Professional Documents
Culture Documents
1997
Insulator and
conductor fittings for
overhead power lines —
Part 1: Performance and general
requirements
--`,``-`-`,,`,,`,`,,`---
Aluminium Federation
Association of Consulting Engineers
BECCAMA (BEAMA Electrical Cable Conductor Accessory Manufacturers’
Association)
British Non-Ferrous Metals Federation
British Railways Board
Department of Trade and Industry
Electrical and Electronic Insulation Association (BEAMA Ltd.)
Electricity Association
Overhead Transmission Line Contractors (BEAMA Ltd.)
--`,``-`-`,,`,,`,`,,`---
Contents
Page
Committees responsible Inside front cover
Foreword ii
1 Scope 1
2 References 1
3 Definitions 1
4 General requirements 3
5 Requirements for insulator pins 4
6 Insulator set fittings and earth conductor fittings 5
7 Tension joints and tension clamps 5
8 Non-tension joints 8
9 Suspension clamps 11
10 Electrical control fittings 11
11 Mechanical protective fittings 12
Annex A (informative) Diagrammatic representation of electrical
type test sequence 15
Annex B (normative) Mathematical acceptance criterion 17
Annex C (normative) Information to be supplied by the purchaser 19
Figure A.1 — Diagrammatic representation of electrical
type test sequence 16
Table 1 — Tolerances 4
Table 2 — Longitudinal slip 13
Table 3 — Torsional slip 13
Table B.1 — Designation of resistance measurements 18
List of references Inside back cover
--`,``-`-`,,`,,`,`,,`---
© BSI 12-1998
Copyright British Standards Institution
i
Provided by IHS under license with BSI
No reproduction or networking permitted without license from IHS Not for Resale
BS 3288-1:1997
Foreword
This Part of BS 3288 has been prepared by Technical Committee PEL/11 and
supersedes BS 3288-1:1973 which is withdrawn.
BS 3288 applies primarily to fittings for overhead electric power lines. The
various Parts of BS 3288 specify the performance, general requirements and
dimensional requirements for insulator and conductor fittings. The general and
dimensional requirements may be applied to similar fittings used on overhead
railway electrification systems and in substations. The Standard is not applicable
to fittings exclusively intended for use on aerial bundled conductor systems or to
--`,``-`-`,,`,,`,`,,`---
Summary of pages
This document comprises a front cover, an inside front cover, pages i and ii,
pages 1 to 20, an inside back cover and a back cover.
This standard has been updated (see copyright date) and may have had
amendments incorporated. This will be indicated in the amendment table on
the inside front cover.
ii © BSI 12-1998
Copyright British Standards Institution
Provided by IHS under license with BSI
No reproduction or networking permitted without license from IHS Not for Resale
BS 3288-1:1997
1 Scope 3.4
pin insulator
This Part of BS 3288 specifies performance and
general requirements for insulator and conductor a rigid insulator consisting of an insulating
fittings for use on overhead power lines. It defines component intended to be mounted rigidly on a
the relevant tests and test procedures together with supporting structure by means of a pin passing up
the acceptance criteria. inside the insulating component which consists of
one or more pieces of insulating material
The tests and test procedures may also be applied to
permanently connected together
similar fittings, outside the scope of this standard,
intended for use in: 3.5
— the overhead equipment of electric traction insulator pin
lines; a rigid fitting for attaching a pin insulator to a
— substations. supporting structure
3.6
2 References line post insulator
2.1 Informative references a rigid insulator consisting of one or more
This Part of BS 3288 incorporates, by dated or components of insulating material permanently
undated reference, provisions from other assembled with a metal base and intended to be
publications. These normative references are made mounted rigidly on a supporting structure
at the appropriate places in the text and the cited 3.7
publications are listed on the inside back cover. For cap and pin insulator
dated references, only the edition cited applies; any an insulator comprising an insulating part having
subsequent amendments to or revisions of the cited the form of a disc or bell, with or without ribs on its
publication apply to this Part of BS 3288 only when lower surface, and fixing devices consisting of an
incorporated in the reference by amendment or outside cap and an inside pin attached axially
revision. For undated references, the latest edition
of the cited publication applies, together with any 3.8
amendments. long rod insulator
2.2 Informative references an insulator comprising an insulating part having
This Part of BS 3288 refers to other publications an approximately cylindrical core, with or without
that provide information or guidance. Editions of sheds, and external or internal fixing devices
attached to each end
these publications current at the time of issue of this
standard are listed on the inside back cover, but 3.9
reference should be made to the latest editions. composite insulator
an insulator made of at least two insulating parts,
3 Definitions namely a core and an external housing
For the purposes of this British Standard the
--`,``-`-`,,`,,`,`,,`---
3.12 3.22
insulator set tension clamp: dead-end clamp
an assembly of one or more insulator strings a clamp which attaches a conductor to a tension
suitably connected together, complete with fixing insulator set or to a support and designed to
and protective devices as required in service withstand the conductor tension
3.13 3.23
suspension set dead-end tension termination
an insulator set complete with all fittings and a tension clamp inserted at the end of a conductor
accessories to support a conductor or a bundle of for attachment to an insulator tension set, designed
conductors at its lower end to carry full current and to provide mechanical
3.14 termination of the conductor
tension set 3.24
an insulator set complete with all fittings and mid-span tension joint
accessories to secure a conductor or a bundle of a joint inserted between two lengths of a conductor
conductors in tension to provide electrical and mechanical continuity of
3.15 the conductor
insulator set fitting NOTE A dead end tension joint may additionally provide
facilities for the connection of droppers or jumpers. Some types
any component of a suspension or tension insulator e.g. bolted and wedge type may not need this facility. The joint
set, other than a string insulator unit, a suspension can also be used on an earth conductor.
clamp, a tension termination, an electrical control 3.25
fitting or a mechanical protective fitting non-tension joint
3.16 a fitting for the connection of two consecutive pieces
earth conductor fitting of conductor which are to be held, but not at line
any component of an assembly for attaching an tension
earth conductor to a supporting structure other 3.26
than a suspension clamp, a tension termination or a non-tension T-joint
mechanical protective fitting a fitting for the connection of the end of one
3.17 conductor to a point on the length of a second
electrical control fitting conductor
any device for controlling the electrical NOTE The connection is not subject to line tension although the
conductor to which the fitting is applied on its length may be at
characteristics of an insulator line tension.
3.18 3.27
mechanical protective fitting non-tension termination
any device attached to a conductor for its a fitting for application to the end of a conductor not
mechanical protection subject to line tension to permit connection to
3.19 equipment or other fittings
factory formed helical conductor fitting 3.28
a fitting in which the force necessary to grip the bi-metallic fitting
conductor is provided by helical wires which are self a fitting which is suitable for the connection of
tightening on the conductor conductors of different materials
3.20 3.29
clamp repair sleeve
any fitting which can be fixed onto a conductor a special fitting which can be installed over a
3.21 damaged conductor in order to restore its electrical
suspension clamp and mechanical properties
a fitting which attaches a conductor to a suspension 3.30
insulator set or an earth conductor fitting patch sleeve
a special fitting which can be installed over a
damaged conductor in order to restore its electrical
properties
--`,``-`-`,,`,,`,`,,`---
2 © BSI 12-1998
Copyright British Standards Institution
Provided by IHS under license with BSI
No reproduction or networking permitted without license from IHS Not for Resale
BS 3288-1:1997
--`,``-`-`,,`,,`,`,,`---
jumper terminal stainless steel, shall be protected by hot dip
galvanizing or other means giving equivalent
the termination of a conductor which permits protection. The threads of nuts and tapped holes
electrical continuity with a jumper lug shall be cut after galvanizing and shall be well oiled
3.35 or greased. All other threads shall be formed before
counterweight (to a suspension insulator set) galvanizing.
a mass attached to a suspension clamp to provide an All fittings shall be so designed that bi-metallic
increase in the vertical load applied to the clamp corrosion within or between fittings or between a
NOTE The effect of the counterweight is to reduce the angle of fitting and the conductor does not occur.
swing of the suspension insulator set under the influence of wind The selection of materials and the design of security
or in the case of flying angle supports. It also prevents
radio-interference caused by bad contacts between metallic parts.
devices shall conform to 10.3 of BS 3288-4:1989.
3.36 4.3 Classification of tests
vibration damper In the following clauses, in which the requirements
a device attached to a conductor in order to suppress for the various types of fittings are given, the tests
or minimize vibrations due to wind are divided into three groups:
3.37 a) Type tests. Type tests are intended to establish
night warning light (for conductor) design characteristics. They are normally made
once only and repeated only when the design or
a device which becomes luminous generally by the material of the fitting is changed.
capacitive induction from the live conductor to
b) Sample tests. Sample tests are intended to
which it is attached
verify the quality of materials and workmanship.
3.38 They are made on fittings taken at random from
aircraft warning marker (for conductor and batches offered for acceptance.
earth wire)
c) Routine tests. Routine tests are intended to
a warning device visible during the day, used on eliminate defective fittings. They are made on
conductors or earth wires every fitting for which routine tests are specified
in later clauses.
4 General requirements 4.4 General requirements for tests
4.1 General 4.4.1 Type tests
All insulator fittings, unless otherwise specified by Test certificates giving the results of the
the purchaser (see item b) of annex C), shall conform appropriate type tests, made on not less than three
to the coupling dimensions specified in BS 3288-3 fittings identical in all essential details with those to
and BS 3288-4. be supplied, shall be regarded as evidence of
conformity.
NOTE If alternative arrangements apply, this should be stated
by the purchaser at the time of enquiry and order (see item c) of
annex C).
© BSI 12-1998
Copyright British Standards Institution
3
Provided by IHS under license with BSI
No reproduction or networking permitted without license from IHS Not for Resale
BS 3288-1:1997
--`,``-`-`,,`,,`,`,,`---
5.3 Sample tests
4.5 Verification of dimensions
5.3.1 Verification of dimensions
It shall be verified either that the test samples
conform to the requirements of Part 2 of this The dimensions of the samples shall be verified as
standard (if relevant) or that they are in accordance specified in 4.5.
with the contract drawings, particularly as regards 5.3.2 Mechanical tests
any dimensions to which special tolerances apply This test shall be the same as the type test specified
and details affecting interchangeability in 5.2.
(e.g. dimensions for which gauges are specified).
5.3.3 Galvanizing test
The tolerances given in Table 1 are allowed on all
dimensions to which special tolerances do not apply. Galvanized parts shall be tested in accordance with
BS 729 and shall conform to the requirements of
Table 1 — Tolerances
that standard.
Dimension Tolerance
mm 5.4 Routine tests
Up to and including 35 ± 0.7 mm No routine tests are specified for insulator pins.
Over 35 ±2%
NOTE Dimensions given in brackets in Part 2 of this standard
are given for guidance only and are not subject to strict
tolerances. These dimensions may vary by twice the tolerances
specified in Table 1.
4 © BSI 12-1998
Copyright British Standards Institution
Provided by IHS under license with BSI
No reproduction or networking permitted without license from IHS Not for Resale
BS 3288-1:1997
6 Insulator set fittings and earth Mechanical type tests shall be carried out on not less
conductor fittings than three fittings. Electrical type tests shall be
carried out on not less than six fittings except for
6.1 General requirements mid-span tension joints, where three samples shall
Insulator set fittings and earth conductor fittings be tested, measurements being taken on each half of
shall conform to the requirements of the following each sample. Fittings supplied for test shall be
tests. Ferrous castings shall be made either of identical with those to be supplied commercially.
malleable cast iron conforming to the requirements Fittings within a manufacturer’s range shall
of BS 6681, or of cast iron containing spheroidal or normally be subject to individual type tests.
nodular graphite, conforming to the requirements of However, it shall be permissible for these to be
BS 2789. Forged steel fittings shall be made from omitted in those instances where an identical
steel of a suitable grade, conforming to the compression tube is employed for different
requirements of BS 970-1. applications within a range of fittings. The
NOTE If the purchaser requires other materials he should state manufacturer shall demonstrate to the purchaser’s
that at the time of enquiry and order (see item d) of annex C). satisfaction, compliance with the requirements of
6.2 Mechanical type test this standard. Where a common compression tube is
used with different die forms, each tube/die
The fitting shall be held in a tensile testing machine combination shall be tested.
in a manner approximating, as nearly as possible, to
the arrangement to be used in service. A tensile load If one size of fitting is offered for more than one size
equal to 75 % of the specified minimum failing load of conductor, the type test shall be carried out on
shall be applied and increased at a steady rate. both the largest and smallest of such conductor sizes
Failure of the fitting shall not occur at a load less or, in the case of T-joints, on both the largest and
than the specified minimum failing load. smallest combinations of conductors.
6.3 Sample tests If a fitting is offered for application to conductors of
more than one material (e.g. copper, copper
6.3.1 Verification of dimensions cadmium, aluminium, aluminium alloy, aluminium
The dimensions of the samples shall be verified as conductor steel reinforced (ACSR)) then the type
specified in 4.5. tests shall be carried out on each conductor material
6.3.2 Mechanical test and stranding.
NOTE The purchaser should state the sizes (or combinations)
This test shall be the same as the type test specified for testing at the time of enquiry and order (see item e) of
in 6.2. annex C).
failing load shall be applied to the fittings and The fitting shall be held in a tensile testing machine
maintained for 30 s. The fitting shall not be in a manner approximating, as nearly as possible, to
damaged by the test. the arrangement to be used in service. A tensile load
shall be applied to the attachment point for
7 Tension joints and tension clamps tensioning equipment and increased at a steady rate
up to 75 % of the rated tensile strength of largest
7.1 General requirements conductor for which the tension termination is
Tension joints and tension clamps shall be so designed. Failure of the attachment point or fitting
designed that they meet the requirements of the shall not occur at less than this load.
following tests.
NOTE Attention is drawn to the need for the designer to take
into account the effects of vibration.
7.2.2 Tension joints and tension clamps A 5 kN load shall be applied to the assembly and the
The fitting shall be assembled in accordance with position of the wedges relative to the clamp body
the manufacturer’s recommendations on conductors noted. Loads equivalent to normal everyday tension,
of the size and type with which it is to be used. The maximum erection tension and maximum working
assembly shall be mounted in a tensile testing tension of the conductor shall be applied to the
machine and anchored in a manner approximating, conductors and the relative position of the wedges
as nearly as possible, to the arrangement to be used noted. After the application of each load the clamp
in service, precautions being taken to avoid bodies shall be removed from the wedges using a
birdcaging of the conductor. The length of conductor wedge extractor tool.
between the fitting under test and any other clamp A tensile load of about 50 % of the rated tensile
or joint in the test assembly shall be not less strength of the conductor shall be applied and the
than 100 times the overall diameter of the conductor shall be marked in such a way that
conductor. movement relative to the fitting can easily be
A tensile load of about 50 % of the rated tensile detected. Without any subsequent adjustment of the
strength of the conductor shall be applied and the fitting, the load shall be steadily increased to 95 %
conductor shall be marked in such a way that of the rated tensile strength and then reduced
movement relative to the fitting can easily be to 90 % of the rated tensile strength and maintained
detected. Without any subsequent adjustment of the for 1 min. There shall be no movement of the
fitting, the load shall be steadily increased to 95 % conductor relative to the fitting due to slip during
of the rated tensile strength and then reduced this period of 1 min and no failure of the fitting. The
to 90 % of the rated tensile strength and maintained final position of the wedges shall be noted.
for 1 min. There shall be no movement of the For the purpose of this test the rated tensile
conductor relative to the fitting due to slip during strength of the conductor shall be taken as the value
this period of 1 min and no failure of the fitting. given in the appropriate British Standard, or, in the
For the purpose of this test the rated tensile case of a conductor for which there is no British
strength of the conductor shall be taken as the value Standard, shall be a calculated value.
given in the appropriate British Standard, or in the NOTE The method of calculating the rated tensile strength
should be stated by the purchaser at the time of enquiry and
case of a conductor for which there is no British order (see item f) of annex C).
Standard, shall be a calculated value.
Full details of the conductor used in the test,
NOTE The method of calculating the rated tensile strength
should be stated by the purchaser at the time of enquiry and
including details of the greasing, if any, shall be
order (see item f) of annex C. stated on the test certification.
Full details of the conductor used in the test, 7.2.3.2 Clamp bolt tightening test
including details of the greasing, if any, shall be The wedge fixing bolts and the conductor guide bolts
stated on the test certification. shall be tightened to twice their recommended
7.2.3 Wedge clamps installation torques. The wedges, clamps and bolts
7.2.3.1 Testing of wedge clamps shall be undamaged.
The wedge clamps tested shall include one with 7.2.4 Factory formed helical tension
maximum size body and minimum size wedges and terminations
one with minimum size body and maximum size Factory made tension terminations shall be type
wedges. tested as follows.
The fitting shall be assembled in accordance with The fitting shall be assembled in accordance
the manufacturer’s recommendations on conductors with 7.2.2. A tensile load of 40 % of the rated tensile
of the size and type with which it is to be used. The strength of the conductor shall be applied and
assembly shall be mounted in a tensile testing maintained for 1 min. The load shall be removed
machine and anchored in a manner approximating, and the fitting then removed from the conductor in
as nearly as possible, to the arrangement to be used accordance with the manufacturer’s instructions.
in service, precautions being taken to avoid The fitting shall be reapplied to its original position
birdcaging of the conductor. The length of conductor on the conductor and the procedure repeated as
between the fitting under test and any other clamp detailed in the previous paragraph.
or joint in the test assembly shall be not less
The fitting shall be reapplied to its original position
than 100 times the overall diameter of the
on the conductor and the mechanical type test
conductor.
specified in 7.2.2 completed.
6
--`,``-`-`,,`,,`,`,,`---
© BSI 12-1998
Copyright British Standards Institution
Provided by IHS under license with BSI
No reproduction or networking permitted without license from IHS Not for Resale
BS 3288-1:1997
b) The electrical resistance of the fitting, Where a tension clamp is provided with an
measured at the end of attachment point for use during erection and
every 100 cycles (± 20 cycles) at ambient maintenance, the test load shall be applied between
temperature, shall not exceed 75 % of the this point and the anchor point. Otherwise the test
measured resistance of the equivalent length of load shall be applied as nearly as possible between
conductor. the points of attachment used in normal service.
c) The initial resistance of the fitting shall not A tensile load, which shall be equal to at least 50 %
--`,``-`-`,,`,,`,`,,`---
differ by more than 50 % from the mean of the of the specified minimum failing load shall be
overall resistance of each of the six fittings, or applied to the fitting and maintained for 30 s. The
half fittings in the case of tension joints fitting shall not be damaged by the test.
assembled for test. The supplier shall inform the purchaser if the form
d) The average resistance of the fitting measured of fitting is such that a test load cannot be applied.
over the last 500 cycles shall not exceed the initial 7.5.2 Wedge clamp trunnions
resistance of the fitting by more than 50 %.
A load equal to at least 50 % of the minimum failing
e) A graph of resistance against number of cycles
load of the conductor shall be applied to the
shall demonstrate with a reasonable probability trunnions of the clamp body and maintained
that the rise in resistance over the last 500 cycles for 30 s. The fitting shall not be damaged by the
is not more than 15 % of the average resistance
test.
over the same period. The method employed for
the determination of this probability shall be in 7.5.3 Tension joints
accordance with annex B. No routine tests are specified for tension joints.
7.4 Sample tests
8 Non-tension joints
7.4.1 Verification of dimensions
8.1 General requirements
The dimensions of the samples shall be verified as
specified in 4.5. Non-tension joints (including T-joints) shall be
NOTE Attention is drawn to the possible requirement for closer designed so that they meet the appropriate
tolerances to be specified by the manufacturer for those requirements of the following subclauses. Fittings
dimensions which directly affect mechanical and/or electrical intended to connect conductors of two dissimilar
performance.
metals shall be designed to avoid harmful
7.4.2 Mechanical and electrical tests bi-metallic corrosion when erected in accordance
Mechanical and electrical sample tests are not with the manufacturer’s recommendations.
specified in this standard. Mechanical type tests shall be carried out on not less
NOTE If a purchaser wishes to include such tests, this should than three fittings. Electrical type tests shall be
be stated at the time of enquiry and order (see item g) of carried out on not less than six fittings except for
annex C), and should then be as specified in 7.2 and 7.3. non-tension joints, where three samples shall be
7.4.3 Galvanizing test tested, measurements being taken on each half of
Galvanized parts shall be tested in accordance with each sample. Fittings supplied for test shall be
BS 729 and shall conform to the requirements of identical with those to be supplied commercially.
that standard. Fittings within a manufacturer’s range shall
normally be subjected to individual type tests.
7.4.4 Clamp bolt tightening test However, these may be omitted in those instances
The wedge fixing bolts and the conductor guide bolts where an identical compression tube is employed for
shall be tightened to twice their recommended different applications within a range of fittings. The
installation torques. The wedges, clamps and bolts manufacturer shall demonstrate to the purchaser’s
shall be undamaged. satisfaction, conformity to the requirements of this
7.5 Routine tests standard.
7.5.1 Mechanical test on tension clamps Where a common compression tube is used with
different die forms, each tube/die combination shall
This test shall be applied where possible to tension be tested.
clamps incorporating load carrying castings and to
If one size of fitting is offered for more than one size
those which are fabricated by welding, in which the
of conductor, the type test shall be carried out on
weld is stressed in service.
both the largest and smallest of such conductor sizes
or, in the case of T-joints, on both the largest and
smallest combinations of conductors.
8 © BSI 12-1998
Copyright British Standards Institution
Provided by IHS under license with BSI
No reproduction or networking permitted without license from IHS Not for Resale
BS 3288-1:1997
If a fitting is offered for application to conductors of A tensile load equal to 10 % of its rated tensile
more than one material (e.g. copper, copper strength shall be applied to a length of main
cadmium, aluminium, aluminium alloy, aluminium conductor of the size and type with which the joint
conductor steel reinforced (ACSR)) then the type is to be used. The joint, complete with T-conductor,
tests shall be carried out on each conductor material shall be assembled in accordance with the
and stranding. manufacturer’s recommendations on the tensioned
NOTE The purchaser should state the sizes (or combinations) main conductor. The length of conductor on each
for testing at the time of enquiry and order (see item e) of side of the T-joint under test and any other clamp or
annex C). joint in the test assembly shall be not less
8.2 Mechanical requirements than 100 times the overall diameter of the
8.2.1 Mechanical type test on joints other than conductor.
T-joints Without any subsequent adjustment of the joint, the
Non-tension joints other than T-joints shall meet load in the main conductor shall be steadily
the requirements of the following test. increased to 95 % of the rated tensile strength and
then reduced to 90 % of the rated tensile strength
NOTE The purchaser should state if this test is not required at
the time of enquiry and order (see item h) of annex C). and maintained for 1 min. There shall be no failure
of the main conductor.
The joint shall be assembled in accordance with the
manufacturer’s recommendations on conductors of The test specified in 8.2.1 shall be carried out with
the sizes and types with which it is to be used. The the tension applied between the joint and the
assembly shall be mounted in a tensile testing T-conductor in the direction that the T-conductor
machine and anchored in such a way that the test emerges from the joint, the test load being
load is applied in the direction of the conductor. determined, as in 8.2.1, from the rated tensile
strength of the T-conductor. There shall be no
If the rated tensile strength of the conductor is less
movement of the conductor relative to the joint due
than 12 kN a tensile load of about 5 % of the rated
to slip and no failure of the joint.
tensile strength of the conductor shall be applied
and the conductor shall be marked in such a way 8.3 Electrical type tests
that movement relative to the fitting can easily be 8.3.1 General requirements
detected. Without any subsequent adjustment of the
fitting, the load shall be steadily increased to 10 % Non-tension fittings shall be type tested by the
of the rated tensile strength. This load shall be electrical heat cycle method (1 000 cycles) described
in 8.3.2 followed by the current pulse test described
maintained for 1 min. There shall be no movement
in 8.3.3 except in the case of fittings that will not
of the conductor relative to the fitting due to slip
experience high conductor temperatures in service,
during this period of 1 min and no failure of the
when the pulse test may be omitted.
fitting.
NOTE The purchaser should state whether the fittings will
If the rated tensile strength of the conductor experience high conductor temperatures in service, in his enquiry
is 12 kN or more, a tensile load of 0.6 kN shall be and order (see item j) of annex C).
applied and the conductor shall be marked in such a The fitting shall be assembled in accordance with
way that movement relative to the fitting can easily the manufacturer’s recommendations on a
be detected. Without any subsequent adjustment of conductor or conductors of the size and type with
the fitting, the load shall be steadily increased which it will be used.
to 1.2 kN. This load shall be maintained for 1 min. The test assembly shall be designed such that
There shall be no movement of the conductor
current is passed through the fittings from the main
relative to the fitting due to slip during this period
conductor to the jumper conductor on tension
of 1 min and no failure of the fitting.
terminations and from the main conductor to the
8.2.2 Mechanical type test on T-joints T-conductor by the T-joints.
When specified by the purchaser (see item i) of For the purpose of resistance and temperature
annex C), non-tension T-joints shall meet the measurements, the assembly shall contain a length
requirements of the following test. of unjointed conductor of not less than 2 m in length,
the central part of which shall be used as the control
for resistance and temperature measurements. If a
fitting is such that two sizes of conductor are being
connected into the assembly, the smaller of the two
shall be used as the control conductor.
© BSI 12-1998 9
--`,``-`-`,,`,,`,`,,`---
--`,``-`-`,,`,,`,`,,`---
measured as specified in 7.3.1. The resistance of
an equivalent length of conductor shall also be over the same period. The method employed for
measured. the determination of this probability shall be in
accordance with annex B.
b) A test current shall then be passed through the
assembly. The value and duration of the test 8.3.3 Current pulse test
current shall be such as to raise the conductor 8.3.3.1 General
temperature to a minimum of 70 °C above
This test shall be carried out on the same assembly
ambient and maintain this temperature
that has satisfactorily passed the electrical heat
for 30 min. The use of an initial current of value
cycle test (specified in 8.3.2).
not greater than 150 % of the test current, to
reduce the time to raise the conductor to 70 °C 8.3.3.2 Test conditions
above ambient is not precluded. The test conditions shall be as described in 8.3.2.1.
c) At the end of the heating period, the current 8.3.3.3 Test procedure
shall be interrupted and the conductor allowed to
cool to within 5 °C above ambient. The initial current shall be approximately four
times the test current used for heat cycling. The
d) This sequence of operation shall be repeated so duration of the pulse shall be chosen so as to heat
that 100 cycles (± 20 cycles) of heating and cooling the control conductor to 170 °C ± 10 °C. Twenty
are applied. pulses shall be applied to each fitting, the conductor
e) On one occasion during the last 5 cycles of being allowed to cool to within 5 °C above ambient
the 100 cycles (± 20 cycles), the conductor between pulses. On completion of current pulse
temperature and temperature of each fitting testing, each fitting shall be allowed to cool to
shall be measured during the last 15 min of ambient temperature and the resistance measured.
the 30 min period.
8.3.3.4 Acceptance criteria
f) The assembly shall then be allowed to cool to
On completion of the current pulse test the
ambient and the resistance of each fitting
resistance of the fitting shall not exceed:
measured.
g) Heat cycling shall then be continued with 54 × 103
----------------------------------------------------------- µ Ω
temperature and resistance measurement at the Pulse test current (A)
end of each 100 cycles until 500 cycles have been NOTE This criterion reflects the necessity to limit the interface
completed. temperature within the fitting to 150 °C. It has been shown that
this temperature corresponds to an interface voltage of 54 mV
h) A further 500 cycles shall then follow with
when the test current is passing for overhead line fittings.
resistance measurements taken Measurement of resistance is a convenient method of
every 50 cycles (± 10 cycles) and temperature determining interface voltage and, hence, interface temperature.
measurement every 100 cycles (± 20 cycles). The This criterion is valid for all combinations of material.
fittings shall not be tightened or adjusted during
the test. The above sequence is shown in
diagrammatic form in annex A.
10 © BSI 12-1998
Copyright British Standards Institution
Provided by IHS under license with BSI
No reproduction or networking permitted without license from IHS Not for Resale
BS 3288-1:1997
8.4 Sample tests The conductor shall slip through the clamp at a load
8.4.1 Verification of dimensions not greater than 30 % of the rated tensile strength
of the conductor.
The dimensions of the sample shall be verified, as
specified in 4.5. The conductor shall not be damaged other than
some surface flattening of the strands.
8.4.2 Mechanical and electrical tests
9.2.3 Clamp bolt tightening test
Mechanical and electrical sample tests are not
The clamping bolts shall be tightened to twice the
specified in this standard.
recommended installation torque. The clamps and
NOTE If a purchaser wishes to include such tests, this should
be stated at the time of enquiry and order (see item g) of annex
bolts shall be undamaged.
C), and should then be as specified in 8.2 and 8.3. 9.3 Sample tests
8.4.3 Galvanizing tests 9.3.1 Verification of dimensions
Galvanized parts shall be tested in accordance with The dimensions of the sample shall be verified, as
BS 729 and shall conform to the requirements of
--`,``-`-`,,`,,`,`,,`---
specified in 4.5.
that standard.
9.3.2 Mechanical tests
8.5 Routine tests
If mechanical sample tests on suspension clamps
No routine test is required for non-tension joints. are required, such tests shall be the same as the
type tests specified in 9.2.1, 9.2.2 and 9.2.3.
9 Suspension clamps NOTE The purchaser should state if these tests are not
9.1 General requirements required at the time of enquiry and order (see item k) of annex C).
— for line end tension horns: 0.9 kN on the tip; 11.2 Type tests
— for earth end suspension horns: 0.9 kN on each 11.2.1 Visible discharge type test (not
tip; applicable to armour rods)
— for earth end tension horns: 0.9 kN on the tip. Mechanical protective fittings shall conform to the
There shall be no failure of the fitting, but requirements of this test.
permanent deformation of the fitting after removal NOTE The purchaser should state if this test is not required at
of the load is permitted. the time of enquiry and order (see item 1) of annex C).
The mechanical protective fitting shall be attached
--`,``-`-`,,`,,`,`,,`---
10.3 Sample tests
to a length of conductor of the size and type with
10.3.1 Verification of dimensions which the fitting is to be used. The length of the
The dimensions of the samples shall be verified, as conductor and the distance from the test object to
specified in 4.5. any other object shall be sufficient to prevent any
10.3.2 Mechanical test significant effects on the performance.
The test room shall be darkened and a period
This test shall be the same as the type test specified
of 5 min shall be allowed for observers to become
in 10.2.
accustomed to the dark. A power frequency test
10.3.3 Galvanizing test voltage of 0.8 times the system voltage shall be
Galvanized parts shall be tested in accordance with applied to the conductor and shall be maintained at
BS 729 and shall conform to the requirements of this value for 5 min. During this time observations
that standard. shall be made and there shall be no sign of visible
corona.
10.4 Routine test
NOTE If the purchaser requires a different test voltage, this
This test shall be applied only to castings and to should be specified at the time of enquiry or order (see item 1) of
those fittings which are fabricated by welding. The annex C).
fitting shall be rigidly supported and a specified load 11.2.2 Mechanical type test for repair sleeves
shall be applied as shown on the relevant drawing. A length of conductor of the size and type which the
The load shall be applied only momentarily.
sleeve is to be used shall be taken and a number of
There shall be no failure and no permanent adjacent strands in the outermost layer shall be
deformation exceeding the permitted tolerance. severed. The number of severed strands shall be the
nearest whole number to one-third of the total
11 Mechanical protective fittings number of strands in the outermost layer, and
11.1 General requirements where more than one strand is severed the cuts shall
be dispersed over a conductor length of
Mechanical protective fittings such as repair approximately three conductor diameters. The
sleeves, armour rods, vibration dampers and repair sleeve shall then be assembled to make good
spacers shall be designed to avoid damage to the the damaged conductor, in accordance with the
conductor when erected in accordance with the manufacturer’s recommendations.
manufacturer’s recommendations.
The assembly shall be mounted in a tensile testing
Repair sleeves shall be designed to make good a machine and anchored so that service conditions are
conductor of which not more than one-third of the simulated, precautions being taken to avoid
strands in the outermost layer have been severed. birdcaging of the conductor. The clear length of
Repair sleeves shall meet the requirements of the conductor on each side of the repair sleeve shall be
mechanical type test specified in 11.2.2 and the not less than 100 times the overall diameter of the
electrical type test specified in 11.2.3. conductor.
Vibration dampers shall meet the requirements of A tensile load of about 50 % of the rated tensile
the mechanical type tests specified strength of the conductor shall be applied and the
in 11.2.4, 11.2.5, 11.2.6 and 11.2.7. Spacers shall conductor shall be marked in such a way that
meet the requirements of the mechanical type tests movement relative to the sleeve can easily be
specified in 11.2.8 and 11.2.9. detected. Without any subsequent adjustment of the
Sample tests shall be made on mechanical sleeve, the load shall be steadily increased to 95 % of
protective fittings in accordance with 11.3. the rated tensile strength and then reduced to 90 %
of the rated tensile strength and maintained
for 1 min. There shall be no movement of the
conductor relative to the sleeve during this period
of 1 min and no failure of the sleeve.
12 © BSI 12-1998
Copyright British Standards Institution
Provided by IHS under license with BSI
No reproduction or networking permitted without license from IHS Not for Resale
BS 3288-1:1997
For the purpose of this test the rated tensile 11.2.5 Torsional slip type test for vibration
strength of the conductor shall be taken as the value dampers
given in the appropriate British Standard, or in the The same dampers which are used in the
case of a conductor for which there is no British longitudinal slip test may be used for the torsional
Standard, shall be a calculated value. slip test, but they shall be mounted on a different
NOTE The method of calculating the rated tensile strength section of the conductor.
should be stated by the purchaser at the time of enquiry and
order (see item f) of annex C). The minimum torsional force required to cause
Full details of the conductor used in the test, rotation of the clamp around the conductor shall be
including details of the greasing, if any, shall be as given in Table 3.
stated on the test certificate. Table 3 — Torsional slip
11.2.3 Electrical type test for repair sleeves Conductor diameter Minimum force to cause
torsional slip
A length of conductor of the size and type with which mm N·m
the sleeve is to be used shall be taken and a number 12 to 19.49 4.0 plus
of adjacent strands in the outermost layer shall be 2.0 per mm
severed. The number of severed strands shall be the above 12.0 mm
nearest whole number to one-third of the total 19.5 to 25.0 19
number of strands in the outermost layer, and
Above 25.0 29
where more than one strand is severed, the cuts
shall be dispersed over a conductor length of 11.2.6 Mechanical type test of messenger wire
approximately three conductor diameters. The fastening for vibration dampers
repair sleeve shall be assembled to make good the
The samples used for the clamp slip tests may also
damaged conductor, in accordance with the
be used for this test. The axial tensile force required
manufacturer’s recommendations.
to pull the damper weights off the messenger wires
The electrical resistance shall be measured between shall be recorded.
points on the conductor on either side and 25 mm
The minimum acceptable value shall be 10 kN for
clear of the sleeve. The measured value shall not
dampers used on conductors with a diameter up to
exceed 75 % of the measured resistance of the
and including 25 mm, and 15 kN for dampers used
equivalent length of the undamaged conductor. The
on conductors with diameters larger than 25 mm.
test shall be made with direct current. The current
connections shall be at a distance not less 11.2.7 Clamp bolt tightening test for vibration
than 50 times the diameter of the conductor from dampers
the sleeve and shall be made so that effective The clamping bolts shall be tightened to twice the
contact is made with all those strands of the recommended installation torque. The clamps and
conductor which would be taken into account in the bolts shall be undamaged.
calculating its equivalent resistance.
11.2.8 Longitudinal slip test for spacer
The test shall be repeated with the polarity reversed
and the average of the two results taken as the A force shall be applied to the clamp along the axis
measured value. of the conductor. The minimum force required to
cause the clamp to slip shall be 2.5 kN for metal
11.2.4 Longitudinal slip type test for vibration clamps or 1 kN for resiliently lined conductor
dampers clamps.
A force shall be applied to the clamp along the axis 11.2.9 Clamp bolt tightening test for spacer
of the conductor. The minimum force required to
cause the clamp to slip shall be recorded. The The clamping bolts shall be tightened to twice the
minimum acceptable value shall be as given recommended installation torque. The clamps and
in Table 2. the bolts shall be undamaged.
Table 2 — Longitudinal slip 11.3 Sample tests
Conductor diameter Minimum force to cause 11.3.1 Verification of dimensions
longitudinal slip
The dimensions of the sample shall be verified as
mm Kn
specified in 4.5.
12 to 19.49 0.4 plus
0.28 per mm
above 12.0 mm
19.5 and above 2.5
--`,``-`-`,,`,,`,`,,`---
© BSI 12-1998
Copyright British Standards Institution
13
Provided by IHS under license with BSI
No reproduction or networking permitted without license from IHS Not for Resale
BS 3288-1:1997
in 11.2.4, 11.2.5, 11.2.6, 11.2.7, 11.2.8 and 11.2.9. No routine test is required for mechanical protective
fittings.
14 © BSI 12-1998
Copyright British Standards Institution
Provided by IHS under license with BSI
No reproduction or networking permitted without license from IHS Not for Resale
BS 3288-1:1997
Annex A (informative)
Diagrammatic representation of electrical type test sequence
A diagrammatic representation of the test sequences for the electrical type test is shown in Figure A.1.
--`,``-`-`,,`,,`,`,,`---
© BSI 12-1998
Copyright British Standards Institution
15
Provided by IHS under license with BSI
No reproduction or networking permitted without license from IHS Not for Resale
--`,``-`-`,,`,,`,`,,`---
16
BS 3288-1:1997
© BSI 12-1998
B.5 Calculation of change of resistance as fraction of mean resistance based on line of best fit
The change of resistance, M, as a fraction of mean resistance based on the line of best fit shall be calculated
using the following formula:
where
18 --`,``-`-`,,`,,`,`,,`---
© BSI 12-1998
Copyright British Standards Institution
Provided by IHS under license with BSI
No reproduction or networking permitted without license from IHS Not for Resale
BS 3288-1:1997
Annex C (informative)
Information to be supplied by the purchaser
The information supplied by the purchaser in his enquiry or order should include the following.
a) The number and date of this British Standard, i.e. BS 3288-1:1997.
b) If coupling dimensions of insulator fittings other than those specified in BS 3288-3 and BS 3288-4 are
required (see 4.1).
c) If evidence of conformity to type tests is required, other than that specified in 4.4.1.
d) If the purchaser requires the use of materials other than those specified in 6.1.
e) If a fitting is offered for application to conductors of more than one material, the sizes (or combination)
to be type tested (see 7.1 and 8.1).
f) The method of calculating the rated tensile strength (see 7.2.2, 7.2.3.1 and 11.2.2).
g) If the purchaser wishes to include mechanical and electrical sample tests, (see 7.4.2 and 8.4.2).
h) If the mechanical type test on joints other than T-joints is not required, (see 8.2.1).
i) If the mechanical type test on T-joints is required (see 8.2.2).
j) For deciding the necessity or otherwise of carrying out the current pulse test, whether the fittings will
experience high conductor temperatures in service (see 8.3.1).
k) If mechanical sample tests on suspension clamps are not required, (see 9.3.2).
l) If the visible discharge type test is not required, or if it is required but a different test voltage is
required, (see 11.2.1).
--`,``-`-`,,`,,`,`,,`---
© BSI 12-1998
Copyright British Standards Institution
19
Provided by IHS under license with BSI
No reproduction or networking permitted without license from IHS Not for Resale
--`,``-`-`,,`,,`,`,,`---
Normative references
BSI publications
BRITISH STANDARDS INSTITUTION, London
BS 729:1971, Specification for hot dip galvanized coatings on iron and steel articles.
BS 970, Specification for wrought steels for mechanical and allied engineering purposes.
BS 970-1:1996, General inspection and testing procedures and specific requirements for carbon, carbon
manganese alloy and stainless steels.
BS 2789:1985, Specification for spheroidal graphite or nodular graphite cast iron.
BS 3288, Insulator and conductor fittings for overhead power lines.
BS 3288-2:1990, Specification for a range of fittings.
BS 3288-3:1989, Dimensions of ball and socket couplings for string insulator units.
BS 3288-4:1989, Locking devices for ball and socket couplings of string insulator units: dimensions and
tests.
BS 4727, Glossary of electrotechnical, power, telecommunications, electronics, lighting and colour terms.
BS 4872, Specification for approval testing of welders when welding procedure is not required.
BS 4872-1:1982, Fusion welding of steel.
BS 6681:1986, Specification for malleable cast iron.
Informative references
BSI publications
BRITISH STANDARDS INSTITUTION, London
BS 4579, Specification for performance of mechanical and compression joints in electric cable and wire
connectors.
BS 4579-3:1976, Mechanical and compression joints in aluminium conductors.
BS EN ISO 9000, Quality management and quality assurance standards1).
© BSI 12-1998
Copyright British Standards Institution
Provided by IHS under license with BSI
No reproduction or networking permitted without license from IHS Not for Resale
|
|
|
|
|
|
|
|
|
BSI Ð British Standards Institution
|
|
|
|
|
|
| BSI is the independent national body responsible for preparing British Standards. It
|
| presents the UK view on standards in Europe and at the international level. It is
| incorporated by Royal Charter.
|
|
| Revisions
|
|
| British Standards are updated by amendment or revision. Users of British Standards
|
| should make sure that they possess the latest amendments or editions.
|
|
| It is the constant aim of BSI to improve the quality of our products and services. We
|
| would be grateful if anyone finding an inaccuracy or ambiguity while using this
| British Standard would inform the Secretary of the technical committee responsible,
|
| the identity of which can be found on the inside front cover. Tel: 020 8996 9000.
|
| Fax: 020 8996 7400.
|
|
| BSI offers members an individual updating service called PLUS which ensures that
|
| subscribers automatically receive the latest editions of standards.
|
|
| Buying standards
|
| Orders for all BSI, international and foreign standards publications should be
|
| addressed to Customer Services. Tel: 020 8996 9001. Fax: 020 8996 7001.
|
|
| In response to orders for international standards, it is BSI policy to supply the BSI
|
| implementation of those that have been published as British Standards, unless
|
| otherwise requested.
|
|
| Information on standards
|
| BSI provides a wide range of information on national, European and international
|
| standards through its Library and its Technical Help to Exporters Service. Various
|
| BSI electronic information services are also available which give details on all its
|
| products and services. Contact the Information Centre. Tel: 020 8996 7111.
|
| Fax: 020 8996 7048.
|
|
| Subscribing members of BSI are kept up to date with standards developments and
| receive substantial discounts on the purchase price of standards. For details of
|
| these and other benefits contact Membership Administration. Tel: 020 8996 7002.
|
| Fax: 020 8996 7001.
|
|
| Copyright
|
|
| Copyright subsists in all BSI publications. BSI also holds the copyright, in the UK, of
|
| the publications of the international standardization bodies. Except as permitted
| under the Copyright, Designs and Patents Act 1988 no extract may be reproduced,
|
| stored in a retrieval system or transmitted in any form or by any means ± electronic,
|
| photocopying, recording or otherwise ± without prior written permission from BSI.
|
|
| This does not preclude the free use, in the course of implementing the standard, of
|
| necessary details such as symbols, and size, type or grade designations. If these
|
| details are to be used for any other purpose than implementation then the prior
| written permission of BSI must be obtained.
|
|
| If permission is granted, the terms may include royalty payments or a licensing
|
| agreement. Details and advice can be obtained from the Copyright Manager.
|
| Tel: 020 8996 7070.
|
|
|
|
|
|
|
|
|
BSI |
|
389 Chiswick High Road |
|
London |
|
W4 4AL |
|
|
|
|
|
|
--`,``-`-`,,`,,`,`,,`---