Professional Documents
Culture Documents
pp ication o ing in
esonant jroun 48 per cent of systems at 22 kv and above
now resonant grounded were previously
Power Systems in the United States delta cent),(33
systems
(15 per per cent)altogether
whereas or new systems
52pe
cent were operated with some kind of
ERIC T. B. GROSS EDWARD W. ATHERTON neutral grounding before the change to
FELLOW AIEE ASSOCIATE AIEE resonant grounding was made. It is of
particular interest that a large percentage
of systems (35 per cent) had previously
Synopsis: Previous investigations indicated how the number of ground fault neu- been solidly grounded.
a treind toward increased application of tralizers (or Petersen coils, as these This report covers all systems which
resonant grounding in the United States. reactors are called frequently) increased were or had been in operation with res-
The application of resonant grounding in
power systems operating at voltages froni from one in 1921 to 87 in 1949 and that onant grounding at the end of 1949 and
2.4 kv to 230 kv has been analyzed on the resonant grounding had been applied in the breakdown of answers from 51 sys-
basis of answers to a questionnaire received miost systems for much longer periods than tems is given in the left section of Figure
from all organizations using such grounding. one year. Figure 2 shows further that 3. It can be expected that changes from
Experiener
Experience with
been very satisfactory. grunimn
resonant grounding has
withreoaT The equipment re-
quires practically no maintenance and
there is a trend toward greater use of
coils that have continuous rating (or ex-
other grounding methods to resonant
grounding also will be made in future
hardly any attention since detuning is per- tended time rating as defined in AIEE years. However, it may be mentioned
missible within reasonable margins. The Standard number 324). Whereas, in that 9 per cent of all systems' reporting
major field of application of resonant 1943 only IS per cent of the ground fault in 1947 were then ungrounded, most of
grounding is at voltages of 69 kv and below.
Operation on sustained faults has been suc-
194,roly 1per cn oegrod u
neutralizers, then in service, were de-
i
wered the ungounded mso
them at voltages below 115 kv.
v
cessful in many systems for hours anid even signed to permit operation with sustained There also were changes from resonant
days. More equipment designed for ex- ground faults, 40 per cent of nearly twice grounding to some other method, though
tended time rating than for "10-ininute" as many coils permitted such operation in in not many systems. Figure 4 contains a
rating has been installed in the last few 1949 (an increase in the number of such summary of all ground fault neutralizers
years. Many users of "10-minute" equip-
ment feel that operation on sustained faults coils from 9 to 35). The number of 10- (single-phase or 3-phase)'722 built for use
would 'have additional advantages. m-inute" coils decreased accordingly from in this country. The number of coils
82 per cent in 1943 to 60 per cent in 1949 taken out of service is indicated in Figure
and there is reason to believe that the two 5 which contains a classification by volt-
THE latest general AIEE report on curves "B" and "C" on Figure 2 will in- age and by time rating. Most ground
Grounding Practices' indicates that tersect again before long. fault neutralizers taken out of service by
there is a trend toward greater use of res- 1949 were "10-minute" coils (9 of 61 or
onant grounding2 in this country. Figure Questions and Answers 14.8 per cent). The reason for discon-
1, which is based on this report3 shows tinuation of resonant grounding was
this trend clearly. Amongst the many GROUNDING PRACTICES nearly always that interconnection with a
systems at and above 22 kv that were Considering that other grounding meth- large system grounded in a different
investigated, 6.8 per cent of the total ods' are well established (74 per cent of all
mileage consisted of lines which belong to systems', corresponding to 78 per cent of Paper 51-64, recommended by the AWIE Protective
systems using resonant grounding. the whole 1mileage under investigation, Devices Committee and approved by the Technical
Program Committee for presentation at the AIRE
The fact that resonant grounding is were solidly grounded), it would appear Winter General Meeting, New York, N. Y., January
22-26, 1951. Manuscript submitted October 20,
finding wider application in this country, resonant grounding applications would be 1950; made available for printing December 7,
especially at voltages below 115 kv, seems confined to new systems and to existing 1950.
to be of particular significance and this ungrounded (or delta) systems. An analy- ERIC T. B. GRo°SsIsl jProifesIso°rofPoer SystemsOIg
investigation was undertaken in order to sis of the distribution of grounding Chicago, Ill., and EDWARD W. ATHERTON iS writh
answer many pertinent questions with methods as indicated in Figu.re 1 shows, the l-T-E Cicuithl Breaaker Comtpany, Philaelp'trh'i.
information from organizations with however, that many systems that now are Engineering at the Illinois Institute of Technology
operating experience in this field. Ques- resonant grounded were previously not when most of this investigation was made.
~ wer~senllto oeratrs
tionnaires~~~
tionaire ~ sen
Wer wh.nruddbtgone
wro to al oprtr .c ut gouncec .lnnsm
tngronc sme onerte The authors want to express their thanks to Harold
H. Brown, Cedar Rapids, Iowa, and Eugene Herzog.
could provide answers on basis of at least manner. The aitswers to the question Dayton, Ohio, for valuable assistance and informa-
one year's experience and this report "what the grounding practices were be-
covers all systems that had been so oper- fore the installation of resonant groun1d-
nairen and to the adionistrhatidorn of Illinois Institute
heYspecsrtiallly to Eh R. whitehead, for
pofvTecnolgy
ated by the end of 1949. Figure 2 shows ing" are summarized in Figure 3. It is possible.
z
_
zC -EXTENDED TIME 511 (60%)
Figure 2 (right). RATING
Ground fault . ° 42(bi)r 45
0 neutralizers in oC
w
service,14 1921- 2C -
0. SOLID 9(j18I%) I
1920 1925 930 1935 1940 1945 1950
C~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
20 /- ~~~~~~~~~~~~~~~1.
344 22i 1 2
LD1104>Wye * q /@e \N
{ k eWt%)
19-DiK }@e p > \per
0 W os, '>}"£$sj te° t0g8. right.
cent said the number of taps were just
However, answers were received
& * co2°1.
from 48 systenis (100 per cent) about the
/HIier^ilI "E8R. 00 s s e jILi * N J. number of tap changes per year and these
* * L o|L. data are broken down in Table II. The
0 \
5\I100o KAN& s
L
questions
f
taps | %
asked were: "How often are
@ ochanged?" and "What is the average
AR
PM OKLA N number of changes per year?"
Is
> e 1 l 1 A;g;;>j; yIn most cases power transformers are
available for the connection of single-
phase reactors; hence, of 53 systems (100
0 o FL (z_ i nper cent) reporting, 70 per cent use power
transfonners with single-phase coils and
9 MAJOR PART OF SYSTEM ~ < _/ \ \ only 30 per cent use 3-phase equipment.
IN
THINOR
THIS STATE _:
STARTE OF SYSTHowever, in a few systems when more
than one coil is used in the system, and
when a power transformer was not avail-
140
Fiiure6
| Figure6(above).(bov).KV o 5o MAXIMUM AND AVERAGE
115 Geographic dis- 24 33 80 MILEAGE OF SYSTEMS
u0 |tribution of reso- 6.6 63 (EQUIVALENT)
!m - EXTENDED TIME RATING nant grounded 13.8 556
> 88 TEN MINUTE RATING systms, 1949 20
22o 0____________________ (LARGEST SYSTEM
AT THIS VOLTAGE)
69 J b4 |
Figure 7 (left). A IW_465 1500
22
22! Figure 8 (right). e 5
>) 13.8 ~1|Mileage of reso- 9
6. 2 6.6 | ~~~~~~~~~~~~systems
nant grounded 148
classified 14015 -XX,,,,,,,,. 03
MILES
2.4 _2 by voltage
(Iowa Public Service Co.,) Sioux City, Iowa 20. PETERSEN COIL TUNING DETBRMINES PUR-
FORMANCEc, H. W. Hartzell, S. S. Cook, A. A.
Southern California Edison Company, Los Johnson. Electrical World (New York, N. V.),
Angeles, Calif. volume 130, 1948, pages 62-65.
Southern Indiana Gas and Electric Com- 21. RESONANT GROUNDING OF DISTRIBUTION
pany, Evanisville, Ind. SYSTEMS, E. Herzog. Proceedings, Midwest Power
Southwestern Public SrieCmay
Serviceompany, Conference
237-40. (Chicago, Ill.), volume 11, 1949, pages
Amarillo, Tex. 22 OPERATION OF A GROUND-FAULT NBUTRALIlER
]U. S. Departmenit of the Interior, Bureau of ON A REGULATED DISTRIBUTION SYSTEM, H. R.
Reclamationi, Denver, Colo. Tomlinson, F. B. Hunt. AIEE Transactions,
Westinghouse Electric Corporation, East volume 68, part 11, 1949, pages 1321-28.
Pittsburgh, Pa. 23. PRACTICAL EXPERIENCBS WITH RESONANT
Wiascdionsin Michigan Power Coinpany,Appl GROUNDING IN A LARGE 34.5-Ky SYSTEM, H. H.
Brown, Eric T. B. Gross. AIEE Transactions.
ton, Wis. volume 69, plarta s, 1950, pages 1400-05.
References
1. PRESENT D)AY GROUNDING PRACTICES ON
POWER SYsTEms, CAt Committee Report. AaIEE Discussion
Traersactions, volume 6,51947, pages 1525-51.
2. THE WaY AND How op RESONANT GROUNDING,
Eric T. B. Gross. Electric Light and Power (Chi-
cago,UI.), volume 25, July and August 1947. Byron Evans (Uslited States Bureatll o
3. Reference C. page 1526. Reclamatioll, aenver, Colo.): The authors
4. NEUTRAL GROUNDING DEvicEs. m EE Stand- have preseinted data that will be of con-
ard Number 32, 1947. siderable interest to system designers ande
5.
6.
Reference 1, Table 25, page 19543.
THE RELATION OF THE PETERSEN SYSTEM O
Opl
ra tors.owethe groundit mears that
fon pereminta blas, rappea
GRouNDING POWER NETWORKS TO INDUCTIVE increasitig
resonant and solid groundingandareungrounided
EFFECTS IN NEIGIIBORING COMMUNICATION CIR- while reactance, resistance,
CUITS, H. M. Tmeblood. Bell System Technical applicatiolis are decreasing. In general,
Jourrnkal
(New York, N. Y.), volume 1, 1922, page resonant grounding has its best application
39eres maimmcuen.Coe n cilOP PgA on systems of about 69 kv and below, and k
7. 0PERATING PERFORMANCE PETERSEN
EARTH COIL, J. M. Oliver, W. W. Eberhardt.
shuld like to see Figure 1 of this paper
ilo
AIEEtransactions, volume 42, 1923. page 435-45 drawn to show the grounding methods used
and volume 45, 1926, page 165-68. for systems ill this voltage range.
8. PETERSEN COIL TESTS ON 140 Ky SIYSTEM. Figure 6 of the paper seems to indicate the
Figure 12. Ground fault neutralizer For ex- J. R. North, J. R. Eaton. Electrical Engineeri ng greateSt application of resonant grounding
tended time rating for a 69-kv system, 40- (AIEE Transactions), volume 53, January 1934, to be in the mountain states and the more
amperes maximum curfent. Core and coil pages 63-74. northern states extending from the Dakotas
asml.CortesyWestingoueElectric 9. TEST AND OPERATION OP PETERSE&N COIL ON eastward to the Atlantic seaboard, with few
100-Ky SYSTEM OP PUB3LIC SE3RVICE CO0MPANY OF
Corporation COLORADO, W. D. Hardaway, W. W. Lewis. Electri- if any applications in the southeastern
X____ D____ - locating the exact point of the fault. The U0 _C SOLID
o 60 demonstration by the fault is so slight that
z t soL1o operators have walked right by the fault z
without noticing, unless it was very quiet. It
cw 40 _ - To realize fully the advantage of the ground w 70
fault neutralizer, it will therefore be neces-
sary to provide a fault-detection system
oL
925
J