Professional Documents
Culture Documents
Electrical Installation Guide - Residential PDF
Electrical Installation Guide - Residential PDF
Contents
Q1
© Schneider Electric - all rights reserved
Enclosure
Service connection
Distribution board
Incoming-supply
circuit breaker
Lightning protection
Combi surge arrester
Overcurrent
protection
and isolation MCB phase and neutral
Protection against
direct and indirect
contact,
and protection
against fire
Differential Differential load
Q2 MCB switch
Remote control
Remote control switch
TL 16 A
Energy management
© Schneider Electric - all rights reserved
On
On installations
installations which
which are
are TN earthed,
earthed, the
the supply
supply utilities
utilities usually
usually protect
protect the
the
On installations
On installations which
which are TN earthed, the
are TN supply utilities usually protect the
installation
installation simply
installation simply by
simply by means of
by means of sealed fuse
fuse cut-outs immediately
immediately upstream of of the
installation simply by means of sealed
sealed fuse cut-outs
cut-outs immediately upstream
upstream of the
the
meter(s)
meter(s)
meter(s) (see
(see
(see Fig.
Fig.
Fig. N2
Q2).
P2).). The
The
The consumer
consumer
consumer has
has
has no
no
no access
access
access to
to
to these
these
these
meter(s) (see Fig. N2 ). The consumer has no access to these fuses. fuses.
fuses.
fuses.
Meter
Meter
Meter
Meter
Meter
Meter
Fuse
Fuse …
Fuse …
…
… or
or …
or …
…
… Circuit breaker
Circuit breaker
Circuit breaker
breaker
Fuse
Fuse
Fuse …
… or
or
or …
… Circuit
Circuit
Circuit breaker
breaker
depending
depending on
depending on
on
on Distribution
Distribution
Distribution
depending
depending on Distribution
Distribution
earthing
earthing system
earthing system
system board
board
board
earthing
earthing system
system board
board
Fig.
Fig.
Fig. N2
N2 :: Components
Q2
Fig. P2
P2 Components of
of aaacontrol
Components of control and
control and distribution
and distribution board
distribution board
board
Fig.
Fig.
Fig. N2 ::::Components
N2 Components ofaa
Componentsof
of a control
controland
control anddistribution
and distributionboard
distribution board
board
The incoming
The incoming supply
supply circuit
circuit breaker
breaker (see
circuit-breaker (see Fig. N3
(see Fig.
N3
Q3)))
Fig. P3)
Fig.
Fig.
Fig.
N3
N3 :: Incoming-supply
Q3
Fig. P3
P3
Incoming-supply circuit
circuit breaker
Incoming-supply circuit-breaker
breaker
Fig.
Fig.
Fig. N3 ::::Incoming-supply
N3 Incoming-supplycircuit-breaker
Incoming-supply circuit
circuit breaker
breaker The consumer
consumer is allowed allowed to operate
operate this CB CB if necessary (e.g (e.g to to reclose
The
The consumer is is allowed to to operate this necessary (e.g.
this CB ifif necessary (e.g to recloseititititififififthe
toreclose
reclose
the
the CB
the
current
has consumption
tripped due to current has exceeded
exceeded
consumption the authorized
authorized
exceeded the limit; to open
open it in
authorized in case
case of it in
current
current consumption
consumption has
has exceeded the
the authorized limit;
limit; to open ititlimit;
to in caseto open
of
of
emergency
case
emergency or for
of emergency
or for isolation purposes).
or for isolation purposes).
emergency or for isolation
isolation purposes).
purposes).
The rated
rated residual current current of the the incoming circuit-breaker
circuit breaker in the the earth leakage
leakage
The rated residual
The residual current of of the incoming
incoming circuit breaker in in the earth
earth leakage
protection shall
protection shall be be 300
300 mA.mA.
protection shall be 300 mA.
If the
the installation is is TT,
TT, thethe earth
earth electrode
electrode resistance
resistance shall shall be be less
less than
than
If installation is TT,
If the installation the earth electrode
electrode resistance
resistance shallshall be be less
less than
than
50 V V
R = 50 =
R = 300 mA = 166 Ω ...In166 Ω . In practice, the earth electrode resistance of a new installation
installation
In practice,
practice, the the earth
earth electrode
electrode resistance
resistance of of aa new
new installation
300 mA
R
shall
shall be
shall
shall be less
be
be less than
less
less than 80
than
than 80 Ω
80
80 Ω (( R ).)...
Ω
2
2
The control
control and
The control and distribution
distribution board board (consumer
(consumer unit) unit) (see Fig. P4)
(see Fig. Fig. N4
Q4)
N4 ))
The
This board
and
comprises:
distribution board (consumer unit) (see
This
This board
board comprises:
comprises:
b
This
bA board comprises:
control
control panel
panel for for mounting (where appropriate) the the incoming
incoming supply supply circuit-
circuit-
c
c A control
A control panel for mounting (where (where appropriate)
appropriate) the the incoming supply circuit
breaker
breaker andpanelotherfor mounting
control auxiliaries, as required incoming supply circuit
breaker
breaker and other
and other control
control auxiliaries,
auxiliaries, as required
bbA distribution
distribution panel
panel for
for housing 1, 2as or required
3 rows (of 24 Acti multi99units) units)ororsimilar
similarMCBs MCBs
c
c A distribution
A distribution panel
panel for
for housing 1,
housing 1, 2 2 or
or 33 rows
rows (of(of 2424 multi
multi 9 9 units)
units) or or similar
similar MCBs MCBs
or
or fuse
fuse units,
units, etc.
or
or fuse
fuse units,
units, etc.
etc.
b Installation accessories
b Installation accessories for for fixing
fixing conductors,
conductors, and and rails
rails for
for mounting
mounting MCBs, MCBs, fuses fuses
c
c Installation accessories
Installation accessories for fixing fixing conductors,
conductors, and and rails
rails for
for mounting
mounting MCBs, MCBs, fuses fuses
bases,
bases, etc, neutral busbarfor and earthing bar, and so on
bases,
bases, etc, neutral
etc,cable
neutral busbar
busbar and earthing
and earthing bar,
bar, and so
and so on on
bb Service ducts or conduits, surface
surface mounted
mounted or in
or in cable
cable chases
chases embedded
embedded in in
c
c Service cable
Service cable ductsducts or or conduits,
conduits, surfacesurface mounted
mounted or or in
in cable
cable chases
chases embedded
embedded in in
the
the wall
wall
the wall
the wall
Note: to
Note:
Note:
to facilitate future modifications
facilitate future
to facilitate
facilitate future
modifications to
future modifications
modifications to
to the
the installation,
to the
installation, itit is
the installation,
installation, itit is
is recommended
recommended to
is recommended
recommended to
to keep
keep
to keep
keep
Note:
all to
all relevant
relevant documents (photos, diagrams, characteristics,
characteristics, etc.) in
etc.) in aa suitable
suitable location location
all
all relevant
relevant documents
documents (photos,
(photos, diagrams,
diagrams, characteristics,
characteristics, etc.)
etc.) in
in a
a suitable
suitable location
location
close
close to to the
to the distribution
the distribution
distribution board.board.
board.
close
close
The to the distribution board. at N3
P3
N3
The board
The board
board
should
should
should
be
be installed
be installed
installed at a
at
height
height such
aa height
height such that
such that the
that the operating
the operating handles,
operating handles, indicatingindicating
indicating
The boarddials
indicating should
dials (of meters)
(of be installed
meters) etc.,
etc.,atarea
are between
between such 1 metre
1 metre
that and
the
and 1.80 metres
operating
1.80 metres
handles,from the
from the floor
floor
dials
dials (of
(of meters)
meters) etc.,
etc., are
are between
between 1
1 metre
metre and
and 1.80
1.80 metres
metres from the
from the floor
floor
(1.30 metres
(1.30 metres in in situations
situations where
where handicapped
handicapped or
or elderly
elderly people
people are
are concerned).
concerned).
Fig.
Fig. N4
N4 :: Control
Q4
Fig. P4 Control and
Control and distribution
and distribution board
distribution board
board (1.30 metres
metres in in situations
situations wherewhere handicapped
handicapped or or elderly
elderly people
people are are concerned).
concerned).
Fig.
Fig.
Fig.
Fig. P4
N4 ::::Control
N4 Control and
Controland distribution
anddistribution board
distributionboard
board (1.30
Lightning arresters
Lightning arresters
arresters
Lightning
The
The installation of
installation
The installation of lightning
lightning arresters
installation of arresters at
of lightning at the
lightning arrestersthe service
service position
arresters atat theposition of
the service of aa LV
LV installation is
service position
position ofof a
a LV
LV installation is is
The
strongly
strongly recommended
recommended for
for installations which include sensitive (e.g installation
electronic)
strongly
strongly recommended
recommended for
for installations which
installations which include
include sensitive
sensitive (e.g
(e.g electronic)
electronic)
equipment.
equipment.
equipment.
equipment.
These
These devices
devices must automatically disconnect themselves from the installation in
These
These devices
devices must automatically
must automatically disconnect themselves
themselves fromfrom the
the installation
installation in
case
case of
of failure
failure or be protected by adisconnect
MCB. In In the
the case
case ofof residential
residential installations,inthe
installations,
case of
case of failure or
or be
be protected
protected by by a
a MCB.
MCB. In In the
the case
case ofof residential
residential installations,
installations, the
the
the of afailure
use use of
300a 300
mA mA differential
differential incoming
incoming supply
supply circuit-breaker
circuit-breaker typetype S (i.e
S (i.e slightly
slightly time-
use of
use of a
a 300
300 mAmA differential
differential incoming
incoming supply
supply circuit
circuit breaker
breaker type
type S S (i.e
(i.e slightly
slightly time-
time-
time-delayed) will provide
delayed) will provide effective
effective earthearth
leakageleakage protection,
protection, while,while,
at theatsame
the same
time, time,
will
delayed) will
delayed) will provide
provide effective
effective earth
earth leakage
leakage protection,
protection, while,
while, at
at the
the same
same time,
time, will
will
will
not not
trip trip unnecessarily
unnecessarily each each
timetime a lightning
a lightning arrester
arrester discharges
discharges the the current
current (of an
(of an Q3
not
not trip
trip unnecessarily
unnecessarily each
each time
time a
a lightning
lightning arrester
arrester discharges
discharges the
the current
current (of
(of an
an
overvoltage-surge) to
overvoltage-surge) to earth. earth.
overvoltage-surge)
If, in
If, in aa TT
TT scheme, the the value
value of
of 80
of 80 Ω for
Ω
80 Ω
Ω for the
for the
the overvoltage-surge) to earth.
If, in a TT scheme,
scheme, the value
value of 80 for the
resistance of
resistance
resistance of the
of the electrode
the electrode can
electrode can not
can not be
not be met
be met then,
met then,
then, Resistance value
value of
Resistance value of the
the earth electrode
earth electrode
electrode
30 mA RCDs must be installed to take over the Resistance
In
In the
the case
case where
where the
of the
the resistance
earth
resistance to
to earth
earth exceeds
exceeds 80
80 Ω,
30 mA
30 RCDs must
mA RCDs
RCDs must be
must be installed
be installed to
installed to take
to take over
take over the
over the In the
the case where
where the
the resistance
resistance to
to earth exceeds Ω, one
exceeds 80 one or
or several
Ω, one
80 Ω, several 30 mA RCDs
one oror several RCDs
several 30
30 mA
mA RCDs
function of the earth leakage protection of the In
shouldcase
should be
be used
used in
in place of
of the earthearth
the earth leakage
leakage protection of
of the
the incoming supply RCDs
incoming supply
function of the earth leakage
earth
function of the earth leakage protection
leakage protection of
protection of the
of the
the should be used in place
place of the earth leakage protection
protection of the incoming supply circuit
© Schneider Electric - all rights reserved
incoming supply
supply circuit
circuit breaker
breaker should be used in place of the earth leakage protection of the incoming supply circuit
circuit-breaker.
circuit-breaker.
incoming
incoming supply circuit-breaker breaker.
breaker.
Schneider Electric
Electric -- Electrical
Schneider Electric
Schneider Electrical installation
Electrical installation guide
installation guide 2005
guide 2016
2005
Schneider Electric
Schneider
Schneider Electric ---- Electrical
Electric Electrical installation
Electrical installation
installation guide
guide
guide 2007
2007
2005
2005
Q - Residential and other special locations
300 mA
30 mA 30 mA
differential relay
This type of CB affords protection against fault to earth, but by virtue of a short time
delay, provides a measure of discrimination with downstream instantaneous RCDs.
Tripping of the incoming supply CB and its consequences (on deep freezers, for
example) is thereby made less probable in the event of lightning, or other causes of
voltage surges. The discharge of voltage surge current to earth, through the surge
arrester, will leave the type S circuit-breaker unaffected.
300 mA - type S
30 mA 30 mA 30 mA
1
Diverse High-risk location Socket- Bathroom and/or
circuits (laundry room) outlet shower room
circuit
2
Fig. Q6 : Installation with incoming-supply circuit-breaker having short time delay differential
protection, type S
Fig. Q8 : Circuit division according to utilization Fig Q9 : Recommended minimum number of lighting and power points in residential premises
Q6
© Schneider Electric - all rights reserved
Individual-load circuits
Water heater 2.5 mm2 4,600 W Circuit-breaker 25 A
(4 mm2) Fuse 20 A
Fig. Q11 : C. s. a. of conductors and current rating of the protective devices in residential installations (the c. s. a. of aluminium conductors are shown in brackets)
Installation rules
Three principal rules must be respected:
1 - It is imperative that the three lengths of cable used for the installation of the surge
arrester each be less than 50 cm i.e.:
b the live conductors connected to the isolating switch
b from the isolating switch to the surge arrester
b from the surge arrester to the main distribution board (MDB) earth bar (not
to be confused with the main protective-earth (PE) conductor or the main earth
terminal for the installation.The MDB earth bar must evidently be located in the Q7
same cabinet as the surge arrester.
2 - It is necessary to use an isolating switch of a type recommended by the
manufacturer of the surge arrester.
3 - In the interest of a good continuity of supply it is recommended that the
© Schneider Electric - all rights reserved
Bathrooms and showers rooms are areas of high risk, because of the very low
resistance of the human body when wet or immersed in water.
Precaution to be taken are therefore correspondingly rigorous, and the regulations
are more severe than those for most other locations.
The relevant standard is IEC 60364-7-701.
Precautions to observe are based on three aspects:
b The definition of zones, numbered 0,1, 2, 3 in which the placement (or exclusion)
of any electrical device is strictly limited or forbidden and, where permitted, the
electrical and mechanical protection is prescribed
b The establishment of an equipotential bond between all exposed and extraneous
metal parts in the zones concerned
b The strict adherence to the requirements prescribed for each particular zones, as
tabled in clause 3
Zone 1* Zone 1*
Zone 2 Zone 3
Zone 2 Zone 3
Zone 0 Zone 0
0.60 m 2.40 m
2.40 m
0.60 m
2.25 m
Zone 1
Zone 0
0.60 m 2.40 m
Q8
© Schneider Electric - all rights reserved
Zone 0 Zone 0
Zone 1 Zone 2 Zone 3 Zone 1 Zone 2 Zone 3
2.25 m
Zone 1
Zone 0
0.60 m 2.40 m
2.40 m 2.40 m
Zone 3 Zone 3
2.25 m
(1) When the shower head is at the end of a flexible tube, the vertical central axis of
a zone passes through the fixed end of the flexible tube
0.60 m Q9
Prefabricated
shower
cabinet
© Schneider Electric - all rights reserved
0.60 m
Fig. Q15 : No switch or socket-outlet is permitted within 60 cm of the door opening of a shower
cabinet
Classes Classes
of external of external
influences influences
AD 3 AD 3
BB 2 Zone 3 BB 2
BC 3 BC 3
Dressing cubicles (zone 2)
AD 3 AD 3
BB 3
WC BB 2
BC 3 BC 3
AD 7
BB 3
BC 3
Shower cabinets (zone 1)
Classes Classes
of external of external
influences influences
AD 7 Zone 1 AD 3
BB 3 WC BB 2
BC 3 BC 3
Classes Classes
of external of external
influences influences
h < 1.10m
AD 3 Dressing room AD 5
BB 2 1.10m < h < 2.25m
BC 3 Zone 2
AD 3
BB 3
BC 3
h < 1.10m
AD 5 AD 7
1.10m < h < 2.25m BB 3
AD 3 Zone 2 Zone 1 BC 3
BB 3
BC 3
To the earth
electrode Metallic pipes
hi 2m
Water-drainage
piping
Gaz
Socket-outlet
Radiator
Lighting
Q11
© Schneider Electric - all rights reserved
Figure Q20 below summarizes the main requirements prescribed in many national
and international standards.
Note: Section in brackets refer to sections of IEC60364-7
(example: "section 701" means IEC60364-7-701)
v 30 mA RCDs
v Special supplementary
equipotential bonding
Fig. Q20 : Main requirements prescribed in many national and international standards (continued on opposite page)
Fig. Q20 : Main requirements prescribed in many national and international standards (concluded)
Q13
© Schneider Electric - all rights reserved