® OPERATION

2003 Lennox Industries Inc.


Dallas, Texas, USA
MANUAL
Merit® Series Thermostat
CONTROLS (51M32)
504,865M
09/04
Litho U.S.A.

RETAIN THESE INSTRUCTIONS


FOR FUTURE REFERENCE
Table of Contents
Merit® Series Thermostat . . . . . . . . . . . . . . . . . . . . . . 1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Initial Thermostat Power-up . . . . . . . . . . . . . . . . . . . . . . 1
Heating Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Cooling Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Adjusting Temperature Setpoint . . . . . . . . . . . . . . . . . . 3
MeritR Series Thermostat Fan Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
The Lennox Merit® Series Thermostat 51M32 is a nonpro- Filter Reminder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
grammable electronic thermostat that is easy-to-use and Service Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
has a large, easy-to-read display and excellent tempera- Thermostat Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
ture control. The thermostat also includes a programmable Default Thermostat Settings . . . . . . . . . . . . . . . . . . . . . 5
filter change reminder and a system check indicator. The Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 5
system check indicator will notify the user of the need for Thermostat Output Table . . . . . . . . . . . . . . . . . . . . . . . . 6
equipment service.
Thermostat 51M32 is suitable for non-heat pump, single−
Display − Initial Power−Up

88
stage heat/single cool applications that are matched with a
gas or electric furnace. FILTER
General ROOM SERVICE

These instructions are intended as a general guide and do FAN


not supersede local codes in any way. Consult authorities ON
having jurisdiction before installation.

88
AUTO
Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier. SYSTEM
SETPOINT COOL
Introduction OFF
EMG.
This document describes the operation of Lennox thermostat HEAT
51M32. Refer to the installation manual for instructions re-
Figure 1
garding installation and wiring of the thermostat.
All display segments are momentarily activated. This oc-
Initial Thermostat Power-up
curs as a normal part of thermostat initialization. Within a
When power is initially applied to the thermostat, the dis- few seconds, the display will appear as shown in figure 2
play will appear as shown in figure 1. (figure shows temperature in Fahrenheit units).

Page 1
Display − Home Screen Heat Mode Enabled

ROOM
70 FAN
ROOM
69 FAN

AUTO

64
AUTO

SYSTEM SYSTEM
SETPOINT

HEAT HEAT
Figure 2 Figure 4
Figure 2 illustrates the HOME screen. Note that an indoor
room temperature of 70°F is initially displayed. After about
1 minute of warm−up time, the actual room temperature will If the thermostat is in heat mode, heat mode is disabled
be displayed. HEAT mode is the system default (as indi- when the HEAT button is pressed. This is indicated by OFF
cated in the SYSTEM box at lower right). in the SYSTEM box as shown in figure 5.
A pale blue display backlight will turn on each time a key is
pressed. The backlight will turn off 8 seconds after the last
Heat Mode Disabled

69
key is pressed.

Heating Control ROOM


The HEAT button is located behind the small door on the
right−hand side of the thermostat. See figure 3. FAN

Additional Thermostat Buttons

64
AUTO

SYSTEM
SETPOINT
OFF

Figure 5

Heating Demand
The thermostat must be in heat mode in order to properly
Figure 3 control the heating equipment. When in heat mode, if the
Enabling and Disabling Heat Mode actual temperature is lower than the temperature setpoint, a
Use the HEAT button to enable or disable heat mode as de- heating demand is detected by the thermostat. The thermo-
sired. If the thermostat is in off mode, heat mode is enabled stat will then activate the heating equipment to satisfy the de-
when the HEAT button is pressed. This is indicated by mand. Heating operation is indicated by a flame icon in the
HEAT in the SYSTEM box as shown in figure 4. SYSTEM box as shown in figure 6.

Page 2
Heating Demand Cooling Demand

ROOM
72 FAN
ROOM
79 FAN

88
AUTO AUTO

SYSTEM SYSTEM
COOL

HEAT
Figure 6 Figure 7
NOTE − The cooling equipment is activated for at least 4
When the actual temperature rises above the temperature minutes if no buttons are pressed during the demand inter-
setpoint, the flame icon will disappear. This indicates that val. Cooling equipment operation is locked out for 5 min-
the heating demand has been satisfied and that the heating utes after a demand has been satisfied. If another cooling
demand occurs during this 5−minute interval, the snowflake
equipment has been turned off.
icon will flash; however, the cooling equipment will not run
NOTE − The heating equipment is activated for at least 3 until the 5−minute delay has elapsed.
minutes if no buttons are pressed during the demand inter-
val. Adjusting Temperature Setpoint
Cooling Control The temperature setpoint represents the desired tempera-
ture of the space around the thermostat. The default tem-
The COOL button is located behind the small door on the perature setpoint is 70°F. To adjust the setpoint, press the
right-hand side of the thermostat. See figure 3. UP or DOWN arrow keys to the right of the display screen.
The existing setpoint will be displayed just below the actual
Enabling and Disabling Cool Mode
room temperature as shown in figure 8. Use the UP or
Use the COOL button to enable or disable cool mode as DOWN arrow keys to adjust the setpoint up or down. The
necessary. If the thermostat is in off mode, cool mode is en- setpoint will increase by 1°F each time the UP key is
abled when the COOL button is pressed. This is indicated pressed. The setpoint will decrease by 1°F each time the
by COOL in the SYSTEM box. DOWN key is pressed.
If the thermostat is in cool mode, cool mode is disabled
Setpoint Display and Adjustment

69
when the COOL button is pressed. This is indicated by OFF
in the SYSTEM box.
Cooling Demand ROOM
The thermostat must be in cool mode in order to properly FAN
control the cooling equipment. When in cool mode, if the

64
room temperature is higher than the temperature setpoint, AUTO
a cooling demand is detected by the thermostat.
SYSTEM
The thermostat will then activate the cooling equipment to SETPOINT
satisfy the demand. Cooling operation is indicated by a
snowflake icon in the SYSTEM box as shown in figure 7.
When the actual temperature drops below the temperature HEAT
setpoint, the snowflake icon will disappear. This indicates Figure 8
that the cooling demand has been satisfied and that the After the desired setpoint is reached, the HOME screen will
cooling equipment has been turned off. reappear after about 8 seconds.

Page 3
Fan Control Filter Reminder
The FAN button is located behind the small door on the The 51M32 thermostat includes a filter reminder feature.
right-hand side of the thermostat. See figure 3. The FAN The filter reminder can be set for 1, 3, 6, or 12−month inter-
button can be used to select either continuous fan mode or vals. The SETTINGS button, located behind the door on
auto fan mode. the right−hand side of the thermostat is used to set the filter
reminder interval. See figure 3. Press the SETTINGS but-
If continuous fan mode is enabled, the fan will run continu-
ton from the HOME screen to display the Filter Reminder
ously regardless of whether the heating or cooling equip-
Settings screen as shown in figure 11.
ment is running. Also, ON will be displayed in the FAN box
as shown in figure 9. Filter Reminder Settings

Fan ON with Icon


0 Filter

ROOM
73 FAN
ON

SYSTEM

HEAT Figure 11
The default setting for the filter reminder is 0, which dis-
ables the function. Use the UP arrow while in the Filter Re-
Figure 9
minder Settings screen to select the desired interval be-
tween reminders. It may be necessary to press the UP
If auto fan mode is selected, the fan will only run when the arrow several times to access the desired setting. The
heating or cooling equipment is running. In this case, AUTO HOME screen will reappear about 10 seconds after the ar-
will be displayed in the FAN box as shown in figure 10. row key has been pressed for the final time.
After the programmed interval has elapsed, the FILTER re-
Fan AUTO with Icon minder will be displayed as shown in figure 12. After the fil-

73
ter has been changed, reset the filter reminder by pressing
the SETTINGS button for 4 seconds. The screen will blink
ROOM for a few moments to indicate that the timer has been reset.
Display of Filter Reminder

72
FAN

AUTO ROOM FILTER

SYSTEM
FAN
HEAT
AUTO

SYSTEM
Figure 10

To change from continuous to auto fan mode and vice versa,


press the FAN button. Also note the presence of a fan icon in HEAT
the FAN box. This icon indicates that the fan is running. Figure 12

Page 4
Service Indicator Technical Specifications
When abnormal equipment operation is detected, the Thermostat Type
SERVICE indicator will flash on the upper-right corner of Electronic nonprogrammable thermostat for 1H/1C, gas or
the screen. This indicates that the equipment requires ser- electric heat, non−heat pump, non−power robbing applica-
vice from a qualified service technician. The SERVICE indi- tions.
cator is shown in figure 13. Power Supply Range
18VAC − 30VAC (24VAC nominal), 60Hz
Service Indicator Flashing

73
Temperature Display
Display Scale: Fahrenheit or Celsius user selectable (via
ROOM SERVICE
DIP switches)
Display range: 35°F (2°C) to 99°F (37°C)
FAN
Display resolution: 1°F (1°C)
AUTO Display Accuracy: +/−1°F
Temperature Measurement Range
SYSTEM Measurement Scale: Fahrenheit
Measurement Range: 35°F to 99°F
Measurement Resolution: 0.5°F
HEAT Measurement Accuracy: +/−1°F
Field Offset: via DIP switches to +/−3°F
Figure 13
Sampling Method: temperature measurements sampled
every 15 seconds. Displayed temperature is the average of
Thermostat RESET the last four measurements.
Under some abnormal conditions, it may be desirable to Temperature Setpoint Range
reset" the thermostat to its default condition. This can be Setting range: 50°F (10°C) to 90°F (32°C)
useful on rare occasions when the the thermostat is behav- Setting resolution: 1°F (1°C)
ing abnormally (e.g. after an electrical storm or power out- Fan Control
age). The RESET button can be used to recover from this AUTO or ON modes, gas or electric heat compatible via
situation. DIP switches (also see Thermostat Output section).
The RESET button is an unlabeled, recessed button lo- I/O Relays
cated behind the door on the right−hand side of the thermo- All thermostat relays are latching type to minimize power
stat, just below the SETTINGS button. The RESET button consumption.
is visible in figure 3. Use a paper clip or small pencil to press
1. HEAT/COOL relay output
the RESET button. After the RESET button is pressed, the
thermostat settings will return to the defaults listed in the 2. FAN relay output
Default Settings section. 3. SERVICE relay input
Equipment Protection Timers
Default Thermostat Settings Minimum Compressor OFF time: 5 minutes
Default thermostat settings are in table 1. Minimum Compressor ON time: 4 minutes
Minimum Furnace ON time: 3 minutes
Table 1
Minimum furnace cycle time (elapsed time between any
Default Thermostat Settings furnace activation and the next furnace activation): 6 min-
Mode Heat utes.
Setpoint 70°F (or 21°C) Minimum elapsed time between any compressor activation
Fan Auto and the next compressor activation: 6 minutes.
NOTE − All protection timers (except the compressor OFF
Filter Reminder OFF (reminder setting = 0)
timer) can be over−ridden if a heating or cooling demand is
Equipment Protection reset back to zero initiated or terminated using the UP, DOWN, HEAT, or
Timers COOL buttons.

Page 5
Equipment Protection Override Power Loss/Recovery
Both the minimum compressor OFF timer and the mini- Thermostat memory is retained for a minimum of 24 hours
mum equipment cycle timer can be over−ridden by press- during a power loss (includes retention of programmed
ing and holding either the HEAT or COOL button down for 4 temperature setpoint, heat/cool and fan mode settings, fil-
seconds. ter reminder status, and equipment protection timers). Af-
ter 24 hours of power loss, programmed settings will be lost
Over−Temperature Protection and replaced with default settings.
Thermal mechanical switch opens W1 at 93°F+/−6°F.
Filter Reminder IMPORTANT
Settings of 0 (Off), 1, 3, 6 or 12 months are available. When Power must be applied for at least six consecutive
programmed time has elapsed, a FILTER indicator is dis- hours prior to a power loss in order for memory to be
played. retained for the specified time.
Service Reminder LCD Backlight
The SERVICE indicator is displayed only under the follow- Activated for 8 seconds when any key is pressed.
ing conditions: NOTE − During an electrical storm or similar disturbance,
 if the thermostat Y1 terminal has been activated the backlight may activate for a few seconds. This is normal
with 24VAC for at least 5 minutes, AND the L and will no longer occur after the electrical disturbance has
terminal is shorted to the R terminal; passed.
OR Thermostat Operating Conditions
35°F to 105°F, 5% to 90% RH
 if the thermostat Y1 terminal has been activated
with 24VAC for at least 5 minutes, AND the L Thermostat Storage Conditions
terminal is shorted to the C terminal. −40°F to 185°F, 5% to 95% RH

Thermostat Output Table


The following table depicts the 51M32 thermostat output states for various input conditions. See table 2.
Table 2
Thermostat Outputs
Condition W1 Y1 G
Gas Heat, Auto Fan
heat demand X
cool demand X X
no demand
Gas Heat, Continuous Fan
heat demand X X
cool demand X X
no demand X
Electric Heat, Auto Fan
heat demand X X
cool demand X X
no demand
Electric Heat, Continuous Fan
heat demand X X
cool demand X X
no demand X
NOTE −
X = output is activated with 24VAC.

Page 6
® OPERATION
2003 Lennox Industries Inc.
Dallas, Texas, USA
MANUAL
Merit® Series Thermostat
CONTROLS (51M33)
504,931M
09/04
Litho U.S.A.

RETAIN THESE INSTRUCTIONS


FOR FUTURE REFERENCE
Table of Contents
Merit® Series Thermostat . . . . . . . . . . . . . . . . . . . . . . 1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Initial Thermostat Power-up . . . . . . . . . . . . . . . . . . . . . . 1
Heating Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Cooling Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Adjusting Temperature Setpoint . . . . . . . . . . . . . . . . . . 3
MeritR Series Thermostat Fan Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Filter Reminder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
The Lennox Merit® Series Thermostat 51M33 is a nonpro- Balance Point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
grammable electronic thermostat that is easy-to-use and Service Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
has a large, easy-to-read display and excellent tempera- Thermostat Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
ture control. The thermostat also includes a programmable Default Thermostat Settings . . . . . . . . . . . . . . . . . . . . . 6
filter change reminder and a system check indicator. The Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 6
system check indicator will notify the user of the need for Thermostat Output Table . . . . . . . . . . . . . . . . . . . . . . . . 7
equipment service.
Thermostat 51M33 is suitable for heat pump, single−stage
Display − Initial Power−Up

88
heat/single cool applications that are matched with a gas or
electric furnace. FILTER
General ROOM SERVICE

These instructions are intended as a general guide and do FAN


not supersede local codes in any way. Consult authorities ON
having jurisdiction before installation.

88
AUTO
Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier. SYSTEM
SETPOINT COOL
Introduction OFF
EMG.
This document describes the operation of Lennox thermostat HEAT
51M33. Refer to the installation manual for instructions re-
garding installation and wiring of the thermostat.
Figure 1
All display segments are momentarily activated. This oc-
Initial Thermostat Power-up
curs as a normal part of thermostat initialization. Within a
When power is initially applied to the thermostat, the dis- few seconds, the display will appear as shown in figure 2
play will appear as shown in figure 1. (figure shows temperature in Fahrenheit units).

Page 1
Display − Home Screen Enabling and Disabling Heat Mode

70
Use the HEAT button to select normal heat mode, emer-
gency heat mode, or to disable heat modes as desired. If
ROOM
the thermostat is in off mode, normal heat mode is enabled
FAN when the HEAT button is pressed. This is indicated by
HEAT in the SYSTEM box as shown in figure 4.
AUTO

SYSTEM Normal Heat Mode Enabled

Figure 2
HEAT
ROOM
69 FAN
Figure 2 illustrates the HOME screen. Note that an indoor

64
AUTO
room temperature of 70°F is initially displayed. After about
1 minute of warm−up time, the actual room temperature will SYSTEM
be displayed. HEAT mode is the system default (as indi- SETPOINT
cated in the SYSTEM box at lower right).
A pale blue display backlight will turn on each time a key is
HEAT
pressed. The backlight will turn off 8 seconds after the last
key is pressed. Figure 4

Heating Control
If the thermostat is in normal heat mode when the HEAT
The HEAT button is located behind the small door on the
button is pressed, then emergency heat mode is enabled.
right−hand side of the thermostat. See figure 3.
This is indicated by EMG. HEAT in the SYSTEM box as
Additional Thermostat Buttons shown in figure 5.
If the thermostat is in emergency heat mode when the
HEAT button is pressed, then heat modes are disabled.
This is indicated by OFF in the SYSTEM box as shown in
figure 6.

Emergency Heat Mode Enabled

Normal Heat Mode


Figure 3

In normal heat mode, both the heat pump and the backup
ROOM
69 FAN
heat source are used to provide heat. If the thermostat de-

64
AUTO
tects that the heat pump is not able to provide enough heat
(as may be the case in very cold weather), then the backup SYSTEM
heat source is activated. SETPOINT
Emergency Heat Mode EMG.
In emergency heat mode, only the backup heat source is HEAT
used to provide heat. The heat pump is disabled. The back-
Figure 5
up heat source will be activated only when there is a heat
demand.

Page 2
Heat Mode Disabled Enabling and Disabling Cool Mode

69
Use the COOL button to enable or disable cool mode as
necessary. If the thermostat is in off mode, cool mode is en-
ROOM abled when the COOL button is pressed. This is indicated
by COOL in the SYSTEM box.
FAN
If the thermostat is in cool mode, cool mode is disabled
when the COOL button is pressed. This is indicated by OFF

64
AUTO
in the SYSTEM box.
SYSTEM Cooling Demand
SETPOINT
OFF The thermostat must be in cool mode in order to properly
control the cooling equipment. When in cool mode, if the
room temperature is higher than the temperature setpoint,
Figure 6 a cooling demand is detected by the thermostat.
Heating Demand The thermostat will then activate the cooling equipment to
The thermostat must be in either normal or emergency satisfy the demand. Cooling operation is indicated by a
heat mode in order to properly control the heating equip- snowflake icon in the SYSTEM box as shown in figure 8.
ment. When in either heat mode, if the actual temperature is When the actual temperature drops below the temperature
lower than the temperature setpoint, a heating demand is de- setpoint, the snowflake icon will disappear. This indicates
tected by the thermostat. The thermostat will then activate the that the cooling demand has been satisfied and that the
heating equipment to satisfy the demand. Heating operation cooling equipment has been turned off.
is indicated by a flame icon in the SYSTEM box as shown in Cooling Demand

79
figure 7.
Heating Demand

72
ROOM

ROOM FAN

FAN AUTO

SYSTEM

88
AUTO
COOL
SYSTEM

Figure 8
HEAT
NOTE − The cooling equipment is activated for at least 4
Figure 7 minutes if no buttons are pressed during the demand inter-
When the actual temperature rises above the temperature val. Cooling equipment operation is locked out for 5 min-
setpoint, the flame icon will disappear. This indicates that utes after a demand has been satisfied. If another cooling
the heating demand has been satisfied and that the heating demand occurs during this 5−minute interval, the snowflake
equipment has been turned off. icon will flash; however, the cooling equipment will not run
until the 5−minute delay has elapsed.
NOTE − The heat pump is activated for at least 4 minutes if
no buttons are pressed during the demand interval. The Adjusting Temperature Setpoint
backup heat source is activated for at least 3 minutes if no
buttons are pressed during the demand interval. The temperature setpoint represents the desired tempera-
Heat pump operation is locked out for 5 minutes after a de- ture of the space around the thermostat. The default tem-
mand has been satisfied. If another heat pump demand oc- perature setpoint is 70°F. To adjust the setpoint, press the
curs during this 5−minute interval, the flame icon will flash; UP or DOWN arrow keys to the right of the display screen.
however, the heat pump will not run until the 5−minute delay The existing setpoint will be displayed just below the actual
has elapsed. room temperature as shown in figure 9. Use the UP or
DOWN arrow keys to adjust the setpoint up or down. The
Cooling Control
setpoint will increase by 1°F each time the UP key is
The COOL button is located behind the small door on the pressed. The setpoint will decrease by 1°F each time the
right-hand side of the thermostat. See figure 3. DOWN key is pressed.

Page 3
Setpoint Display and Adjustment Fan AUTO with Icon

ROOM
69 FAN
ROOM
73 FAN

AUTO

64
AUTO

SYSTEM SYSTEM
SETPOINT
HEAT

HEAT
Figure 11
Figure 9
To change from continuous to auto fan mode and vice versa,
press the FAN button. Also note the presence of a fan icon in
the FAN box. This icon indicates that the fan is running.
After the desired setpoint is reached, the HOME screen will Filter Reminder
reappear after about 8 seconds.
The 51M33 thermostat includes a filter reminder feature.
The filter reminder can be set for 1, 3, 6, or 12−month inter-
Fan Control vals. The SETTINGS button, located behind the door on
the right−hand side of the thermostat is used to set the filter
The FAN button is located behind the small door on the reminder interval. See figure 3. Press the SETTINGS but-
right-hand side of the thermostat. See figure 3. The FAN ton from the HOME screen to display the Filter Reminder
button can be used to select either continuous fan mode or Settings screen as shown in figure 12.
auto fan mode.
Filter Reminder Settings

0
If continuous fan mode is enabled, the fan will run continu-
ously regardless of whether the heating or cooling equip- Filter
ment is running. Also, ON will be displayed in the FAN box
as shown in figure 10.

Fan ON with Icon

ROOM
73 FAN
ON
Figure 12
The default setting for the filter reminder is 0, which dis-
SYSTEM ables the function. Use the UP arrow while in the Filter Re-
minder Settings screen to select the desired interval be-
tween reminders. It may be necessary to press the UP
HEAT
arrow several times to access the desired setting. The
HOME screen will reappear about 10 seconds after the ar-
Figure 10 row key has been pressed for the final time.
After the programmed interval has elapsed, the FILTER re-
minder will be displayed as shown in figure 13. After the fil-
If auto fan mode is selected, the fan will only run when the ter has been changed, reset the filter reminder by pressing
heating or cooling equipment is running. In this case, AUTO the SETTINGS button for 4 seconds. The screen will blink
will be displayed in the FAN box as shown in figure 11. for a few moments to indicate that the timer has been reset.

Page 4
Display of Filter Reminder DOWN arrow keys to the right of the display screen. The

72
balance point setting will increase by 1°F each time the UP
key is pressed. The balance point setting will decrease by
ROOM FILTER
1°F each time the DOWN key is pressed.
After the desired balance point is reached, the HOME
FAN
screen will reappear after about eight seconds.
AUTO NOTE − The balance point feature allows the temperature
to rise or fall 3°F above or below the setpoint. This prevents
SYSTEM excessive cycling of the equipment when the outdoor tem-
perature is near the balance point. For example, if the bal-
ance point is 40°F and the actual outdoor temperature is
35°F, the outdoor temperature must rise to 43°F before
HEAT
equipment adjustment occurs. Conversely, if the balance
Figure 13 point is 40°F and the actual outdoor temperature is 45°F,
the outdoor temperature must drop to 37°F before equip-
ment adjustment occurs.
Balance Point Service Indicator
NOTE − The balance point is only available with the out- When abnormal equipment operation is detected, the
door sensor. SERVICE indicator will flash on the upper-right corner of
If the optional outdoor sensor (X2658) is connected to the the screen. This indicates that the equipment requires ser-
thermostat, balance point adjustment is available. The bal- vice from a qualified service technician. The SERVICE indi-
ance point feature allows the measured outdoor tempera- cator is shown in figure 15.
ture to govern operation of the heat pump and backup heat Service Indicator Flashing

73
source.
Use the SETTINGS button to access the balance point set- SERVICE
ROOM
ting. If the outdoor sensor is attached to the thermostat,
press the SETTINGS button twice to access the Balance FAN
Point Settings screen (see figure 14).
AUTO
Balance Point Setting
SYSTEM

6P Figure 15
HEAT

SETPOINT 55 Thermostat RESET


Under some abnormal conditions, it may be desirable to re-
set the thermostat to its default condition. The RESET but-
ton can be used to return the unit to normal operation after
Figure 14 an occurrence such as an electrical storm or power outage.
The RESET button is an unlabeled, recessed button lo-
The balance point can be set at any temperature between cated behind the door on the right−hand side of the thermo-
1°F and 55°F (−17°C to 13°C). A balance point setting of stat, just below the SETTINGS button. The RESET button
zero disables the balance point function (in this case, the is visible in figure 3. Use a paper clip or small pencil to press
thermostat behaves as if no outdoor sensor is attached). the RESET button. After the RESET button is pressed, the
The default balance point setting is 55°F. thermostat settings will return to the defaults listed in the
To adjust the balance point up or down, press the UP or Default Settings section.

Page 5
Default Thermostat Settings Table 2
Default Thermostat settings are in table 1.
51M33 Terminal Designations
Connections Description
Table 1
Default Thermostat Settings O Reversing valve, cool active

Mode Heat B Reversing valve, heat active

Setpoint 70°F (or 21°C) R 24VAC

Fan Auto G Fan control

Filter Reminder OFF (reminder setting = 0) Y1 First stage cooling/heating, compres-


sor generated
Equipment Protection reset back to zero
W1 Auxiliary heating, furnace generated
Timers
L Service Indicator
Technical Specifications C 24VAC common
Thermostat Type E Emergency heat
Electronic nonprogrammable thermostat for 1H/1C, heat T Outdoor temperature sensor
pump with electric or gas backup heat source, non−power connection 1
robbing applications. T Outdoor temperature sensor
Power Supply Range connection 2
18VAC − 30VAC (24VAC nominal), 60Hz
Equipment Protection Timers
Temperature Display Minimum Compressor OFF time: 5 minutes
Display Scale: Fahrenheit or Celsius user selectable (via
Minimum Compressor ON time: 4 minutes
DIP switches)
Minimum Furnace ON time: 3 minutes
Display range: 35°F (2°C) to 99°F (37°C)
Display resolution: 1°F (1°C) Minimum backup furnace cycle time (elapsed time be-
Display Accuracy: +/−1°F tween any furnace activation and the next furnace activa-
tion): 6 minutes.
Temperature Measurement Range
Minimum elapsed time between any compressor activation
Measurement Scale: Fahrenheit
and the next compressor activation: 6 minutes.
Measurement Range: 35°F to 99°F
Measurement Resolution: 0.5°F NOTE − All protection timers (except the compressor OFF
Measurement Accuracy: +/−1°F timer) can be over−ridden if a heating or cooling demand is
Field Offset: via DIP switches to +/−3°F initiated or terminated using the UP, DOWN, HEAT, or
COOL buttons.
Sampling Method: temperature measurements sampled
every 15 seconds. Displayed temperature is the average of Equipment Protection Override
the last four measurements. Both the minimum compressor OFF timer and the mini-
Temperature Setpoint Range mum equipment cycle timer can be over−ridden by press-
Setting range: 50°F (10°C) to 90°F (32°C) ing and holding either the HEAT or COOL button down for 4
Setting resolution: 1°F (1°C) seconds.

Fan Control Over−Temperature Protection


AUTO or ON modes. Thermal mechanical switch opens W1 at 93°F+/−6°F.
Backup Heat Source Selection Filter Reminder
Electric or gas furnace, selectable via DIP switch #5 (Aux or Settings of 0 (Off), 1, 3, 6 or 12 months are available. When
Dual, respectively). See also Thermostat Output section. programmed time has elapsed, a FILTER indicator is dis-
I/O Relays played.
All thermostat relays are latching type to minimize power Balance Point
consumption. See table 2. 0°F (OFF) to 55°F, user selectable.

Page 6
Service Reminder
The SERVICE indicator is displayed only under the follow-
IMPORTANT
ing conditions: Power must be applied for at least six consecutive
hours prior to a power loss in order for memory to be
 if the thermostat Y1 terminal has been activated retained for the specified time.
with 24VAC for at least 5 minutes, AND the L
terminal is shorted to the R terminal; LCD Backlight
Activated for 8 seconds when any key is pressed.
OR
NOTE − During an electrical storm or similar disturbance,
 if the thermostat Y1 terminal has been activated the backlight may activate for a few seconds. This is normal
with 24VAC for at least 5 minutes, AND the L and will no longer occur after the electrical disturbance has
terminal is shorted to the C terminal. passed.
Thermostat Operating Conditions
Power Loss/Recovery
35°F to 105°F, 5% to 90% RH
Thermostat memory is retained for a minimum of 24 hours Thermostat Storage Conditions
during a power loss (includes retention of programmed −40°F to 185°F, 5% to 95% RH
temperature setpoint, heat/cool and fan mode settings, fil-
ter reminder status, and equipment protection timers). Af- Thermostat Output Table
ter 24 hours of power loss, programmed settings will be lost Table 3 (see page 8) provides details of the 51M33 ther-
and replaced with default settings. mostat output states for various input conditions.

Page 7
Table 3
Thermostat Output States
Condition W1 Y1 G O E
Electric Heat Backup − No Outdoor Sensor
small heat demand X X
large heat demand X X X
emergency heat demand X X
cool demand X X X
no demand dc
Gas Heat Backup (Dual Fuel) − No Outdoor Sensor
small heat demand X X
large heat demand X
emergency heat demand X
cool demand X X X
no demand dc
Electric Heat Backup − Outdoor Sensor Attached
small heat demand (BBP) X X
large heat demand (BBP) X X X
small heat demand (ABP) X X
large heat demand (ABP) X X
emergency heat demand X X
cool demand X X X
no demand dc
Gas Heat Backup (Dual Fuel) − Outdoor Sensor Attached
small heat demand (BBP) X
large heat demand (BBP) X
small heat demand (ABP) X X
large heat demand (ABP) X
emergency heat demand X
cool demand X X X
no demand dc
NOTE −
 X = output is activated with 24VAC
 dc: does not care (output can be in either state, i.e., either active or inactive)
 BBP: outdoor temperature is below balance point
 ABP: outdoor temperature is above balance point
 small heat demand: temperature is between (setpoint − 1.5°F) and (setpoint − 0.5°F), and 30-minute upstage
timer has not expired (see Normal Heat Mode graph)
 large heat demand: temperature is below (setpoint − 1.5°F), or 30-minute upstage timer has expired (see Nor-
mal Heat Mode graph)
 the state of the B terminal is opposite the state of the O terminal.
 data above are tabulated for AUTO fan setting. If fan setting is ON, the fan is activated in all cases.

Page 8