You are on page 1of 34

Application &

Installation Guide

Engine Room Ventilation

LEBW4971-07
Contents
Engine Room Ventilation ..................................................................1
Sizing Considerations .................................................................. 2
Cooling Air ............................................................................... 2
Combustion Air ....................................................................... 2
Ventilation Airflow .................................................................. 3
Calculating Required Ventilation Airflow ......................... 3
Engine Room Enclosure Temperature .............................. 4
Atmospheric Heat Rejection Correction Factor ................ 4
Ventilation Fans ........................................................................... 7
Fan Types ................................................................................. 7
Fan Location ............................................................................ 7
Fan Sizing ................................................................................. 7
Exhaust Fans ............................................................................ 7
Two Speed Fan Motors ........................................................... 8
Routing Considerations ............................................................... 9
General Routing Principles ..................................................... 9
Single & Dual Engine Applications ................................. 10
Multiple Engine Applications ........................................... 14
Special Application Routing ............................................ 17
Marine Exhaust Ejector – Automatic
Ventilation System ........................................................... 24
Additional Considerations .................................................... 24
Radiator Sizing .................................................................. 24
Radiator Fan Sizing ........................................................... 24
Moveable Louvers ............................................................ 25
Refrigeration Equipment .................................................. 25
Exhaust Pipe Insulation .................................................... 25
Test With Doors and Windows Closed ........................... 25
Ducting Considerations .................................................... 25
Cold Weather Considerations .............................................. 26
Air Cleaner Icing ............................................................... 26
Extreme Cold ..................................................................... 27
Boost Control .................................................................... 27
Foreword
This section of the Application and Installation Guide generally describes
Engine Room Ventilation for Cat® engines listed on the cover of this section.
Additional engine systems, components and dynamics are addressed in
other sections of this Application and Installation Guide.
Engine-specific information and data is available from a variety of sources.
Refer to the Introduction section of this guide for additional references.
Systems and components described in this guide may not be available or
applicable for every engine.
Engine Room Ventilation Application and Installation Guide

Engine Room Ventilation


This guide addresses engine room ventilation considerations that apply to
the successful installation, operation and maintenance of Cat engines,
generator sets, compressor units, and other packaged units.
The primary aspects of a properly designed engine room ventilation system
are cooling air and combustion air. Cooling air refers to the flow of air that
removes radiant heat from the engine, generator, other driven equipment
and other engine room components. Combustion air describes the air the
engine requires to burn fuel.
Cooling and combustion air directly impact engine and package unit
performance and dependable service life; these must be considered in the
design of an engine room ventilation system. It is also important to
consider all engine room equipment in the design of a ventilation system
and provide a comfortable environment for service personnel to perform
maintenance.
Some driven equipment, such as a generator in a large engine installation,
may require a dedicated ventilation source.

SECTION CONTENTS

Sizing Considerations................... 2 Additional Considerations ......... 24


• Cooling Air • Radiator Sizing
• Combustion Air • Louvers
• Ventilation Airflow • Refrigeration Equipment
Ventilation Fans ............................ 7 • Exhaust Pipe Insulation
• Fan Types
• Ducting
• Fan Location Cold Weather
• Fan Sizing Considerations ............................ 26
Routing Considerations................ 9 • Air Cleaner Icing
• General Routing Principles • Extreme Cold
• Boost Control

©2017 Caterpillar
All rights reserved. Page 1
Application and Installation Guide Engine Room Ventilation

Sizing Considerations
The use of insulation on exhaust
Cooling Air pipes, silencers, and jacket water
A portion of fuel consumed by an pipes will reduce the amount of
engine is lost to the environment in heat radiated by auxiliary sources.
the form of heat radiated to the
surrounding air. In addition, heat Radiated heat from the engines
from generator inefficiencies and and other machinery in the engine
exhaust piping can easily equal room is absorbed by engine room
engine-radiated heat. Any resulting surfaces. Some of the heat is
elevated temperatures in the engine transferred to atmosphere or, on
room may adversely affect marine installations, to the sea through
maintenance, personnel, the ship’s hull. The remaining radiated
switchgear, and engine or generator heat must be carried away by the
set performance. ventilation system.
Engine room ventilation air (cooling A system for exhausting ventilation
air) has two basic purposes. air from the engine room must be
included in the ventilation system
• To provide an environment that design.
permits the machinery and
equipment to function properly Combustion Air
with dependable service life. Combustion air is discussed in
detail in the Air Intake Systems
• To provide an environment in section of the Application and
which personnel can work Installation Guide. Some aspects of
comfortably and effectively. the intake air system are discussed
It is important to note that cooling in this guide because they
air is needed for more than just the significantly impact the engine
engine; the generator intake also room ventilation system design.
requires cool clean air. The most In many installations, combustion
effective way to do this is to provide air is drawn from outside the engine
a ventilation air source low to the room via ductwork that is designed
ground at the rear of the package. to move a large amount of air with
It is also good practice to include air very little restriction. These
intake filters on the engine room installations have very little impact
ventilation system, especially in on engine room ventilation design.
dusty environments. The use of Other installations, however,
filters will extend the life of rotating require that combustion air be
equipment in the engine room, such drawn directly from the engine
as generators, pumps, and room. In these installations,
compressors. They will also extend combustion air requirements
the life of the engine air cleaners. become a significant ventilation
Care must be taken when selecting system design parameter.
engine room air intake filters to Approximate consumption of
ensure filter restriction when new combustion air for a diesel engine is
and at end of life still allow for 0.1 m3 of air/min/brake kW (2.5 ft3 of
sufficient air flow within the engine air/min/bhp) produced. Engine-
room for both cooling and specific combustion air
combustion air. requirements can be found using
the resources mentioned in the
foreword of this guide.

©2017 Caterpillar
Page 2 All rights reserved.
Engine Room Ventilation Application and Installation Guide

Ventilation Airflow F = Routing factor based on the


Required ventilation airflow ventilation type discussed in the
depends on the desired engine Routing Considerations section of
room air temperature as well as the this guide.
cooling air and combustion air Note: If combustion air is supplied
requirements outlined above. While to the engine through dedicated
it is understood that total engine duct work, “Combustion Air”
room ventilation airflow must take should be omitted from the formula.
all equipment and machinery into
account, the following sections Example:
provide a means for estimating the The engine room for a 3412 DITA
airflow required for the successful genset has a Type 1 ventilation
operation of Cat engines and routing configuration and a
packages. dedicated duct for combustion air.
It has a heat rejection value of
Calculating Required Ventilation 659 kW (37,478 Btu/min) and a
Airflow permissible rise in engine room
Engine room ventilation air required temperature of 11°C (20°F).
for Cat engines and packages can
be estimated by the following Solution:
formula. The estimated engine room
ventilation required for this
H arrangement:
V= + Combustion Air xF
D x C P x ∆T
659
V= +0 x1
1.099 x 0.017 x 11
Where:
V = 3206.61 m3/min
V = Ventilating Air (m3/min), (cfm)
H = Heat Radiation i.e. engine, 37478
V= +0 x1
generator, aux (kW), 0.071 x 0.24 x 20
(Btu/min)
V = 109970.7 cfm
D = Density of Air at air
temperature 38°C (100°F). The
density is equal to Proper ventilation is heavily
1.099 kg/m3 (0.071 lb/ft3) dependent on the path of the
ventilation air. Applications
CP = Specific Heat of Air involving high load factors and
(0.017 kW x min/kg x °C), continuous full power operation
(0.24 Btu/LBS/°F) require a rigorous approach based
∆T = Permissible temperature rise on classical heat transfer
in engine room (°C), (°F) calculations accounting for radiant
heat and allowable room
(Note: Max engine room temperature rise and adjusting with
temperature is 120°F) a ventilation routing factor.

©2017 Caterpillar
All rights reserved. Page 3
Application and Installation Guide Engine Room Ventilation

Engine Room/Enclosure If the engine room temperature


Temperature exceeds 40°C (104°F), the generator
The primary reason for maintaining must be derated per the generator
engine room temperature at an derate schedule and cool outside air
appropriate level is to protect must be ducted directly to the
various components from excessive generator air intake. Alternatively,
temperatures. Items that require custom generators can be sized to
cool air are: handle specific ambient conditions.
In larger multiple engine sites, the
• Electrical and electronic normal 8.5 to 12.5°C (15 to 22.5°F)
components. temperature rise guidelines for
• Cool air to the air cleaner inlet. engine rooms may require
unobtainable or uncomfortable air
• Cool air to the torsional vibration velocities. For these larger sites, a
damper. ventilation system needs to give
• Habitable temperatures for the priority to the five items listed
engine operator or service above and provides a bottom to top
personnel. airflow similar to that shown in
Figure 8 and Figure 9. In all cases,
• Cooling air for the generator or engine room/enclosure design must
other driven equipment. ensure that air temperature around
A properly designed engine room the engine will not exceed 50°C
ventilation system will maintain (122°F). Critical locations include the
engine room air temperatures engine torsional damper and
within 8.5 to 12.5°C (15 to 22.5°F) generator coupling. Air temperature
above the ambient air temperature. reading should be taken no more
For example, if the engine room than 6 inches away from these
temperature is 24°C (75°F) without components. Note that in these
the engine running, the ventilation extreme situations, it may be
system should maintain the room necessary to duct cool air directly
temperature between 32.5°C (90°F) to these critical components.
and 36.5°C (97.5°F) while the engine Atmospheric Heat Rejection
is in operation. Correction Factor
Caterpillar recommends a Atmospheric heat rejection values
ventilation design that ensures published in TMI are based on
engine room temperature does not ambient cell conditions between
exceed 49°C (120°F). If the engine 25°C and 29°C. Engine rooms can be
room temperature cannot be designed at much higher ambient
maintained below 49°C (120°F), conditions; therefore a correction
cooler air should be ducted directly factor can be utilized to define the
to the engine air cleaners. atmospheric heat rejection at the
higher ambient condition.
Temperature limits of the driven
equipment must also be considered. The correction factors defined
For model-specific electronic below have been developed using
components, reference the fundamentals of heat transfer and
appropriate service manual or EDS can be applied to any object under
sheet for that component’s allowed the same conditions.
surface temperatures.

©2017 Caterpillar
Page 4 All rights reserved.
Engine Room Ventilation Application and Installation Guide

There are two distinct correction Radiant Heat


factors, one is used with wet Radiant heat values for the engine
exhaust and turbo manifolds, the and driven equipment is needed to
other is used with dry exhaust and calculate the required ventilation
turbo manifolds. The skin airflow.
temperature utilized in the dry Note: For the packaged generator
manifold calculation is 200°C, sets, ensure that there is adequate
approx value of the wrapped, or airflow near the engine torsional
insulated manifold. damper. Excessive piping and
Wet exhaust and turbo manifold cooling system structures may
correction factor. prohibit proper airflow near the
WCF = -.0156 * TER + 1.4505 torsional damper. Monitor damper
temperatures per the
Where: recommendations found in the
WCF = Wet Correction Factor Operation and Maintenance
Service Manual.
TER = Ambient Engine Room This data is available in the TMI for
Ambient (°C) Cat products. It is located in the
Dry exhaust and turbo manifold Performance Data section.
correction factor. Engine
DCF = -.011* TER +1.3187 Engine generated radiant heat (heat
Where: rejection to atmosphere) is routinely
provided with published engine
DCF = Dry Correction Factor technical data. Values are typically
nominal with their tolerance noted.
TER = Ambient Engine Room Tolerance should always be added
Temperature (°C) before using published data in
To obtain the corrected atmospheric calculations.
heat rejection value, multiply the
TMI value by the WCF or DCF.

©2017 Caterpillar
All rights reserved. Page 5
Application and Installation Guide Engine Room Ventilation

Generator Example:
For generator set installations, the A 3512B, 975 ekW standby
heat radiated by the generator can generator set has a generator
be estimated by the following efficiency of 92%. The generator
formulas. radiant heat for this genset can be
HRG (kW) = P x calculated as follows.
[(1/Eff) – 1] Solution:
P = 975 ekW
HRG (Btu/min) = P x [(1/Eff) –
1] x 56.9 Efficiency = 92% / 100% = 0.92
HRG = 975 x (0.92 – 1)
Where: HRG = 84.78 kW
HRG = Heat Radiated by the HRG = 975 x (0.92 – 1) x 56.9
Generator (kW), (Btu/min)
HRG = 4824 Btu/min
P= Generator Output at
Maximum Engine Rating
(ekW) Note: This data is available in the
TMI for Cat generators. It is located
Eff = Generator Efficiency % / 100% in the Performance Data section.

©2017 Caterpillar
Page 6 All rights reserved.
Engine Room Ventilation Application and Installation Guide

Ventilation Fans
Except for special applications, natural Fan Sizing
draft ventilation is too bulky for Fan sizing involves much more than
practical consideration. Adequate just selecting a fan that will deliver
quantities of fresh air are best the airflow volume needed to meet
supplied by powered (fan-assisted) the cooling air and combustion air
ventilation systems. requirements. It requires a basic
Fan Types understanding of fan performance
The following types of ventilation characteristics and ventilation
fans are typically used. system design parameters.
Similar to a centrifugal pump, a fan
• Vane-axial operates along a specific fan curve
• Tube-axial that relates a fan’s volume flow rate
(m3/min or cfm) to pressure rise
• Propeller (mm H2O or in. H2O) at a constant
• Centrifugal fan speed. Therefore, fan selection
(squirrel cage blowers) not only requires that the volume
flow rate be known, but also that
The selection of fan type is usually the ventilation distribution system
determined by ventilation air be known in order to estimate
volume, pressure requirements and the system pressure rise. This
space limitations within the engine information allows the optimum
room. The fans have various fan to be selected from a set of
qualities that make them better manufacturers’ fan curves or tables.
suited to certain applications.
Exhaust Fans
Fan Location Ventilation air exhaust systems
Fans are most effective when they should be designed to maintain a
withdraw ventilation air from the slight positive or negative pressure
engine room and exhaust the hot air in the engine room, depending on
to the atmosphere. However, ideal the specific application.
engine room ventilation systems
will utilize both supply and exhaust Positive pressure should normally
fans. This will allow the system not exceed .050 kPa or (0.2 in. H2O).
designer the maximum amount of This positive pressure provides the
control over ventilation air following advantages.
distribution.
The fan motors should be mounted
outside the direct flow of hot
ventilating air for longest motor life.
The design of centrifugal fans
(squirrel cage blowers) is ideal in
this regard, but their size, relative to
the vane-axial or tube-axial fans,
sometimes puts them at a
disadvantage.

©2017 Caterpillar
All rights reserved. Page 7
Application and Installation Guide Engine Room Ventilation

• It prevents the ingress of dust exhaust ventilation provides the


and dirt, which is especially following advantages.
beneficial for those applications • It compensates for the thermal
involving engines that draw their expansion of incoming air.
combustion air from the engine
room. • It creates an in draft to confine
heat and odor to the engine room.
• It creates an out draft to expel
heat and odor from the engine Two Speed Fan Motors
room. Operation in extreme cold weather
Some applications, such as a may require reducing ventilation
marine application where the airflow to avoid uncomfortably cold
engine room is adjacent to living working conditions in the engine
quarters, require that a slight room. This can be easily done by
negative pressure be maintained in providing ventilation fans with two
the engine room. This negative speed (100% and 50% or 67%
pressure should not normally exceed speeds) motors.
0.1275 kPa (0.5 in. H2O). The excess

©2017 Caterpillar
Page 8 All rights reserved.
Engine Room Ventilation Application and Installation Guide

Routing Considerations
• Avoid ventilation air supply
General Routing Principles ducts that blow cool air directly
Correct ventilation air routing is toward hot engine components.
vital for proper operation of Cat This mixes the hottest air in the
engines and packaged units. engine room with incoming cool
Maintaining recommended air air, raising the average engine
temperatures in the engine room is room temperature. This also
impossible without proper routing leaves areas of the engine room
of the ventilation air. The following with no appreciable ventilation.
principles should be considered
when designing an engine room • For installations where
ventilation system. engines draw combustion air
from inside the engine room, the
• Fresh air inlets should be located routing should provide the coolest
as far from the sources of heat as possible combustion air to the
practical and as low as possible. turbocharger inlets.
• Ventilation air should be • For marine and offshore
exhausted from the engine room applications, the potential exists
at the highest point possible, for seawater to be drawn into the
preferably directly over the ventilation air supply; systems
engine. for these applications must be
• Ventilation air inlets and outlets designed to prevent seawater
should be positioned to prevent from being drawn into the air
exhaust air from being drawn intake filters and ingested by
into the ventilation inlets the turbocharger. Generator
(recirculation). cooling air must also be filtered
to minimize the ingestion of salt.
• Ventilation air inlets and outlets These general routing principles,
should be positioned to prevent while driven by the same basic
pockets of stagnant or principles of heat transfer, will
recirculating air, especially in the vary with the specific application.
vicinity of the generator air inlet. This section discusses the general
• Where possible, individual considerations relating to single and
exhaust suction points should be dual engine applications, multiple
located directly above the engine (3+) applications, and several
primary heat sources. This will special applications.
remove heat before it has a
chance to mix with engine room
air and raise the average
temperature. It must be noted
that this practice will also require
that ventilation supply air be
properly distributed around the
primary heat sources.

©2017 Caterpillar
All rights reserved. Page 9
Application and Installation Guide Engine Room Ventilation

Single & Dual Engine Applications Outside air is brought into the
Single and dual engine applications engine room through a system of
are arguably the most common ducts. These ducts should be routed
applications encountered, between engines, at floor level, and
regardless of engine market. discharge air near the bottom of the
These applications will generally engine and generator as shown in
require smaller engine rooms, Figure 1.
which are especially challenging in Ventilation air exhaust fans should
regard to the use of good routing be mounted or ducted at the highest
practices. point in the engine room. They should
Recommended ventilation systems be directly over heat sources.
for these applications, presented in This system provides the best
order of preference, are Type 1, ventilation with the least amount of
Type 2, Type 3 and Type 4. air required. In addition, the upward
Ventilation Type 1 (Preferred flow of air around the engine serves
Design) as a shield which minimizes the
Note: In ventilation airflow amount of heat released into the
calculations, Type 1 systems have engine room. Air temperature in the
a Routing Factor of 1. exhaust air duct will be higher than
engine room air temperature.

Ventilation Type 1

Figure 1

Ventilation Type 2 (Skid Design) room through a system of ducts


Note: In ventilation airflow and routes it between engines.
calculations, Type 2 systems Type 2, however, directs airflow
have a Routing Factor of 1. under the engine and generator so
A skid design may be preferred the air is discharged upward at the
in petroleum applications. Similar engines and generators as shown
to the Type 1 system, Type 2 in Figure 2.
brings outside air into the engine

©2017 Caterpillar
Page 10 All rights reserved.
Engine Room Ventilation Application and Installation Guide

The most economical method to This system provides the best


achieve this design is to use a ventilation with the least amount of
service platform. The platform is air required. In addition, the upward
built up around the engines and flow of air around the engine serves
serves as the top of the duct. This as a shield which minimizes the
requires the service platform to be amount of heat released into the
constructed of solid, nonskid plate engine room. Air temperature in
rather than perforated or expanded the exhaust air duct will be higher
grating. The duct outlet will be the than engine room air temperature.
clearance between the decking and Although the Type 1 system provides
oilfield base. Regular care must be effective ventilation for the engine,
used to ensure grating remains it does not consider the special
clean and the airflow unrestricted. ventilation needs of the driven
Ventilation air exhaust fans should equipment. Large generators,
be mounted or ducted at the highest configured with an air inlet
point in the engine room. They should positioned high on the generator,
be directly over heat sources. will require an additional source of
ventilation air.
Ventilation Type 2

Figure 2

Ventilation Type 3 (Alternate Note: In ventilation airflow


Design) calculations, Type 3 systems have
If Ventilation Type 1 or Type 2 a Routing Factor of 1.5.
is not feasible, an alternative As shown in Figure 3, outside air
is Type 3; however, this routing is brought into the engine room
configuration will require utilizing fans or large intake ducts.
approximately 50% more airflow The inlet is placed as far away as
than Type 1. practical from heat sources and

©2017 Caterpillar
All rights reserved. Page 11
Application and Installation Guide Engine Room Ventilation

discharged into the engine room as Engine heat will be dissipated with
low as possible. The air them flows this system, but a certain amount of
across the engine room from the heat will still radiate and heat up all
cool air entry point(s) toward the adjacent engine room surfaces.
sources of engine and equipment If the air is not properly routed, it
heat; these include the engine, will rise to the ceiling before it gets
exposed exhaust components, to the engines.
generators, or other large sources
of heat. This system will work only where
Ventilation air exhaust fans should the air inlets circulate the air between
be mounted or ducted at the highest the engines, for dual engine
point in the engine room. applications. Air inlets located at
Preferably, they should be directly the end of the engine room will
over heat sources. provide adequate ventilation to only
the engine closest to the inlet.

Ventilation Type 3

Figure 3

©2017 Caterpillar
Page 12 All rights reserved.
Engine Room Ventilation Application and Installation Guide

Ventilation Type 4 This system mixes the hottest air in


(Less Effective Design) the engine room with the incoming
If Ventilation Type 1, Type 2 cool air, raising the temperature of
and Type 3 are not feasible, the all air in the engine room. It also
following method can be used; interferes with the natural convection
however, it provides the least flow of hot air rising to exhaust fans.
efficient ventilation and requires Engine rooms can be ventilated this
approximately two and a half times way, but it requires extra large
the airflow of Ventilation Type 1. capacity ventilating fans.
Note: In ventilation airflow Incorrect Airflow
calculations, Type 4 systems have Figure 5 illustrates an incorrect
a Routing Factor of 2.5. method to vent engine room heat.
As shown in Figure 4, outside air is Although the inlet duct has louvers
brought into the engine room using to direct airflow toward the engine,
supply fans, and discharged toward rising heat will warm the cool air
the turbocharger air inlets on the before it can reach the engine.
engines.
Ventilation exhaust fans should be
mounted or ducted from the corners
of the engine room.

Ventilation Type 4

Figure 4

©2017 Caterpillar
All rights reserved. Page 13
Application and Installation Guide Engine Room Ventilation

Incorrect Airflow

Figure 5

Multiple Engine Applications Large multiple engine sites will


The ventilation systems generally utilize multiple ventilation
recommended for single and dual fans. These sites often use one or
engine applications also apply to two fans for each engine and an
multiple engine applications. additional fan to direct air to the
However, there are additional inlet of the generator or other
considerations that are specific to driven equipment. This practice
multiple engines. allows for a very simple
As previously mentioned, using arrangement requiring minimal
normal temperature rise guidelines ductwork.
will likely result in the requirement The use of multiple ventilation fans,
for extremely large volumes of air for either supply or exhaust, will
on multiple engine installations. require that airflow between the
Although the guidelines for these engines be arranged, either by fan
sites may be more generous placement or by distribution
in regard to temperature rise ductwork.
allowance, the ventilation system Figure 6 and Figure 7 show examples
must be designed to provide of correct and incorrect airflow
sufficiently cool air in the immediate patterns for multiple engine sites.
vicinity of the engine and driven (Note: generator ends would be
equipment to meet their ventilation on right side of diagrams)
requirements.

©2017 Caterpillar
Page 14 All rights reserved.
Engine Room Ventilation Application and Installation Guide

Correct Airflow

Figure 6

Incorrect Airflow

Figure 7

©2017 Caterpillar
All rights reserved. Page 15
Application and Installation Guide Engine Room Ventilation

Figure 8 and Figure 9 show


examples of the bottom-to-top
airflow pattern generally used in
large power plant applications.

Bottom-to-Top Airflow

Figure 8
Bottom-to-Top Airflow

Figure 9

©2017 Caterpillar
Page 16 All rights reserved.
Engine Room Ventilation Application and Installation Guide

Special Application Routing Two methods can be used to


Engine Mounted Radiators overcome this problem.
Applications with engine-mounted • Remote mounted and specially
radiators using engine room air ducted engine-mounted
for cooling generally provide radiators do not require engine
more airflow than is necessary room air for cooling; refer to
for adequate ventilation; refer Figure 11. One advantage of such
to Figure 10. The high airflow a system is that the air used to
combined with low ambient cool the radiator is not pre-
temperatures, below 21°C (70°F), can heated by the engine, thus
cause water to condense inside increasing the ambient capability
exposed engine components, such (or reducing the size) of the unit.
as valve covers. This can result The disadvantage is that motor-
in oil and maintenance problems. driven fans must be installed to
Therefore, special installation provide ventilation for the engine
considerations must be made in which increase the overall cost
cold climates. of the system.
Engine-Driven Fan Arrangement

Figure 10

©2017 Caterpillar
All rights reserved. Page 17
Application and Installation Guide Engine Room Ventilation

Engine-Driven Fan Arrangement

Figure 11

Radiator with Thermostatically Controlled Louvers

Figure 12

• Thermostatically controlled air is reintroduced upstream of


louvers can be installed to the engine and is well mixed by
recirculate some of the radiator the time it reaches the radiator.
exhaust in order to maintain a
warm airflow across the engine.
Refer to Figure 12. This also
maintains a comfortable working
environment for maintenance
personnel. Caution must be
exercised so that the recirculated

©2017 Caterpillar
Page 18 All rights reserved.
Engine Room Ventilation Application and Installation Guide

For any arrangement where a radiator Air Curtains


fan is used to ventilate an engine
room, the vacuum created in the
engine room must not exceed
0.1275 kPa (0.5 in. H2O). Any
restriction above this limit could
reduce airflow through the radiator
and overheat the engine.
Air Curtains
Air curtains, totally enveloping the
generator set, provide ventilation
without exposing the equipment
room to high air velocities. Refer to Figure 13
Figure 13. Radiated heat is removed
with approximately half the airflow
of a horizontal flow system. It is important to stretch the air curtain
inlet the full length of generator set.
Special care must be used to ensure
adequate cool airflow at the generator
air intake and at the generator
coupling.
Air curtains present ducting
challenges when local fan radiators
are used.

©2017 Caterpillar
All rights reserved. Page 19
Application and Installation Guide Engine Room Ventilation

Power Modules can derate 5 to 7°C (9 to 13°F) when


Power modules generally utilize enclosed. Refer to the Enclosure
radiator cooled diesel generator Installation section of the
sets. The power module enclosures Application & Installation Guide for
trap the radiated heat from the spacing recommendations for
engine and generator, and direct it power modules. Figure 14 and
through the radiator, decreasing Figure 15 show examples of typical
cooling capabilities 8 to 10°C (14 to Cat containerized power modules.
18°F). Even with doors open, radiators
40’ Containerized Power Module

Figure 14
1. Cat D/G Set 5. Fuel/Water Separator
2. Radiator 6. Fuel Tank
3. Switchgear 7. Vertical Discharge Chute
4. Silencer

40’ Containerized Power Module

Figure 15
1. Cat D/G Set 5. Fuel/Water Separator
2. Radiator 6. Fuel Tank
3. Switchgear 7. Partition Wall
4. Silencer

©2017 Caterpillar
Page 20 All rights reserved.
Engine Room Ventilation Application and Installation Guide

Drop-Over Enclosures system that is subject to the same


Drop-over enclosures are utilized requirements as previously outlined
for applications requiring some for single and dual engine
degree of weather protection or applications.
noise attenuation, when a standard Figure 16 illustrates a typical diesel
building is not available for generator set with a drop-over
housing. If the enclosed package is enclosure. While this example uses
cooled by an engine-mounted exhaust fans for ventilation, the
radiator, then the power module use of supply or exhaust fans
requirements outlined above apply. on a particular application will be
If the enclosed package is cooled by determined by the need to maintain
a remote radiator or other means, either a slight positive or negative
then the enclosure must be pressure inside the enclosure.
provided with a fixed ventilation
Drop-Over Enclosure Example

Figure 16

©2017 Caterpillar
All rights reserved. Page 21
Application and Installation Guide Engine Room Ventilation

Land SCR Rig Ventilation Systems Figure 18 shows an engine room


Land SCR rig engines equipped with designed to provide a combination
suction or blower fan radiators have of ventilation and engine/generator
airflow in excess of that required for air inlet ducting.
recommended engine ventilation. Ventilation is provided by the air
As long as radiator airflow is not discharged from the generator. In
obstructed, no further ventilation warm weather, the air source valve
requirements are needed. is positioned to provide outside air
Land rig engine installations with to the generator ventilation air inlet.
remote radiators or vertical discharge Air discharged from the generator
radiators should be inspected to exits through the roof vent door and
determine if sufficient engine open rear of base, providing engine
ventilation is provided. ventilation as a secondary result.
Figure 17 illustrates a land rig In cold weather, the air source valve
installation where ventilation will be positioned to provide partial
should be considered. Natural or total generator ventilation air
draft ventilation is almost completely from within engine room.
blocked by roofs, SCR house, If doors are added to rear of base,
tool room, and vertical discharge make sure that total enclosure is not
radiators. Warm weather operation airtight. This prevents pressurizing
may result in unacceptable engine engine room (reducing generator
and generator temperatures. ventilation airflow) when doors
are closed and air source valve is
Land Rig Engines Requiring positioned to provide outside air
Ventilation to generator.
An air duct size of 2.0 sq. ft.
(0.19 m2) is adequate for 3508,
3512, and 3516’s on up to 40 ft. (12.2
m) bases. The ducting to the air
cleaners from air source valve can
match the sizes of the optional air
cleaner inlet rectangular adapters.

Figure 17

©2017 Caterpillar
Page 22 All rights reserved.
Engine Room Ventilation Application and Installation Guide

Typical SCR Land Rig Ventilation

Figure 18

Marine Through-Hull Opening


Design Features of Through-Hull Ventilation
There must be openings for air to Openings
enter the engine room and
openings for air to leave the engine
room.
There should be an inlet for cool air
to enter, and a discharge for hot air
to leave, on each side of the hull. If
it is impractical to have two
separate openings per side, then
avoid having hot discharged air mix
with cool air entering the engine
room.
Features of the Marine Through-Hull
Opening are shown in Figure 19.
Opening ‘A’ should be sized to
maintain air velocity through the
openings below 610 m/min
(2000 ft/min).
Air Entering the Engine Room Figure 19
The engine room must have openings
for air to enter. The intake air opening If air is to enter the engine room from
should be located forward of, and, the accommodation spaces, good
if convenient, at a lower elevation, design practice will include sound
than the discharge. The air may deadening treatments for the
also enter from the accommodation opening(s) that conduct air from the
spaces, such as the galley and accommodation spaces to the
staterooms, or directly through the engine room. Heating and/or air
hull or deck. Engine room air inlets conditioning of accommodation
through accommodation spaces can spaces will be made much more
be troublesome.

©2017 Caterpillar
All rights reserved. Page 23
Application and Installation Guide Engine Room Ventilation

complicated if the engines must rely Additional Considerations


on that heated/cooled air for
combustion. Engine room air inlets Radiator Sizing
through accommodation spaces The frontal area of a radiator core
simplify the task of ensuring the should be as large as possible to
engine room inlet air is kept clean minimize restriction of airflow. Low
and free from rain or spray. radiator core restriction allows the
use of a larger slower turning fan.
Air Leaving the Engine Room
The through-hull or through-deck Radiators that are nearly square
openings for discharge of heated can provide the most effective fan
ventilation air should be located aft performance. They can be installed
of and higher than all intake openings with a minimum of unswept core
to minimize recirculation. area. As a rule, keep core thickness
to a minimum, with a maximum
The ventilation air opening, of 11 fins per 2.54 cm (1.0 in.).
discharging heated ventilation air, Increasing the number of fins per
should be located aft of, and at a cm (in.) does increase the radiator
higher elevation than the intake heat rejection for a given air velocity
air opening in order to minimize through the core, but also increases
recirculation. Cross- and following- the resistance to airflow.
winds make total elimination of
ventilation air recirculation nearly While the most economical initial cost
impossible. will be maximum core thickness
and fins per cm (in.), this involves
Marine Exhaust Ejector – Automatic higher fan horsepower with
Ventilation System consequent operating cost and
A relatively simple system utilizing noise penalties throughout the life of
an engine’s exhaust for ventilating the installation. In addition, a
an engine room can be arranged radiator with more fins per cm (in.) is
with most dry exhaust systems. much more susceptible to plugging
Ductwork can be installed around from insects and debris.
the engine exhaust piping in such a Radiator Fan Sizing
way that the exhaust flow creates As a rule, the most desirable fan is
a vacuum that is utilized to draw the one having the largest diameter and
hot air out of the upper part of the turning at the lowest speed to deliver
engine room. the required airflow. This also
An exhaust ejector system may results in lower fan noise and
draw out a quantity of ventilating air lowest fan horsepower draw from
approximately equal to the flow of the engine.
exhaust gas. This method has been Blade tip speed, while being only
used successfully in marine one of the elements of cooling fan
applications with small engine design, is an item easily changed
rooms and minimal ventilation by choosing an appropriate fan
requirements, and is discussed in drive ratio. An optimum fan tip
more detail in the Exhaust Systems velocity of 6096 cm/s (12,000 fpm) is
section of the Application and a good choice for meeting noise
Installation Guide. legislation requirements and

©2017 Caterpillar
Page 24 All rights reserved.
Engine Room Ventilation Application and Installation Guide

cooling system performance Refrigeration Equipment


requirements. The maximum When refrigeration equipment is
acceptable fan blade tip speed is installed within the engine room
7620 cm/s (15,000 fpm) for Cat fans. space, ensure its location is such
Moveable Louvers that any refrigerant leakage will not
If moveable louvers are used, be drawn into the engine’s
specify those which open in a combustion airflow. Refrigerant
positive manner. Pneumatic and chemicals, such as Freon and
electric-actuated louvers are ammonia, become highly corrosive
satisfactory. Refer to Figure 20. acids in engine combustion
chambers. This corrosion will cause
severe damage. Locating refrigerant
compressors near an engine room
air exhaust area is appropriate.
Exhaust Pipe Insulation
Long runs of hot, uninsulated exhaust
piping can dissipate more heat into
the engine room than all other
machinery surfaces combined.
Completely insulate all exhaust
piping within the engine room area.
All hot surfaces within the engine
Figure 20 room should be insulated if high air
temperatures are to be avoided. Do
not insulate engine turbochargers.
Louver Operation
Test With Doors and Windows
• Louvers which open from the Closed
discharge pressure of the Ventilating systems must be designed
radiator fan are discouraged. to provide safe working temperatures
Rain, ice and snow can render and adequate airflow when windows,
them inoperative within a short doors, and other normally closed
time and result in engine ports are secured for bad weather
overheating and shutdown. conditions. Test the ventilation
• Do not wait to activate the system fully secured for bad weather.
louvers until the engine warms This condition will reflect the most
up. In an emergency, the engine severe test of the ventilation
will be loaded immediately and system. Remember that a small
require full airflow. Open the room suction can exert a large
louvers as soon as the engine pressure on an entrance door
starts and install them to open or window.
fully in case of an emergency. Ducting Considerations
• Heat sensors needlessly Design all ducting to withstand
complicate the system and their extremes of vacuum or pressure
malfunction can reduce airflow and still maintain tight joints.
to the engine which can cause
shutdown.

©2017 Caterpillar
All rights reserved. Page 25
Application and Installation Guide Engine Room Ventilation

Provide inspection ports (or areas changes at the air cleaner inlet
that are easily disassembled) to reduce the moisture-holding
allow removal of foreign objects. capacity of the air. This results in
Inspection ports are especially moisture condensation and ice
important for standby applications. crystal formation. The ice buildup
reduces the airflow area and
Cold Weather Considerations increases the pressure differential
Air Cleaner Icing across the air cleaner. Eventually, a
Air cleaner icing can occur in plateau is reached where the pressure
saturated air environments when the differential remains constant even
dew point of the ambient air is near though ice buildup may continue.
freezing. Small disturbances to the Power loss and increased fuel
air such as velocity and pressure consumption will result during
these periods.

Typical Air Plenum Arrangement

Figure 21

©2017 Caterpillar
Page 26 All rights reserved.
Engine Room Ventilation Application and Installation Guide

Typical Warm Air Arrangement

Figure 22

Several techniques may be used building, and the engine is


to overcome air cleaner icing. One preconditioned with pre-heaters for
solution is to heat the intake air metal, water and oil temperatures
slightly. It is not necessary to heat of 0°C (32°F). Admitting engine
the air above freezing. The air requires room air must be done without the
only enough heat to be above the possibility of allowing dirt or debris
dew point. Heat can be supplied to into the air inlet system of the
the air cleaner housing by engine. Figure 12 and Figure 22,
recirculating warm engine room air; 10as indicated above, will also
Figure 12 shows how this can be apply here.
accomplished for a radiator cooled Boost Control
application. Figure 21 shows a A boost control valve is available for
typical air plenum arrangement for the 3600 diesel engine family for use
a marine application and Figure 22 in extremely cold ambient conditions,
illustrates the how a warm air 0°C (32°F). The valve is used to limit
arrangement may be configured. the air inlet manifold pressure
Extreme Cold during low air temperature conditions
Heated engine room air may be to maintain acceptable cylinder
required (for starting purposes only) pressure.
in applications at very cold ambient
temperatures, -25°C (-13°F). This
assumes combustion air is being
drawn from outside the engine

©2017 Caterpillar
All rights reserved. Page 27
www.cat.com/power-systems

LEBW4971-07
Information contained in this publication may be considered confidential. Discretion is recommended when distributing.
Materials and specifications are subject to change without notice.
©2017 Caterpillar. All rights reserved. CAT, CATERPILLAR, BUILT FOR IT, their respective logos, “Caterpillar Yellow”, the
“Power Edge” trade dress as well as corporate ad product identity used herein, are trademarks of Caterpillar and may
not be used without permission.

You might also like