NEW FD-G Series
Clamp-On
to Access
Limitless Data
FD - G Series
Monitor Compressed
Air and Gases
Throughout
Your Facility
NEW
Clamp-On
Gas Flow Meter
FD-G Series
2
ENDLESS
OPPORTUNITIES
❚ Variety of Applications
P.6
EFFORTLESS
INSTALLATION
❚ No Pipe Modification
❚ Completely Non-Invasive
P.8
LIMITLESS
INFORMATION
❚ Impressive Display
P.10
3
ENDLESS
OPPORTUNITIES
Main/Compressor Pipes
Branch Pipes
4
Nitrogen tank
Die-casting machines
Inspection machines
Molding machines
Welding machines
Energy saving
Stable operation
(cost reduction)
5
ENDLESS
OPPORTUNITIES
1 ¼"
¾" 1 ½" 2 ½" 4" 6"
1" 2" 3" 5" 8"
Range of Sizes NPS (Nominal Pipe Size) DN (Diameter Nominal) Compatible model
6
Compatible Pipes
Clamp directly onto a variety of metal pipes
throughout your facility. This includes
painted pipes, as well as pipes that may be
rusted on the inside, which will not affect the
detection stability of the unit.
Stainless
Iron
steel
Compatible Gases
Monitor air as it moves through the
compressors, receiving tanks, main lines,
and machines throughout the facility. Along
with compressed air, the FD-G Series is
designed to detect Nitrogen, as well as
other pressurized* gases in the facility.
*Gases must be pressurized to 58 PSI or greater to be detected Air Nitrogen
7
EFFORTLESS
INSTALLATION
No pipe modification
required for installation
8
Mount in Minutes
With zero pipe modification necessary and
no special tools or knowledge required for
installation, the FD-G Series units can be
mounted in mere minutes.
Completely Non-Invasive
Unlike conventional air flow meters that
require probes or pipe modifications, the
FD-G Series has zero impact on the air or
gas inside the pipe.
Zero
intrusion into
the pipe
9
LIMITLESS
INFORMATION
Conventional
unit
External device
required to log data
PC is needed for
data analysis
10
A wide range of functions and displays are at your fingertips
Easily determine the amount of leakage, and If it is not possible to shut down your equipment,
associated costs, by shutting down the the Dynamic Leak Function can judge and update
equipment that is consuming the air/gas, and the leakage rate during operation. By monitoring
then measuring the amount of air that is still the change in leakage rate, you can also identify
flowing through the leak points. when preventative maintenance is necessary.
Observe the impacts of your consumption Clearly calculate the true ROI of your efforts by
reduction efforts, or simply look for anomalies, by converting the consumption and leakage
comparing your current data against previous amounts into true monetary values. The results
days, months, or years. With up to 5 years of data of any cost or energy saving projects can now
storage, comparison has never been easier. be easily visualized and monetized.
11
LIMITLESS INFORMATION
Versatile Outputs
Server
Touch
Demand
panel Data
PLC control
Monitor, logger
system, etc.
etc.
P1
(P2)
Time 4 mA
Output 3.8 mA
ON
(N.O.) OFF
Output ON Lower limit Upper limit Instantaneous flow
(N.C.) OFF
If the flow exceeds the specified lower or upper limits, the signal outputs 3.8 mA or 20.5 mA.
12
Intuitive Software
Equipment A
Equipment B
Ethernet * Equipment C
Office
Can be used to
Screen capture create reports, etc. Setting values, target values,
alarm settings, etc.
Improvement
report
Energy analysis
report
Line A Line B Line C Line D Line E
13
ADDITIONAL FEATURES
Pressure sensor
AC power
unit
NTP STP
(Normal conversion) (Standard conversion)
English
CFM (S)
Display m3/h (N)
Japanese method
m3/h (S)
L/min (N)
L/min (S)
Chinese Volume at Volume at
0ºC 32°F , 20ºC* 68°F ,
Definition 101.3 kPa 14.7 psi 101.3 kPa 14.7 psi
German (atmospheric pressure) (atmospheric pressure)
14
CLEAR RETURNS
Situation
Compressors are one of the largest energy consumers in most
facilities, and in turn have some of the biggest impacts on electricity
costs. Sadly most facilities do not understand how much air is
consumed on a regular basis and only know the risk associated with
not having compressed air available. Due to this, multiple compressors
are run continuously to make sure there is always enough.
Cost Savings
Situation
Air and gas leakage is all too common throughout any facility, but it
is near impossible to recognize how much air or gas is being lost
and the associated energy costs. Due to this, most facilities rarely
take actions to reduce leakage, as the impacts are hard to realize.
Cost Savings
15
DETECTION PRINCIPLES
Delta TOF The FD-G monitors gas flow by emitting and receiving two different sets of ultrasonic pulses. One pulse
travels in the same direction as the gas flow and the other travels in the opposite direction of the gas flow.
( Time of Flight) By doing this, the FD-G can monitor the gas flow rate by measuring the time differences between the two
signals. This method offers stable detection and eliminates the effects of external factors.
Detection head
Transceiver Transceiver
Ultrasonic wave
(guided wave)
From detecting tiny leaks to measuring all the air coming from a
receiving tank, the FD-G Series can monitor it all. This series
0.018 CFM
*2
Minimum detectable flow :
boasts an impressive ±2% RD accuracy rating, which is even
more impressive with its 1:100 rangeability.
Rangeability *3 : 1:100
*1 Value obtained under conditions specified by KEYENCE. For details, see the specifications.
*2 Detectable flow taking account of zero point error in a 3/4" pipe.
*3 "Rangeability" is the ratio of the maximum to minimum flow for which accuracy is guaranteed.
16
How to Choose a Clamp-On Gas Flow Meter
To select the best FD-G series components for your installation location, follow the steps shown below.
STEP
1 Select a flow meter main unit and unit damping material P. 18
STEP
2 Select upstream/downstream damping material(s), if deemed necessary P. 19
FD-GDxxB
STEP
3 Determine mounting and power supply requirements P. 20
Unit connection cable M12 power supply cable AC power unit Separate system mounting bracket
FD-GU1 OP-88394
STEP
4 Select any additional components that may be necessary P. 22
Robust protection cover Pressure sensor connection cable and connector Communication cables
FD-GP1 M8 power supply cable Loose wires - M12 adapter USB cable Ethernet cable
connector (female) (A-mini B)
17
How to select an FD-G series setup
STEP
1 Check the diameter of the pipe on which the FD-G is to be mounted
B Flow meter
[Display unit + detection head +
mounting bracket]
3/4" (20 A)
ø25 to ø29 FD-GD20U Approx. 0.19 kg
ø0.98" to ø1.14" Approx.
FD-G25 2.2 kg
1" (25 A)
ø32 to ø36 FD-GD25U Approx. 0.21 kg
ø1.26" to ø1.42"
1 1/4" (32 A)
ø41 to ø45 FD-GD32U Approx. 0.29 kg
ø1.61" to ø1.77"
1 1/2" (40 A)
Approx.
ø47 to ø51 FD-GD40U Approx. 0.31 kg FD-G50 2.7 kg
ø1.85" to ø2.01"
2" (50 A)
ø58 to ø62 FD-GD50U Approx. 0.34 kg
ø2.28" to ø2.44"
2 1/2" (65 A)
ø72 to ø78 FD-GD65U Approx. 0.41 kg
ø2.83" to ø3.07" Approx.
FD-G80 3.6 kg
3" (80 A)
ø86 to ø92 FD-GD80U Approx. 0.46 kg
ø3.39" to ø3.62"
4" (100 A)
ø111 to ø117 FD-GD100U Approx. 0.56 kg
ø4.37" to ø4.61" Approx.
FD-G125 2.7 kg
5" (125 A)
ø138 to ø144 FD-GD125U Approx. 0.65 kg
ø5.43" to ø5.67"
6" (150 A)
ø163 to ø171 FD-GD150U Approx. 0.77 kg
ø6.42" to ø6.73"
Approx.
FD-G200 2.8 kg
8" (200 A)
ø214 to ø222 FD-GD200U Approx. 0.96 kg
ø8.43" to ø8.74"
18
STEP
2 Check the location where the FD-G will be installed
In order to detect the ultrasonic signals correctly, upstream/downstream damping material may be required,
depending on the FD-G unit's installation location.
1 Check the distance "L" to the nearest upstream and downstream junctions
U-bolt
❙ Weld L ❙ Branch in L
pipe
The length "L" from the sensor head to the junction on the upstream
and downstream sides determines whether or not upstream/downstream damping material is required.
If L is smaller than Lmin: The flow meter cannot be installed in this location. Look for another installation location.
If Lmin < L < Lmax: Upstream/downstream damping material is required on that side of the unit.
If L is greater than Lmax: Upstream/downstream damping material is not required on that side of the unit.
[Example] When the meter is mounted in the *Install the upstream/downstream damping
following location on a 2" (50 A) pipe: material in any position between the flow meter
and the junction.
500 mm 19.69" 1700 mm 66.93"
*If using the FD-GD100B/FD-GD125B/FD-
GD150B/FD-GD200B, 2 upstream/downstream
Upstream/downstream damping damping materials need to be installed on one
U-bolt
material installation side.
Lmin is 387 mm 15.24", and Lmax is 1500 mm 59.06", so the
flow meter can be used if upstream/downstream damping *Ensure that the upstream/downstream damping
material is installed on the upstream side. There is no need to material does not interfere with U-bolts and
install upstream/downstream damping material on the other such piping supports. If it does interfere,
downstream side. Therefore, only one upstream/downstream mount the piping support around the upstream/
damping material is needed. downstream damping material. U-bolt
19
How to select an FD-G series setup
STEP
3 Determine the mounting style and power supply method for the display unit
The components required vary depending on the mounting style and power supply method for the display unit.
Determine the most appropriate mounting style and power supply method for the display unit from the table below.
Then select the appropriate components shown in the diagram from the tables on the right.
vertical pipe
G Round
terminals
H AC cable
M12 power
supply cable E
DC power AC power
supply supply
F AC power unit
Integrated
Detection head Detection head
system on a display unit display unit Unit
D connection
horizontal pipe D Unit
cable
connection
cable
M12 power G Round
terminals
supply cable E
H AC cable
DC power AC power
supply supply
system
regardless of Display unit Separate
system Unit
the pipe Separate mounting I D connection
system bracket* cable
orientation mounting I Unit connection
bracket D cable
AC power
unit F
M12 power G R
ound terminals
supply cable E
H AC cable
DC power AC power
supply supply
* 2 Mounting brackets are required.
20
Unit connection cable
Cable for DC power supply options Select a M12 power supply cable according to the required cable length and specification.
AC power supply options The AC power unit convert AC power to 24 VDC for the FD-G.
Display unit
M12 cable*1 F AC power unit G Round terminals H Cables
F AC power unit
Appearance Model Material Weight
B ød G Round terminals (to be provided separately by customer) H Cables ( to be provided separately by customer)
Round Number No. of Overall outer Nominal cross-
Type terminal size required B (outer diameter) ød (inner diameter) Type core wires diameter sectional area
AC power supply M4 2 8.2 mm 0.32" or less 4.3 mm 0.17" or more AC power supply cable 2 ø6.5 to ø12.5 1.2 to 2.1 mm2
Analog output*2 M3 2 5.5 mm 0.22" or less 3.2 mm 0.13" or more Analog output cable*2 2 ø0.26" to ø 0.49" 0.3 to 1.75 mm2
*1 A 350mm 13.78" M12 cable is supplied with the AC power unit. If the display unit is to be installed distant from the AC power unit, an extension cable such as OP-85503 (2 m 6.56') or
OP-85504 (5 m 16.40') must be purchased separately. *2 The use of an analog output cable is optional.
*If the flow meter is to be installed as a separate system with an AC power supply, 2 separate system mounting brackets will be required.
21
How to select an FD-G series setup
STEP
4 Select any additional components that may be necessary
OP-51580 2 m 6.56'
USB cable A-mini B
OP-86941 5 m 16.40'
Name Model
USB cable PC Software
Software FD-GH1
Connections to PC, PLC, data logger, and other external devices on LAN
OP-88086 2 m 6.56'
Ethernet PLC
cable
Name Model
Software FD-GH1
EtherNet/IP™
Data
Modbus TCP
logger
22
Specifications
23
Specifications
AC power unit
Model FD-GU1
System Switching type
Input supply voltage 100 to 240 VAC; +10%/−15% (50/60 Hz)
Output voltage 24 VDC ±5%
Overvoltage category ll
Ripple noise 260 mV (p-p) or lower
Output capacity 9.1 W (0.38 A) (Class 2)
Power consumption 100 VAC: 0.3 A or lower; 200 VAC: 0.2 A or lower
Pollution degree 2
Withstand voltage 3000 VAC, 1 minute (between input and output, between all external terminals and case)
Momentary interruption 20 ms or lower
Wiring specifications AC input: power supply M4 terminal block, 2 poles; Analog output: M3 terminal block, 2 poles; DC output: M12 4-pin connector
Protection circuit Protection against power supply surge, protection against output short-circuiting
Enclosure rating IP65/67 (IEC60529)
Operating ambient temperature -20 to +50ºC -4 to 122°F (no freezing)
Environmental
Operating ambient humidity 5 to 90%RH (no condensation)
resistance
Vibration resistance 10 to 500 Hz power spectral density: 0.816 G2/Hz in X, Y, Z axis directions
Shock resistance Shock resistance 50 m/s2; 16 ms pulses, 1000 times each for X, Y, and Z axes
Material PBT
Weight Approx. 400 g
Main unit size 63 2.48" × 240 9.45" × 40 1.57" mm
Wiring examples
When control output + external input is used When control output + analog output is used
Inside AC terminal block cover Inside DC terminal block cover M12 connector
Terminal Terminal symbol Terminal Terminal symbol cable (female)
Role Role
block A block pin layout 1
A ANLG Analog output B A ANLG Analog output A 4 2
B
B COM Common (0 VDC) B N.C. (Not used)
3
C C
D
C N D C 0V 0 V DC
AC power
D L supply D 24 V 24 V DC
24
Dimensions Unit: mm inch
Flow meter
FD-G25
Max. 97 3.82"
3.17"
Max. 80.5
2.36"
Max. 60
1.10"
Max.
36.3 162.5
28
1.43" 6.40"
FD-G50/FD-G80
A
B D
9 11.3
0.35" 0.44"
FD-G50 FD-G80
A 98.8 3.89" 139.6 5.50"
G
C
F
B 89.6 3.53" 130.3 5.13"
C Max.80.5 3.17" Max.90.5 3.56"
D 278.9 10.98" 296.1 11.66"
E 58.2 2.29" 66.8 2.63"
F Max.60 2.36" Max.70 2.76"
Max.97 3.82" Max.107 4.21"
0.87"
G
Max.
E 162.5
22
6.40"
FD-G125/FD-G200
A
81.8 3.22" B
9 11.3
0.35" 0.44"
Max. 107 4.21"
3.56"
Max. 90.5
Max. 70 2.76"
12.4
0.49" FD-G125 FD-G200
A 96.8 3.81" 97.5 3.84"
B 332.4 13.09" 347.4 13.68"
C 105.3 4.15" 112.8 4.44"
0.28"
C 162.5
Max. 7
6.40"
25
Dimensions Unit: mm inch
When mounted on a horizontal pipe When tilted When USB cable is connected
60
2.36"
FD-G25/
27.9 1.10"
17°
3.33"
84.5
FD-G80/
38 1.50"
G125/
G200: 81.6 3.21"
15.7 0.62"
64.1 2.52"
100.5 3.96"
3.33"
84.5
FD-G25/G50: 37 1.46"
FD-G80/G125/G200: 52.1 2.05"
0.47"
27.1
12
1.07"
Model A B
FD-GD20B/FD-GD25B 200 7.87"
A
FD-GD32B/FD-GD40B/
245 9.65"
FD-GD50B
Max. 18
M4 FD-GD65B/FD-GD80B 320 12.60"
B
OP-88394
When used with display unit
254 10.00"
5 0.20" 227.5 8.96" 254 10.00"
.4
ø 6 5"
0.2
90 3.54"
72 2.83"
90 3.54"
1.34"
2.05"
34
52
107 4.21" 16
0.63"
45 1.77"
11.5 0.45"
Material: SUS304
Grounding
38.1 1.50"
surface
0.25"
6.4
Material: SUS304
Polycarbonate
26
M12 power supply cable
0.54" 13.7 30
ø12 ø0.47" ø4 ø0.16" 4 × 0.28 mm
2
1.18"
ø14
ø0.55"
67.4 2.65"
Oil proof PUR
OP-87636/87637
0. 15
"
R
59
Pin layout
44 1.73" OP-87636: 2000 78.74"/OP-87637: 10000 393.70"
M12 2 Number Colour
ø14.8 0.58"
1 3
4 1 Brown
2 White
ø4.7 ø0.19" (4 × 0.34 mm )
2
3 Blue
4 Black
AC power unit
FD-GU1
When separate system mounting bracket OP-88394 is used
254 10.00"
M4×2 M3×4 M3×4 5 0.20" 227.5 8.96" ø6.4 0.25"
63 2.48"
90 3.54"
72 2.83"
14.8 0.58"
49.5 1.95"
40 1.57"
M8 power supply cable (for use with pressure sensor signal input) Loose wires - M12 adapter connector (female)
OP-87632/87633 OP-88395
5° 1 Number Colour
2
18.9 0.74"
4 3 1 Brown
2 White
27.9 Material: Nylon
ø4.4 ø0.17" (4 × 0.25 mm 2) 3 Blue
1.10 " Zinc nickel plating
4 Black
C A D D ATA D O W N L O A D
www.keyence.com/CADG
27
PRESSURE SENSORS
Accessories
Adapters Display protection cover
Appearance Type Model Appearance Material Model
Amplifiers Accessories
Key Features Type Appearance
Model Appearance Designation Model
NPN PNP Panel mounting bracket kit
for OP-51476
> IP67 full stainless steel structure Standard AP-V80W AP-V80WP AP-V85W(P)
28
LIQUID LEVEL SENSOR
Sensors
CONTROLLER (Required) PROBE (Required)
FL-P20 (200 mm 0.66')
Key Features FL-P40 (400 mm 1.31')
FL-P60 (600 mm 1.97')
FL-P80 (800 mm 2.62')
> Completely trouble-free operation Standard type FL-P100 (1000 mm 3.28')
FL-001 FL-P120 (1200 mm 3.94')
> Sensing Guide-Pulse Technology FL-P140 (1400 mm 4.59')
FL-P160 (1600 mm 5.25')
> Multiple output options FL-P180 (1800 mm 5.91')
FL-P200 (2000 mm 6.56')
Cables
Appearance Standard power supply cable Model
29
LIQUID FLOW SENSORS/METERS
Appearance Model
Sensor head
Appearance Model
Rated
flow range
diameter* range
Clamp-On Flow Sensors ø3
ø2.7 to 3.7
1/8" FD-XC1R1
0.11" to 0.15" 0 to 1000
(3.18 mm) FD-XS1
mL/min
ø3.5 to 4.5
ø4 FD-XC1R2
0.14" to 0.18"
ø5.5 to 6.5
ø6 FD-XC8R1
0.22" to 0.26" 0 to 3000
1/4" ø5.9 to 6.9 mL/min
FD-XC8R2 FD-XS8
Plastic (6.35 mm) 0.23" to 0.27"
piping/ ø7.5 to 8.5
tubing ø8 FD-XC8R3 0 to 8000 mL/min
0.30" to 0.33"
3/8" ø9.0 to 10.0
FD-XC20R1
(9.53 mm) 0.35" to 0.39"
0 to 15 L/min
ø9.5 to 10.5
ø10 FD-XC20R2
0.37" to 0.41"
FD-XS20
ø11.5 to 12.5
Key Features ø12
0.45" to 0.49"
FD-XC20R3
0 to 20 L/min
1/2" ø12.2 to 13.2
> Detect micro flow rates FD-XC20R4
(12.7 mm) 0.48" to 0.52"
ø3
> Compatible with tubes and metal
1/8" ø2.8 to 5.5 mm 0 to 1000
pipes (3.18 mm) 0.11" to 0.22"
FD-XC1M FD-XS1
mL/min
> Stable detection of nearly any liquid ø4
ø6
0 to 3000
1/4" ø5.5 to 8.3 mm mL/min
FD-XC8M FD-XS8
(6.35 mm) 0.22" to 0.33"
Metal ø8 0 to 8000 mL/min
piping 3/8"
(9.53 mm) ø8.3 to 10.8 mm
FD-XC20M1 0 to 15 L/min
ø10 0.33" to 0.43"
ø10.5
FD-XS20
ø12
1/2" ø10.8 to 14 mm
FD-XC20M2 0 to 20 L/min
(12.7 mm) 0.43" to 0.55"
ø13.8
*Inch notation does not refer to the B-nominal in the JIS or ANSI standards, but to the standard whereby 1 inch = 25.4 mm.
*For a complete FD-X Series setup, please reference the FD-X Series brochure or contact your local KEYENCE office.
60 L/min
1/2"(15 A)
15.9 gal/min
FD-Q20C
100 L/min
3/4"(20 A)
26.4 gal/min
200 L/min
1"(25 A)
52.8 gal/min
FD-Q32C
Key Features 300 L/min
1 1/4"(32 A)
79.3 gal/min
> No pipe modification necessary
400 L/min
> Detects a large variety of liquid 1 1/2"(40 A)
105.7 gal/min
types FD-Q50C
500 L/min
> Adapts to all sorts of pipe materials 2"(50 A)
132.1 gal/min
30
FD-R Series Flow Meters
Supported pipe size Rated flow
Appearance Flow rate range (Typical) Weight Model
(Outer diameter) velocity range
Clamp-On Flow Meters 36 to 400 L/min 9 to 100 gal/min 2.4 to 24 m3/h
1 1/2" (40A)
(ø44 to ø55)
Approx.
FD-R50
2.5 kg
36 to 600 L/min 9 to 150 gal/min 2.4 to 36 m3/h
2" (50A)
(ø55 to ø64)
*The minimum flow rates (zero cut flow rates) can be changed in the settings.
Cables
Specifications Appearance Length Material Weight Model
Approx. 20 g
PA/FKM/EPDM ø7 to ø12 2 Pieces OP-88199
2 pieces
Accessories
Description Appearance Usage Weight Model
Approx.
Modular cable OP-26487
72 g
RS-232C
Approx.
conversion OP-26401
25 g
adapter [9-pin]
31
Clamp-On Gas Flow Meter
FD-G Series
CALL T O C O N TA C T Y O U R L O C A L O F F I C E
TOLL
FREE
1-888-KEYENCE
1 - 8 8 8 - 5 3 9 - 3 6 2 3
www.keyence.com SAFETY INFORMATION
Please read the instruction manual carefully in
order to safely operate any KEYENCE product.
The information in this publication is based on KEYENCE’s internal research/evaluation at the time of release and is subject to change without notice. KA1-1099
Company and product names mentioned in this catalog are either trademarks or registered trademarks of their respective companies.
The specifications are expressed in metric units. The English units have been converted from the original metric units. Unauthorized reproduction of this catalog is strictly prohibited.
Copyright © 2019 KEYENCE CORPORATION. All rights reserved. FDGSeriesCatalog-KA-C-US 1109-2 611K09