APTA5DC- BDF- D B
Dual Band Integrated dc Passing Surge Arrestor for AVA5­50 cable, 806–960 MHz and 
1700–2170 MHz, with interface type DIN Female Bulkhead 

CHARACTERISTICS

General Specifications
Interface 7-16 DIN Female Bulkhead
Body Style Bulkhead

Electrical Specifications
Operating Frequency Band 1710 – 2000 MHz | 2000 – 2170 MHz | 806 – 960 MHz
3rd Order IMD -116.0 dB
3rd Order IMD Test Method Two +43 dBm Carriers
Average Power 3000 W
Cable Impedance 50 ohm
Connector Impedance 50 ohm
Gas Tube Voltage 350 V
Insertion Loss, typical 0.10 dB
Insulation Resistance, minimum 5000 MOhm
Lightning Strike Capability 10 times @ 20 kA
Lightning Strike Capability Test Method IEEE C62.42-1991
Lightning Strike Capability Waveform 8/20 waveform
Lightning Strike Current 30 kA
Lightning Strike Current Waveform 8/20 waveform
Peak Power, maximum 40.00 kW
Shielding Effectiveness -130 dB

From North America, toll free Outside North America © 2007 Andrew Corporation, Westchester, IL 60154 US
Telephone: 1-800-255-1479 Telephone: +1-708-873-2307 All specifications are subject to change. Please see page 1 of 3
Fax: 1-800-349-5444 Fax: +1-779-435-8579 www.andrew.com for the most current information. 8/14/2007
Product Specifications
Outline Drawing

Mechanical Specifications
Attachment Durability 25 cycles
Connector Retention Tensile Force 495 lbf | 2200 N
Connector Retention Torque 119 in lb | 13 N-m
Inner Contact Attachment Method Captivated
Inner Contact Plating Silver
Interface Durability 500 cycles
Interface Durability Method IEC 169-16:9.5
Outer Contact Attachment Method RingFlare™
Outer Contact Plating Trimetal
Pressurizable No

Dimensions
Height 2.91 in | 73.91 mm
Length 5.24 in | 133.10 mm
Weight 1.65 lb | 0.75 kg
Width 1.93 in | 49.02 mm

Environmental Specifications
Corrosion Test Method MIL-STD-1344A, Method 1001.1, Test Condition A
Immersion Depth 1m
Immersion Test Mating Unmated
Immersion Test Method IEC 60529:2001, IPX8
Mechanical Shock Test Method MIL-STD-202F, Method 213B, Test Condition C
Moisture Resistance Test Method MIL-STD-202F, Method 106F
Operating Temperature -55 °C to +85 °C (-67 °F to +185 °F)

From North America, toll free Outside North America © 2007 Andrew Corporation, Westchester, IL 60154 US
Telephone: 1-800-255-1479 Telephone: +1-708-873-2307 All specifications are subject to change. Please see page 2 of 3
Fax: 1-800-349-5444 Fax: +1-779-435-8579 www.andrew.com for the most current information. 8/14/2007
Product Specifications
Storage Temperature -55 °C to +85 °C (-67 °F to +185 °F)
Thermal Shock Test Method MIL-STD-202, Method 107, Test Condition A-1, Low Temperature -55 °C
Vibration Test Method MIL-STD-202F, Method 204D, Test Condition B
Water Jetting Test Mating Unmated
Water Jetting Test Method IEC 60529:2001, IPX6

Standard Conditions
Attenuation, Ambient Temperature 20 °C | 68 °F
Average Power, Ambient Temperature 40 °C | 104 °F

Return Loss
Frequency Band VSWR Return Loss (dB)
806–960 MHz 1.12 25.00
1710–2000 MHz 1.13 24.00
2000–2170 MHz 1.07 29.00

* Footnotes
Immersion Depth Immersion at specified depth for 24 hours
Insertion Loss, typical 0.05√¯freq (GHz) (not applicable for Ellilptical Waveguide)

From North America, toll free Outside North America © 2007 Andrew Corporation, Westchester, IL 60154 US
Telephone: 1-800-255-1479 Telephone: +1-708-873-2307 All specifications are subject to change. Please see page 3 of 3
Fax: 1-800-349-5444 Fax: +1-779-435-8579 www.andrew.com for the most current information. 8/14/2007

You might also like