Date SECTION 13400

Project Number MEASUREMENT AND CONTROL INSTRUMENTATION


Project Name Page 1

PART 1 GENERAL

1.1 Section includes

A. Dissolved oxygen transmitter for continuous monitoring in water.

1.2 Measurement Procedures

A. The method of measuring dissolved oxygen will be with replaceable Clark sensor.

1.3 Alternates

A. Techniques such as luminescent detection methods are not acceptable.


B. Techniques that do not use an ion membrane are not acceptable.

1.4 System Description

A. Performance Requirements
1. Measurement range: 0 to 50 mg/L
2. Accuracy: ±0.5% of full scale
3. Response time: 22 seconds

1.5 Certifications

A. CE and C-tick approval


B. Emission: IEC/EN 61000-6-3
C. Immunity: IEC/EN 61000-6-2

1.6 Environmental Requirements

A. Operational Criteria
1. Sample temperature: 0 to 40 °C
2. Operating temperature: -40 to 60 °C

1.7 Warranty

A. The product includes a one-year warranty from the date of shipment.

1.8 Maintenance Service

A. Scheduled maintenance:
1. Replace sensor every 2 years
2. Calibrate every 4 months
B. Unscheduled maintenance: Cleaning as needed based on environmental conditions.

PART 2 PRODUCTS

2.1 Manufacturer
Date SECTION 13400
Project Number MEASUREMENT AND CONTROL INSTRUMENTATION
Project Name Page 2

A. Hach Company, Loveland, CO

2.2 Manufactured Unit

A. EVITA INSITU OXY Dissolved Oxygen Transmitter


1. Model 4100 ball float style
2. Model 4150 probe style
3. Model 3150 probe style specific to fish farming applications

2.3 Equipment
A. Ion-selective membrane is antibacterial.
B. Transmitter enclosure is PBT/PC, rated at IP68
C. Stainless steel mounting bracket with pivot function.
D. Power supply needed: 12 to 30 Vdc

2.4 Components

A. Standard equipment
1. Transmitter
2. Universal signal converter (USC)
3. Mounting bracket
B. Included replacement parts
1. Membrane cartridge
C. Dimensions
1. Model 4100: 240 mm diameter
2. Models 4150 and 3150
a. Diameter: 50 mm
b. Length: 180 mm
D. Weight
1. Model 4100: 2 kg
2. Models 4150 and 3150: 1 kg

2.5 Accessories

A. Telecommunications module
B. Moisture barrier paste

PART 3 EXECUTION

3.1 Preparation

A. Can be mounted to handrail or flat surface.

3.2 Installation

A. Contractor will install the sensor in strict accordance with the manufacturer’s instructions and
recommendation.
B. Manufacturer’s representative will include a half-day of start-up service by a factory-trained
technician, if requested.
Date SECTION 13400
Project Number MEASUREMENT AND CONTROL INSTRUMENTATION
Project Name Page 3

1. Contractor will schedule a date and time for start-up.


2. Contractor will require the following people to be present during the start-up procedure.
a. General contractor
b. Electrical contractor
c. Hach Company factory trained representative
d. Owner’s personnel
e. Engineer

END OF SECTION