Piston Booklet 2014: The Guide For Refrigeration Experts
Piston Booklet 2014: The Guide For Refrigeration Experts
A-222-1
Umschlag_Innenseiten.qxd
Headquaters:
22.11.2013
BITZER Austria GmbH Austria Tel +43 316 58 27 67-0 Fax +43 316 58 27 67-67 office@bitzer.at
BITZER Benelux B.V.B.A. Belgium Tel +32 11 325353 Fax +32 11 325363 info@bitzer.be
BITZER Compressores Ltda. Brazil Tel +55 11 46 17 91-00 Fax +55 11 46 17 91-28 marketing@bitzer.com.br
BITZER Canada Inc. Canada Tel +1-514-697-3363 Fax +1-514-697-9768 sales@bitzer.ca
11:18 Uhr
BITZER Compressors (Beijing) Ltd. China Tel +86 10 6781-9000 Fax +86 10 6957-4544 info@bitzer.cn
BITZER Refrigeration Technology China Tel +86 10 67 81-90 00 Fax +86 10 67 81-90 02 info@bitzer.cn
BITZER Columbia S.A.S Columbia Tel +1 770 503 9226 Fax +1 770 503 9440 columbia@bitzerus.com
BITZER Middle East Dubai, U.A.E. Tel +971 4 221-8780 Fax +971 4 221-9905 mail@bitzer.ae
Seite 1
BITZER France S.A.R.L. France Tel +33 4 721486-86 Fax +33 4 721486-87 bitzer@bitzer.fr
S. R. S. BITZER France Tel +33 (0) 1 74591010 Fax +33 (0) 1 74591019 contact@bybitzer.fr
Umschlag_Innenseiten.qxd
BITZER Refrigeration Asia Limited Hong Kong Tel +852 286802-06 Fax +852 286802-99 contactus@bitzerasia.com
BITZER India Private Ltd. India Tel +91 22 27 60 17 30 Fax +9122 27 60 17 40 office@bitzer.in
PT. BITZER Compressors Indonesia Tel +62 21 867-1041 Fax +62 21 867-0386 indonesia@bitzer.co.id
BITZER Italia S.R.L. Italy Tel +39 0444 96 20 20 Fax +39 0444 29 18 48 bitzer@bitzer.it
BITZER Japan K.K. Japan Tel +81 6 6873 8555 Fax +81 6 6873 8556 info@bitzer.jp
BITZER (South East Asia) SDN. BHD. Malaysia Tel +60 3 7806-1220 Fax +60 3 7806-5122 kwan.cw@bitzerasia.com
BITZER México, S. de R.L. de C.V. Mexico Tel +52 81 1522-4500 Fax +52 81 1522-4505 ventas@bitzermexico.com
22.11.2013
BITZER New Zealand New Zealand Tel +64 9 4152030 Fax +64 9 4152031 steve.miller@bitzer.co.nz
BITZER Compressores para Frio Portugal Tel +351 272 34 85 50 Fax +351 272 32 39 61 mail@bitzer.pt
BITZER CIS LLC Russia Tel +7 495 6284178 Fax +7 495 6070738 center@bitzer.ru
BITZER Refrigeration Asia Limited Singapore Tel +65 6220-4942 Fax +65 6220-4794 contactus@bitzerasia.com
11:18 Uhr
BITZER Kühlmaschinenbau (S.A.) South Africa Tel +27 21 51046-80 Fax +27 21 510-8368 info@bitzer.co.za
BITZER Korea Representative Office South Korea Tel +82 31 452 3931 Fax +82 31 452 3930 byun.jh@bitzerasia.com
BITZER UK UK Tel +44 845 2303-007 Fax +44 845 2303-006 sales@bitzeruk.com
BITZER Scroll, Inc. U.S.A. Tel +1 315 463-21 01 Fax +1 315 463-21 07 sales@bitzerus.com
Seite 2
BITZER US Inc. U.S.A. Tel +1 770 503-9226 Fax +1 770 503-9440 sales@bitzerus.com
BITZER Vietnam Representative Office Vietnam Tel +84 8 3822 7024 Fax +84 8 3822 7026 truong.ngo@bitzerasia.com
Content
Calendar 2014 / 2015 4
1 Safety and Warnings 6
2 Compressor Data 10
2.1 Model designation 10
2.2 Technical data 12
2.3 Application limits at full load 34
2.4 Dimensional drawings and connections 50
2.5 Replacement table old / current models 106
2.6 Compressors data for previous models 110
3 Electrical Connections 126
3.1 Circuit diagrams in the terminal box 126
3.2 Motor codes 137
3.3 Instructions for the selection of
contactors, cables and fuses 141
3.4 Motor protection devices,
overview voltage variations 146
3.5 Integration into electric circuit 148
4 Accessories 162
4.1 Oil monitoring (Delta-PII, OLC-K1) 162
4.2 Crankcase Heater 182
4.3 Start unloading 188
4.4 CRII –System
capacity control for NEW ECOLINE compressors 193
4.5 Capacity control for reciprocating compressors
(previous models) 211
4.6 Additional cooling 223
5 Lubricants and Refrigerants 230
5.1 Overview refrigeration oils 230
5.2 The temperature glide 232
6 Application Advices 236
6.1 Compressor mounting 236
6.2 Switching frequency 245
6.3 Special recommendations for safe
compressor and plant operation 246
6.4 Vibrations 248
6.5 Operating temperatures 253
6.6 Heat transmission of semi-hermetic
reciprocating compressors 254
6.7 Tightening Torques 255
7 Explanations and Application Limits 258
8 Overview Technical Documentation 262
9 Measurement Protocol 268
A_222_1_3-32.qxp
4
JANUARY FEBRUARY MARCH APRIL MAY JUNE JULY AUGUST SEPTEMBER OCTOBER NOVEMBER DECEMBER
Calendar 2014
1 WE 1 SA 1 SA 1 TH 1 TH 1 SU 1 TH 1 FR 1 MO 36 1 WE 1 SA 1 MO 49
2 TH 1 2 SU 2 SU 2 WE 2 FR 2 MO 23 2 WE 2 SA 2 TH 2 TH 2 SU 2 TH
3 FR 3 MO 6 3 MO 10 3 TH 3 SA 3 TH 3 TH 3 SU 3 WE 3 FR 3 MO 45 3 WE
4 SA 4 TH 4 TH 4 FR 4 SU 4 WE 4 FR 4 MO 32 4 TH 4 SA 4 TH 4 TH
5 SU 5 WE 5 WE 5 SA 5 MO 19 5 TH 5 SA 5 TH 5 FR 5 SU 5 WE 5 FR
6 MO 6 TH 6 TH 6 SU 6 TH 6 FR 6 SU 6 WE 6 SA 6 MO 41 6 TH 6 SA
7 TH 2 7 FR 7 FR 7 MO 15 7 WE 7 SA 7 MO 28 7 TH 7 SU 7 TH 7 FR 7 SU
8 WE 8 SA 8 SA 8 TH 8 TH 8 SU 8 TH 8 FR 8 MO 37 8 WE 8 SA 8 MO 50
22.11.2013
9 TH 9 SU 9 SU 9 WE 9 FR 9 MO 9 WE 9 SA 9 TH 9 TH 9 SU 9 TH
10 FR 10 MO 7 10 MO 11 10 TH 10 SA 10 TH 24 10 TH 10 SU 10 WE 10 FR 10 MO 46 10 WE
11 SA 11 TH 11 TH 11 FR 11 SU 11 WE 11 FR 11 MO 33 11 TH 11 SA 11 TH 11 TH
12 SU 12 WE 12 WE 12 SA 12 MO 20 12 TH 12 SA 12 TH 12 FR 12 SU 12 WE 12 FR
www.bitzer.de
13 MO 3 13 TH 13 TH 13 SU 13 TH 13 FR 13 SU 13 WE 13 SA 13 MO 42 13 TH 13 SA
CHILLVENTA 2014
14 TH 14 FR 14 FR 14 MO 16 14 WE 14 SA 14 MO 29 14 TH 14 SU 14 TH 14 FR 14 SU
15 WE 15 SA 15 SA 15 TH 15 TH 15 SU 15 TH 15 FR 15 MO 38 15 WE 15 SA 15 MO 51
16 TH 16 SU 16 SU 16 WE 16 FR 16 MO 25 16 WE 16 SA 16 TH 16 TH 16 SU 16 TH
11:56 Uhr
17 FR 17 MO 8 17 MO 12 17 TH 17 SA 17 TH 17 TH 17 SU 17 WE 17 FR 17 MO 47 17 WE
18 SA 18 TH 18 TH 18 FR 18 SU 18 WE 18 FR 18 MO 34 18 TH 18 SA 18 TH 18 TH
19 SU 19 WE 19 WE 19 SA 19 MO 21 19 TH 19 SA 19 TH 19 FR 19 SU 19 WE 19 FR
20 MO 4 20 TH 20 TH 20 SU 20 TH 20 FR 20 SU 20 WE 20 SA 20 MO 43 20 TH 20 SA
21 TH 21 FR 21 FR 21 MO 21 WE 21 SA 21 MO 30 21 TH 21 SU 21 TH 21 FR 21 SU
22 WE 22 SA 22 SA 22 TH 17 22 TH 22 SU 22 TH 22 FR 22 MO 39 22 WE 22 SA 22 MO 52
23 TH 23 SU 23 SU 23 WE 23 FR 23 MO 26 23 WE 23 SA 23 TH 23 TH 23 SU 23 TH
24 FR 24 MO 9 24 MO 13 24 TH 24 SA 24 TH 24 TH 24 SU 24 WE 24 FR 24 MO 48 24 WE
Seite 4
25 SA 25 TH 25 TH 25 FR 25 SU 25 WE 25 FR 25 MO 35 25 TH 25 SA 25 TH 25 TH
26 SU 26 We 26 WE 26 SA 26 MO 22 26 TH 26 SA 26 TH 26 FR 26 SU 26 WE 26 FR
27 MO 5 27 TH 27 TH 27 SU 27 TH 27 FR 27 SU 27 WE 27 SA 27 MO 44 27 TH 27 SA
A-222-1
28 TH 28 FR 28 FR 28 MO 18 28 WE 28 SA 28 MO 31 28 TH 28 SU 28 TH 28 FR 28 SU
29 WE 29 SA 29 TH 29 TH 29 SU 29 TH 29 FR 29 MO 40 29 WE 29 SA 29 MO 53
30 TH 30 SU 30 WE 30 FR 30 MO 27 30 WE 30 SA 30 TH 30 TH 30 SU 30 TH
31 FR 31 MO 14 31 SA 31 TH 31 SU 31 FR 31 WE
A_222_1_3-32.qxp
A-222-1
JANUARY FEBRUARY MARCH APRIL MAy JUNE JULY AUGUST SEPTEMBER OCTOBER NOVEMBER DECEMBER
1 TH 1 SU 1 SU 1 WE 1 FR 1 MO 23 1 WE 1 SA 1 TH 1 TH 1 SU 1 TH
2 FR 1 2 MO 6 2 MO 10 2 TH 2 SA 2 TH 2 TH 2 SU 2 WE 2 FR 2 MO 45 2 WE
3 SA 3 TH 3 TH 3 FR 3 SU 3 WE 3 FR 3 MO 32 3 TH 3 SA 3 TH 3 TH
4 SU 4 WE 4 WE 4 SA 4 MO 19 4 TH 4 SA 4 TH 4 FR 4 SU 4 WE 4 FR
5 MO 2 5 TH 5 TH 5 SU 5 TH 5 FR 5 SU 5 WE 5 SA 5 MO 41 5 TH 5 SA
6 TH 6 FR 6 FR 6 MO 6 WE 6 SA 6 MO 28 6 TH 6 SU 6 TH 6 FR 6 SU
22.11.2013
7 WE 7 SA 7 SA 7 TH 15 7 TH 7 SU 7 TH 7 FR 7 MO 37 7 WE 7 SA 7 MO 50
8 TH 8 SU 8 SU 8 WE 8 FR 8 MO 24 8 WE 8 SA 8 TH 8 TH 8 SU 8 TH
9 FR 9 MO 7 9 MO 11 9 TH 9 SA 9 TH 9 TH 9 SU 9 WE 9 FR 9 MO 46 9 WE
10 SA 10 TH 10 TH 10 FR 10 SU 10 WE 10 FR 10 MO 33 10 TH 10 SA 10 TH 10 TH
11 SU 11 WE 11 WE 11 SA 11 MO 20 11 TH 11 SA 11 TH 11 FR 11 SU 11 WE 11 FR
12 MO 3 12 TH 12 TH 12 SU 12 TH 12 FR 12 SU 12 WE 12 SA 12 MO 42 12 TH 12 SA
www.bitzer.de
13 TH 13 FR 13 FR 13 MO 16 13 WE 13 SA 13 MO 29 13 TH 13 SU 13 TH 13 FR 13 SU
14 WE 14 SA 14 SA 14 TH 14 TH 14 SU 14 TH 14 FR 14 MO 38 14 WE 14 SA 14 MO 51
11:56 Uhr
15 TH 15 SU 15 SU 15 WE 15 FR 15 MO 25 15 WE 15 SA 15 TH 15 TH 15 SU 15 TH
16 FR 16 MO 8 16 MO 12 16 TH 16 SA 16 TH 16 TH 16 SU 16 WE 16 FR 16 MO 47 16 WE
17 SA 17 TH 17 TH 17 FR 17 SU 17 WE 17 FR 17 MO 34 17 TH 17 SA 17 TH 17 TH
18 SU 18 WE 18 WE 18 SA 18 MO 21 18 TH 18 SA 18 TH 18 FR 18 SU 18 WE 18 FR
19 MO 4 19 TH 19 TH 19 SU 19 TH 19 FR 19 SU 19 WE 19 SA 19 MO 43 19 TH 19 SA
20 TH 20 FR 20 FR 20 MO 17 20 WE 20 SA 20 MO 30 20 TH 20 SU 20 TH 20 FR 20 SU
21 WE 21 SA 21 SA 21 TH 21 TH 21 SU 21 TH 21 FR 21 MO 39 21 WE 21 SA 21 MO 52
Calendar 2015
22 TH 22 SU 22 SU 22 WE 22 FR 22 MO 26 22 WE 22 SA 22 TH 22 TH 22 SU 22 TH
Seite 5
23 FR 23 MO 9 23 MO 13 23 TH 23 SA 23 TH 23 TH 23 SU 23 WE 23 FR 23 MO 48 23 WE
24 SA 24 TH 24 TH 24 FR 24 SU 24 WE 24 FR 24 MO 35 24 TH 24 SA 24 TH 24 TH
25 SU 25 We 25 WE 25 SA 25 MO 25 TH 25 SA 25 TH 25 FR 25 SU 25 WE 25 FR
26 MO 5 26 TH 26 TH 26 SU 26 TH 22 26 FR 26 SU 26 WE 26 SA 26 MO 44 26 TH 26 SA
27 TH 27 FR 27 FR 27 MO 18 27 WE 27 SA 27 MO 31 27 TH 27 SU 27 TH 27 FR 27 SU
28 WE 28 SA 28 SA 28 TH 28 TH 28 SU 28 TH 28 FR 28 MO 40 28 WE 28 SA 28 MO 1
29 TH 29 SU 29 WE 29 FR 29 MO 27 29 WE 29 SA 29 TH 29 TH 29 SU 29 TH
30 FR 30 MO 14 30 TH 30 SA 30 TH 30 TH 30 SU 30 WE 30 FR 30 MO 49 30 WE
31 SA 31 TH 31 SU 31 FR 31 MO 36 31 SA 31 TH
5
A_222_1_3-32.qxp 22.11.2013 11:56 Uhr Seite 6
Residual hazards
Certain residual hazards from the compressors are
unavoidable.
All persons working on these units must therefore read
the Operating Instructions carefully!
Absolute validity have:
• specific safety regulations and standards
(e. g. EN 378, EN 60204 and EN 60335),
• generally acknowledged safety standards,
• EU directives,
• national regulations.
6 www.bitzer.de A-222-1
A_222_1_3-32.qxp 22.11.2013 11:56 Uhr Seite 7
Safety references
are instructions intended to prevent hazards.
Safety instructions must be stringently observed!
Attention!
Caution!
Instructions on preventing a possible minor
hazard to persons.
Warning!
Instructions on preventing a possible severe
hazard to persons.
Danger!
Instructions on preventing an immediate risk
of severe hazard to persons.
A-222-1 www.bitzer.de 7
A_222_1_3-32.qxp 22.11.2013 11:56 Uhr Seite 8
Caution!
During operation surface temperatures
exceeding 60°C or below 0°C can be reached.
Serious burnings possible.
Lock and mark accessible sectors.
Before working on the compressor:
Switch off and let cool down.
8 www.bitzer.de A-222-1
A_222_1_3-32.qxp 22.11.2013 11:56 Uhr Seite 9
NOTES
A-222-1 www.bitzer.de 9
10
1 2 3 4 5 6 7 8 9 10 11 12
2 D E S - 2 Y -40S
2 D C - 3 .2 Y -40P
2 D E S - 3 F. 1 Y -40P
A_222_1_3-32.qxp
4 E E S - 4 Y -40S
4 D E S P - 7 P -40S
4 P E S - 12 F. 3 Y -40P 2 Compressor Data
4 D SL - 7 K -40S
4 H T C - 20 K -40P
6 J E - 33 Y -40S
www.bitzer.de
6 G E P - 40 P -40P
11:56 Uhr
6 F - 50 .2 -40P
2 2 D C - 14 .2 Y -40S
Semi-hermetic reciprocating compressors
4 4 P C S - 30 .2 Y -40P
6 6 G E - 80 Y -40P
Seite 10
S 6 G - 25 .2 Y -40P
S 6 6 F - 60 .2 -40P
A-222-1
A_222_1_3-32.qxp
A-222-1
Legend Explanation
1 Stages w/o = 1-stage, S = 2-stage
2 Number of cylinders 2, 4, 6, 8 (double with tandem:
66 = 12 cylinder)
22.11.2013
3 Identification letter for bore x stroke K, E, D, C, V, T, P, N, J, H, G, F
4 Identification letter for special series D = R410A, E = ECOLINE,
of compressors SL = CO2 subcritical, T = CO2 transcritical
5 Identification letter for Octagon® series C
www.bitzer.de
11:56 Uhr
lubrication
7 Code for Propane execution P
8 Code for motor size Tandem = 2 x single compressor
9 Series code .2 = .2 generation,
F = integrated frequency inverter
Seite 11
10 Code for frequency inverter size 1, 3, 4
11 Identification letter for oil charge w/o = B5.2, Y = BSE32 (option BSE55),
K = BSE60K/BSE85K, P = SHC226E,
(P for R290, R1270)
12 Motor code
11
A_222_1_3-32.qxp 22.11.2013 11:56 Uhr Seite 12
2 Compressor Data
2HES-1(Y) 2 44
6,51 2 1,0 12 1/ 16 5/
2 8
2HES-2(Y) 1 45
2GES-2(Y) 1 7,58 2 1,0 45 12 1/ 16 5/
2 8
2FES-2(Y) 2 45
9,54 2 1,0 12 1/ 16 5/
2 8
2FES-3(Y) 1 47
2EES-2(Y) 2 68
11,4 2 1,5 16 5/ 22 7/
8 8
2EES-3(Y) 1 71
2DES-2(Y) 2 68
13,4 2 1,5 16 5/ 22 7/
8 8
2DES-3(Y) 1 71
2CES-3(Y) 2 70
16,2 2 1,5 16 5/ 22 7/
8 8
2CES-4(Y) 1 70
4FES-3(Y) 2 82
18,1 4 2,0 16 5/ 22 7/
8 8
4FES-5(Y) 1 86
4EES-4(Y) 2 84
22,7 4 2,0 16 5/ 28 11/8
8
4EES-6(Y) 1 86
4DES-5(Y) 2 86
26,8 4 2,0 22 7/ 28 11/8
8
4DES-7(Y) 1 89
4CES-6(Y) 2 91
32,5 4 2,0 22 7/ 28 11/8
8
4CES-9(Y) 1 91
12 www.bitzer.de A-222-1
A_222_1_3-32.qxp 22.11.2013 11:56 Uhr Seite 13
2 Compressor Data
Electrical data
CR Motor Max. Max.
–Steps– connection operating current power consumption
2
%1 Volt Amp. 3
kW 3
4,9/2,8 1,5
6,4/3,7 1,9
6,7/3,8 2,0
7,8/4,5 2,4
8,7/5,0 2,7
9,2/5,3 2,9
– 10,7/6,1 3,4
6/Y 10,4/6,0 3,3
13,4/7,5 3,8
220..2406/ 13,4/7,5 4,0
380..420Y/3/50 15,0/8,6 4,6
265..2906/ 15,8/9,1 5,0
440..480Y/3/60 17,4/10,0 5,6
16,5/9,5 5,3
18,8/10,8 5,8
21,2/12,2 6,9
23,7/13,6 7,6
50
25,2/14,5 8,1
28,7/16,5 8,9
30,8/17,7 9,7
35,1/20,2 11,3
A-222-1 www.bitzer.de 13
A_222_1_3-32.qxp 22.11.2013 11:56 Uhr Seite 14
2 Compressor Data
4VES-6Y 3 129
4VES-7(Y) 2 34,7 4 2,6 129 22 7/
8 28 11/8
4VES-10(Y) 1 139
4TES-8Y 3 134
4TES-9(Y) 2 41,3 4 2,6 134 28 11/8 35 13/8
4TES-12(Y) 1 141
4PES-10Y 3 139 35 13/8
4PES-12(Y) 2 48,5 4 2,6 139 28 11/8 35 13/8
4PES-15(Y) 1 147 42 15/8
4NES-12Y 3 141 35 13/8
4NES-14(Y) 2 56,2 4 2,6 141 28 11/8 35 13/8
4NES-20(Y) 1 150 42 15/8
4JE-13Y 3 179
4JE-15(Y) 2 63,5 4 4,0 190 28 11/8 42 15/8
4JE-22(Y) 1 190
4HE-15Y 3 183 42 15/8
4HE-18(Y) 2 73,7 4 4,0 190 28 11/8 42 15/8
4HE-25(Y) 1 194 54 21/8
4GE-20Y 3 192
4GE-23(Y) 2 84,6 4 4,5 192 28 11/8 54 21/8
4GE-30(Y) 1 206
4FE-25Y 3 196
4FE-28(Y) 2 101,8 4 4,5 207 28 11/8 54 21/8
4FE-35(Y) 1 207
14 www.bitzer.de A-222-1
A_222_1_3-32.qxp 22.11.2013 11:56 Uhr Seite 15
2 Compressor Data
Electrical data
CR Motor Max. Max. Selection
–Steps– connection operating power con- current for
current sumption 70 Hz FI
operation
2
%1 Volt Amp. 3 kW 3
Amp. 5
9,4 6 14,8
16,6 11
19,9 12
11,4 7 17,6
19,9 13
25,1 14
12,9 8 21,0
22,7 14
28,2 16
14,9 9 25,2
PW 4 26,6 17
33,2 19
50
380..420YY/3/50 18,8 11 28,6
440..480YY/3/60 30,8 19
37,2 21
21,4 13 32,5
36,7 22
44 25
24,6 16 38,1
43,9 27
51,2 28
30,5 19 46,6
52,8 31
62,1 35
A-222-1 www.bitzer.de 15
A_222_1_3-32.qxp 22.11.2013 11:56 Uhr Seite 16
2 Compressor Data
6JE-22Y 3 213
6JE-25(Y) 2 95,3 6 4,75 228 35 13/8 54 21/8
6JE-33(Y) 1 231
6HE-25Y 3 224
6HE-28(Y) 2 110,5 6 4,75 228 35 13/8 54 21/8
6HE-35(Y) 1 235
6GE-30Y 3 228
6GE-34(Y) 2 126,8 6 4,75 228 35 13/8 54 21/8
6GE-40(Y) 1 238
6FE-40Y 3 238
6FE-44(Y) 2 151,6 6 4,75 241 42 15/8 54 21/8
6FE-50(Y) 1 241
8GE-50(Y) 2 342
185 8 5,0 42 15/8 76 31/8
8GE-60(Y) 1 350
8FE-60(Y) 2 361
221 8 5,0 54 21/8 76 31/8
8FE-70(Y) 1 374
16 www.bitzer.de A-222-1
A_222_1_3-32.qxp 22.11.2013 11:56 Uhr Seite 17
2 Compressor Data
Electrical data
CR Motor Max. Max. Selection
–Steps– connection operating power con- current for
current sumption 70 Hz FI
operation
1 2
% Volt Amp. 3 kW 3
Amp. 5
26,6 16 42,4
46,4 27
53,2 30
31,3 19 48,2
380..420YY/3/50 53,2 33
66
440..480YY/3/60 64,4 36
altern.
38 23 58,4
33
4
PW 65,5 40
73,9 42
48,5 27 75,5
83,2 46
380..400YY/3/50 96,2 51
440..460YY/3/60
92 51
75 PW 4
113 63
altern. 380..42066/3/50
440..48066/3/60 113 63
50
139 78
A-222-1 www.bitzer.de 17
A_222_1_3-32.qxp 22.11.2013 11:56 Uhr Seite 18
2 Compressor Data
Explanations
18 www.bitzer.de A-222-1
A_222_1_3-32.qxp 22.11.2013 11:56 Uhr Seite 19
2 Compressor Data
NOTES
A-222-1 www.bitzer.de 19
A_222_1_3-32.qxp 22.11.2013 11:56 Uhr Seite 20
2 Compressor Data
m3/h dm3 kg 1
20 www.bitzer.de A-222-1
A_222_1_3-32.qxp 22.11.2013 11:56 Uhr Seite 21
2 Compressor Data
2
Pipe connections Electrical data
DL SL FI Max. Max.
Discharge line Suction line connection operating power con-
current for sumption
380V/3/50Hz compressor
mm inch mm inch Volt Amp. kW
16 5/ 22 7/ 15 9
8 8
16 5/ 28 11/8 20 11
8
16 5/ 28 11/8 22 12
8
22 7/ 35 13/8 22 12
8
380..480 V/3/50 Hz
380..480 V/3/60 Hz
22 7/ 35 13/8 28 17
8
22 7/ 35 13/8 22 12
8
22 7/ 35 13/8 34 21
8
28 11/8 42 15/8 23 14
28 11/8 42 15/8 35 22
28 11/8 42 15/8 26 16
28 11/8 42 15/8 42 26
A-222-1 www.bitzer.de 21
A_222_1_3-32.qxp 22.11.2013 11:56 Uhr Seite 22
2 Compressor Data
m3/h dm3 kg 1
22 www.bitzer.de A-222-1
A_222_1_3-32.qxp 22.11.2013 11:56 Uhr Seite 23
2 Compressor Data
2
Pipe connections Electrical data
DL SL FI Max. Max.
Discharge line Suction line connection operating power con-
current for sumption
380V/3/50Hz compressor
mm inch mm inch Volt
380..480 V/3/50 Hz
Amp. kW
28 11/8 42 15/8 380..480 V/3/60 Hz 23 14
28 11/8 42 15/8 48 30
28 11/8 42 15/8 27 17
28 11/8 42 15/8 55 36
Frequency range
2DES-3.F1Y: 30 .. 87 Hz
4FES-5.F1Y .. 4NES-20.F4Y: 25 .. 87 Hz
Explanations
1 Including frequency inverter
A-222-1 www.bitzer.de 23
A_222_1_3-32.qxp 22.11.2013 11:56 Uhr Seite 24
2 Compressor Data
m3/h dm3 kg
22EES-4(Y) 144
22,8 4 3,5
22EES-6(Y) 150
22DES-4(Y) 144
26,8 4 3,5
22DES-6(Y) 150
22CES-6(Y) 148
32,4 4 3,5
22CES-8(Y) 148
44FES-6(Y) 172
36,2 8 4,5
44FES-10(Y) 180
44EES-8(Y) 176
45,4 8 4,5
44EES-12(Y) 180
44DES-10(Y) 180
53,6 8 4,5
44DES-14(Y) 181
44CES-12(Y) 185
65,0 8 4,5
44CES-18(Y) 185
24 www.bitzer.de A-222-1
A_222_1_3-32.qxp 22.11.2013 11:56 Uhr Seite 25
2 Compressor Data
2 x 10,4/6,0 2 x 3,3
2 x 16 5/ 28 11/8
8
2 x 13,4/7,5 2 x 3,8
2 x 13,4/7,5 2 x 4,0
2 x 16 5/ 28 11/8
8
2 x 15,0/8,6 2 x 4,6
220 .. 2406/380 .. 420Y/3/50
2 x 15,8/9,1 2 x 5,0
2 x 16 5/ 28 11/8
8
2 x 17,4/10,0 2 x 5,6
2 x 16,5/9,5 2 x 5,3
2 x 16 5/ 35 13/8
8
2 x 18,8/10,8 2 x 5,8
2 x 21,2/12,2 2 x 6,9
2 x 16 5/ 35 13/8
8
2 x 23,7/13,6 2 x 7,6
2 x 25,2/14,5 2 x 8,1
2 x 22 7/ 35 13/8
8
2 x 28,7/16,5 2 x 8,9
2 x 30,8/17,7 2 x 9,7
2 x 22 7/ 35 13/8
8
2 x 35,1/20,2 2 x 11,3
A-222-1 www.bitzer.de 25
A_222_1_3-32.qxp 22.11.2013 11:56 Uhr Seite 26
2 Compressor Data
m3/h dm3 kg
44VES-14(Y) 268
69,4 8 6,1
44VES-20(Y) 288
44TES-18(Y) 282
82,6 8 6,1
44TES-24(Y) 296
44PES-24(Y) 292
97,0 8 6,1
44PES-30(Y) 302
44NES-28(Y) 296
112,4 8 6,1
44NES-40(Y) 308
44JE-30(Y) 425
127,0 8 8,0
44JE-44(Y) 426
44HE-36(Y) 437
147,4 8 8,0
44HE-50(Y) 446
44GE-46(Y) 436
169,2 8 9,0
44GE-60(Y) 484
44FE-56(Y) 486
203,6 8 9,0
44FE-70(Y) 486
26 www.bitzer.de A-222-1
A_222_1_3-32.qxp 22.11.2013 11:56 Uhr Seite 27
2 Compressor Data
7/
2 x 16,6 2 x 11
2 x 22 8 42 15/8
2 x 19,9 2 x 12
2 x 19,9 2 x 13
2 x 28 11/8 54 21/8
2 x 25,1 2 x 14
2 x 22,7 2 x 14
2 x 28 11/8 54 21/8
2 x 28,2 2 x 16
PW 2 x 26,6 2 x 17
2 x 28 11/8 54 21/8
3 2 x 33,2 2 x 19
54 21/8 380..420YY/3/50 2 x 30,8 2 x 19
2 x 28 11/8
76 31/8 440..480YY/3/60 2 x 37,2 2 x 21
54 21/8 2 x 36,7 2 x 22
2 x 28 11/8
76 31/8 2 x 44,0 2 x 25
2 x 43,9 2 x 27
2 x 28 11/8 76 31/8
2 x 51,2 2 x 28
2 x 52,8 2 x 31
2 x 28 11/8 76 31/8
2 x 62,1 2 x 35
A-222-1 www.bitzer.de 27
A_222_1_3-32.qxp 22.11.2013 11:56 Uhr Seite 28
2 Compressor Data
m3/h dm3 kg
66JE-50(Y) 491
190,6 12 9,5
66JE-66(Y) 497
66HE-56(Y) 485
221,0 12 9,5
66HE-70(Y) 493
66GE-68(Y) 518
253,6 12 9,5
66GE-80(Y) 518
66FE-88(Y) 521
303,2 12 9,5
66FE-100(Y) 521
28 www.bitzer.de A-222-1
A_222_1_3-32.qxp 22.11.2013 11:56 Uhr Seite 29
2 Compressor Data
2 x 46,4 2 x 27
2 x 35 13/8 76 31/8
PW 2 x 53,2 2 x 30
2 x 53,2 2 x 33
2 x 35 13/8 76 31/8
380..420YY/3/50 2 x 64,4 2 x 36
440..480YY/3/60 2 x 65,5 2 x 40
2 x 35 13/8 76 31/8
3 2 x 73,9 2 x 42
2 x 83,2 2 x 46
2 x 42 15/8 76 31/8 380..400YY/3/50
440..460YY/3/60 2 x 96,2 2 x 51
Explanations
1 Tolerance (±10%) based on mean value of voltage range.
Other voltages and electrical supplies on request.
2 For the selection of contactors, cables and fuses the max.
working current / max. power consumption must be consi-
dered.
Contactors: operational category AC3.
Select both motor contactors for approx. 60% of the maxi-
mum operating current.
3 Motor for part winding start Y/YY.
Winding partition 50%/50%.
Designs for Y/6 upon request.
A-222-1 www.bitzer.de 29
A_222_1_3-32.qxp 22.11.2013 11:56 Uhr Seite 30
2 Compressor Data
42 15/8
S6G-25.2(Y) 84,5 42,3 6 4,75 233 35 13/8
54 21/8
42 15/8
S6F-30.2(Y) 101,1 50,5 6 4,75 234 35 13/8
54 21/8
2 x 42 15/8
S66G-50.2(Y) 2 x 84,5 2 x 42,3 2 x 6 9,5 459 2 x 35 13/8 5
2 x 54 21/8
2 x 42 15/8
S66F-60.2(Y) 2 x 101,1 2 x 50,5 2 x 6 9,5 461 2 x 35 13/8 5
2 x 54 21/8
30 www.bitzer.de A-222-1
A_222_1_3-32.qxp 22.11.2013 11:56 Uhr Seite 31
2 Compressor Data
Electrical data
Motor Max. Max. Starting
connection operating power con- current
current sumption (locked rotor)
2 3 4
Volt ± 10%/Ph/Hz Amp. kW Amp./Y/YY
14 6,9 39/68
17 9,7 49/81
24 13,8 69/113
31 18,1 81/132
37 21,5 97/158
380..420YY/3/50
53 30,1 135/220
2 x 31 2 x 18,1 2 x 81/132
2 x 37 2 x 21,5 2 x 97/158
2 x 45 2 x 24,9 2 x 116/193
2 x 53 2 x 30,1 2 x 135/220
A-222-1 www.bitzer.de 31
A_222_1_3-32.qxp 22.11.2013 11:56 Uhr Seite 32
2 Compressor Data
Explanations
➀ LP Low pressure stage
HP High pressure stage
➁ Motors for part winding start. Designs for Y/6 and for other
voltages and electrical supplies are available upon request.
➂ For the selection of contactors, cables and fuses the max.
working current / max. power consumption must be consi-
dered ("Electrical Data").
Contactors: operational category AC3
Select both motor contactors for approx. 60% of the maxi-
mum operating current.
➃ Data for compressors with voltage 380 .. 420 V (220 .. 240V)
are based on an average voltage of 400 V (230 V).
Conversion factors:
380 V (220 V) 0.95
420 V (240 V) 1.05
➄ Inside diameter of the bush: 42 mm A 54 mm pipe fits to
the outside diameter of the bush.
32 www.bitzer.de A-222-1
A_222_1_33-62.qxp 22.11.2013 11:58 Uhr Seite 33
2 Compressor Data
NOTES
A-222-1 www.bitzer.de 33
A_222_1_33-62.qxp 22.11.2013 11:58 Uhr Seite 34
2 Compressor Data
100
tc [ C]
80
Motor 1
Motor 2
60
40
Motor 3
20
toh = 20 C
0
-40 -30 -20 -10 0 10 30
to [ C]
R407C ➀, ➁, ➂
70
tc [ C]
60 Δttoh < 20K
oh < 20K
50
40
Motor 1
30
20
Motor 2 toh = 20 C
10
-30 -20 -10 0 20
to[ C]
34 www.bitzer.de A-222-1
A_222_1_33-62.qxp 22.11.2013 11:58 Uhr Seite 35
2 Compressor Data
R407A
2KES-05Y .. 4CES-9Y ➂
70
tc [°C]
60
Motor 1
40
30
Motor 2
20
toh = 20 C
10
-40 -30 -20 -10 0 20
to[°C]
R407A
4VES-7Y .. 6FE-50Y ➂, ➃
70
tc [ C]
60
50
Motor 1
40
30
Motor 2
20
toh = 20 C
10
-40 -30 -20 -10 0 20
to[ C]
Legend see page 40.
A-222-1 www.bitzer.de 35
A_222_1_33-62.qxp 22.11.2013 11:58 Uhr Seite 36
2 Compressor Data
R407F
2KES-05Y .. 4CES-9Y ➂
70
tc [°C]
60
Motor 1
40
30
Motor 2
20
toh = 20 C
10
-40 -30 -20 -10 0 20
to[°C]
R407F
4VES-7Y .. 6FE-50Y ➂, ➃
70
tc [ C]
60
50
Motor 1
40
30
Motor 2
20
toh = 20 C
10
-40 -30 -20 -10 0 20
to[ C]
36 www.bitzer.de A-222-1
A_222_1_33-62.qxp 22.11.2013 11:58 Uhr Seite 37
2 Compressor Data
R404A ■ R507A
2KES-05Y .. 6FE-50Y
70
tc [ C]
60
50
Motor 1
40
30
Motor 2
20
toh = 20 C
10
- 50 -40 -30 -20 -10 10
to [ C]
R404A ■ R507A
8GE-50Y .. 8FE-70Y ➀
70
tc [ C]
60
50
40
Motor 1
30
Motor 2
20
toh = 20 C
10
-50 -40 -30 -20 -10 10
to [ C]
Legend see page 40.
A-222-1 www.bitzer.de 37
A_222_1_33-62.qxp 22.11.2013 11:58 Uhr Seite 38
2 Compressor Data
R22
2KES-05 .. 4CES-9
70
tc [ C]
60
toh < 20K
50
40
Motor 1
30
20
Motor 2 toh = 20 C
10
-50 -40 -30 -20 -10 0 to [ C] 20
2 Compressor Data
R22
®
4VES-7 .. 6FE-40 mit / with / avec
70
tc [ C]
60
50
40
Motor 2
30
20
toh = 20 C
10
-50 -40 -30 -20 0
to [ C]
R22
4VES-7 .. 8FE-70 ➀
70
tc [ C] toh < 20K
60
50
40
30 Motor 1
20
Motor 2 toh = 20 C
10
-30 -20 -10 0 to [ C] 20
A-222-1 www.bitzer.de 39
A_222_1_33-62.qxp 22.11.2013 11:58 Uhr Seite 40
2 Compressor Data
Legend
➀ 8GE-50Y .. 8FE-70Y:
minimum evaporating temperature -20°C
➁ For R134a, at tc >70°C the oil BSE55 has to be used
(instead of BSE32).
➂ Evaporating and condensing temperatures are based
on dew point conditions (saturated vapour).
➃ Lower evaporating temperatures are possible with
®
40 www.bitzer.de A-222-1
A_222_1_33-62.qxp 22.11.2013 11:58 Uhr Seite 41
2 Compressor Data
NOTES
A-222-1 www.bitzer.de 41
A_222_1_33-62.qxp 22.11.2013 11:58 Uhr Seite 42
2 Compressor Data
60
40
Motor 2
20
toh = 20 C
0
-40 -30 -20 -10 0 to [ C] 20
R404A ■ R507A
2DES-3.F1Y .. 4NES-20.F4Y
70
tc [ C]
60
1
50
Motor 1
40
30
20
toh = 20 C
10
-50 -40 -30 -20 -10 10
to[ C]
Explanations of the application limits see chapter 7.
42 www.bitzer.de A-222-1
A_222_1_33-62.qxp 22.11.2013 11:58 Uhr Seite 43
2 Compressor Data
R407A
70
tc [ C]
60
50
Motor 1
40
30
20
toh = 20 C
10
-40 -30 -20 -10 0 20
to[ C]
R407F
70
tc [ C]
60
50
Motor 1
40
30
20
toh = 20 C
10
-40 -30 -20 -10 0 20
to[ C]
Legend see page 44.
A-222-1 www.bitzer.de 43
A_222_1_33-62.qxp 22.11.2013 11:58 Uhr Seite 44
2 Compressor Data
Legend
➀ Effective application limits of the individual compressors
are determined by max. power consumption of frequency
inverter. See performance data in KP-102-4 and BITZER
Software.
➁ For R134a and tc >70°C the oil BSE55 has to be used
(instead of BSE32).
➂ Max. suction gas temperature 20°C Applications >12.5°C
evaporating temperature upon request.
to Evaporating temperature (°C)
toh Suction gas temperature (°C)
Δtoh Suction gas superheat (K)
tc Condensing temperature (°C)
Additional cooling
Additional cooling or max. 20K suction superheat
Additional cooling and max. 20K suction superheat
Application limits for R407C upon request.
44 www.bitzer.de A-222-1
A_222_1_33-62.qxp 22.11.2013 11:58 Uhr Seite 45
2 Compressor Data
NOTES
A-222-1 www.bitzer.de 45
A_222_1_33-62.qxp 22.11.2013 11:58 Uhr Seite 46
2 Compressor Data
40
30
20 t oh = 20 C
10
-70 -60 -50 -40 -20
to [ C]
R22
60
tc [ C]
50
40
30
20 t oh = 20 C
10
-60 -50 -40 -30 -15
to [ C]
Explanations of the application limits see chapter 7.
46 www.bitzer.de A-222-1
A_222_1_33-62.qxp 22.11.2013 11:58 Uhr Seite 47
2 Compressor Data
Legende
to Evaporating temperature (°C)
toh Suction gas temperature (°C)
tc Condensing temperature (°C)
A-222-1 www.bitzer.de 47
A_222_1_33-62.qxp 22.11.2013 11:58 Uhr Seite 48
2 Compressor Data
13 12 11 9 10
TC
8 14 3 2 1 5 7* 6
®
6 a Spray nozzle
7 Liquid subcooler
8 Oil separator
9 Condenser
10 Liquid receiver
11 Expansion valve (evaporator)
12 Evaporator
13 Suction separator
14 Suction line filter
48 www.bitzer.de A-222-1
A_222_1_33-62.qxp 22.11.2013 11:58 Uhr Seite 49
2 Compressor Data
NOTES
A-222-1 www.bitzer.de 49
A_222_1_33-62.qxp
50
CE1 Series
2 Compressor Data
Types Motor version Standard motor
2KES-05(Y) 1+2 -40S
2JES-07(Y) 1+2 -40S
2HES-1(Y) 2 -40S
2HES-2(Y) 1 -40S
22.11.2013
2GES-2(Y) 1+2 -40S
www.bitzer.de
2FES-2(Y) 2 -40S
2FES-3(Y) 1 -40S
Centrifugal lubrication
13:45 Uhr
Seite 50
A-222-1
A_222_1_33-62.qxp
A-222-1
2KES-05(Y) .. 2FES-3(Y)
SL J DL B
22.11.2013
F K 105
G
www.bitzer.de
74
68
C
L
11:58 Uhr
106
2 Compressor Data
9 E D1 D
202 A
Seite 51
3 (LP) 1 (HP) 6 5/8 10
1/8"-27 NPTF 1/8"-27 NPTF M8x1,5 7/16"-20 UNF Ø11
51
2 Compressor Data
Types Motor version Standard motor
2EES-2(Y) 2 -40S
2EES-3(Y) 1 -40S
2DES-2(Y) 2 -40S
2DES-3(Y) 1 -40S
22.11.2013
2CES-3(Y) 2 -40S
www.bitzer.de
2CES-4(Y) 1 -40S
Centrifugal lubrication
11:58 Uhr
Seite 52
A-222-1
A_222_1_33-62.qxp
A-222-1
2EES-2(Y) .. 2CES-4(Y)
DL 3 (LP)
1/8"-27 NPTF
22.11.2013
SL 1 (HP) B
1/8"-27 NPTF
121
K J F 90
www.bitzer.de
11:58 Uhr
C
H
2 Compressor Data
81
123
G
Seite 53
D D1 13 E
A 241
5/8 6 10
7/16"-20 UNF M10x1,5 12
53
2 Compressor Data
Types Motor version Standard motor
4FES-3(Y) 2 -40S
4FES-5(Y) 1 -40S
4EES-4(Y) 2 -40S
4EES-6(Y) 1 -40S
22.11.2013
4DES-5(Y) 2 -40S
www.bitzer.de
4DES-7(Y) 1 -40S
4CES-6(Y) 2 -40S
4CES-9(Y) 1 -40S
11:58 Uhr
Centrifugal lubrication
Seite 54
A-222-1
A_222_1_33-62.qxp
A-222-1
4FES-3(Y) .. 4CES-9(Y)
DL SL 3 (LP) 1 (HP)
1/8"-27 NPTF 1/8"-27 NPTF
22.11.2013
B
J G
F K
www.bitzer.de
11:58 Uhr
C
H
L
2 Compressor Data
125
Seite 55
D D1 13 E
A 241
5/8 6 10
7/16"-20 UNF M10x1,5 12
55
2 Compressor Data
mm mm mm mm mm mm mm mm mm mm mm mm
2KES-05(Y), 2JES-07(Y), 2HES-1(Y), 2HES-2(Y) 343 220 273 208 65 162 148 37 242 247 32 232
2GES-2(Y), 2FES-2(Y), 2FES-3(Y)
2EES-2(Y), 2EES-3(Y), 2DES-2(Y), 2DES-3(Y)
398 259 307 223 85 198 167 42 266 275 37 262
2CES-3(Y), 2CES-4(Y)
22.11.2013
4FES-3(Y), 4FES-5(Y) 432 309 347 293 75 198 221 42 313 361 37 306
4EES-4(Y), 4EES-6(Y) 432 309 352 293 75 198 221 56 316 361 37 306
www.bitzer.de
4DES-5(Y) 432 309 352 293 75 198 221 56 316 361 42 310
4DES-7(Y), 4CES-6(Y), 4CES-9(Y) 457 309 352 293 101 198 246 56 316 386 42 310
11:58 Uhr
Seite 56
A-222-1
A_222_1_33-62.qxp 22.11.2013 11:58 Uhr Seite 57
2 Compressor Data
NOTES
A-222-1 www.bitzer.de 57
A_222_1_33-62.qxp
58
CE4 Series
2 Compressor Data
Types Motor version Standard motor
4VE(S)-6Y 3 -40P
4VE(S)-7(Y) 2 -40P
4VE(S)-10(Y) 1 -40P
4TE(S)-8Y 3 -40P
22.11.2013
4TE(S)-9(Y) 2 -40P
www.bitzer.de
4TE(S)-12(Y) 1 -40P
4PE(S)-10Y 3 -40P
4PE(S)-12(Y) 2 -40P
11:58 Uhr
4PC(S)-15(Y) 1 -40P
4NE(S)-12Y 3 -40P
4NE(S)-14(Y) 2 -40P
4NE(S)-20(Y) 1 -40P
S = centrifugal lubrication (standard)
Seite 58
w/o S = oil pump versions
A-222-1
DL SL 1 (HP) 2 (HP)
22.11.2013
1/8"-27 NPTF 1/8"-27 NPTF
A
3 (LP)
K J B
7/16"-20 UNF
F 152 5
www.bitzer.de
11:58 Uhr
C
G
L
2 Compressor Data
142
19
D D1 21 E
300
Seite 59
4
1/8"-27 NPTF
5/8 21 6 10 16
1/4"-18 NPTF 1/2"-14 NPTF M10x1,5 12 M20x1,5
59
2 Compressor Data
Types Motor version Standard motorr
4JE-13Y 3 -40P
4JE-15(Y) 2 -40P
4JE-22(Y) 1 -40P
4HE-15Y 3 -40P
22.11.2013
4HE-18(Y) 2 -40P
www.bitzer.de
4HE-25(Y) 1 -40P
4GE-20Y 3 -40P
4GE-23(Y) 2 -40P
11:58 Uhr
4GE-30(Y) 1 -40P
4FE-25Y 3 -40P
4FE-28(Y) 2 -40P
4FE-35(Y) 1 -40P
Compressors with oil pump
Seite 60
Motor version 3 only for R134a
A-222-1
A_222_1_33-62.qxp
A-222-1
4JE-13Y .. 4FE-35(Y)
DL SL 11 1 (HP)
7/16"-20 UNF 1/8"-27 NPTF
3 (LP) 4 A
1/8"-27 NPTF 1/8"-27 NPTF
22.11.2013
K J
J B
F G
www.bitzer.de
11:58 Uhr
12
C
7/16"-20 UNF
H
L
9a
2 Compressor Data
3/4"-14 NPTF
157
12
9b
1/2"-14 NPTF
D D1 E
Seite 61
21 360
2 (HP) 16 5 8 10 6/7
1/8"-27 NPTF M20x1,5 1/4"-18 NPTF 1/4"-18 NPTF 3/8"-18 NPTF M26x1,5
61
2 Compressor Data
mm mm mm mm mm mm mm mm mm mm mm mm
4VES-6Y, 4VES-7(Y), 4VES-10(Y) 633 303 385 367 140 256 44 61 161 558 42 338
4TES-8Y, 4TES-9(Y), 4TES-12(Y) 633 303 385 367 140 256 44 64 161 557 56 342
4PES-10Y, 4PES-12(Y) 633 303 385 367 140 256 44 64 161 557 56 342
4PES-15(Y) 658 303 385 367 162 256 48 110 173 582 56 342
22.11.2013
4NES-12Y, 4NES-14(Y) 633 303 385 367 140 256 44 64 161 557 56 342
4NES-20(Y) 658 303 385 367 162 256 48 110 173 582 56 342
www.bitzer.de
4JE-13Y, 4JE-15(Y) 688 456 452 381 151 305 66 110 361 501 56 362
4JE-22(Y) 688 456 452 381 151 305 66 110 361 501 56 362
4HE-15Y, 4HE-18(Y) 688 456 452 381 151 305 66 110 361 501 56 362
4HE-25(Y) 737 456 452 381 200 305 87 127 377 549 56 362
11:58 Uhr
4GE-20Y, 4GE-23(Y) 706 456 452 381 169 305 76 127 377 519 56 362
4GE-30(Y) 737 456 452 381 200 305 87 127 377 549 56 362
4FE-25Y, 4FE-28(Y) 737 456 452 381 200 305 87 127 377 549 56 362
4FE-35(Y) 737 456 452 381 200 305 87 127 377 549 56 362
Seite 62
A-222-1
A_222_1_63-92.qxp 22.11.2013 11:59 Uhr Seite 63
2 Compressor Data
NOTES
A-222-1 www.bitzer.de 63
A_222_1_63-92.qxp
64
BE6 Series
2 Compressor Data
Types Motor version Standard motor
6JE-22Y 3 -40P
6JE-25(Y) 2 -40P
6JE-33(Y) 1 -40P
6HE-25Y 3 -40P
22.11.2013
6HE-28(Y) 2 -40P
www.bitzer.de
6HE-35Y) 1 -40P
6GE-30Y 3 -40P
6GE-34(Y) 2 -40P
11:59 Uhr
6GE-40(Y) 1 -40P
6FE-40Y 3 -40P
6FE-44(Y) 2 -40P
6FE-50(Y) 1 -40P
Compressors with oil pump
Seite 64
Motor version 3 only for R134a
A-222-1
A_222_1_63-92.qxp
A-222-1
6JE-22Y .. 6GE-40(Y)
3 (LP) DL SL
1/8"-27 NPTF
22.11.2013
A
2 (HP) J B
1/8"-27 NPTF
F K 70 G
11
7/16"-20 UNF
www.bitzer.de
12
7/16"-20 UNF
11:59 Uhr
4
C
H
1/8"-27 NPTF
L
9a
158
2 Compressor Data
12
3/4"-14 NPTF
9b
D D1 1/2"-14 NPTF E
21 360
Seite 65
1 (HP) 4 16 5 8 10 6/7
1/8"-27 NPTF 1/8"-27 NPTF M20x1,5 1/4"-18 NPTF 1/4"-18 NPTF 3/8"-27 NPTF M26x1,5
65
2 Compressor Data
3 (LP) DL SL
1/8"-27 NPTF
A B
2 (HP) J G
22.11.2013
1/8"-27 NPTF
F K
11
7/16"-20 UNF
www.bitzer.de
12
7/16"-20 UNF
C
1/8"-27 NPTF
H
L
11:59 Uhr
9a
158
12
3/4"-14 NPTF
9b
D D1 1/2"-14 NPTF E
21 360
1 (HP) 4 16 5 8 10 6/7
Seite 66
1/8"-27 NPTF M20x1,5 1/4"-18 NPTF 1/4"-18 NPTF 3/8"-27 NPTF M26x1,5
A-222-1
22.11.2013
6HE-35(Y) 797 503 447 381 242 305 87 127 377 771 64 271
6GE-30Y, 6GE-34(Y) 766 503 447 381 211 305 76 127 377 740 64 271
6GE-40(Y) 797 503 447 381 242 305 87 127 377 771 64 271
www.bitzer.de
6FE-40Y, 6FE-44(Y) 790 503 447 381 242 305 87 127 377 729 111 381
6FE-50(Y) 790 503 447 381 242 305 87 127 377 729 111 381
11:59 Uhr
2 Compressor Data
Seite 67
67
A_222_1_63-92.qxp
68
CE8 Series
2 Compressor Data
Types Motor version Standard moto
8GE-50(Y) 2 -40P
8GE-60(Y) 1 -40P
8FE-60(Y) 2 -40P
8FE-70(Y) 1 -40P
22.11.2013
Compressors with oil pump
www.bitzer.de
11:59 Uhr
Seite 68
A-222-1
A_222_1_63-92.qxp
A-222-1
8GE-50(Y) .. 8FE-70(Y)
DL SL
B
22.11.2013
A G
2 (HP)
J F K
1/8"-27 NPTF
11
7/16"-20 UNF
www.bitzer.de
12
7/16"-20 UNF
515
5
11:59 Uhr
H
L 1/4"-18 NPTF
8
198
1/4"-18 NPTF
2 Compressor Data
12
D D1 21 E
Seite 69
360
3 (LP) 16 1 (HP) 9b 9a 10 6/7
1/8"-27 NPTF M20x1,5 1/8"-27 NPTF 1/2"-14 NPTF 3/4"-14 NPTF 3/8"-18 NPTF M26x1,5
69
2 Compressor Data
mm mm mm mm mm mm mm mm mm mm mm mm
8GE-50(Y), 8GE-60(Y) 886 485 538 457 281 305 82 158 445 757 110 336
8FE-60(Y), 8FE-70(Y) 902 485 538 457 281 305 82 158 445 764 129 336
22.11.2013
www.bitzer.de
11:59 Uhr
Seite 70
A-222-1
A_222_1_63-92.qxp 22.11.2013 11:59 Uhr Seite 71
2 Compressor Data
Connection positions
1 High pressure connection (HP)
2 Discharge gas temp. sensor (HP) or CIC sensor
3 Low pressure connection (LP)
4 CIC System: spray nozzle (LP)
5 Oil fill plug
6 Oil drain
7 Oil filter (magnetic screw)
8 Oil return (oil separator)
9a Gas equalisation (parallel operation)
9b Oil equalisation (parallel operation)
10 Crankcase heater
11 Oil pressure connection +
12 Oil pressure connection -
16 Connection for oil monitoring
(oil sensor or differential oil pressure switch "Delta-P")
21 Connection for oil service valve
A-222-1 www.bitzer.de 71
A_222_1_63-92.qxp
72
CE-F1 VARISPEED Series
2 Compressor Data
Types Inverter Motor
2DES-3.F1Y F1 -40S
4FES-5.F1Y F1 -40S
4EES-6.F1Y F1 -40S
4DES-7.F1Y F1 -40S
22.11.2013
4CES-6.F1Y F1 -40S
www.bitzer.de
Centrifugal lubrication
11:59 Uhr
Seite 72
A-222-1
A_222_1_63-92.qxp
A-222-1
2DES-3.F1Y
3 (HP)
281
1/8"-27 NPTF
22.11.2013
160
37 392 SL 285 DL 238
1 (HP)
1/8"-27 NPTF
www.bitzer.de
359
90
11:59 Uhr
269
263
81
123
2 Compressor Data
42
Seite 73
5/8 6 10
7/16"-20 UNF M10x1,5 12
73
2 Compressor Data
DL SL 1 (HP)
324
1/8"-27 NPTF
238
478 3 (LP) G
1/8"-27 NPTF
22.11.2013
338 K 169
www.bitzer.de
361
M
H
L
11:59 Uhr
125
293 193 13 198
549 241
5/8 6 10
Seite 74
7/16"-20 UNF M10x1,5 12
A-222-1
22.11.2013
4CES-6.F1Y 64 321 42 310 369
www.bitzer.de
11:59 Uhr
2 Compressor Data
Seite 75
75
A_222_1_63-92.qxp
76
CE-F3 VARISPEED Series
2 Compressor Data
Types Inverter Motor
4DES-7.F3Y F3 -40S
4CES-9.F3Y F3 -40S
4VES-7.F3Y F3 -40S
4TES-9.F3Y F3 -40S
22.11.2013
4PES-12.F3Y F3 -40S
www.bitzer.de
4NES-14.F3Y F3 -40S
Centrifugal lubrication
11:59 Uhr
CE-F4 VARISPEED Series
Seite 76
4PES-15.F4 F4 -40S
4NES-20.F4 F4 -40S
A-222-1
Centrifugal lubrication
A_222_1_63-92.qxp
A-222-1
4DES-7.F3Y .. 4CES-9.F3Y
DL SL 1 (HP) 309
1/8"-27 NPTF
219
22.11.2013
511 3 (LP) 64
1/8"-27 NPTF
140 371 42 155
www.bitzer.de
11:59 Uhr
382
325
310
2 Compressor Data
125
293 226 13 198
Seite 77
582 241
5/8 6 10
7/16"-20 UNF M10x1,5 12
77
2 Compressor Data
DL SL 2 (HP) 321
1/8"-27 NPTF
221
680 1 (HP) 169
22.11.2013
3 (LP) 4 1/8"-27 NPTF
56 185 152 5
7/16"-20 UNF 1/8"-27 NPTF
www.bitzer.de
429
110
380
351
341
11:59 Uhr
142
19
367 307 21 256
756 300
5/8 21 16 6 10
1/4"-18 NPTF 1/2"-14 NPTF M20x1,5 M10x1,5 12
Seite 78
A-222-1
2 Compressor Data
Connection positions
1 High pressure connection (HP)
2 Connection for discharge gas temperature sensor (HP)
3 Low pressure connection (LP)
4 CIC System: spray nozzle (LP)
5 Oil fill plug
6 Oil drain
8 Oil return (oil separator)
10 Connection for crankcase heater
16 Connection for oil servo
21 Connection for oil service valve
A-222-1 www.bitzer.de 79
A_222_1_63-92.qxp
80
CE2 Tandem Series
2 Compressor Data
Types Motor version Standard motor
22EES-4(Y) 2 -40S
22EES-6(Y) 1 -40S
22DES-4(Y) 2 -40S
22DES-6(Y) 1 -40S
22.11.2013
22CES-6(Y) 2 -40S
www.bitzer.de
22CES-8(Y) 1 -40S
Centrifugal lubrication
11:59 Uhr
Seite 80
A-222-1
A_222_1_63-92.qxp
A-222-1
22EES-4(Y) .. 22CES-8(Y)
22.11.2013
350 37 90
244
www.bitzer.de
307
262
11:59 Uhr
123
18
2 Compressor Data
223 320 223 90 13 198
945 241
Seite 81
278
5 8 6 10
7/16"-20 UNF 1/4"-18 NPTF M10x1,5 12
81
2 Compressor Data
Types Motor version Standard motor
44FES-6(Y) 2 -40S
44FES-10(Y) 1 -40S
44EES-8(Y) 2 -40S
44EES-12(Y) 1 -40S
22.11.2013
44DES-10(Y) 2 -40S
www.bitzer.de
44DES-14(Y) 1 -40S
44CES-12(Y) 2 -40S
44CES-18(Y) 1 -40S
11:59 Uhr
Centrifugal lubrication
Seite 82
A-222-1
A_222_1_63-92.qxp
A-222-1
44FES-6(Y) .. 44CES-18(Y)
3 (LP) SL DL 1 (HP)
1/8"-27 NPTF 1/8"-27 NPTF
435 435 71 K
22.11.2013
254
www.bitzer.de
L
M
11:59 Uhr
125
19
2 Compressor Data
293 299 293 64 13 198
1012 241
Seite 83
5 8 309
7/16"-20 UNF 1/8"-27 NPTF
6 10
M10x1,5 12
83
336
344
mm
L
mm
37
42
K
44DES-10(Y) .. 44CES-18(Y)
44FES-6(Y) .. 44EES-12(Y)
84 www.bitzer.de A-222-1
A_222_1_63-92.qxp 22.11.2013 11:59 Uhr Seite 85
2 Compressor Data
NOTES
A-222-1 www.bitzer.de 85
A_222_1_63-92.qxp
86
CE4 Tandem Series
2 Compressor Data
Types Motor version Standard motor
44VE(S)-14(Y) 2 -40P
44VE(S)-20(Y) 1 -40P
44TE(S)-18(Y) 2 -40P
44TE(S)-24(Y) 1 -40P
22.11.2013
44PE(S)-24(Y) 2 -40P
www.bitzer.de
44PE(S)-30(Y) 1 -40P
44NE(S)-28(Y) 2 -40P
44NE(S)-40(Y) 1 -40P
11:59 Uhr
S = centrifugal lubrication (standard)
w/o S = oil pump versions
Seite 86
A-222-1
A_222_1_63-92.qxp
A-222-1
44VES-14(Y) .. 44NES-40(Y)
DL SL 4 3 (LP) DL 1 (HP)
1/8"-27 NPTF 7/16"-20 UNF B 1/8"-27 NPTF
22.11.2013
1278 F 2 (HP)
1/8"-27 NPTF
87 552 552 5 K
H
www.bitzer.de
385
11:59 Uhr
L
142
19
2 Compressor Data
93 367 358 367 21 256
Seite 87
5 21 8 311
1/4"-18 NPTF 1/2"-14 NPTF 1/8"-27 NPTF 6 10 16
M10x1,5 12 M20x1,5
87
2 Compressor Data
mm mm mm mm mm
44VES-14(Y), 44VES-20(Y) 303 110 287 42 338
44TES-18(Y) .. 44NES-40(Y) 330 127 302 56 342
22.11.2013
www.bitzer.de
11:59 Uhr
Seite 88
A-222-1
A_222_1_63-92.qxp 22.11.2013 11:59 Uhr Seite 89
2 Compressor Data
NOTES
A-222-1 www.bitzer.de 89
A_222_1_63-92.qxp
90
BE5 Tandem Series
2 Compressor Data
Types Motor version Standard motor
44JE-30(Y) 2 -40P
44JE-44(Y) 1 -40P
44HE-36(Y) 2 -40P
44HE-50(Y) 1 -40P
22.11.2013
44GE-46(Y) 2 -40P
www.bitzer.de
44GE-60(Y) 1 -40P
44FE-56(Y) 2 -40P
44FE-70(Y) 1 -40P
11:59 Uhr
Compressors with oil pump
Seite 90
A-222-1
A_222_1_63-92.qxp
A-222-1
BE6 Tandem Series
22.11.2013
66HE-56(Y) 2 -40P
66HE-70(Y) 1 -40P
66GE-68(Y) 2 -40P
www.bitzer.de
66GE-80(Y) 1 -40P
66FE-88(Y) 2 -40P
11:59 Uhr
66FE-100(Y) 1 -40P
Compressors with oil pump
2 Compressor Data
Seite 91
91
A_222_1_63-92.qxp
92
44JE-30(Y) .. 66FE-100(Y)
2 Compressor Data
DL 16 5 SL 8 9a 9b DL
M20x1,5 1/4"-18 NPTF 3/8"-18 NPTF 3/4"-14 NPTF 1/2"-14 NPTF
A
J
22.11.2013
www.bitzer.de
11:59 Uhr
80 35
8
13 1000 13
1282
1342
Seite 92
A-222-1
22.11.2013
www.bitzer.de
C
C
L
H
H
H
12:02 Uhr
2 Compressor Data
21 305 21 305 21 305
420 420 420
470
470 470
Seite 93
12 10 11 6/7 4 12 10 6/7 4 12 10 6/7
7/16"-20 UNF 3/8"-18 NPTF 7/16"-20 UNF M26x1,5 1/8"-27 NPTF 7/16"-20 UNF 3/8"-18 NPTF M26x1,5 1/8"-27 NPTF 7/16"-20 UNF 3/8"-18 NPTF M26x1,5
2 Compressor Data
mm mm mm mm mm mm mm mm mm mm
44JE-30(Y) 1496 456 452 328 127 1446 101 – 294 156
44JE-44(Y) 1553 456 452 372 158 1503 101 – 294 156
44HE-36(Y) 1496 456 452 328 127 1446 101 – 294 156
44HE-50(Y) 1553 456 452 372 158 1503 101 – 294 156
22.11.2013
44GE-46(Y), 44GE-60(Y) 1553 456 452 372 158 1503 101 – 294 156
www.bitzer.de
44FE-56(Y), 44FE-70(Y) 1553 456 452 372 158 1503 101 – 294 156
66JE-50(Y), 66JE-66(Y) 1664 503 447 374 158 1614 64 70 271 158
66HE-56(Y), 66HE-70(Y) 1664 503 447 374 158 1614 64 70 271 158
66GE-68(Y), 66GE-80(Y) 1664 503 447 374 158 1614 64 70 271 158
12:02 Uhr
66FE-88(Y), 66FE-100(Y) 1616 503 447 374 158 1496 111 – 381 158
Further dimensions see the single compressors (KP-104).
Seite 94
A-222-1
A_222_1_93-130.qxp 22.11.2013 12:02 Uhr Seite 95
2 Compressor Data
Connection positions
1 High pressure connection (HP)
2 Connection for discharge gas temperature sensor (HP)
3 Low pressure connection (LP)
4 CIC system: spray nozzle (LP)
5 Oil fill plug
6 Oil drain
7 Oil filter (magnetic screw)
8 Oil return (oil separator)
9a Connection for gas equalisation
(parallel operation)
9b Connection for oil equalisation
(parallel operation)
10 Crankcase heater connection
11 Oil pressure connection +
12 Oil pressure connection –
16 Connection for oil monitoring
(opto-electronical oil sensor "OLC-K1" or
differential oil pressure switch "Delta-PII")
21 Connection for oil service valve
A-222-1 www.bitzer.de 95
A_222_1_93-130.qxp
96
BS4 Series
2 Compressor Data
Types Standard motor
S4T-5.2(Y) -40P
S4N-8.2(Y) -40P
Compressors with oil pump
22.11.2013
www.bitzer.de
BS5 Series
12:02 Uhr
S4G-12.2(Y) -40P
Compressors with oil pump
Seite 96
A-222-1
A_222_1_93-130.qxp
A-222-1
S4T-5.2(Y) & S4N-8.2(Y)
22.11.2013
15 4 17 DL 164 202 SL 31 630 / 654
5/8"-18 UNF 1/8"-27 NPTF
MP
HP
www.bitzer.de
MP
453
439
HP
366
278
328
LP
12:02 Uhr
165
12
MP
2 Compressor Data
LP
32
34
275 M10 21
Seite 97
10 6/7 12 16 4c 8 5
3/8"-18 NPTF M26x1,5 7/16"-20 UNF M20x1,5 1/8"-27 NPTF 1/4"-18 NPTF 1/4"-18 NPTF
97
2 Compressor Data
1 (HP) 482 3 (LP) 4c 14 (MP) 2 / 4b
1/8"-27 NPTF 1/8"-27 NPTF 1/8"-27 NPTF 1/8"-27 NPTF 1/8"-27 NPTF
245 209
15 2 / 4b 11 167 167 SL 711
7/8"-14 UNF 1/8"-27 NPTF 7/16"-20 UNF
22.11.2013
17 DL
www.bitzer.de
HP
MP
HP
X
492
479
372
372
278
158
12
12:02 Uhr
LP
32
34
305 M10 21
12 10 6/7 8 5
Seite 98
7/16"-20 UNF 3/8"-18 NPTF M26x1,5 1/4"-18 NPTF 1/4"-18 NPTF
A-222-1
2 Compressor Data
NOTES
A-222-1 www.bitzer.de 99
A_222_1_93-130.qxp
100
BS6 Series
2 Compressor Data
Types Standard motor
S6J-16.2(Y) -40P
S6H-20.2(Y) -40P
S6G-25.2(Y) -40P
S6F-30.2(Y) -40P
22.11.2013
Compressors with oil pump
www.bitzer.de
12:02 Uhr
Seite 100
A-222-1
A_222_1_93-130.qxp
A-222-1
S6J-16.2(Y) .. S6F-30.2(Y)
22.11.2013
15 11 222 117 112 714
7/8"-14 UNF 7/16"-20 UNF
1 (HP)
1/8"-27 NPTF
17 DL
HP
www.bitzer.de
HP
~523
510
LP
443
443
MP
ND
MP
278
324
12:02 Uhr
158
12
LP
2 Compressor Data
MP
ND
18
32
34
305 21 M10
12 90 360 211 381
545 764
Seite 101
12 10 6/7 16 8 14 (MP) 5
7/16"-20 UNF 3/8"-18 NPTF M26x1,5 M20x1,5 1/4"-18 NPTF 1/8"-27 NPTF 1/4"-18 NPTF
101
2 Compressor Data
Types Standard motor
S66J-32.2(Y) -40P
S66H-40.2(Y) -40P
S66G-50.2(Y) -40P
S66F-60.2(Y) -40P
22.11.2013
Compressors with oil pump
www.bitzer.de
12:02 Uhr
Seite 102
A-222-1
A_222_1_93-130.qxp
A-222-1
S66J-32.2(Y) .. S66F-60.2(Y)
16 ~520 SL 5 8 4c 14 (MP) SL
M20x1,5 1/4"-18 NPTF 3/8"-18 NPTF 1/8"-27 NPTF 1/8"-27 NPTF
245 ~263
DL
22.11.2013
222 78 1471
17
www.bitzer.de
18
LP HP
523
MP
ND
MP
646
12:02 Uhr
35
2 Compressor Data
80
Seite 103
470 128 1342
562 1626
103
2 Compressor Data
Connection positions
1 High pressure connection (HP)
2 Discharge gas temperature sensor (HP)
3 Low pressure connection (LP)
®
4 system: spray nozzle (operation without liquid
subcooler)
®
4b sensor (HP)
®
4c sensor (MP / operation with liquid subcooler)
5 Oil fill plug
6 Oil drain (magnetic screw)
7 Oil filter
8 Oil return (oil separator)
10 Crankcase heater
11 Oil pressure connection +
12 Oil pressure connection –
14 Intermediate pressure connection (MP)
15 Liquid injection (operation without liquid subcooler and
with thermostatic expansion valve)
16 Connection for oil differential pressure switch "Delta-P"
17 Refrigerant inlet at liquid subcooler
18 Refrigerant outlet at liquid subcooler
Liquid subcooler
®
Connections for system see Operating Instruction KB-150.
2 Compressor Data
Liquid subcooler
Arrow indicates
mounting position
to Evaporator
2 Compressor Data
2 Compressor Data
- - - - - - 4TES-8Y 41,3
BHS 1102 39,36 4T-8.2 39,36 4TCS-8.2 41,3 4TES-9 41,3
BHS 1702 39,36 4T-12.2 39,36 4TCS-12.2 41,3 4TES-12 41,3
- - - - - - 4PES-10Y 48,5
BHS 1282 47,14 4P-10.2 47,14 4PCS-10.2 48,5 4PES-12 48,5
BHS 2022 47,14 4P-15.2 47,14 4PCS-15.2 48,5 4PES-15 48,5
4L-10 49,6 - - - - - -
4L-15 49,6 - - - - - -
- - - - - - 4NES-12Y 56,2
BHS 1522 56,1 4N-12.2 56,1 4NCS-12.2 56,2 4NES-14 56,2
BHS 2402 56,1 4N-20.2 56,1 4NCS-20.2 56,2 4NES-20 56,2
4M-10 57,7 - - - - - -
4M-20 57,7 - - - - - -
- - - - - - 4JE-13Y 63,5
- - - - 4J-13.2 63,5 4JE-15 63,5
- - - - 4J-22.2 63,5 4JE-22 63,5
- - - - - - 4HE-15Y 73,7
4H-15 73,6 - - 4H-15.2 73,7 4HE-18 73,7
4H-25 73,6 - - 4H-25.2 73,7 4HE-25 73,7
- - - - - - 4GE-20Y 84,6
4G-20 84,5 - - 4G-20.2 84,6 4GE-23 84,6
4G-30 84,5 - - 4G-30.2 84,6 4GE-30 84,6
2 Compressor Data
6M-20 86,6 - - - - - -
6M-30 86,6 - - - - - -
- - - - - - 4FE-25Y 101,8
- - - - - - 4FE-28 101,8
- - - - - - 4FE-35 101,8
- - - - - - 6JE-22Y 95,3
- - - - 6J-22.2 95,3 6JE-25 95,3
- - - - 6J-33.2 95,3 6JE-33 95,3
- - - - - - 6HE-25Y 110,5
6H-25 110,5 - - 6H-25.2 110,5 6HE-28 110,5
6H-35 110,5 - - 6H-35.2 110,5 6HE-35 110,5
- - - - - - 6GE-30Y 126,8
6G-30 126,8 - - 6G-30.2 126,8 6GE-34 126,8
6G-40 126,8 - - 6G-40.2 126,8 6GE-40 126,8
- - - - - - 6FE-40Y 151,6
- - - - 6F-40.2 151,6 6FE-44 151,6
- - - - 6F-50.2 151,6 6FE-50 151,6
- - - - 8GC-50.2 185 8GE-50 185
6E-60.2 183,2 8E-60.2 184,4 8GC-60.2 185 8GE-60 185
- - - - 8FC-60.2 221 8FE-60 221
6D-70.2 219,1 8D-70.2 210,6 8FC-70.2 221 8FE-70 221
2 Compressor Data
Current types
Available on request, same dimensions as BHS types
No longer available
Notes:
2 Compressor Data
Comments
In the following chapter the technical data of the pre-
vious models (Octagon and .2-Generation) is shown.
Since the models of the NEW ECOLINE series have
been only slightly changed, only the technical data
of the previous models is shown. The drawings are
almost identical to the corresponding types of the
NEW ECOLINE series (see comparative table on pages
106-108).
There are some dimensional changes in the shut-off
valves for BE5 & BE6 series compared to previous
models. All other dimensions remain unchanged.
Dimensional drawings of the previous models see the
BITZER Software.
2 Compressor Data
NOTIZEN
2 Compressor Data
2HC-1.2(Y) 2 44
6,51 2 1,0 12 1/ 16 5/
2 8
2HC-2.2(Y) 1 45
2GC-2.2(Y) 1+2 7,58 2 1,0 45 12 1/ 16 5/
2 8
2FC-2.2(Y) 2 45
9,54 2 1,0 12 1/ 16 5/
2 8
2FC-3.2(Y) 1 47
2EC-2.2(Y) 2 67,5
11,4 2 1,5 16 5/ 22 7/
8 8
2EC-3.2(Y) 1 70,5
2DC-2.2(Y) 2 67,5
13,4 2 1,5 16 5/ 22 7/
8 8
2DC-3.2(Y) 1 70,5
2CC-3.2(Y) 2 70
16,2 2 1,5 16 5/ 22 7/
8 8
2CC-4.2(Y) 1 70
4FC-3.2(Y) 2 82
18,1 4 2,0 16 5/ 22 7/
8 8
4FC-5.2(Y) 1 86
4EC-4.2(Y) 2 84
22,7 4 2,0 16 5/ 28 11/8
8
4EC-6.2(Y) 1 86
4DC-5.2(Y) 2 85,5
26,8 4 2,0 22 7/ 28 11/8
8
4DC-7.2(Y) 1 88,5
4CC-6.2(Y) 2 90,5
32,5 4 2,0 22 7/ 28 11/8
8
4CC-9.2(Y) 1 90,5
2 Compressor Data
Electrical data
CR Motor Max. Max. Starting
–Steps– connection operating power current
current consumption (locked
rotor
2
%1 Volt Amp. kW Amp. 4
2 Compressor Data
4VCS-6.2(Y) 2 129
34,7 4 2,6 22 7/ 28 11/8
8
4VCS-10.2(Y) 1 139
4TCS-8.2(Y) 2 134
41,3 4 2,6 28 11/8 35 13/8
4TCS-12.2(Y) 1 141
4PCS-10.2(Y) 2 139 35 13/8
48,5 4 2,6 28 11/8
4PCS-15.2(Y) 1 147 42 15/8
4NCS-12.2(Y) 2 141 35 13/8
56,2 4 2,6 28 11/8
4NCS-20.2(Y) 1 150 42 15/8
4J-13.2(Y) 2 179
63,5 4 4,0 28 11/8 42 15/8
4J-22.2(Y) 1 190
4H-15.2(Y) 2 4,0 183 42 15/8
73,7 4 28 11/8
4H-25.2(Y) 1 4,5 203 54 21/8
4G-20.2(Y) 2 192
84,6 4 4,5 28 11/8 54 21/8
4G-30.2(Y) 1 206
6J-22.2(Y) 2 213
95,3 6 4,75 35 13/8 54 21/8
6J-33.2(Y) 1 231
6H-25.2(Y) 2 224
110,5 6 4,75 35 13/8 54 21/8
6H-35.2(Y) 1 235
6G-30.2(Y) 2 228
126,8 6 4,75 35 13/8 54 21/8
6G-40.2(Y) 1 238
6F-40.2(Y) 2 239
151,6 6 4,75 42 15/8 54 21/8
6F-50.2(Y) 1 241
2 Compressor Data
Electrical data
CR Motor Max. Max. Starting
–Steps– connection operating power current
current consumption (locked
rotor)
2
%1 Volt Amp. kW Amp. 4
14 8,1 39/68
21 11,3 59/99
17 9,4 49/81
24 13,8 69/113
21 11,7 59/99
3
PW
31 16,3 81/132
24 14,1 69/113
50
37 19,5 97/158
380..420YY/3/50 27 15,7 81/132
440..480YY/3/60 39 21,5 97/158
31 18,1 81/132
45 24,9 116/193
37 21,5 97/158
53 30,1 135/220
39 23,5 116/193
380..420YY/3/50 60 32,2 147/262
440..480 YY/3/60 45 27,2 116/193
66
61 37,4 147/262
altern. 3
PW 53 31,9 135/220
33
78 45,1 180/323
78 38,6 180/323
380..400YY/3/50 92 53,2 226/404
440..460YY/3/60
2 Compressor Data
8GC-50.2(Y) 2 342
185 8 5,0 42 15/8 76 31/8
8GC-60.2(Y) 1 350
8FC-60.2(Y) 2 361
221 8 5,0 54 21/8 76 31/8
8FC-70.2(Y) 1 374
2 Compressor Data
Electrical data
CR Motor- max. Max. Starting
–Steps– connection operating power current
current consumption (locked
rotor)
2
%1 Volt Amp. kW Amp. 4
92 50,5 285/426
75 PW 3
113 62,5 340/500
altern. 380..420ΔΔ/3/50
440..480ΔΔ/3/60 113 62,5 340/500
50
139 77,8 380/570
Explanations
➀ CR capacity control (option) 220 .. 240 V/1/50/60 Hz
➁ Tolerance (±10%) based on mean value of voltage range.
Other voltages and power supplies on request.
➂ Motor for Part-Winding start
• 4VCS-6.2(Y) .. 6F-50.2(Y) Y/YY, 4VES-6Y .. 6FE-50Y
winding ratio 50%/50%
• 8GC-50.2(Y) .. 8FC-70.2(Y) Δ/ΔΔ
winding ratio 60%/40%
• motor versions for Y/Δ on request.
➃ Data for compressors with voltage 380 .. 420 V
(220 .. 240 V) based on mean voltage 400 V (230 V).
Conversion factors:
380 V (220 V) 0.95
420 V (240 V) 1.05
2 Compressor Data
1
m3/h dm3 kg
2DC-3.F1Y 1 23,7 2 1,5 88
2 Compressor Data
2
Pipe connections Electrical data
DL SL FU Max. Max.
Discharge line Suction line connection operating power con-
current for sumption
380V/3/50Hz compressor
mm inch mm inch Volt Amp. kW
16 5/ 22 7/ 15 9
8 8
16 5/ 28 11/8 20 11
8
16 5/ 28 11/8 22 12
8
22 7/ 35 13/8 22 12
8
380..480 V/3/50 Hz
380..480 V/3/60 Hz
22 7/ 35 13/8 28 17
8
22 7/ 35 13/8 22 12
8
22 7/ 35 13/8 34 21
8
28 11/8 42 15/8 35 22
28 11/8 42 15/8 42 26
28 11/8 42 15/8 48 30
28 11/8 42 15/8 55 36
Frequency range
2DC-3.F1Y: 30...87 Hz
4FC-5.F1Y...4NCS-20.F4Y: 25...87 Hz
Explanations
1 Including frequency inverter
2 Compressor Data
22EC-4.2(Y) 143
22,7 4 3,5 2 x 16 5/ 28 11/8
8
22EC-6.2(Y) 149
22DC-4.2(Y) 143
26,8 4 3,5 2 x 16 5/ 28 11/8
8
22DC-6.2(Y) 149
22CC-6.2(Y) 148
32,5 4 3,5 2 x 16 5/ 28 11/8
8
22CC-8.2 (Y) 148
44FC-6.2(Y) 172
36,1 8 4,5 2 x 16 5/ 35 13/8
8
44FC-10.2(Y) 180
44EC-8.2(Y) 176
45,4 8 4,5 2 x 16 5/ 35 13/8
8
44EC-12.2(Y) 180
44DC-10.2(Y) 179
53,7 8 4,5 2 x 22 7/ 35 13/8
8
44DC-14.2(Y) 180
44CC-12.2(Y) 184
65 8 4,5 2 x 22 7/ 35 13/8
8
44CC-18.2(Y) 184
2 Compressor Data
Electrical data
CR Motor Max. Max. Starting
–Steps– connection operating power con- current
current sumption (locked
rotor)
2
%1 Volt Amp. kW Amp. 4
2 Compressor Data
44VCS-12.2(Y) 268
69,4 8 6,1 2 x 22 7/ 42 15/8
8
44VCS-20.2(Y) 288
44TCS-16.2(Y) 282
82,6 8 6,1 2 x 28 11/8 54 21/8
44TCS-24.2(Y) 296
44PCS-20.2(Y) 292
97,0 8 6,1 2 x 28 11/8 54 21/8
44PCS-30.2(Y) 302
44NCS-24.2(Y) 296
112,4 8 6,1 2 x 28 11/8 54 21/8
44NCS-40.2(Y) 308
44J-26.2(Y) 404 54 21/8
127,0 8 8,0 2 x 28 11/8
44J-44.2(Y) 426 76 31/8
44H-30.2(Y) 8,0 412 54 21/8
147,3 8 2 x 28 11/8
44H-50.2(Y) 9,0 446 76 31/8
44G-40.2(Y) 436
169 8 9,0 2 x 28 11/8 76 31/8
44G-60.2(Y) 484
2 Compressor Data
Electrical data
CR Motor Max. Max. Starting
–Steps– connection operating power con- current
current sumption (locked
rotor)
2
%1 Volt Amp. kW Amp. 4
2 x 14 2 x 8,1 2 x 39/68
2 x 21 2 x 11,3 2 x 59/99
2 x 17 2 x 9,4 2 x 49/81
2 x 24 2 x 13,8 2 x 69/113
2 x 21 2 x 11,7 2 x 59/99
PW
2 x 31 2 x 16,3 2 x 81/132
50 3
2 x 24 2 x 14,1 2 x 69/113
altern.
380..420YY/3/50 2 x 37 2 x 19,5 2 x 97/158
75/50/25
440..480 YY/3/60 2 x 27 2 x 15,7 2 x 81/132
2 x 39 2 x 21,5 2 x 97/158
2 x 31 2 x 18,1 2 x 81/132
2 x 45 2 x 24,9 2 x 116/193
2 x 37 2 x 21,5 2 x 97/158
2 x 53 2 x 30,1 2 x 135/220
2 Compressor Data
66J-44.2(Y) 461
191 12 9,5 2 x 35 13/8 76 31/8
66J-66.2(Y) 497
66H-50.2(Y) 483
221 12 9,5 2 x 35 13/8 76 31/8
66H-70.2(Y) 493
66G-60.2(Y) 491
254 12 9,5 2 x 35 13/8 76 31/8
66G-80.2(Y) 518
66F-80.2(Y) 519
303 12 9,5 2 x 42 15/8 76 31/8
66F-100.2(Y) 521
2 Compressor Data
Electrical data
CR Motor Max. Max. Starting
–Steps– connection operating power con- current
current sumption (locked
rotor)
2
%1 Volt Amp. kW Amp. 4
2 x 39 2 x 23,5 2 x 116/193
50 PW 2 x 60 2 x 32,2 2 x 147/262
altern. 3 2 x 45 2 x 27,2 2 x 116/193
83/50/33 2 x 61 2 x 37,4 2 x 147/262
380..420YY/3/50
altern. 2 x 53 2 x 31,9 2 x 135/220
440..480 YY/3/60
83/66/50/ 2 x 78 2 x 45,1 2 x 180/323
33/17
2 x 78 2 x 38,6 2 x 180/323
380..400YY/3/50
440..460YY/3/60 2 x 92 2 x 53,2 2 x 226/404
Explanations
1 CR capacity control (option) 220 .. 240 V/1/50/60 Hz
3 Electrical Connection
Attention!
Compressor is fitted with electronic protection device!
• Electrical connection according to wiring diagram.
• Follow advices in operating instructions!
• In case of tripping of the protection device there is a
thermal overload:
Check cause and eliminate before restart!
Attention!
• PTC and B1-B2 connections of motor protection
device must not come in contact with the control
and supply voltages!
(SE-B1) HK
Reset
-Connection
L1 L2 L3
L N B1 B2 12 14 11
U V W
SE-B1
Z X Y 1
PTC
2
3
U V W 4
-Connection
5
L1 L2 L3 Z X Y 6
7
U V W 8
9
10
11
37800645
12
Z X Y
3 Electrical Connection
(SE-B* ) HK
L1 L2 L3 L1 L2 L3
U1 V1 W1 U1 V1 W1
1 2 3 M1 1 2 3 M1
6 4 5 M2 6 4 5 M2
37800722
W2 U2 V2 W2 U2 V2
3 Electrical Connection
PW (SE-B1 / SE-B2) HK
14
11
Control circuit
Discharge gas temperature sensor (option)
L1 L2 L3
2U1 2V1 2W1 2U1 2V1 2W1
M1 7 8 9 M1 7 8 9
PW 2
PW 1
M2 1 2 3 M2 1 2 3
37800649
L1 L2 L3 L1 L2 L3
3 Electrical Connection
(SE-B1 / SE-B2) HK
14
11
37800651
Control circuit
Discharge gas temperature sensor (option)
W2 U2 V2 W2 U2 V2 W2 U2 V2
M1 7 8 9 M1 7 8 9 M1 7 8 9
M2 1 2 3 M2 1 2 3 M2 1 2 3
U1 V1 W1 U1 V1 W1 U1 V1 W1
L1 L2 L3 L1 L2 L3 L1 L2 L3
3 Electrical Connection
PW (SE-B2) HK
1
2 1U1 1V1 1W1
T1 1 2 3
L
7 8 9 T2
Reset
SE-B2 N 2U1 2V1 2W1
B1
Relais max
2,5A 250 V B2 SL
300 VA
12
14
11
Control Circuit
Discharge gas temperature sensor (option)
L1 L2 L3 L1 L2 L3
1U1 1V1 1W1 1U1 1V1 1W1
1 2 3 1 2 3
T1 PW 2
T1 T2
T2 PW 1
7 8 9 7 8 9
37800650
3 Electrical Connection
FI integrated HK
Reset
VSD Operation
L1 L2 L3
L N B1 B2 12 14 11
FU / VSD / CF
U V W SE-B1
1
Z X Y PTC
2
3
U V W 4
Emergency service 5
Z X Y 6
L1 L2 L3 7
8
U V W
9
10
400V / 50Hz
11
37800668
460V / 60Hz
12
Z X Y
3 Electrical Connection
4DES-7.F3Y .. 4NES-20.F4Y
FI integrated (SE-B*) HK
6 4 5 M2 6 4 5 M2
W2 U2 V2 W2 U2 V2
3 Electrical Connection
4DC-7.F3Y .. 4NCS-20.F4Y
FI integrated HK
1
(Z) (Y) (X)
2 W2 U2 V2
M1 1 2 3
L
Reset
SE-B1 N M2 1 2 3
B1 U1 V1 W1
Relais max
2,5A 250 V B2 SL
300 VA
12
14
11
Control circuit
Discharge gas temperature sensor (option)
W2 U2 V2 W2 U2 V2
M1 7 8 9 M1 7 8 9
M2 1 2 3 M2 1 2 3
U1 V1 W1 U1 V1 W1
FU / FI / CF
37800715
L1 L2 L3
L1 L2 L3
400V-50 Hz
380..480V-50/60 Hz 460V-60 Hz
3 Electrical Connection
integrated FI HK
380 to 480 V
50 / 60 Hz
L1 L2 L3
L1 L2 L3
37800669
3 Electrical Connection
integrated FI HK
380 to 480 V
50 / 60 Hz
PE L1 L2 L3
L1 L2 L3
37800716
3 Electrical Connection
Example:
4CC-6.2Y-40S
Compressor type
Indication for nominal voltage:
400 V / 50 Hz
Motor connection:
S = Star wiring
D = Delta wiring
P = Part winding
N = Dual voltage
E = Single phase
U = UL approval
For motor code 40S the table on page 138 - 140 shows
the different motor connections for the respective ope-
rating voltages and frequencies:
220 – 240 / 3 / 50 Hz / Δ
380 – 420 / 3 / 50 Hz / Y
440 – 480 / 3 / 60 Hz / Y
3 Electrical Connection
3 Electrical Connection
380 – 420 (400) 400 40P* 460 440 – 480 (460) Y/YY
3 Electrical Connection
3 Electrical Connection
Electrical wiring
General recommendations
Compressor and electrical accessories are in accor-
dance with the EC Low Voltage Directive 73/23/EEC
(CE 96).
The electrical installation is to be carried out according
to the wiring diagram. Observe the safety standards
EN 60204, IEC 60364 and national safety regulations.
Attention!
! Danger of short circuit caused by condensing
water in the terminal box!
Use standard cable bushings only and ensure
proper sealing when mounting.
3 Electrical Connection
Motor version
2KES-05(Y) .. 4CES-9(Y) // 2KC-05.2(Y) .. 4CC-9.2(Y)
The motor is designed for two different voltages. For
motor connection (Y or Δ) see instructions on cover
of terminal box.
3 Electrical Connection
3 Electrical Connection
3 Electrical Connection
NOTES
3 Electrical Connection
current type
former type, still available
no longer available
3 Electrical Connection
Listed current types replace the old version without the need of
additional measures.
3 Electrical Connection
• SE-B1
• SE-B2
SE-B1
• used in compressor models 2KES-05(Y) .. 4NE(S)-
20(Y) / 2KC-05.2(Y) .. 4NC(S)-20.2(Y)
• clip-on in terminal box
• PTC lead length approx. 11 cm
• Previous model: INT69V/7-II
SE-B2
• used in compressor models 4JE-13(Y) .. 8FE-70(Y) /
4Z-5.2(Y) .. 8FC-70.2(Y)
• screwed into terminal box
• can be clipped on top hat rail
• PTC lead length approx. 35 cm
• Previous model: INT69VS, INT69V/7-II and
UL version of INT69
3 Electrical Connection
Electrical connection
Electrical connection according to schematic wiring
diagrams (see page 150 - 159).
Further information see KT-120 or KT122.
3 Electrical Connection
F2
S2
L 11 B1 B2
SE-B1 / SE-B2
K1 K2 N 12 14
11 14
2 1 F13
3
F13 F14 F14
9 9 5
M1
1W1 M3 2W1
1V1 2V1
1U1 2U1
R1..6 H1
R7
3 Electrical Connection
... 9 10 11 12 13 14 15 16 17 18 19
F12 4A
K1 K3 K3 K1T K2 K1 K2 K1 K1
11 9 9 12 14 11 14 11 11
F5 P>
K1
F6 P< 11 B2
K2T
18
B1
Option
brown
red
F4
orange
black
H2 R8
K3 K1 K1T K2 Y1 Y2 Y3 K2T
max. 0.5 sec
11 3/3/3/10/ 14 5/5/5/17
15/16
13 18/19 15 11
3 Electrical Connection
K1
11 S2
L 11 B1 B2
F13 SE-B1 / SE-B2
9
N 12 14
2 1 F13
3
M1
1W1 M3
1V1
1U1
R1..6 H1
R7
3 Electrical Connection
... 9 10 11 12 13 14 15 16 17 18 19
F12 4A
K1 K3 K3 K1 K1 K1
11 9 9 11 B2 11 11
F5 P>
F6 P<
K2T
18
B1
Option
brown
red
F4
orange
black
H2 R8
K3 K1 Y2 Y3 K2T
11 3/3/3/10/
16
13 18/19 11
3 Electrical Connection
3 Electrical Connection
Technical data
• Operating voltage:
230 V +10%/-15%, 50/60 Hz
(other voltages upon request)
• Relay:
Switch voltage 250 V ~
Continuous current max. 2,5 A
Switching capacity 300 VA
• Permitted ambient temperature:
- 30°C .. + 60°C
• Fuse required:
4 A quick blow
• Enclosure class:
Terminals IP00
3 Electrical Connection
L1
L2 01
L3 S1
N F1 1
PE 0
F3 4A
Q1
K1
13
L1 L2 L3
N1 1 4 .. 20 mA
2 0 .. 10 V
PE 3~ 3
4
X101
5 K8 S4 B3
9
6
7
8 0V
9
3~
1
X102
2
3
B1
M1 K1
1U1 1 7
M3~ 13
1V1 2 8
1W1 3 9 K2T
18
R1..6 3
4
5
R7, Option
K4T K8
5s
Details concerning connections 15/16 4/14/17
see inside the terminal box and
18/19
chapter 3.1,
3 Electrical Connection
... 10 11 12 13 14 15 16 17 18 19
L1.1
F12 4A
L1.2
S2 S3
K8 K8 K8 K8
9 9 9 9
K4T K4T
8 8
L 11 B2 B2
B1
1
2
SE-B1 K1
N 12 14 13
braun violett
grau brown violet
grey/gris marron violet Option
OLC-K1
F6 P<
H1 H2 H8 H3 R8
K1 Y2 K2T
N
120 s
2/2/2/9
15
9
3 Electrical Connection
L1
L2 01
L3 S1
N F1 1
PE 0
F3 4A
Q1
K1
13
L1 L2 L3
1 10V
2 ADI1 4 .. 20 mA
X101a
3 0V 0V
4 ADI2 0 .. 10 V
N1 5 0V
6 ADIO3
0V
PE
B3
7 DI01
8 24V
9 DI2
X101b
3~ 10 DI3
11 24V K8 S4
8
12 DI4
3~ 13 SDI1
14 SDI2
15 COM
16 RL1C
X102
17 RL10
18 SD01
19 SD02
schwarz wei§ B1
black white
noir blanc M1 K1
U1 1 7
M3~ 13
rot / red / rouge V1 2 8
W1 3 9 K2T
18
R1..6 3
4
5
R7, Option
K8 K4T
5s
3 Electrical Connection
... 10 11 12 13 14 15 16 17 18 19
L1.1
F12 4A
L1.2
S2 S3
K8 K8 K8 K8
8 8 8 8
K4T K4T
9 9
L 11 B2 B2
B1
1
2
SE-B1 K1
N 12 14 13
braun violett
grau brown violet
grey/gris marron violet
Option
OLC-K1
F6 P<
H1 H2 H8 H3 R8
K1 Y2 K2T
N
120 s
2/2/2/9
15
9
3 Electrical Connection
B1 Regulator ON/OFF
B3 Regulator for compressor speed
F1 Main fuse
F3 Control circuit fuse
F5 High pressure cut out
F6 Low pressure cut out
F12 Fuse of crankcase heater
H1 Signal lamp "over temperature
(motor and discharge gas)"
H2 Signal lamp "oil supply fault"
H3 Signal lamp "main fault"
H8 Signal lamp"FI fault"
K1 Main contactor
K8 Auxiliary relay FI
K2T Time relay "pause time" 120 s
K4T Time relay "alarm delay" 5 s
M1 Compressor
N1 Frequency inverter (FI)
Q1 Main switch
R1-6 PTC sensors in motor windings
R7 Discharge gas temperature sensor (option)
R8 Crankase heater (option)
S1 Control switch
S2 Fault reset "over temperature (motor /
discharge gas)"
S3 Fault reset "lack of oil"
S4 Fault reset "FI fault"
Y2 Solenoid valve "liquid line"
SE-B1 Compressor protection device
OLC-K1 Opto-electronical oil level monitoring
(option)
3 Electrical Connection
NOTES
4 Accessories
Technical features
• The differential oil pressure switch Delta-PII consists
of two parts: a sensor unit and an electronic unit
• The sensor unit is screwed directly into the pump
housing of the compressor (bearing cover). It
contains a switching element which is connected by
channels with the suction and discharge pressure of
the oil pump. Therefore external tubes and flare
connections are omitted.
• The electronic unit is not in direct contact with the
oil circuit. It is screwed into the sensor unit. Thus,
the mounting and dismantling is possible without
intervention into the refrigeration circuit. An external
control module is not required.
• The red LED at front end of the electronic unit
signals the operating condition of Delta-PII while
compressor is running.
Technical data
• Operating voltage:
115 .. 230 V AC +10% / -15%, 50/60 Hz
also available with UL approval
• Power consumption: 3 VA
• Relay output:
Switch voltage 250 V ~
Switching current max. 2,5 A
Switching capacity 300 VA ind.
• Connecting cables:
6 x AWG18 (0,75 mm2) L = 1 m color coded
• Differential cut-out pressure: 0,65 bar
• Time delay with insufficient differential oil pressure:
90 s ± 5 s
• Lock out: electronical
• Admissible ambient temperature: -30°C .. +70°C
• Fuse for protection device and switch contacts:
max. 6 A
• Enclosure class: IP54
when electronic unit is mounted and connecting
cable points downwards
4 Accessories
Function
Compressor start
The oil pressure monitoring is activated when supply
voltage is applied via an auxiliary contact of the motor
contactor K1 (operating recognition, see also schematic
wiring diagram). The LED at the front end of the elec-
tronic unit immediately signals an insufficient differen-
tial oil pressure.
Operation
Once the preset value has been reached, this LED
extinguishes. The output contact remains closed if the
differential oil pressure reaches or exceeds the preset
value.
4 Accessories
Manual reset
Interrupt power supply (L/N) for at least 5 seconds (reset
button S3, see schematic wiring diagram, page 147).
Fault of Delta-PII
In case the supply voltage is too low or if the electronic
unit is not completely mounted, the Delta-PII locks out.
The LED at at the front end of the electronic unit is
flashing.
LED indications
• LED is on:
lack of oil
The signal lamp H2 is also on.
• LED is flashing:
fault of Delta-PII
• LED is off:
sufficient oil supply
Electrical connection
Connect Delta-PII according to schematic wiring dia-
gram. Mount reset buttons S2 and S3 into switchboard.
The following schematic wiring diagram applies to part
winding start. For direct start K2, K1T and Y1 can be
omitted.
4 Accessories
4 Accessories
brown
violet
grey
blue
pink
4 Accessories
B1 Control unit
B2 Control unit of capacity regulator (option)
F1 Main fuse
F2 Compressor fuse
F3 Control circuit fuse
F5 High pressure cut out
F6 Low pressure cut out
F12 Fuse of crankcase heater
F13 Thermal overload "motor" PW1 (recommended)
F14 Thermal overload "motor" PW2 (recommended)
H1 Signal lamp "over temperature (motor and
discharge gas)" and "oil supply fault"
H2 Signal lamp "oil supply fault"
K1 Contactor "first PW"
K2 Contactor "second PW"
K1T Time relay "part winding"
K2T Time relay "pause time" 300 s
M1 Compressor
Q1 Main switch
R1-6 PTC sensors in motor windings
R7 Discharge gas temperature sensor (option)
R8 Crankcase heater (option)
S1 Control switch
S2 Fault reset
"over temperature (motor / discharge gas)"
S3 Fault reset "lack of oil"
Y1 Solenoid valve "start unloading" (option)
Y2 Solenoid valve "liquid line"
Y3 Solenoid valve "capacity control" (option)
4 Accessories
4 Accessories
Delta-P
(Previous model)
See Technical Information KT-170.
4 Accessories
Reset
The new Delta-PII switch is reset by reset button (S2)
together with compressor protection device – see
schematic wiring diagram. Interrupt power supply (L/N)
for at least 5 seconds.
The previous model was reset by button at front end of
Delta-P
4 Accessories
L
F1
01
➀
S2
K1
brown
violet
grau
➁L 11
SE-B1
Delta-PII
SE-B2
N 12 14
blue
orange
pink
1 2
➂
P>
H1 P<
PTC
H2
➃
K1
4 Accessories
F1 Main fuse
H1 Signal lamp "over temperature
(motor and discharge gas)"
H2 Signal lamp "oil supply fault"
K1 Contactor "first PW"
S2 Reset of compressor protection device and of
Delta-PII (motor & discharge gas-temperature and
lack of oil)
4 Accessories
Technical features
The OLC-K1 is an opto-electronic oil sensor for con-
tactless monitoring of the oil supply by means of
infrared light. It consists of two parts: a prism unit and
an opto-electronic unit.
• The prism unit is screwed into the bearing cover
directly at the oil supply areas for the bearings.
• The opto-electronic unit is not in direct contact with
the oil circuit. It is screwed into the prism unit and
integrated into the control circuit of the plant. An
external control module is not required.
4 Accessories
Technical data
• Supply voltage: 230 V AC +10%*
• Supply frequency: 50 / 60 Hz
• Relay output:
Switching voltage max. 250 V AC
Switching current max. 2,5 A
Switching capacity max. 300 VA
• Fusing for device and switch contacts:
max. 4 A
• Maximum allowable pressure: 32 bar
• Enclosure class (mounted): IP54
• Connecting cable: 6 x AWG 20 (0.5 mm2)
L = 1 m➀
• Refrigerants: HFKW, (H)FCKW, HFC, (H)CFC➁
• Allowable ambient temperature: -30 .. +60°C
• Weight: 160g
4 Accessories
Function
Ready-to-operate
The oil supply monitoring is activated when the com-
pressor is switched on (operating recognition).
Lock out
If the lack of oil takes longer than the delay time, the
compressor is shut off.
Delay time:
• after compressor start 90 s
• in operation 5 s
The OLC-K1 then opens the output contact and locks
out electronically: The control voltage to the compressor
contactor is interrupted. The red LED at the face side
of the opto-electronic unit lights up (figure 1) as well as
the signal lamp H2.
Reset
The OLC-K1 can be manually reset by pressing the
reset button. This reset button (S3) has to be mounted
into the swich board. (Connection see schematic wiring
diagram).
• Before resetting, determine the reason for the oil
supply problem and fix it.
• Interrupt supply voltage (L/N) for at least 5 seconds.
4 Accessories
Electrical connection
Connect OLC-K1 according to schematic wiring dia-
gram (page 178-179). Mount reset buttons S2 and S3
into switch board.
The following schematic wiring diagram applies to part
winding start. For direct start K2, K1T and Y1 can be
omitted.
4 Accessories
4 Accessories
violet (black)
grey (yellow)
brown
pink (red)
blue
4 Accessories
B1 Control unit
B2 Control unit of capacity regulator (option)
F1 Main fuse
F2 Compressor fuse
F3 Control circuit fuse
F5 High pressure cut out
F6 Low pressure cut out
F12 Fuse of crankcase heater
F13 Thermal overload "motor" PW1 (recommended)
F14 Thermal overload "motor" PW2 (recommended)
H1 Signal lamp "over temperature (motor and
discharge gas)" and "oil supply fault"
H2 Signal lamp "oil supply fault"
K1 Contactor "first PW"
K2 Contactor "second PW"
K1T Time relay "part winding"
K2T Time relay "pause time" 300 s
M1 Compressor
Q1 Main switch
R1-6 PTC sensors in motor windings
R7 Discharge gas temperature sensor (option)
R8 Crankcase heater (option)
S1 Control switch
S2 Fault reset
"over temperature (motor / discharge gas)"
S3 Fault reset "lack of oil"
U1 EMC screening unit (if required)
Y1 Solenoid valve "start unloading" (option)
Y2 Solenoid valve "liquid line"
Y3 Solenoid valve "capacity control" (option)
4 Accessories
4 Accessories
General
During the shut-off periods a high amount of refrigerant
can be dissolved in the crankcase oil depending on
system type and refrigerant charge. The consequences
are increased oil carry over, liquid slugging and
reduced lubricity during the next start. In critical cases
the compressor might fail.
The operation of a crankcase heater keeps the dilution
of the refrigerant down on a level which gives no cause
for concern in most cases.
The heating is particularly important under the following
conditions:
• in case the oil temperature (crankcase) drops to a
value which is less than 15 .. 20 K above the tempe-
rature of the evaporator (saturation temperature) –
e. g. during longer shut-off periods.
• in case of temperatures of less than 10°C at the
location of the compressor.
4 Accessories
4VES-6(Y) .. 4NES-20(Y)
4VC(S)-6.2(Y) .. 4NC(S)-20.2(Y)
⎫
4VDC-10Y .. 4NDC-20Y ⎬ 00 .... 140 W – 100 .. 140 V ➀➁ 343 219 03 IP54
140 W – 200 .. 260 V ➀➁ 343 219 04 IP54
➃
4VES-6.F3Y .. 4NES-20.F4Y
(4NCS-20.F4Y)
⎭
III(Y), IV(Y), V(Y) ⎫ 7070 WW –– 1224 VV ➁➁ 343 208 14 IP65
4 Accessories
Mounting
The heaters are mounted in a bore in the bottom part
of the housing or with a heater sleeve directly into the
crankcase oil. So the heater can be replaced without
intervention into the refrigeration circuit.
If a heater is to be replaced:
Open heater circuit first.
If the heater sleeve is removed or a heater is to be
replaced, which is mounted without a heater sleeve:
Warning!
Compressor can be under pressure!
Severe injuries possible.
Wear safety goggles!
Switch off system and close shut-off valves at
compressor. Pump-off refrigerant and drain oil.
Open heater circuit.
A-222-1
Heaters
2DES-3.F1Y .. 4NES-20.F4Y
2DC-3.F1Y .. 4NCS-20.F4Y
A_222_1_167-192.qxp
22.11.2013
www.bitzer.de
12:10 Uhr
Seite 185
4 Accessories
185
III(Y), IV(Y), V(Y) VIW(Y), VIIW(Y) 4H.2(Y) .. 6F.2(Y)
186
2T.2(Y) .. 2N.2(Y) 4T.2(Y) .. 4N.2(Y) W4HA .. W6FA
W2TA .. W2NA W4TA .. W4NA S6H.2(Y) .. S6F.2(Y)
Heaters
2HL-1.2(Y) .. 2N-7.2(Y) S4T-5.2(Y), S4N-8.2(Y) 4J-13.2(Y) .. 6F-50.2(Y)
4JE-13Y .. 6FE-50Y
8GC-50.2(Y) .. 8FC-70.2(Y)
S4G-12.2(Y) .. S6F-30.2(Y)
A_222_1_167-192.qxp
4 Accessories
22.11.2013
www.bitzer.de
12:10 Uhr
A-222-1
Seite 186
A_222_1_167-192.qxp 22.11.2013 12:10 Uhr Seite 187
4 Accessories
Mounting
• Remove plastic plug.
Replacement:
Remove sealing plug. Take out heater.
• Fill the enclosed heat transfer paste into heater
sleeve.
• Fit the heating element completely into heater sleeve.
Insert the rubber plug of the heater up to the stopper
edge. This plug fits very tightly.
The rubber plug assures a safe fit.
4 Accessories
Function
The start unloader basically consists of a by-pass
device which is controlled by a solenoid valve.
For part winding and star-delta start this solenoid valve
is connected with the first part winding contactor or
the star contactor respectively. It is open for a short
time during the starting phase (part winding 0.5 s, star-
delta 1 .. 2 s). So an equalization occurs for a short
time between the high and low pressure sides: The
compressor starts unloaded. A check valve has to be
built into the discharge gas line. This prevents that dis-
charge gas flows back from the condenser during the
pressure equalization.
Unloaded start
The solenoid coil (1) is energized. With the aid of a
servo valve the control piston (2) is raised and the
bypass port is opened. The gas passes directly from
the discharge gas to the suction gas chamber.
4 Accessories
Normal operation
At normal operation the solenoid coil is de-energized.
The by-pass port in the cylinder head is closed.
1 Solenoid coil
2 Control piston
3 By-pass port
4 Suction gas chamber
5 Discharge gas chamber
6 Check valve in discharge gas line
7 Discharge gas temperature sensor
Connection position see dimensional drawings
4 Accessories
Normal operation
7
1
6
Legend see page 189.
Unloaded start
4 Accessories
K1
K1T K2
K1 K1T K2 Y2
N
0,5 s
4 Accessories
Star-delta-start
L
01
S
K1 K3
K3
K1 K1T K3 K2 Y2
N
1 .. 2 s Y
K1 "Main contactor"
K2 "Delta contactor"
K3 "Star contactor"
K1T Time relay "star-delta"
S Control switch "compressor on"
Y2 Solenoid valve "start unloading"
4 Accessories
4.4 CRII–system
capacity control for NEW ECOLINE compressors
Types:
• 4FES-3(Y) .. 8FE-70(Y)
• 44FES-6(Y) .. 66FE-100(Y)
General information
System Capacity Control is available for all BITZER
one stage 4 -, 6 - and 8-cylinder compressors of
NEW ECOLINE series as well as for the corresponding
tandem compressors. It is either fully assembled or
supplied as kit for retrofitting.
4 Accessories
Compressor type Capacity control Number required
range CRII cylinder heads
4FES-3(Y), 4FES-5(Y), 4EES-4(Y), 4EES-6(Y),
4DES-5(Y), 4DES-7(Y), 4CES-6(Y), 4CES-9(Y),
4VES-6Y, 4VES-7(Y), 4VES-10(Y), 4TES-8Y, 4TES-9(Y), 4TES-12(Y), 100% .. 10% ➀ 2
4PES-10Y, 4PES-12(Y), 4PES-15(Y), 4NES-12Y, 4NES-14(Y), 4NES-20(Y) 100% .. 50% ➁ 1
4JE-13Y, 4JE-15(Y), 4JE-22(Y), 4HE-15Y, 4HE-18(Y), 4HE-25(Y),
22.11.2013
4GE-20Y, 4GE-23(Y), 4GE-30(Y), 4FE-25Y, 4FE-28(Y), 4FE-35(Y)
6JE-22Y, 6JE-25(Y), 6JE-33(Y), 6HE-25Y, 6HE-28(Y), 6HE-35(Y), 100% .. 10% ➀ 3
www.bitzer.de
100% .. 50% ➀ 2
8GE-50(Y), 8 GE-60(Y), 8FE-60(Y), 8FE-70(Y)
100% .. 75% .. 50% ➁ 2
12:14 Uhr
44FES-6(Y), 44FES-10(Y), 44EES-8(Y), 44EES-12(Y),
44DES-10(Y), 44DES-14(Y), 44CES-12(Y), 44CES-18(Y),
44VES-14(Y), 44VES-20(Y), 44TES-18(Y), 44TES-24(Y), 100% .. 5% ➀ 4
44PES-24(Y), 44PES-30(Y), 44NES-28(Y), 44NES-40(Y), 100% .. 75% .. 50% .. 25% ➁ 2
44JE-30(Y), 44JE-44(Y), 44HE-36(Y), 44HE-50(Y),
44GE-46(Y), 44GE-60(Y), 44FE-56(Y), 44FE-70(Y)
100% .. 5% ➀
Seite 194
66JE-50(Y), 66JE-66(Y), 66HE-56(Y), 66HE-70(Y), 6
66GE-68(Y), 66GE-80(Y), 66FE-88(Y), 66FE-100(Y) 100 .. 83 .. 66 .. 50 .. 33 .. 17% ➁ 4
A-222-1
4 Accessories
Control principle
The CRII system for capacity control based on the
principle of blocked suction. Hereby the suction-side
gas flow to the individual cylinder bank is blocked by
means of a control piston (see fig.).
Full-load operation
In full-load operation the compressor delivers on all
cylinders. The solenoid coil (1) is de-energized. The gas
ports in the valve plate and cylinder head are opened.
Part-load operation
In part-load operation the refrigerant gas flow of the
switched off cylinder bank is blocked. The solenoid coil
(1) is energized, the suction port in the corresponding
cylinder head is shut off by means of a control piston.
4 Accessories
Full-load operation
5 6
Part-load operation
4 Accessories
Application limits
• always refer to the nominal voltage of the
compressor,
• are also valid for the corresponding
tandem comressor.
• Application limits for 8GE-50(Y) and
8FE-70(Y) upon request.
Minimum residual capacity 50%
(max. two CRII capacity contollers)
4 Accessories
Additional fan
Additional fans are available for all compressor types
upon request. Mounting positions, dimensions and
technical data see KT-140.
The compressor might also be located in the condenser
air flow. For a cooling effect equal to additional fan the
air velocity must be at least 3 m/s.
Air-cooled units
The unit fans can be equipped with a speed contoller.
The air flow must be controlled in such a way that a
sufficient cooling of the compressor is always guaran-
teed.
4 Accessories
Attention!
4 Accessories
4 Accessories
brown
violet
grey
blue
pink
4 Accessories
4 Accessories
4 Accessories
4FES-3(Y) .. 4CES-9(Y) 4VES-6Y .. 4NES-20(Y)
22.11.2013
www.bitzer.de
394
365
12:14 Uhr
Seite 204
A-222-1
A_222_1_193-222.qxp
A-222-1
Semi-hermetic compressors, capacity control mounting position
4JE-13Y .. 4FE-35(Y)
22.11.2013
268 244
www.bitzer.de
12:14 Uhr
452
425
401
4 Accessories
Seite 205
205
A_222_1_193-222.qxp
206
Semi-hermetic compressors, capacity control mounting position
4 Accessories
6JE-22Y .. 6FE-50(Y)
22.11.2013
www.bitzer.de
12:14 Uhr
488
447
365
342
Seite 206
A-222-1
A_222_1_193-222.qxp
A-222-1
Semi-hermetic compressors, capacity control mounting position
8GE-50(Y) .. 8FE-70(Y)
22.11.2013
324 324
www.bitzer.de
12:14 Uhr
537
4 Accessories
251
Seite 207
207
A_222_1_193-222.qxp 22.11.2013 12:14 Uhr Seite 208
4 Accessories
Subsequent mounting
The capacity control can be retrofitted on 4FES-3(Y) to
8FE-70(Y) as a complete kit. Arrangement see KT-101,
chapter 3, fig. 4.
The previous compressors (4FC-3.2 to 8FC-70.2) can
also be equipped with this system on the cylinder banks
intended for this purpose (refer to KT-101).
Warning!
Compressor is under pressure! In case of inproper
handling severe injuries are possible.
Release the pressure in the compressor!
Wear safety goggles!
4 Accessories
Danger!
Incorrect mounting may cause bursting of the
cylinder head.
Before commissioning of the modified compressor
run a strength pressure test!
• Test pressure:
1.1-fold of the maximum allowable pressure
(see name plate)
• Check compressor for refrigerant tightness.
3 9
1
4FES-3(Y), 4FES-5(Y) 4VES-6Y, 4VES-7(Y), 4VES-10(Y)
4EES-4(Y), 4EES-6(Y) 4TES-8Y, 4TES-9(Y), 4TES-12(Y)
4DES-5(Y), 4DES-7(Y) 4PES-10Y, 4PES-12(Y), 4PES-15(Y)
4CES-6(Y), 4CES-9(Y) 4NES-12Y, 4NES-14(Y), 4NES-20(Y)
Legend see page 210
4 Accessories
8
3
6
5
4
1
4JE-13Y, 4JE-15(Y), 4JE-22(Y) 6JE-22Y, 6JE-25(Y), 6JE-33(Y)
4HE-15Y, 4HE-18(Y), 4HE-25(Y) 6HE-25Y, 6HE-28(Y), 6HE-35(Y)
4GE-20Y, 4GE-23(Y), 4GE-30(Y) 6GE-30Y, 6GE-34(Y), 6GE-40(Y)
4FE-25Y, 4FE-28(Y), 4FE-35(Y) 6FE-40Y, 6FE-44(Y), 6FE-50(Y)
4 Accessories
General
All 4, 6 and 8 cylinder BITZER single-stage compressors
as well as corresponding tandems are available with
capacity control. It is supplied either completely fitted or in
kit form for retrofit. Subsequent mounting see chapter 8.
The following combinations are possible:
Compressor Possible residual Number of
type capacity capacity
regulators
4-Cylinder 50% 1
6-Cylinder 66% 1
66% – 33% 2
8-Cylinder 75% 1
75% – 50% 2
4-Cylinder-Tandem➀ 75% – 50%➁ – 25%➁ 1 (2➀)
4 Accessories
Full-load operation
In full-load operation the compressor delivers on all
cylinders. The solenoid coil (1) is de-energized. The gas
ports in the valve plate and cylinder head are opened.
Part-load operation
In part-load operation the pistons of the switched-off
cylinder bank run idle without gas pressure. The solenoid
coil (1) is energized, the suction port in the corresponding
cylinder head is shut off by means of a servo valve.
4 Accessories
Semi-hermetic compressors
With capacity regulator operation the temperature level
rises due to:
• reduced refrigerant mass flow,
• reduced motor cooling and
• electrical and mechanical losses.
Therefore the application ranges of the capacity
controlled compressors are restricted to some extent.
Application limits
• always refer to the nominal voltage of the
compressor,
• are also valid for the corresponding tandem
comressor.
• For 8GC-50.2(Y) and 8FC-70.2(Y) upon request.
Capacity steps: 100 – 75 – 50%
(max. two capacity regulators)
4 Accessories
Additional fan
Additional fans are available for all compressor types
upon request. Dimensions see KT-140 and section 4.6.
4 Accessories
Attention!
L1
F1 F3
01
S1
Safety chain
B1
K1 K1 K1
K1T K2 B2
K1
K1 K2 K1T Y1 Y2 Y3 R8
N
PW1 PW2 0,5 .. 1 sec CR
4 Accessories
4FC-3.2(Y) .. 4CC-9.2(Y) 4VC(S)-6.2(Y) .. 4NC(S)-20.2(Y)
305
303 152
22.11.2013
www.bitzer.de
366
395
353
385
12:15 Uhr
304
Seite 216
A-222-1
A_222_1_193-222.qxp
A-222-1
Semi-hermetic compressors, capacity control mounting positions
453 478
22.11.2013
www.bitzer.de
439 / 458
453
12:15 Uhr
408
382
4 Accessories
Seite 217
420 417
217
A_222_1_193-222.qxp
218
Semi-hermetic compressors, capacity control mounting positions
4 Accessories
6J-22.2(Y) .. 6G-40.2(Y) 6F-40.2(Y) & 6F-50.2(Y)
22.11.2013
www.bitzer.de
484
445
445
365
308
308
12:15 Uhr
226 226 226 226
Seite 218
309 276 309
A-222-1
A_222_1_193-222.qxp
A-222-1
Semi-hermetic compressors, capacity control mounting positions
22.11.2013
www.bitzer.de
537
537
12:15 Uhr
506
251
4 Accessories
Seite 219
237 237 237 237
219
A_222_1_193-222.qxp
220
Open drive compressors, capacity control mounting positions
4 Accessories
4T.2(Y) .. 4N.2(Y) & W4TA .. W4NA 4H.2(Y) & 4G.2(Y), W4HA & W4GA
451 477
22.11.2013
www.bitzer.de
469
421
419
422
12:15 Uhr
419 417
Seite 220
A-222-1
A_222_1_193-222.qxp
A-222-1
Open drive compressors, capacity control mounting positions
22.11.2013
www.bitzer.de
527
492
492
12:15 Uhr
407
351
351
4 Accessories
Seite 221
228 228 228 228
4 Accessories
Type Position
4FC-3.2(Y) .. 4NC(S)-20.2(Y)
4Z-5.2(Y) .. 4N-20.2(Y)
cylinder bank opposite to the sightglass
4T.2(Y) .. 4N.2(Y)
W4TA .. W4NA
4J-13.2(Y) .. 4G-30.2(Y)
4H.2(Y) & 4G.2(Y) both cylinder banks possible
W4HA & W4GA
6J-22.2(Y) .. 6G-40.2(Y)
6H.2(Y) & 6G.2(Y) outer cylinder banks
W6HA & W6GA
4 Accessories
General
It may be necessary to provide supplementary cooling
for the compressor when subjected to high thermal
load (refer to application limits in brochures and
BITZER Software).
Additional fan
This cooling method can be used universally. It offers a
uniform cooling effect and its performance can be
monitored easily (by means of electrical protection). The
fan is usually electrically connected in parallel to the
compressor. If the compressor is located in the air
stream of the condenser fan (at least 3 m/s), it is not
necessary to install an auxiliary fan.
4 Accessories
4 Accessories
4 Accessories
Assembly
Connect the cooling water according to page 227.
Four and six cylinder compressors may be connected
in series or in parallel. For parallel connection a mini-
mum water flow rate of 150 I/h at each cylinder head
must be ensured.
LP HP LP HP HP LP LP HP HP LP
22.11.2013
3/8" 1/2" (3/4") 1/2" 1/2"
www.bitzer.de
12:16 Uhr
4J-13.2(Y) .. 4G-30.2(Y) 6J-22.2(Y) .. 6F-50.2(Y)
W4HA & W4GA W6HA .. WAFA
4H.2(Y) & 4G.2(Y) 6H.2(Y) .. 6F.2(Y)
4 Accessories
Seite 227
LP HP LP HP LP HP LP HP LP HP
3/4" 3/4"
227
A_222_1_223-250.qxp 22.11.2013 12:16 Uhr Seite 228
4 Accessories
1 PC
1 Flow restrictor
2 Flexible pipe elements
3 Water regulator / solenoid valve
4 Accessories
• Outlet:
The cooling water temperature must not exceed
50°C. Adequate heat transfer is normally achieved
when the inlet / outlet water temperature difference
is between 5 and 10 K or with a water volume fIow
of approx. 150 l/h.
Compressor standstill
When the compressor is off, the cooling water supply
to the cylinder heads must be interrupted (e. g. water
regulator, solenoid valve) to avoid condensation of
refrigerant back into the cylinder head.
Legend
PAO poly alpha olefin
POE polyol ester
MO/AB mineral oil / alkyl benzene
MO mineral oil
Isotherms
tcm B B1
C1
Saturated vapor line
C tg
e
lin
g
Pressure
ilin
Bo
D1 D tom
tg A A1
Enthalpy
6 Application Advices
Compressor transport
Transport the compressor either screwed on a
pallet or lift it using the eyebolt.
Lift tandem compressors with spreader-bar only.
6 Application Advices
Compressor installation
Place of installation
Install the compressor horizontally.
For operation under extreme conditions (e. g. aggres-
sive or corrosive atmospheres, low ambient tempera-
tures etc.) suitable measures must be taken. Consulta-
tion with BITZER is recommended.
Anti-vibration mountings
The compressor can be rigidly mounted, if no danger
of breakage due to vibration exists in the associated
pipeline system. For compressors 2KES-05(Y) ..
4CES-9(Y) put a washer between each compressor
foot and frame (part No. 313 095-01).
Otherwise the compressor must be fixed on anti-vibra-
tion mountings (page 239). This is particulary required
with mounting on shell and tube heat exchangers:
Attention!
! Do not mount the compressor solidly onto the
heat exchanger.
Damage of the heat exchanger is possible
(vibration fractures).
6 Application Advices
A B
Transport Operation
3
Type I 2
M8
1
Type II 2
3
M10
1
4
Type III 2
3
M10
Anti-vibration mountings
6 Application Advices
Type II
Type III
44JE-30(Y) .. 44HE-50(Y)
2 x 370 002 01 brown
44GE-46(Y)
Anti-vibration mountings
6 Application Advices
Type II
Type III
44JE-30(Y) .. 44HE-50(Y)
2 x 370 002 02 red
44GE-46(Y)
6 Application Advices
Anti-vibration mountings
6 Application Advices
6 Application Advices
6 Application Advices
6 Application Advices
6 Application Advices
6 Application Advices
6.4 Vibrations
Pulsations
Pulsations (longitidunal gas vibrations on the high pres-
sure side) are created by the discharge process of the
gas out of the cylinders. Their amplitude and frequency
depend on:
• Compressor speed
• Number of cylinders
• Cylinder alignment
• Refrigerant properties (Pressure, temperature and
sonic speed)
Critical discharge gas vibrations can be found if the fre-
quency of the oscillating gas column in a straight disch-
arge tube section gets into resonance with the natural
frequency of the pipework. In the worst case this could
result in a fracture of the piping.
The length of the pipe segment with a resonance fre-
quency corresponding to the natural frequency of the
gas flow is designated as "critical pipe length".
Calculation of the critical pipe length for our com-
pressors is possible upon request after submittal
of refrigerant and the operating conditions.
248 www.bitzer.de A-222-1
A_222_1_223-250.qxp 22.11.2013 12:16 Uhr Seite 249
6 Application Advices
6 Application Advices
Structure-borne vibrations
Structure-borne vibrations are caused by unsteady
rotations and reaction forces at the compressor’s
mounting. Main cause are mass-forces of the com-
pressor’s crank drive.
6 Application Advices
6 Application Advices
6 Application Advices
Remarks:
Dischage gas temperature min. 20 K above condensing temperature
max. 120 °C measured at discharge
connection
Oil temperature min. 35 … 40 °C 10 … 20 K above evaporation
temperature
max. 75 … 80 °C during compressor start
min. 20 K above ambient
temperature➁
Suction gas superheat (DX) min. > 5 K stable superheat (measured)
6 Application Advices
6 Application Advices
Notes
• Use new gaskets only!
• Moisten gaskets with oil.
Do not oil gaskets with metallic support or teflon gaskets!
• Tighten screws crosswise and at least in two steps (50/100%).
1/8"-27 NPTF 15 .. 20 Nm 35 .. 40 Nm
1/4"-18 NPTF 30 .. 35 Nm 50 .. 55 Nm
3/8"-18 NPTF 50 .. 55 Nm 85 .. 90 Nm
1/2"-14 NPTF 60 .. 65 Nm 95 .. 100 Nm
3/4"-14 NPTF 80 .. 85 Nm 120 .. 125 Nm
6 Application Advices
Oil drain
M 22 Al 90 Nm
M 22 Cu 135 .. 155 Nm
M 26 Al 110 Nm
M 26 Cu 155 .. 175 Nm
M6 (8.8) 8 Nm
M6 (10.9) 10 Nm
6 Application Advices
Rotor screws ➂
M10 (10.9) 20 Nm
M12 (10.9) 20 Nm
M16 (10.9) 60 Nm
M6 (10.9) 16 Nm
M8 (8.8) 25.5 Nm
Oil pump
M8 23 Nm
oil centrifige
M6 16 Nm
M8 23 Nm
➀ with O-ring
➁ Clean and inspect the sealing surface, threads and sight glass.
Tighten screws crosswise with a torque spanner.
After pressurizing tighten the screws again with the torque spanner.
➂ with adhesive coating DIN267-27
4
Condensing Temperature °C
6 3
1
Evaporating Temperature °C
➂ Motor load
The motor load of a semi hermetic reciprocating com-
pressor depends on the operating point. The higher the
evaporating temperature and the higher the condensing
temperature, the higher the corresponding motor load.
➅ Thermal limit
At low evaporating temperatures in combination with
high condensing temperatures the thermal load limit of
the compressor restricts the operation. There are vario-
us possibilities to extend the application limits such as
water cooled cylinder heads, additional fans, restricting
the allowable suction gas superheat or, in individual
cases, a direct liquid injection into the suction side of the
compressor. The recommended methods for additional
cooling are displayed in the application limits diagram as
icons
General information
A-500 Refrigerant Report
A-600 Competence in Capacity Control
Brochures
KP-090 NEW ECOLINE - Progress al along the line
KP-101 Semi-hermetic Reciprocating Compressor for
R410A
KP-102 Semi-hermetic Reciprocating Compressor –
NEW ECOLINE VARISPEED with integrated
frequency inverter
KP-104 Semi-hermetic Reciprocating Compressor –
NEW ECOLINE
KP-114 Semi-hermetic Reciprocating Compressor –
NEW ECOLINE Tandem
KP-120 Octagon Series for CO2 – subcritical
KP-130 Octagon Series for CO2 – transcritical
KP-150 Semi-hermetic Reciprocating Compressor (2-stage)
KP-200 Air-cooled Condensing Units with
Semi-hermetic Recip. Compr. NEW ECOLINE
KP-202 Air-cooled Condensing Units LD032 .. LH114
KP-207 Air-cooled Condensing Units with frequency
regulated semi-hermetic compressors -
ECOSTAR
KP-220 Water-cooled Condensing Units with Semi-
hermetic Reciprocating Compressor
KP-230 Compressor Units with Receiver
(Semi-hermetic Reciprocating Compressor)
KP-250 Air-cooled Condensing Units with 2-stage
Semi-hermetic Reciprocating Compressor
Technical information
KT-100 Capacity Control for Reciprocating Compressors
KT-101 CRII - Capacity Control for NEW ECOLINE
Compressors
KT-110 Start Unloading for BITZER-Semi-hermetic
Compressors
KT-120 Protection Devices INT69VS and INT69/7-II
KT-122 Protection Devices SE-B
KT-130 CIC-System (1-stage Compressors)
KT-131 CIC-System (2-stage Compressors)
KT-140 Additional cooling
KT-150 Crankcase Heater
KT-160 Couplings for Reciprocating Compressors
KT-170 Oil Pressure Monitoring
KT-180 Opto-electronical Oil Level Monitoring
OLC-K1
KT-200 ECOSTAR Control
KT-210 NEW ECOLINE VARISPEED Compressors with
mounted suction gas-cooled F1 Frequency
Inverter (FI)
KT-220 NEW ECOLINE VARISPEED Compressors with
mounted suction gas-cooled F3-F4 Frequency
Inverter (FI)
A-222-1 www.bitzer.de 263
A_222_1_251-274.qxp 22.11.2013 12:20 Uhr Seite 264
Operating instructions
KB-100 Semi-hermetic Reciprocating Compressors
OCTAGON® Series 2KC-05.2(Y) .. 4NCS-20.2(Y)
KB-104 Semi-hermetic Recip. Compressors NEW
ECOLINE / Types 2KES-05(Y) .. 8FE-70(Y) //
22EES-4(Y).. 66FE-100(Y)
KB-110 Semi-hermetic Recip. Compressors 2HL-
1.2..2N-7.2/4VC-6.2..4NC-20.2/4Z-5.2..8FC-
70.2/44J-26.2..66F-100.2
KB-120 Semi-hermetic Recip. Compressors for
subcritical CO2 Application
KB-130 Semi-hermetic Recip. Compressors for
transcritical CO2 Application
KB-150 Reciprocating Compressors - Supplement
"2-stage"
264 www.bitzer.de A-222-1
A_222_1_251-274.qxp 22.11.2013 12:20 Uhr Seite 265
Maintenance instructions
KW-100 Tightening Torques for Screw Fixings of
Reciprocating Compressors
KW-510 Exchanging the shaft seal
KW-511 Exchanging the steel bellows type shaft seal
KW-520 Axial clearances for open type piston com
pressors
A-222-1 www.bitzer.de 265
A_222_1_251-274.qxp 22.11.2013 12:20 Uhr Seite 266
NOTES
9 Measurement Protocol
7 2 6 1
3
11
9 10
General information
Compressor data
9 Measurement Protocol
Condenser data
Evaporator data