GOVERNMENT OF INDIA
MINISTRY OF COMMERCE & INDUSTRY
PETROLEUM AND EXPLOSIVES SAFETY ORGANISATION (PESO)
(Formerly Department of Explosives)
‘CGO COMPLEX SEMINARY HILLS
NAGPUR 440006
Leer No: A/PIHQUMIIO4 1656
(P27388),
Email :explosives@explosives.gov.in
Phone/Fax No.2510248/2510577
Dated: 4/12/2008
fo
‘Nils. Asco India Ltd
No. $7, Kundrathur Main Road,
Gerugambalckam, Porur,
CHENNAI-602101
Tamil Nadu(State).
‘Sub :Approval of Inrinsically Safe Solenoid Operators,
Dear Sir(s),
‘The following equipment(s) manufactured by you according to 1S:5780:2002 standards ate approved for use
{in Zone 1 , group TIC hazardous areas coming under the purview of the Petroleum Rules, 2002 administezed
by this Organization ‘|
CCE
Safety Test
rN Description Identification
[Protection] ne | House
[intrinsically Safe Solenoid Operator 7
hype 18: MI2-1 [ex ia P223838/1
intrinsically Safe Solenoid Operator :
R fiype iS MXXEE. lex ia 223838/2 «
‘This Approval is granted subject to observance of the following conditions:-
1 The design end construction of the equipment shall be strictly in accordance with description,
condition and drawings as mentioned in the CIMFR Test Reports referred to above,
2 The equipment shall be used only with approved type of accessories and associated apparatus.
3 Bach equipment shall be marked either by raised lettering cast integrally or by plate attached to the
‘ain structure to indicate conspicuously:-
1) Name of the manufacturer
2) Name and number by which the equipment is identified,
3) Number & date of the test report of the CIMFR applicable to the equipment.
4) _CCEs Idenfification Number ofthis letter by which use of apparatus is approved.
4 Acertificate to the effect that the equipment has been manufactured strictly in accordance with the
drawing referred fo in the CIMFR Test report and is identical with the one tested and certified at
CIMFR, Dhanbad shall be furnished with each equipment.5 The customer shall be supplied with a copy of this leiter, an extract of the conditions and
‘maintenence schedule, if any, recommended by CIMER in their test reports and copy of instructions
booklet detailing operation & maintenance of the equipment so as to maintain its Intrinsically Safe
characteresties.
This approval also covers the permissible variations as approved under the CIMER test
reports reffered to above. This approval may be deemed to have been revoked with immediate effect,
at any time, ifany of the conditions subject to which approval has been granted is violated or not
complied with. The approval may also be amended or with drawn at any time, if considered
necessary in the interest of safety.
The field performance report from actual users/your customers of the subject equipment may
please be collected and furnished to this office for verification and record at regular intervals.
‘The Approval otherwise is valid for a period of five years from the date of issue
Yours faithfully,
Hire
(R.A.GUIAR)
Controller of Explosives
for Chief Controller of Explosives
Nagpur
Copy to:
1.The Jt. Chief Controller of Explosives, West Circle, Mumbai; East Circle, Kolkatta; South
Circle, Chennai; North Circle, Faridabad; Central Circle, Agra,
/
for Chief Controller of Explosives: esta waa wd gq sydem dens
Gants wer stetfre argent GR)
War Ws, TT — 926015, ARGS (Ra)
GRIGINAL CUPY
CENTRAL INSTITUTE OF MINING AND FUEL RESEARCH
Formerly : Central Mining Research Institute
(COUNCIL OF SCIENTIFIC & INDUSTRIAL RESEARCH)
BARWA ROAD, DHANBAD - 826015, JHARKHAND (INDIA)
REGISTERED POST/COURIER
No, CIMFRITCIPIS 7 Dated: 177 October 2008
EQUIPMENT ID NO, 97/08 CODE NO. FLP/139A/08-09
To
IMjs. ASCO (INDIA) Limited,
‘No. 57, Kundrathur Main road,
Gerugamoakkam, Porur,
Chennai-60210% (Tamil Nadu)
‘Sub: Intrinsic safety testing of Intrinsically Safe Solenoid Operator, Type: IS-M12-1
2s per 1S: 5780- 2002 for use in Gas Groups ITA, IIB & IIC and Zone ~1 & 2 atmosphere
only.
fanaa bg eee EEE ee PCRS
Your Ref. No.: EX/AI/001/2008 Dated: 02/08/2008
Dear Sir,
Please find enclosed the test report of the above sample, submitted by you.
‘This Institute reserves the right to review, amend or withdraw this report at any time
if considered necessary in the interest of safety.
[An amount of Rs, 62,551/- (Rupees Sixty two thousand Five hundred Fifty
fone only) including applicable service charges involved towards the testing/issuing the
schedule has been adjusted against the advance deposit made by you.
Kindly acknowledge receipt.
“Thanking you.
- Yours faithfully,
Endl: As above. (G.M. PRASAD)
Proto Test Report in Quaruplate copies HEAD OF THE DEPARTMENT
Copy to: 1 Head, Fame & Expoion Lb Testing cet
2 il Section.
Lots
= Ree Director nee eae
Ph. 0081 326.
2202326/2203043 Ph, x 0 326 2256027/2296028/2296029/2296010/2296013 Ph. 0091 326 2286019/2202429/2083397203150
‘e-mail : demrips@yahoo.co.in,demri@csirres.in. Website
www.cmnriindia.nic.in‘Go Go Ud go so tio Team WHIT-CIMFR TESTING CELL
vaftse )
SRIGINAL COPY
CENTRAL INSTITO Ne AND FUEL RESEARCH
Formerl Yesearch institute
{Council 3 sstrial Research)
= BARWA ROAD, DHANBAD-826 001 (INDIA)
Weta WAL UT - TEST CERTIFICATE
[FORM NOT CMP DOMFCPUZFUZT
LD No. 97/08 ‘CODE NO. FLP/139A/08-09
SCHEDULE
[for association with the repogt of test sent (under cover of this office Letter No
CIMFRITC/P/S74 Dated 17° October, 2008) to M/s. ASCO (INDIA) Limited, No. 57,
Kundrathor Main road, Gerugambakkam, Porur, Chennai-602101 (Tamil Nadu) in respect
of testing as regards intrinsic safety of the equipment mentioned below submitted by
NAME & DESCRIPTION OF THE APPARATUS: Intrinsically Safe Solenoid Operator,
Type: IS-M12-1.
‘The intrinsically safe coil is used for operating the plunger. The coil is shunted by bridge
diodes D1 to D4 (Philips make BYW 56). The input points of coil which will be connected
through external certified & approval intrinsically safe 32VDC/80mA (max.) power suppIY.
‘The complete circultry is encapsulated by moulding epoxy compound and housed in a
stainless steel housing, The 32VDC/80mA (max.) comes from certified and approved
intrinsically safe power supply. DC resistance and inductance of solenoid coll are 406 ohm.
and negligible respectively. The effective. internal capacitance and inductance are
negligibly small
Applicant: M/s. ASCO (INDIA) Limited,
No. 57, Kundrathur Main road,
Gerugambakkam, Porur,
Chennai-602101 (Tamil Nadu)
Manufacturer: (1) M/S. Asco Controls BV, P.O. Box, NL-3925 26
DRAWING: a _
Scherpenzeel, The Netherlands.
(2) M/s. Asco Joucomatic Limited,
Pit Hey Place, West Pimbo,
‘Skelmersdale Lancashire WN 9PG (UK).
‘Drg.No., | Date | Sheet [ Rev. Tite
No.
126.046 | 15/07/2008 | 1/1_-| D | NAMEPLATE FOR INTRINSICALLY
SOLENOID OPERATOR AS PER IS: 5780-
2002
131896" | 3i70172003 | 12 to | E | EXPLOSTONPROOF SOLENOID OPERATOR
22
a
20f3Continuation Sheet
Bo Go UE fo Ho {.CIMFR TESTING CELL
ORIGINAL COPY
2:02]
LD No. 97/08 CODE NO FLP/1394/08-09
APPLICABLE ZONE AND GAS GROUP: Zone 1 & 2 and Gas Groups ~ IIA, IIB & IIC only.
TEMPERATURE CLASS : T6 at 50°C ambient
STANDARD REFERENCE: 1S: 5780- 2002 & 1S; 13346-2004,
‘SECOND SCHEDULE
‘These are the following variations without changing any component of the circult/circultry
which can affect the intrinsic safety.
Solenoid coil Cat. No, Description
4, 1S-12-21ND + Operator with 2 way valves having Pg 13.5 cable gland.
2. ISMi23IND + Operator with 2 way valves having Pg 13.5 cable gland.
3. IS-M12-MRIND Threed Operator for Marwal reset valves with 12” NPT Condut.
4, IS-M12-ETMRIND Thread: Operator for Manual reset vaives with M20x1.5 Conduit,
5. IS-M12-2ETINDT Thread: Operator with 2 way valves having M20x1.5 Conduit,
6. IS-MI2-3ETINDT Thread: Operator with 3 way valves having MZ0x1,5 Condult.
7. The solenoid housing and cover may be with $5 304/316 material and Prefixed "WS",
8. The above coil may be spade connector construction as shown in the drg. No.
131896, sheet 1/2, Rev. E and Date: 31/01/2003, in this case cat. No. may be IS-
M12-SC-2IND OR TS-M12-SC-3IND.
be[FORM No.: eFLPO2:F-02)
1. No. 97/08 CODE NO FLP/139A/08-09
REPORT OF TEST
[Accompanies this office letter No: CIMFR/TC/PIAS74 dated JP” October,2008 and
pertains to the report of testing 3s regards intrinsic safety of the Intrinsicaly Safe
Solenoid Operator, Type: 1S-M12-1, submited for test by M/s. ASCO (INDIA) Limited, No.
57, Kundrathur Min road, Gerugamnbakkam Porur, Chennei - 602101 (Tamil Nadu}
‘TESTING /ASSESSMENT FOR INTRINSIC SAFETY:
POWER SUPPLY: As declared by the applicant, the external 32VDC/80mA (max.)
Certified and approved intrinsically safe power supply must be used. Hence the above
power supply deserve no further considerations for intrinsic safety.
: The coil is shunted by bridge diodes to nullify the inductive effect of
the col, Since the coll and diodes are totally encapsulated, the diodes form integral part of
the solenoid coll, The solenoid coll, connected with an external 32VDC/80mA (max.)
ower source was tested in Spark Test Apparatus with Group IC gas miauré as per
clause 10.4 of 1S-5780-2002 individually. There was no ignition of the gas mixture.
CREEPAGE DISTANCE & CLEARANCE: Creepage distance and clearance between the
input terminals is greater than 3mm and complies with Table 4 of 1S: 5780-2002.
TEMPERATURE RISE: As the coll is totally encapsulated and at 32VDC/80mA (max.)
ower supply the maximum temperature class for intrinsically safe coll comes under T6
temperature dass with respect to 50 degree centigrade ambient.
INSULATION: The insulation between Intrinsically safe coil and the enclosure withstood
‘an ac test voltage of 500V rms for one min.
INTERNAL WIRING: The insuiated conductors of intrinsically safe coll withstood an ac
test voltage of SOOV rms for one minute,
SMALL COMPONENTS TEST: The ignition test was conducted on the components as
per the dause 10.7 of 1S:5780-2002 there was no explosion during the testing
IMPACT TEST: 1kg mass of hardened steel fallen vertically on the surface of the
enclosure to create impact eneray for Gr. II apparatus,
(CABLE PULL TEST: The cable pull test conducted satisfactorily as per the clause 10.13 of
15:5780-2002.
MATERIAL OF CONSTRUCTION OF ENCLOSURE: The IS coll with circuit is
‘encepsulated and housed inside @ stainless steel enclosure having IP-67 as per IS:12063-
1987.
EQUIPMENT USED.
(2) Motwane Digital Multimeter
(b) Break Flash Apparatus
(c) High Volt Test Set R—
(d) Temperature set up
4ofs
Continuation Sheet126 046 {
age HOE aK
Ed
A wone-7-~ |
Ma. AMBIENT 1
VALVE. CATALOGU
13) 2] 8
3 _ conn =
86
as eRe ne en
INTRINISCALLY SAFE
sia no 76
|] Ae mee
i
coe OF NG g
ia ON onarann "Mey
I mn)
APOIO LAR
E ‘oh
peeceiien sins jelusze. %
Lie
Fares fer pen
1) =
eames |
msn eeu eR
a bem
NOTES:
TIOLFRANCES £0.2 UNLESS OTNERWSE sprcine.
JASCO TRADEWARIC TO. BE Sm HIGH PER FV-034~ 002
| ‘SAIL, LETTERING TO BE t-2mm HicH UNESS ONLRMSE STAID
"VAED AREA TO BE BLUE [Light french blue]
‘VPUATE MUST BE TLAT WHT N00 (O.002")F8
‘yj SESIEEL. 216. 516,.{S0lL contin)
MESS: GAUGE. 0.240 Seal d2u)
i WtaISH_REQD: SATIN SEMI.GLOSS. YARNIUIL
a eases
{ NAMEPLATE FOR INTRINSICALLY SAFE FESUED M. ae [oat 13a
| SOLENOID OPERATOR AS PER IS:57H0-2002 526) INITINL” 0
fm rewina Pas Jane [nat
Tt ts
Po
ASCO (INDIA) LIMITED |.
TuiRo_anece [op : ows Hea sa
AUTOCAD Iveayenac] TOMERANCES ccoraomiamewsenes ay unity teen] sic socants oF ors af BRTR 3
1 ion Deon n70 | Parr oeh uae tsa tein ate Seu 126 046 ean
ete > | ; eg vn