CATALOGUE
GLOBAL
RANGE
1. MCCB
Moulded Case Circuit Breakers
low voltage
Product Overview
MCCB 15A - 125A FIXED 3P MCCB 150A - 250A FIXED 3P MCCB 250A - 400A FIXED 3P MCCB 500A - 1200A FIXED 3P
MCCB 37kA @ 415V 37kA @ 415V 50kA @ 415V 65kA @ 415V
Current Icu = Ics Icu = Ics Icu = Ics Icu = Ics
15 A G37D015
20 A G37D020
30 A G37D030
40 A G37D040
50 A G37D050
60 A G37D060
75 A G37D075
100 A G37D100
DIS DIS 125A FIXED 3P DIS 250A FIXED 3P DIS 400A FIXED 3P DIS 630A - 1200A FIXED 3P
CBI - X = 1.2 kA CBI - X = 1.2 kA CBI - X = 3.2 kA CBI - X = 6.4 kA/3.6 kA*
Current
125 A G37DN125
250 A F37DN250
400 A K50DN400
630 A L65DN630
800 A L65DN800
1200 A N65DN1200*
Calibrated for 40°C In=40 to 100 110.2% 109.8% 108.7% 107.0% 105.8% 104.3% 102.4% 100.0% 97.2% 94.0%
In=100 to 225 114.3% 113.2% 110.6% 107.5% 105.8% 104.0% 102.0% 100.0% 97.9% 95.6%
In=225 to 800 110.0% 109.0% 107.0% 105.0% 104.0% 103.0% 101.5% 100.0% 98.5% 97.0%
3990A806 Catalogue
Global Range Page 1.1 of 1.22
Standard MCCB
low voltage
MCCB Specifications
voltage, Uimp kV 8 8 8 8 6 6
Rated short circuit breaking capacity (Icu) kA (Sym)
AC 690V 8 8 8 10 x x
525/550V** 25 25 35 35 x x
480/500V 25 26 35 45 50 50
415/460V 37 37 50 65 65 65
380V 42 42 65 75 65 65
220/250V 85 85 75 85 100 100
DC (3P) 500V 20 20 20 20 x x
Service breaking capacity (%Icu), Ics 100** 100** 100** 100** 50 50
Category of use A A A A A A
Accessories
Electrical auxiliaries Auxiliary switch
Alarm switch
Shunt trip
Undervoltage trip
External accessories Direct rotary handle* x x
Insulation barrier
Rear connection*
Mechanical interlock* x x
Plug in device* x x
Dimensions (mm) W x H x D (3p) 90 x 155 x 60 105 x 165 x 60 140 x 257 x 109 210 x 280 x 109 220 x 400 x 105 220 x 400 x 105
Weight (kg) 3 pole 1 1.2 6.2 11.5 21 21
Note: Available or supplied as standard * Optional - Please specify x Not available * Contact CBI-elelctric for availability
** Icu = Ics 525,550 V
Catalogue 3990A806
Page 1.2 of 1.22 Global Range
Standard MCCB
low voltage
Switch Disconnector
480/500 V 25 26 35 45 50 50
415/460 V 37 37 50 65 65 65
380 V 42 42 65 75 65 65
220/250 V 85 85 75 85 100 100
CBI - X = Min kA 1.2 kA 1.2 kA 3.2 kA 6.4 kA 6.4 kA 3.6 kA
DC (3P) 500 V 20 20 20 20 x x
Category of use A A A A A A
Insulation barrier
Rear connection*
Mechanical interlock* x x
Plug in device* x x
Note: Available or supplied as standard Optional - Please specify x Not available * Contact CBI-elelctric for availability
3990A806 Catalogue
Global Range Page 1.3 of 1.22
Standard MCCB
low voltage
MCCB Dimensions
30 30 30
80
80
50
50
5
50
8.2
22 22
Moulded Case Circuit Breakers
16.5
16.5
155
155
135
100
135
100
50
50
37 37
4
8
8
60 30 58
10
10
3P 4P*
M8×14
8
9
16
8
18 24
10
M4 or Ø5 M4 or Ø5
132
52
52
132
30 30 92 122
3P 4P* 3P 4P*
Dimensions: mm
* Contact CBI for availability
3990A806 Catalogue
Global Range Page 1.4 of 1.22
Standard MCCB
low voltage
MCCB Dimensions
Insulation barrier
Insulation barrier
3P 4P*
3P 4P* 3P 4P*
Catalogue 3990A806
Page 1.5 of 1.22 Global Range
Standard MCCB
low voltage
MCCBMCCB
Dimensions
Dimensions
3P 4P*
"A" (Handle only) "B" (Handle and name plate) "C" (Handle, name plate & button)
M5 or Ø 6
Slot "A"
Slot "B"
Slot "C"
142(3p) 142(3p)
187(4p) 187(4p)
Catalogue 3990A806
Page 1.6 of 1.22 Global Range
Standard MCCB
low voltage
MCCB Dimensions
Connecting
Terminal details
"A" (Handle only) "B" (Handle and name plate) "C" (Handle, name plate & button)
Slot "A"
Slot "B"
Slot "C"
212(3p) 212(3p)
282(4p) 282(4p)
Dimensions: mm
* Contact CBI for availability
Catalogue 3990A806
Page 1.7 of 1.22 Global Range
Standard MCCB
low voltage
MCCB Dimensions
Auxiliary handle
Moulded Case Circuit Breakers
3P 4P*
or or
3P 4P* 3P 4P*
3990A806 Catalogue
Global Range Page 1.8 of 1.22
Standard MCCB
low voltage
Safety clearance
When installing a circuit breaker, safety clearances must be kept between the breaker and the panels,
bars and other protection devices installed nearby. These safety clearances are dependant on the
ultimate breaking capacity and are defined by tests carried out in accordance with standard IEC 60947-2.
When a short circuit interruption does occur, high temperatures and high pressures occur in the
circuit-breaker. In order to allow the pressure to be distributed and to prevent fire and arcing
of short circuit currents, safety clearances are required.
A
size
Frame B (mm)
Description
size
3990A806 Catalogue
Global Range Page 1.9 of 1.22
Standard MCCB
low voltage
MCCB environment
1. Ambient temperature within the range of -5ºC ~ +40ºC (However, the average per 24 hour period
Moulded Case Circuit Breakers
- If a standard circuit breaker is used at high temperatures exceeding 40ºC, it is advised to use the
Circuit Breaker according to the current correction for each level of ambient temperature in
catalogue. Refer to derating curve/s: Holds less load.
- If used in conditions of high humidity, the electric strength or electric performance may be degraded.
- Conduction, switch, trip or short circuit isolation functions normally at temperature of -20ºC.
- Storage in extreme cold areas are allowed in temperatures of -40ºC
- Refer to de-rating curve/s : Holds more load.
- It is highly recommended to use a dust cover or anti-humidty agent if the Circuit Breaker is
used in dusty and humid conditions.
- Long term humidity may corrode metal parts and prevent operation.
- Excessive vibration may cause a nuisance trip.
- If the Circuit Breaker is ON or OFF for a long time, it is recommended to manually switch the load
current on a regular basis.
- It is recommended to put the Circuit Breaker in sealed protection if corrosive gas is prevalent.
For assistance in regular examination of Moulded Case Circuit Breakers see the
“Moulded Case Circuit Breaker Deterioration Diagnostic Table” on the next page
Catalogue 3990A806
Page 1.10 of 1.22 Global Range
Standard MCCB
low voltage
Sample No.
Installation location
Model, number of poles, rating
Specifications
Accessories
Serial number
Installation date
Item Factor Condition Points
1. Age of use x3 Less than 10 years 1
Less than 15 years 2
3990A806 Catalogue
Global Range Page 1.11 of 1.22
Standard MCCB
low voltage
Characteristics curves
Min.
Max.
Operational time
Moulded Case Circuit Breakers
Rated current
Ambient temp 40ºC
Min.
Max.
Operational time
Rated current
3990A806 Catalogue
Global Range Page 1.12 of 1.22
Standard MCCB
low voltage
Characteristics curves
F37D MCCB
Min.
Compensation curves
Rated current: 150~225A
Max.
150
Rated current compensation rate (%)
Operational time
50
0 10 20 30 40 50
Rated current
150
120
100
80
60
40
Min.
20
100
10
8
6
4
50 2
0 10 20 30 40 50 Max.
1
Ambient temp 40ºC 40
Operational time
20
10
8
6 Min.
4
2
Sec.
1
0.8
0.6
0.4
Magnetic trip
0.2
range
(960~1440%)
0.1
0.08
0.06
0.04
Max. breaking time
0.02
0.01
1 1.5 2 3 4 5 6 7 8 9 10 15 20 30 40 50 60 80 100
Rated current
Catalogue 3990A806
Page 1.13 of 1.22 Global Range
Standard MCCB
low voltage
Characteristics curves
Min.
Max.
Operational time
Moulded Case Circuit Breakers
Compensation curves
Min.
Rated current compensation rate (%)
100
Magnetic trip range
50
0 10 20 30 40 50
240
180
120
60
40
100
Min.
20
10
8
6
50 4
0 10 20 30 40 50 Max.
2
20
10
8
6
Min.
4
2
Sec.
1
0.8
0.6
0.4
0.2
Magnetic trip range
0.1
0.08 (800~1200%)
0.06
0.04 Max. breaking time
0.02
0.01
1 1.25 2 3 4 5 6 7 8 9 10 15 20 30 40 50 70 100
Rated current
3990A806 Catalogue
Global Range Page 1.14 of 1.22
Standard MCCB
low voltage
Characteristics curves
N65D MCCB
Rated current: 1000~1200A
Min.
Compensation curves
Max.
Rated current
Catalogue 3990A806
Page 1.15 of 1.22 Global Range
Standard MCCB
Moulded Case Circuit Breakers
3990A806
Global Range
Standard MCCB
Type G37D 15 - 125 A F37D 150 - 250 A K50D 250 - 400 A L65D 500 - 800 A
No of Poles 3 3 3 3 3 3 3 3 3 3 3 3 3 3
BUSBAR
RATING
Fault 15 25 35 15 25 35 15 25 35 50 25 35 50 kA RMS
Catalogue
Cascading Table
65
Level kA
QF QF QF QF
G37D/ G37D/ G37D/ G37D/ G37D/ G37D/ G37D/
20 F37D F37D F37D F37D F37D F37D F37D
Standard MCCB
Global Range
3990A806
Page 1.17 of 1.22
CBI-Electric MCCB Type Transfer Switch wiring diagram
Catalogue
NORMAL SUPPLY EMERGENCY SUPPLY
N L3 L2 L1 L1 L2 L3 N
PIN NO. DESCRIPTION
ø ø ø ø ø ø ø ø
CN1-7
CN1-5
CN1-6
CN1-8
CN1-9
CN1-4
CN1-1 Normal power L1 voltage output
CN1-3
CN1-2
CN1-1
CN1-11
CN1-10
CN1-12
CN1-2 Normal power L3 voltage output
CN1-3 Normal Power L2 voltage output
YELLOW
PURPLE
GREEN
WHITE
GRAY
BLUE
CN1-4 Emergency ON motor AC power input
CN1-5 Normal ON signal output
RED / WHITE
ORANGE
BLACK
BROWN
Normal ON motor AC power input
PINK
CN1-6
RED
CN1-7 Normal ON motor AC power input
NLS ELS
CN1-8 Emergency ON signal output
M 220V
CN1-9 Emergency ON motor AC power input
CN-10 Emergency power L2 voltage output NLS ELS
CN1-11 Emergency power L3 voltage output
CN1-12 Emergency power L1 voltage output
#NLS>>Normal Auxiliary Switch
#ELS>>Emergency Auxiliary Switch CB1 CB2
low voltage
10 7 4 1
11 8 5 2
12 9 6 3
12P AMP Housing
(Neutral Phase may be optional) ø ø ø ø
L1 L2 L3 N
LOAD
low voltage
Motor specifications
200 - 240 VAC (50 / 60Hz)
Ui AC 750 V
Ue 220 V
3990A806 Catalogue
Global Range Page 1.18 of 1.22
Standard MCCB
low voltage
MCCB Accessories
AX
Undervoltage
trip
AL
Left-hand seat Right-hand seat
Alarm Switch
AX*
Auxiliary
Switch
AX+AL
A*
Alarm
Combination switch Switch
* Non standard: Contact CBI for availability Option of connecting SHT or UVT
or AX or AL or AX+AL
Maximum possibilities
Position Type GD FD
3p 3p
AX 1 1
Left-hand
AL 1 1
seat
AX+AL 1 1
AX 1 1
Right-hand AL 1 1
seat AX+AL 1 1
SHT/UVT 1 1
Catalogue 3990A806
Page 1.19 of 1.22 Global Range
Standard MCCB
low voltage
MCCB Accessories
AL AL*
*SHT SHT
*UVT UVT
AX AX*
Option of connecting
AX or AL or AX+AL
Maximum possibilities
KD/LD
Position Type
400~800 A
AX 2
Left-hand
AL 2
seat
SHT/UVT * 1
AX * 2
Right-hand
AL * 2
seat
SHT/UVT 1
3990A806 Catalogue
Global Range Page 1.20 of 1.22
Standard MCCB
low voltage
MCCB Accessories
Catalogue 3990A806
Page 1.21 of 1.22 Global Range
Standard MCCB
low voltage
MCCB Accessories
The undervoltage release automatically opens a circuit breaker when voltage drops to a value ranging between
20% to 70% of the line voltage. The operation is instantaneous, and after tripping, the circuit breaker cannot be
re-closed again until the voltage returns to 85% of line voltage.
Continuously energized, the undervoltage release must be functioning before the circuit breaker can be closed.
AC 525~550*
* 550 V in process of being tested
Terminal numbering
Auxiliary Switch (AX) Alarm Switch (AL) Shunt Trip (SHT) Undervoltage trip (UVT)
3990A806 Catalogue
Global Range Page 1.22 of 1.22
Standard MCCB