Ptouch Service PRV - P0098 - AZ - 0001 PDF
Ptouch Service PRV - P0098 - AZ - 0001 PDF
Ptouch
Service manual
3 INSTALLATION .......................................................................................................................... 4
4 SERVICE ........................................................................................................................................ 5
Features:
• Simple use;
• Surface mounted;
• 4.3 touch-screen;
• Display of functions and set points;
• Acoustic response to touch;
• Maximum fan speed setting for limited time period (BOOST);
• Blocking (locking) - protection from children;
• User menu for fan speed, mode, status, CO2 control settings.
Package includes:
• 1x Ptouch control panel;
• 1x Cable;
• 1x Manual;
• 2x Fastening elements (screw 3,9 x 25 DIN 7981 – 2 pcs nylon plug 5x25 – 2 pcs, hammered steel plug
12x30 – 2 pcs).
DIMENSIONS 2
3
EN
3 Ptouch installation on a plaster-board wall:
Ptouch installation on a plaster-board wall:
1 2 3
4 5 6
7 8
IMPORTANT: IT IS FORBID-
DEN to leave the remaining
remote controller’s cable in
the AHU’s control box!
1-2 Turn over the panel. Use a screwdriver to lift the cover as shown in fig. 2.
3 Take the cover apart.
4 Put it at desired location on the wall. The arrow must point upwards. Mark the positions of mounting
holes (distance center-to-center is 106 ± 0.5 mm). Also mark the position of the square hole for the cable
(30 x 20 mm).
5 Drill two 5 mm holes at the marked positions for nylon plugs and the hole throughout the wall to install
the cable. Insert the nylon plugs.
NOTE: You can use special metal plugs (included) instead of nylon ones.
6 Use included 2,9x16 DIN7981C screws and mount the panel to the wall as indicated in fig. 6.
Connect the included cable to the panel and pass another end of the cable through the square hole in
the wall.
7-8 Put the panel on the mounting bracket by aligning the upper identations. Then push the lower part
of the panel.
IMPORTANT: Do not forget to connect the cable before attaching the panel.
4
EN
SERVICE 4
4.1 Service login
I1
B1 B2
Number Function
I1 Entered code (masked) 4444
Number Function
B1 Clear last entered digit
5
EN
4 4.2 Service menu
B2 B3
B1 B4
B5 B8
B6 B7
B10 B11
B9 B12
B13
Number Function
B1 Ventilation mode settings
B2 Cooling settings
B3 Fan settings
B5 System settings
B7 Ventilation settings
B8 PI controller settings
6
EN
B11
B12
Anti-freezing settings
Filter settings
4
B13 Factory settings
F1 F4
F2 F3
Number Function
Ventilation mode:
Supply: maintain supplied air temperature;
Room: maintain extracted air temperature;
ByOutDoor: ventilation is controlled by supplied or extracted air tem-
F1
perature depending on OutDoor T.C setting. If outdoor temperature
exceeds OutDoor T.C setting, ventilation is controlled by extracted
air temperature. If outdoor temperature is lower than OutDoor T.C -
ventilation is controlled by supplied air temperature.
7
EN
4 2.4 Cooling settings
F1 F4
F2
F3
Number Function
Minimum allowed supplied air temperature when cooling.
F1 Range: [0-15 °C]
B2
B1
8
EN
Number Function
4
B1 Air supply fan settings
F1 F4
F2 F3
Number Function
Supply fan speed for Boost function.
F1 Range: [0-100 %]
9
EN
4 4.5.2 Air extraction fan settings
F1 F4
F2 F3
Number Function
Extract fan speed for Boost function.
F1 Range: [0-100 %]
10
EN
4.6 Modbus interface settings 4
F1 F4
F2 F3
Number Function
Parity:
None;
F1 Odd;
Even.
Baud rate:
F2
2400; 4800; 9600; 19200; 38400.
Stop bits:
F3 1 stop bit;
2 stop bits.
11
EN
4 4.7 System settings
F1 F4
F2 F3
Number Function
Heater type:
E_On/Off: Relay-controlled electrical heater;
E_0_10: 0-10V signal-controlled electrical heater;
F1
E_ESKM: Triac-controlled electrical heater;
W_VAL+-: 3-way valve actuator for water heating.
W_0_10: 0-10V signal-controlled valve actuator for water heating.
AHU type:
TK: Air supply chamber;
F3 RHEC: Re-cooperator with heat exchanger control;
RHEC: Re-cooperator without heat exchanger control;
Fan type:
F4 EC: 0-10V signal-controlled EC motor;
AC: AC motor controlled using three fixed voltages;
12
EN
4.8 Water heater settings 4
F1 F4
F2 F3
Number Function
F1 Threshold to force an increase of a returning water temperature.
13
EN
4 4.9 Ventilation settings
F1
F2 F3
Number Function
Supplied air fan indication:
F1 Percent: indicate fan state in %;
Pressure: indicate fan state in Pa.
14
EN
4.10 PI controller settings 4
B2 B3
B1 B4
B5
B6
Number Function
Adjustments of PI controller used by system to react to heating or
B1
cooling.
15
EN
4 4.10.1 PID adjustment screen
I1
F1
F2
Number Function
I1 Current setting indication
Number Function
Proportional coefficient.
F1
Range: [0-1000]
Integral coefficient.
F2 Range: [0-1000]
16
EN
4.11 Pressure sensor settings 4
F1
F2
Number Function
Pressure corresponding to 0V input signal.
F1
Range: [0-2000 Pa]
F1
F2 F3
17
EN
4 Number Function
CO2 level (in ppm) at minimum voltage (0 VDC).
F1
Range: [0-2000 ppm]
F1 F4
F2 F3
Number Function
Anti-freeze protection algorithm:
DewP/PlateT: Dew point and heat exchanger surface temperature
calculation-based;
F1
Toutside: Outside temperature based (DIBT);
TEsetpoint: Exhausted air temperature based;
Heat exchanger anti-freezing diagram-based;
Heat exchanger anti-freezing diagram-based.
18
EN
F1
Number Function
F1 Working hours till reminder to replace air filters.
F1
Number Function
F1
19