Technical Workshop

Technical Service & Condition Monitoring


E T HS, Madrid, 10/11 October 2011

HV Testing @ E T HS

Energy Sector
Power Transmission
High Voltage Substations

Vogeler, René
E T HS MF B 12 Copyright© Siemens AG
E T HS – confidential Power Transmission High Voltage Substations
TEAM Technical Service and GIS Diagnostic

Team for HV-Test Sets BERLIN

calibration
consulting
invest planning
HV test plans René Vogeler Benjamin Lange E T HS
T: +49 30 386 21667 T: +49 30 386 27057
common planning M: +49 172 6678548 M: +49 173 7074563

logistics for rental


test accessories worldwide
maintenance
repair work
test adaptors Olaf Harnass Stefan Hagemeister
T: +49 30 386 22376 +49 30 386 28813
etc. M: +49 173 707 4557

Copyright© Siemens AG
Page 2 10 October 2011 E T HS – confidential Power Transmission High Voltage Substations
HV-Test Sets for on-site testing of GIS
Portfolio

Number HV-Test Set Parameter Transport LINK


TES510 20’ Container
1 Transformer
750kV 10 to.
TES100 20’ Container
1 Engine-Generator set
275kV, 90kVA 8,7 to
WRV0.35/140 10’Container
1 140kV, 0.35A, 900H, SF6 2,8 to.
Resonant Test WRV1.5/680 10’Container
10 (+ 2) System 680kV, 1,5A, 720H, SF6 4,2 to.

2 (with variable WRV3.6/680 20’ Container


Frequency) 680kV, 3,5A, 525H, oil 8,7 to

1 PowerVT-Feeder unit
3 Boxes á 40kg
235kV, 1500pF
IMP22,5 20’ Container
2 Impulse Generator
1550 kV OLI, 1100 kV OSI 4.5 to

Copyright© Siemens AG
Page 3 10 October 2011 E T HS – confidential Power Transmission High Voltage Substations
HV Test Sets for on-site testing of GIS
WRV 0.35/140

4,5 to

2,4 to - 47%

Standard NEW
Transport weight

3,2 m
1,9 m - 40%

Standard NEW
Dimensions of HV-Test set

WRV 0,35/140 G
Resonant test set for 72,5-kV-GIS New Documentation

Copyright© Siemens AG
Page 4 10 October 2011 E T HS – confidential Power Transmission High Voltage Substations
HV Test Sets for on-site testing of GIS
WRV 0.35/140

Specification
Max test voltage: 140 kV
Test cycle:
Condition1 60 kV, 15 min
Condition 2 90 kV, 3 min
HV-Test 120 kV, 1 min
PD-Level 90 kV, >1 min

Min Load: 0.35 nF


Max. Load: 4.97 nF
Test frequency: 50-200 Hz

Projects
SUI Poste de Croix 02/11
USA City of Glandale 04/11
NED Rotterdam 05/11
DEN Vesterhaching 07/11
WRV 0,35/140 G
NCA Koniambo Project 10/11
Resonant test set for 72,5-kV-GIS

Copyright© Siemens AG
Page 5 10 October 2011 E T HS – confidential Power Transmission High Voltage Substations
HV Test Sets for on-site testing of GIS
WRV 1.5/680

Copyright© Siemens AG
Page 6 10 October 2011 E T HS – confidential Power Transmission High Voltage Substations
HV Test Sets for on-site testing of GIS
WRV 3.6/680

Copyright© Siemens AG
Page 7 10 October 2011 E T HS – confidential Power Transmission High Voltage Substations
HV Test Sets for on-site testing of GIS
IMP 22,5

Copyright© Siemens AG
Page 8 10 October 2011 E T HS – confidential Power Transmission High Voltage Substations
HV Test Sets for on-site testing of GIS
Power VT up to 145-kV-GIS

Power VT is an enhanced
voltage transformer

PowerVT is a main part


of GIS and
is used as VT

Separate injection unit


for HV-Test
(reduced dimension &
reduced weight)

Princip of Resonant
(ftest = ca. 90 - 110 Hz)

Ctest = ca. 1,5 nF

Power VT is available
No assembling and SF6 work
for 72,5 / 145-kV-GIS for HV-test necessary

Copyright© Siemens AG
Page 9 10 October 2011 E T HS – confidential Power Transmission High Voltage Substations