Product Specification

03244E

MFR 11
Multi Function Relay
Protection

APPLICATIONS DESCRIPTION

The MFR 1 Series is a family of industrial Features (all versions)


grade protective relays that offer multiple · True RMS voltage · True RMS sensing
protective features in a single package. · Configurable trip/control set points
· Configurable delays for each alarm · Synch-check
Using a digital processor to measure true · Two-line LC display · Programmable relay
RMS values enables a high degree of
measuring accuracy regardless of harmonics, MFR 11/MP outputs
transients or disturbing pulses. · 24 Vdc power supply
· Discrete inputs for
· 3 configurable relays
The MFR 11 model is a generator or mains · Over-/undervoltage monit. (59/27)
enabling or remote
protection unit packaged into one compact · Over-/underfrequency monit. (81O/U) acknowledgment
device. Typical applications are generators · Voltage asymmetry monitoring (47)
and switchgear equipment that require · PC and front panel
independent protection architecture. Different MFR 11/NU configurable
packages offer additional functionality. Same features as MFR 11/MP, plus:
· Wide-range power supply (no 24 Vdc)
· Microprocessor
The MFR 11/MP is for mains protection use (90 to 265 Vac/dc) technology for
with over-/undervoltage, -frequency and accurate, repeatable
voltage asymmetry with 24 Vdc power supply MFR 11/VDEW and reliable
while the MFR 11/NU has the same Same features as MFR 11/MP, plus:
operation
functions, but utilizes a wide-range power · Vector/phase shift monitoring (78)
supply. · Programmable
MFR 11/G59
The MFR 11/VDEW adds phase/vector jump Same features as MFR 11/MP, plus: threshold setpoints
monitoring to the MP package. The · 8 configurable relays with individual time
MFR 11/G59 package adds df/dt (ROCOF) · Vector/phase shift monitoring (78) delays
protection. The MFR 11/G59N has the same · df/dt ROCOF monitoring (81RL)
features as the G59 package, but utilizes the · CE marked
wide-range power supply. MFR 11/G59N
Same features as MFR 11/G59, plus:
· UL/cUL Listed
The MFR 11/SC is used for synch-check and · Wide-range power supply (no 24 Vdc) · GL Approval
zero voltage detection to check whether two (90 to 265 Vac/dc)
systems are synchronous or de-energized.
MFR 11/SC
The compact size and multiple functions of Same features as MFR 11/MP, plus:
the MFR 11 help to simplify switchgear · 2 configurable relays
design. The digital display offers a user- · Synch-check (fixed to relay 3) (25)
friendly interface to setup the unit as well as · Zero voltage monitoring: dead bus start
monitor the operation and display any alarms. functionality (close CB to dead busbar)

MFR 11/SC+N
Same features as MFR 11/SC, but
· Wide-range power supply (no 24 Vdc)
(90 to 265 Vac/dc)
SPECIFICATIONS
Accuracy .......................................................................................... Class 1 Relay outputs ................................................................................ isolated
Power supply ............................................................. 24 Vdc (18 to 30 Vdc) Contact material ............................................................................... AgCdO
Packages NU / G59N / SC+N: 90 to 265 Vac/dc Load (GP) .................................................24 Vdc@2 Adc, 250 Vac@2 Aac
Intrinsic consumption ..................................................................max. 12 W Pilot duty (PD) ......................................................................24 Vdc@1 Adc
Ambient temperature ................................................................ -20 to 70 °C Housing ...................................................... Type APRANORM DIN 43 700
Ambient humidity...................................................... 95 %, non-condensing Dimensions .........................................................................96×72×130 mm
Voltage Rated /D:.......... [1] 66/115 Vac ....... [4] 230/400 Vac Front cutout .................................................................................91×67 mm
Maximum value (Vmax):.......... [1] 150 Vac ............ [4] 300 Vac Connection ................................................ screw/plug terminals depending
Rated voltage Vph-ground:.......... [1] 150 Vac ............ [4] 300 Vac on connector 1.5 mm² or 2.5 mm²
Rated surge voltage:.......... [1] 2.5 kV ............... [4] 4.0 kV Front .................................................................................insulating surface
Linear measuring range up to ....................................................... 1.3×Vrated Protection system................................................................................ IP 21
Measuring frequency ................................................50/60 Hz (40 to 70 Hz) Weight ............................................... depending on version, approx. 800 g
Input resistance ..................................................... [1] 0.21 MW, [4] 0.7 MW Disturbance test (CE) .................................................. tested according to
Max. power consumption per path ................................................ < 0.15 W applicable EN guidelines
Discrete inputs .............................................................................. isolated Listings ..................................... UL/cUL listed (note: max. voltages apply)
Input range ....................................................................18 to 250 Vac or dc for ordinary loc., file E231544
Input resistance .....................................................................approx. 68 kW Approvals........................................................... GL (Germanischer Lloyd)

DIMENSIONS
Front view

Configuration port 35 mm
65 mm
72 mm

27 mm

Back plate mounting


optional (please order
brackets P/N 8923-1023)
Bottom view
130 mm 50 mm
Back view with
connecting terminals
8

Configuration port
1 16
96 mm

90 mm

130 mm

70 75

32 17

Configuration port 2005-09-09 | MFR 11 Dimensions r1ww-3605-ab.skf


WIRING DIAGRAM

Packages G59 / G59N


19 20 21 22 23 24 25 26 27 28 29 30 31 32
Relay 8

Relay 7

Relay 6

Relay 5
3/4

Relay 4
supervised system (variable)

all Packages
1 2 3 4

(Measuring voltage N)
3/4

Measuring voltage Measuring voltage L3


three-wire or
four-wire system Measuring voltage L2
all Packages

9 10 11 12 13 14 15 16
Measuring voltage L1
Relay 3
(Package SC: Synch-check)
CB

Relay 2
MFR 11 (Multi Function Relay)
Pack. SC
70 71 72

not measured Synchronizing voltage L3


Relay 1
2/3
synchronizing system (fixed)

Synchronizing voltage L2 (Ready for operation)

Synchronizing voltage L1
The synchronizing voltage must be connected three-
phase if the measuring voltage is connected three-
phase (N not connected). If the measuring voltage is
connected four-phase (L1-L2-L3-N), the synchronizing
voltage may be connected two-phase (L1-L2). L3 is
connected only for compensation and is not measured.
24 Vdc
all Packages
5 6 7 8

Packages SC+N/NU/G59N: 90 to 265 Vac/dc


Measuring voltage: 100 V AC or 400 V AC
0 Vdc
The socket for the PC parameterization is situated
on the side of the unit. This is where the DPC
Blocking of protective functions must be plugged in.
or remote acknowledgement
Subject to technical modifications. 2005-09-13 | MFR 11 Wiring Diagram r13ww-3705-ap.skf
FEATURES OVERVIEW
International
Woodward
PO Box 1519 MFR 11
Fort Collins CO, USA

VDEW

SC+N
80522-1519

G59N
G59
MP

NU

SC
1000 East Drake Road
Fort Collins CO 80525
ANSI
Ph: +1 (970) 498-3634 Measuring/Display
Fax: +1 (970) 498-3058 Voltage ü ü ü ü ü ü ü
email: Voltage (2nd input for synch-check) ü ü
SalesPGD_NAandCA@woodward.com
Accessories
Europe Configuration via PC #1 ü ü ü ü ü ü ü
Woodward GmbH
Handwerkstrasse 29
Protection
70565 Stuttgart, Germany Overvoltage 59 ü ü ü ü ü ü ü
Ph: +49 (0) 711 789 54-510 Undervoltage 27 ü ü ü ü ü ü ü
Fax: +49 (0) 711 789 54-101 Overfrequency 81O ü ü ü ü ü ü ü
email: Underfrequency 81U ü ü ü ü ü ü ü
SalesPGD_EMEA@woodward.com
Voltage asymmetry 47 ü ü ü ü ü ü ü
Distributors & Service vector/phase shift (dj/dt) 78 ü ü ü
Woodward has an international df/dt (ROCOF) 81RL ü ü
network of distributors and Function
service facilities. For your
nearest representative, call the
Synch-check 25 ü ü
Fort Collins plant or see the Zero voltage monitoring: dead bus
ü ü
Worldwide Directory on our start (close CB to dead busbar)
website. I/O's
Output relays (configurable) 74 3 3 3 8 8 3 3
www.woodward.com Power Supply
24 Vdc ü ü ü ü
90 to 265 Vac/dc ü ü ü
Listings/Approvals
CE marked ü ü ü ü ü ü ü
For more information contact:

UL/cUL listed ü ü ü ü
GL (Marine) ü ü ü ü
Product Number P/N
Measuring inputs 110 Vac 5448-884 LR20610 8441-1003 5448-885 8441-1004 8441-1005 8441-1110
Measuring inputs 400 Vac 8441-1023 8441-1027 8441-1049 LR20406 8441-1103 8441-1097 8441-1111

#1 Cable incl. software necessary (DPC, Product Number P/N 5417-557)

TYPICAL APPLICATIONS
MFR 11/MP MFR 11/G59 MFR 11/SC

MFR 11/G59 MFR 11/SC


MFR 11/MP
Subject to technical modifications.
27
This document is distributed for 25
informational purposes only. It is not 27 59
to be construed as creating or
59 81O
becoming part of any Woodward
Governor Company contractual or 81U
warranty obligation unless expressly
81O
stated in a written sales contract. 81U
47
52 off
78
We appreciate your comments about 52 off 52 off
47
the content of our publications. 81RL
Please send comments including the I/O I/O I/O
document number below to
stgt-doc@woodward.com

© Woodward

All Rights Reserved

03244E - 2012/6/Stuttgart