx [m/s] T [°C] x/H = 0.5
Figure 5. Comparison of the optimal velocity and temperature profiles determined by the adjoint method with the design objective at
x/H = 0.5.
2–1 y in , Vx,in , Vy,in , Tin , hin Equation (21) with Q = 0.01026 m2 /s, y in /H = 0.5, 10−1 10−1 7000 7000
α = 100, β = 1 Twl = 15 °C, hin = 0.0513 m,
Tfl = 35.5 °C Vx,in = 0.2 m/s,
Vy,in = − 0.2
m/s, Tin = 10 °C
2–2 y in /H = 0.025,
hin = 0.0513 m,
Vx,in = 0.2 m/s,
Vy,in = 0 m/s,
Tin = 10 °C
2–3 Twl = 15 °C, y in /H = 0.049,
Tfl = 35.5 °C hin = 0.1026 m,
Vx,in = 0.1 m/s,
Vy,in = 0 m/s,
Tin = 20 °C
(a) (b)
1000 Scenario 2-1 1 Scenario 2-1
Scenario 2-2 Scenario 2-2
Scenario 2-3 Scenario 2-3
0.8
Objective function
100
0.6
y/H
0.4
10
0.2
1 0
0 10 20 30 40 50 60 70 0 10 20 30 40 50 60 70
Design cycles Design cycles
Figure 7. (a) Objective function and (b) inlet location (solid lines) and size (vertical bars) determined versus design cycle (number of
updating the design variables).
of the occupied zone in a room. Then, Equation (21) was supply location, size, and parameters. Scenario 2–1 had a
again used as the objective function. sudden jump at the 19th design cycle for the objective func-
This study conducted the optimization with three sce- tion due to a rapid change in the flow pattern, as depicted in
narios. The first two scenarios were constrained by an Figure 8. The flow at the lower part of the cavity at design
airflow rate in Equation (22) and were with two arbitrarily cycle 18 was clockwise and became counter-clockwise at
initial air supply location and air supply parameters. For design cycle 19. The optimization process can change the
example, Scenario 2–1 had the initial air supply location in flow fields dramatically. Figure 9 further shows that the
the middle of the left wall (y in /H = 0.5), while Scenario change in the flow features made the temperature profiles
2–2 had the air supply location at the lower end of the differ a lot. We can also see that the optimal velocity and
left wall (y in /H = 0.025). Scenario 2–3 did not have the temperature profiles at design cycle 46 for Scenario 2–1
constraint on the airflow rate arbitrarily set its initial con- differed significantly from the initial condition.
ditions. Table 2 summarizes the detailed information for The vertical bars in Figure 7(b) show the inlet size vari-
the three scenarios. ations versus the design cycles. At the optimal condition,
Figure 7(a) shows that the variation of the objective the inlet size of the three scenarios was 0.0725, 0.0384,
function |Onew − Oold | in all three scenarios can be smaller and 0.7018 m, respectively. The airflow rate at the opti-
than 10–1 with more than 50 design cycles. This means the mal condition for Scenario 2–3 was 0.07199 m2 /s, which
convergence was achieved although the optimal air supply was about seven times higher than the constrained airflow
locations were different, as shown in Figure 7(b). There- rate for Scenarios 2–1 and 2–2. Figure 10 shows the veloc-
fore, this method could inversely identify local optimal air ity and temperature profiles calculated by the forwarded
158 W. Liu et al.
(a) (b)
Figure 8. Computed flow fields at (a) design cycle (number of updating the design variables) 18 and (b) design cycle 19 for Scenario
2–1.
y [m]
0 0 0
-0.3 -0.15 0 0.15 0.3 -0.1 0 0.1 15 17 19 21 23 25
Vx [m/s] Vy [m/s] T [°C]
Design objective Initial condition Design cycle = 18
Design cycle = 19 Design cycle = 46
Figure 9. Comparison of the velocity and temperature profiles determined by the CFD with air supply location, size, and parameters
obtained by the adjoint method and the design objective on the design domain for Scenario 2–1.
y [m]
y [m]
0 0 0
-0.1 0 0.1 0.2 0.3 -0.2 -0.1 0 0.1 0.2 20 21 22 23 24 25
Vx [m/s] Vy [m/s] T [°C]
Design objective Scenario 2-1 Scenario 2-2 Scenario 2-3
Figure 10. Comparison of the optimal velocity and temperature profiles determined by the adjoint method under different constraint
conditions with the design objective.
Journal of Building Performance Simulation 159
CFD simulation with the air supply location, size, and simplifications on the design variables make it easier to
parameters obtained by the adjoint method as inputs. With show the strength of the method, although the adjoint
the constrained airflow rate, the velocity and temperature method can handle more complex cases. This study also
profiles obtained significantly deviated from the desired simplified the turbulence models used in the adjoint equa-
design objective. Only the air velocity and temperature tions by “frozing” the turbulence level in order to reduce
profiles for Scenarios 2–3 were similar to those set in the the computing time. According to Dwight and Brezil-
objective function. This means that the desirable design lon (2006), the accuracy of approximating the turbulence
objective can only be obtained with sufficient freedom to was case dependent. Fortunately, the simplification seemed
choose the corresponding boundary conditions. acceptable in our case.
4. Discussions 5. Conclusions
The calculations in Sections 3.1 and 3.2 both converged, This study presented a CFD-based adjoint method for
but led to different values for the objective functions. In the inverse identification of air supply location, size, and
Section 3.1, the objective function was expected to be parameters. The method used local contributions of the
zero if the experimental data had no errors and the pre- derivative of the NS equations over the node positions
dicted air distributions by the CFD simulation were the by the FEM. This method was tested by applying it to a
same as the experimental data. However, the experimental two-dimensional, ventilated cavity. The study led to the
data inevitably had errors as the measuring instruments had following conclusions.
uncertainties and the turbulence models used in the CFD By using the measured air velocity and temperature
simulation had approximations. The predicted air veloc- in several locations in a ventilated cavity, the CFD-based
ity and temperature profiles by the CFD simulation in the adjoint method can identify the air supply location, size,
design procedures thus had differences from the design and parameters that can lead to the same air velocity and
objective. These explain the relatively large final objective temperature in those locations. However, the results show
functions in Section 3.1. In Section 3.2, the final objec- that different air supply location, size, and parameters could
tive functions of Scenarios 2–1 and 2–2 differed because result in the same air velocity and temperature in those
of the existence of multiple solutions. Furthermore, the locations. This implies that multiple solutions exist and can
final objective function of Scenario 2–3 was much smaller be identified by the method.
than that in Section 3.1. The possible reasons were a By using different air supply location, size, and param-
smaller design domain and more freedom to choose the eters as design variables, the adjoint method could simulta-
corresponding boundary conditions in Scenario 2–3. neously identify the locally optimal design variables. The
The CFD-based adjoint method for the two-dimensional computing costs did not vary with the number of design
cases can yield multiple optimal solutions even with a sin- variables.
gle design variable. It requires multiple trials to obtain the This study has successfully demonstrated that it is pos-
global optimal solutions, which would be time-consuming. sible to set desirable design objectives in the flow domain
To improve the computational efficiency, one may first and to obtain the corresponding air supply location, size,
take advantage of the CFD-based GA method to determine and parameters needed for achieving the design objective.
the initial air supply locations and parameters, which may The initial boundary conditions can be arbitrarily set. With
lead to multiple solutions. Then, the optimization with the different constraints used, the air supply location, size, and
CFD-based adjoint method can be conducted with these parameters found can be very different.
pre-determined initial air supply locations and parameters
to check if these initial conditions would lead to a unique
solution. Theoretically, the combined CFD-based GA and Funding
adjoint method can be faster than the pure CFD-based The research presented in this paper was supported financially
GA and can find the global optima that makes up for the by the National Basic Research Program of China (The 973
Program) through Grant No. 2012CB720100.
shortcomings of the pure CFD-based adjoint method. For
example, Xue and Zhai (2014) recently tried to acceler-
ate the GA method by integrating with the adjoint method. 6. Nomenclature
This new integrated method has a great advantage when the Symbol definition
number of variables for optimization is large. In addition, d variation
our future study will try to solve the NS/adjoint equations D rate of strain tensor
by fast fluid dynamics (Zuo and Chen 2009), which can e number of Lagrange linear shape functions
further decrease the computational effort. per element
E element
The major simplifications in this study were on design g gravity vector
variables and the adjoint of turbulence models. For exam- gE(k) global node number of node k of element E
ple, we assumed the inlet air velocity to be uniform. The h air supply size
160 W. Liu et al.
J Jacobian of element mapping Dwight, R. P., and J. Brezillon. 2006. “Effect of Various
L augmented objective function Approximations of the Discrete Adjoint on Gradient-based
M iteration number Optimization.” Proceedings of the 44th AIAA aerospace
n number of internal nodes sciences meeting and exhibit, Reno, NV.
N shape function GAMBIT CFD Preprocessor. 1998. User’s Guide. Lebanon, NH:
n unit vector in the normal direction Fluent Inc.
O objective function Giles, M. B., and N. A. Pierce. 2000. “An Introduction to
p pressure the Adjoint Approach to Design.” Flow, Turbulence and
q quadrature point Combustion 65 (3–4): 393–415.
Q airflow rate Gill, P. E., W. Murray, and M. H. Wright. 1981. Practical
S NS equations, vector form Optimization. London: Academic Press.
T air temperature Griwank, A. 2000. Evaluating Derivatives, Principles and Tech-
V air velocity, vector niques of Algorithmic Differentiation. Philadelphia: SIAM.
x, y index of coordinates
Gunzburger, M. D. 2003. Perspectives in Flow Control and
Subscripts Optimization. Philadelphia: SIAM.
0 design objective Haasdonk, B., and M. Ohlberger. 2011. “Efficient Reduced Mod-
1, 2, 3, 4, 5 component of a vector els and A Posteriori Error Estimation for Parametrized
a adjoint parameter Dynamical Systems by Offline/Online Decomposition.”
fl value at the floor Mathematical and Computer Modelling of Dynamical Sys-
i component of a vector tems 17 (2): 145–161.
initial initialized value Hedge, A., W. A. Erickson, and G. Rubin. 1996. “Predicting Sick
in value at the air supply inlet Building Syndrome at the Individual and Aggregate Levels.”
j node number Environment International 22 (1): 3–19.
l quadrature point number Holland, J. 1975. Adaptation in Natural and Artificial Systems.
old value at prior design cycle Ann Arbor: University of Michigan Press.
new value updated at current design cycle International Facility Management Association. 2003. “IFMA
op operating value Survey Ranks Top 10 Office Complaints.” Accessed July 1,
outlet value at the outlet 2012. http://www.buildings.com/tabid/3334/ArticleID/1689/
wl value at the wall Default.aspx
x, y component in the x and y direction, respec- Jameson, A. 1995. “Optimum Aerodynamic Design Using CFD
tively and Control Theory.” AIAA Paper 1729: 124–131.
Jameson, A., L. Martinelli, and N. A. Pierce. 1998. “Optimum
Greek symbols Aerodynamic Design Using the Navier–Stokes Equations.”
α, β weighting factor, positive constant Theoretical and Computational Fluid Dynamics 10 (1–4):
γ thermal expansion coefficient 213–237.
δ node coordinates Jimack, P. K. 1997. “An Optimal Finite Element Mesh for
θ design domain Elastostatic Structural Analysis Problems.” Computers and
κ effective conductivity Structures 64 (1): 197–208.
λ step size, positive constant Kämpf, J. H., M. Wetter, and D. Robinson. 2010. “A Com-
ν effective viscosity parison of Global Optimization Algorithms with Standard
ξ design variable, vector Benchmark Functions and Real-World Applications Using
ψ positive constant EnergyPlus.” Journal of Building Performance Simulation
ω quadrature weight 3 (2): 103–120.
ϕ positive constant Li, K., H. Su, J. Chu, and C. Xu. 2012. “A Fast-POD Model for
computation domain Simulation and Control of Indoor Thermal Environment of
Buildings.” Building and Environment 60: 150–157.
Li, K., W. Xue, C. Xu, and H. Su. 2013. “Optimization of
ORCID Ventilation System Operation in Office Environment Using
POD Model Reduction and Genetic Algorithm.” Energy and
Qingyan Chen http://orcid.org/0000-0002-3204-9488
Buildings 67: 34–43.
Liu, W., and Q. Chen. 2014. “Optimal Air Distribution Design in
Enclosed Spaces Using an Adjoint Method.” Submitted to
References Inverse Problems in Science & Engineering.
ASHRAE (American Society of Heating, Refrigerating, and Air- Mendell, M. J. 1993. “Non-specific Symptoms in Office Workers:
Conditioning Engineers). 2010. ANSI/ASHRAE Standard A Review and Summary of the Epidemiologic Literature.”
62.1–2010, Ventilation for Acceptable Indoor Air Quality. Indoor Air 3 (4): 227–236.
Atlanta, GA: American Society of Heating, Refrigerating, Menzies, R. D., J. Pasztor, J. Leduc, and F. Nunes. 1994. “The
and Air-Conditioning Engineers. ‘Sick Building’–A Misleading Term that should be Aban-
Blay, D., S. Mergui, and C. Niculae. 1992. “Confined Turbulent doned.” In Indoor Air Quality, 37–48. Atlanta: ASHRAE.
Mixed Convection in the Presence of a Horizontal Buoyant Nguyen, A. T., and S. Reiter. 2014. “Passive Designs and Strate-
Wall Jet, Fundamentals of Mixed Convection.” ASME HTD gies for low-cost Housing Using Simulation-Based Opti-
213: 65–72. mization and Different Thermal Comfort Criteria.” Journal
Boussinesq, J. 1903. Theorie Analytique de la Chaleur. Paris: of Building Performance Simulation 7 (1): 68–81.
Gauthier-Villars. OpenFOAM. 2007. “The Open Source CFD Toolbox.”
Bryson, A. E., and Y. C. Ho. 1975. Applied Optimal Control. http://www.opencfd.co.uk/openfoam.html
Washington, DC: Hemisphere.
Journal of Building Performance Simulation 161
Othmer, C. 2008. “A Continuous Adjoint Formulation for the Indoor Environments.” Proceedings of the 13th international
Computation of Topological and Surface Sensitivities of conference on indoor air quality and climate (indoor air
Ducted Flows.” International Journal for Numerical Meth- 2014, Hong Kong).
ods in Fluids 58: 861–877. Xue, Y., Z. Zhai, and Q. Chen. 2013. “Inverse Prediction and
Patankar, S. V., and D. B. Spalding. 1972. “A Calculation Optimization of Flow Control Conditions for Confined
Procedure for Heat, Mass and Momentum Transfer in Spaces Using a CFD-Based Genetic Algorithm.” Building
Three-Dimensional Parabolic Flows.” International Journal and Environment 64: 77–84.
of Heat and Mass Transfer 15 (10): 1787–1806. Yakhot, V., and S. A. Orszag. 1986. “Renormalization Group
Rozza, G., D. Huynh, and A. Patera. 2007. “Reduced Basis Analysis of Turbulence.” Journal of Scientific Computing 1
Approximation and A Posteriori Error Estimation for (1): 3–51.
Affinely Parametrized Elliptic Coercive Partial Differential Zhai, Z., Z. Zhang, W. Zhang, and Q. Chen. 2007. “Evalua-
Equations.” Archives of Computational Methods in Engi- tion of Various Turbulence Models in Predicting Airflow
neering 15 (3): 1–47. and Turbulence in Enclosed Environments by CFD: Part-
Schneider, R. 2006. “Applications of the Discrete Adjoint 1: Summary of Prevalent Turbulence Models.” HVAC&R
Method in Computational Fluid Dynamics.” Doctoral diss., Research 13 (6): 853–870.
The University of Leeds. Zhang, Z., W. Zhang, Z. Zhai, and Q. Chen. 2007. “Evalua-
Schneider, R., and P. K. Jimack. 2008. “On the Evaluation of tion of Various Turbulence Models in Predicting Airflow
Finite Element Sensitivities to Nodal Coordinates.” Elec- and Turbulence in Enclosed Environments by CFD: Part-
tronic Transactions on Numerical Analysis 32: 134–144. 2: Comparison with Experimental Data From Literature.”
Sokolowski, J., and J. P. Zolesio. 1992. Introduction to Shape HVAC&R Research 13 (6): 871–886.
Optimization. Berlin Heidelberg: Springer. Zhou, L., and F. Haghighat. 2009a. “Optimization of Ventilation
U.S. Department of Energy. 2011. “Building Energy Data Book.” System Design and Operation in Office Environment, Part I:
http://buildingsdatabook.eren.doe.gov/ChapterIntro1.aspx Methodology.” Building and Environment 44 (4): 651–656.
“Wikipedia.” http://en.wikipedia.org/wiki/Automatic_different Zhou, L., and F. Haghighat. 2009b. “Optimization of Ventila-
iation tion Systems in Office Environment, Part II: Results and
Wright, J. A., A. Brownlee, M. M. Mourshed, and M. Wang. Discussions.” Building and Environment 44 (4): 657–665.
2014. “Multi-objective Optimization of Cellular Fenestra- Zuo, W., and Q. Chen. 2009. “Real Time or Faster-Than-Real-
tion by an Evolutionary Algorithm.” Journal of Building Time Simulation of Airflow in Buildings.” Indoor Air 19 (1):
Performance Simulation 7 (1): 33–51. 33–44.
Xue, Y., and Z. Zhai. 2014. “Comparison and Integration of
Genetic Algorithm and Adjoint Algorithm for Optimizing