Remote control panel PRV

Ptouch
Service manual

Ragainės g. 100, LT-78109 Šiauliai, Lithuania


Tel. (+370 41) 540415
Fax. (+370 41) 540417
office@salda.lt
Art.-no. PRGPU081
www.salda.lt PRV_P0098_AZ_0001
TABLE OF 1 GENERAL INFORMATION ...................................................................................................... 3
CONTENTS
2 DIMENSIONS ............................................................................................................................. 3

3 INSTALLATION .......................................................................................................................... 4

4 SERVICE ........................................................................................................................................ 5

4.1 Service login ...................................................................................................................... 5

4.2 Service menu .................................................................................................................... 6

4.3 Ventilation mode settings ............................................................................................ 7

4.4 Cooling settings ............................................................................................................... 8

4.5 Fan settings menu ........................................................................................................... 8

4.5.1 Air supply fan settings ......................................................................................... 9

4.5.2 Air extraction fan settings ................................................................................ 10

4.6 Modbus interface settings ......................................................................................... 11

4.7 System settings ...............................................................................................................12

4.8 Water heater settings ................................................................................................... 13

4.9 Ventilation settings ........................................................................................................14

4.10 PI controller settings................................................................................................... 15

4.10.1 PID adjustment screen ................................................................................... 16

4.11 Pressure sensor settings ............................................................................................17

4.12 CO2 sensor settings ....................................................................................................17

4.13 Anti-freezing settings .................................................................................................18

4.14 Air filter settings .......................................................................................................... 19

4.15 Factory settings ........................................................................................................... 19


EN
GENERAL INFORMATION 1
Ptouch remote control panel is designed for:
• SALDA ventilation units and other devices based on PRV, MCB or ECO controllers;
• Modbus-controlled devices.
Remote control panels guarantee optimal comfort of operation, monitoring, maintenance and service. All
operations can be performed using remote panel, which displays the status of the system, fault reports
and service settings.

Features:
• Simple use;
• Surface mounted;
• 4.3 touch-screen;
• Display of functions and set points;
• Acoustic response to touch;
• Maximum fan speed setting for limited time period (BOOST);
• Blocking (locking) - protection from children;
• User menu for fan speed, mode, status, CO2 control settings.

Package includes:
• 1x Ptouch control panel;
• 1x Cable;
• 1x Manual;
• 2x Fastening elements (screw 3,9 x 25 DIN 7981 – 2 pcs nylon plug 5x25 – 2 pcs, hammered steel plug
12x30 – 2 pcs).

DIMENSIONS 2

3
EN
3 Ptouch installation on a plaster-board wall:
Ptouch installation on a plaster-board wall:

1 2 3

4 5 6

7 8

IMPORTANT: IT IS FORBID-
DEN to leave the remaining
remote controller’s cable in
the AHU’s control box!

1-2 Turn over the panel. Use a screwdriver to lift the cover as shown in fig. 2.
3 Take the cover apart.
4 Put it at desired location on the wall. The arrow must point upwards. Mark the positions of mounting
holes (distance center-to-center is 106 ± 0.5 mm). Also mark the position of the square hole for the cable
(30 x 20 mm).
5 Drill two 5 mm holes at the marked positions for nylon plugs and the hole throughout the wall to install
the cable. Insert the nylon plugs.
NOTE: You can use special metal plugs (included) instead of nylon ones.
6 Use included 2,9x16 DIN7981C screws and mount the panel to the wall as indicated in fig. 6.
Connect the included cable to the panel and pass another end of the cable through the square hole in
the wall.
7-8 Put the panel on the mounting bracket by aligning the upper identations. Then push the lower part
of the panel.
IMPORTANT: Do not forget to connect the cable before attaching the panel.

4
EN
SERVICE 4
4.1 Service login

I1

B1 B2

Number Function
I1 Entered code (masked) 4444

Number Function
B1 Clear last entered digit

B2 Confirm entered code

5
EN
4 4.2 Service menu

B2 B3

B1 B4

B5 B8

B6 B7

B10 B11

B9 B12

B13

Number Function
B1 Ventilation mode settings

B2 Cooling settings

B3 Fan settings

B4 Modbus interface settings

B5 System settings

B6 Water heater settings

B7 Ventilation settings

B8 PI controller settings

B9 Pressure sensor settings

B10 CO2 sensor settings

6
EN
B11

B12
Anti-freezing settings

Filter settings
4
B13 Factory settings

4.3 Ventilation mode settings

F1 F4

F2 F3

Number Function
Ventilation mode:
Supply: maintain supplied air temperature;
Room: maintain extracted air temperature;
ByOutDoor: ventilation is controlled by supplied or extracted air tem-
F1
perature depending on OutDoor T.C setting. If outdoor temperature
exceeds OutDoor T.C setting, ventilation is controlled by extracted
air temperature. If outdoor temperature is lower than OutDoor T.C -
ventilation is controlled by supplied air temperature.

Minimum allowed supplied air temperature.


F2 Range: [12-24 °C]

Maximum allowed supplied air temperature.


F3
Range: [25-40 °C]

Summer – winter temperature selection.


F4
Range: [10-30 °C]

7
EN
4 2.4 Cooling settings

F1 F4

F2
F3

Number Function
Minimum allowed supplied air temperature when cooling.
F1 Range: [0-15 °C]

Freon-based cooling enabling temperature.


F2 Range: [12-24 °C]

Freon-based cooling disabling temperature.


F3
Range: [25-40 °C]

Minimum outside temperature to allow cooling.


F4
Range: [10-30 °C]

4.5 Fan settings menu

B2

B1

8
EN

Number Function
4
B1 Air supply fan settings

B2 Air extraction fan settings

4.5.1 Air supply fan settings

F1 F4

F2 F3

Number Function
Supply fan speed for Boost function.
F1 Range: [0-100 %]

Supply fan speed for 1st mode.


F2 Range: [0-100 %]

Supply fan speed for 2nd mode.


F3
Range: [0-100 %]

Supply fan speed for 3rd mode.


F4
Range: [0-100 %]

9
EN
4 4.5.2 Air extraction fan settings

F1 F4

F2 F3

Number Function
Extract fan speed for Boost function.
F1 Range: [0-100 %]

Extract fan speed for 1st mode.


F2 Range: [0-100 %]

Extract fan speed for 2nd mode.


F3
Range: [0-100 %]

Extract fan speed for 3rd mode.


F4
Range: [0-100 %]

10
EN
4.6 Modbus interface settings 4

F1 F4

F2 F3

Number Function
Parity:
None;
F1 Odd;
Even.

Baud rate:
F2
2400; 4800; 9600; 19200; 38400.

Stop bits:
F3 1 stop bit;
2 stop bits.

AHU Control unit Modbus address.


F4
Range: [1-247]

11
EN
4 4.7 System settings

F1 F4

F2 F3

Number Function
Heater type:
E_On/Off: Relay-controlled electrical heater;
E_0_10: 0-10V signal-controlled electrical heater;
F1
E_ESKM: Triac-controlled electrical heater;
W_VAL+-: 3-way valve actuator for water heating.
W_0_10: 0-10V signal-controlled valve actuator for water heating.

Heat exchanger type:


R_0_10: 0-10V signal-controlled rotary heat exchanger;
R_On/Off: Relay-controlled rotary heat exchanger;
F2 B_0_10: 0-10V signal-controlled bypass valve for plate heat
exchanger;
B_DMP: 3-way bypass valve actuator for plate heat exchanger.

AHU type:
TK: Air supply chamber;
F3 RHEC: Re-cooperator with heat exchanger control;
RHEC: Re-cooperator without heat exchanger control;

Fan type:
F4 EC: 0-10V signal-controlled EC motor;
AC: AC motor controlled using three fixed voltages;

12
EN
4.8 Water heater settings 4

F1 F4

F2 F3

Number Function
F1 Threshold to force an increase of a returning water temperature.

F2 Threshold to stop fans.

Maximum idle water pump operation (when there is no need for


F3 heating).
Range: [10-30 minutes]

Interval of water pump prophylactic. In Pump-stopped state, pump


F4 is exercised for „Pump stop minutes“ period.
Range: [0-5 h]

13
EN
4 4.9 Ventilation settings

F1

F2 F3

Number Function
Supplied air fan indication:
F1 Percent: indicate fan state in %;
Pressure: indicate fan state in Pa.

Extracted air fan indication:


Percent: indicate fan state in %;
F2 Pressure: indicate fan state in Pa;
SAF + Pressure: indicate fan state as difference from supplied air
pressure (in Pa).

Use of extracted air CO2 sensor:


F3 On;
Off.

14
EN
4.10 PI controller settings 4

B2 B3

B1 B4

B5

B6

Number Function
Adjustments of PI controller used by system to react to heating or
B1
cooling.

Adjustments of PI controller used in the mode of maintaining ex-


B2
tracted air temperature.

B3 Electrical heater PI controller adjustments.

B4 Adjustments of PI controller for bypass valve or rotor heat ex-changer.

B5 Cooler PI controller adjustments.

B6 Pre-heater PI controller adjustments.

15
EN
4 4.10.1 PID adjustment screen

I1

F1

F2

NOTE: This screen is applicable for all PID controller adjustments.

Number Function
I1 Current setting indication

Number Function
Proportional coefficient.
F1
Range: [0-1000]

Integral coefficient.
F2 Range: [0-1000]

16
EN
4.11 Pressure sensor settings 4

F1

F2

Number Function
Pressure corresponding to 0V input signal.
F1
Range: [0-2000 Pa]

Pressure corresponding to 10V input signal.


F2 Range: [0-2000 Pa]

4.12 CO2 sensor settings

F1

F2 F3

17
EN
4 Number Function
CO2 level (in ppm) at minimum voltage (0 VDC).
F1
Range: [0-2000 ppm]

CO2 level (in ppm) at maximum voltage (10 VDC).


F2
Range: [0-2000 ppm]

Voltage at 100 ppm CO2 level


F3
Range: [0-10 V*10]

4.13 Anti-freezing settings

F1 F4

F2 F3

Number Function
Anti-freeze protection algorithm:
DewP/PlateT: Dew point and heat exchanger surface temperature
calculation-based;
F1
Toutside: Outside temperature based (DIBT);
TEsetpoint: Exhausted air temperature based;
Heat exchanger anti-freezing diagram-based;
Heat exchanger anti-freezing diagram-based.

Air supply fan speed decrease:


On: allowed;
F2 Off: forbidden.

Action on likely-freezing condition:


On: bypass valve is allowed to be opened or rotor is allowed to
be stopped;
Off: bypass valve is not allowed to be opened or rotor is not
F3 allowed to be stopped.

18
EN

Fault alert if too-cold air is supplied longer than allowed period:


4
F4 On: alert will be shown;
Off: alert will be suppressed.

4.14 Air filter settings

F1

Number Function
F1 Working hours till reminder to replace air filters.

4.15 Factory settings

F1

Number Function
F1

19