Door Controller Operating Manual
THE EL Date 2010.11.11
Page 1 / 12
Contents
1. Specification --------------------------------------------- 3
5. Calibration ------------------------------------------------ 6
5.1 Data
5.1.1 Monitor/01_BASIC MENU
5.1.2 Monitor/03_ERROR MENU
5.1.3 Program/01_CONTROL MENU
5.1.4 Interface Menu
5.1.5 Factory Menu
1. Specification
Applicable motor 3Φ AC220V, 400 W, 4P, 1.9 A 3Φ AC220V, 750 W, 4P, 3.8 A
2. System Diagram
3. External Connectors
4. HHT Operation
4.1 HHT Display & Key
The keypad menu of HIDC uses a tree data structure as shown in Figure.
Door controller logo is displayed in the topmost node. It has 2 sub.menu, [MONITOR] and
[PROGRAM] [MONITOR] is composed of [BASIC], [I/O] and [ERROR] [PROGRAM] is
composed of [CONTROL], [INTERFACE], [FACTORY] Each menu has its own information
according to the properties.
5. Calibration
The total moving length should be accurately measured in order to drive the door with
programmed Open/Close pattern. In case of first installment, replacement of a door
inverter or changing a parameter of [33_System_Ratio] or [36_Motor_Select] in
[01_CONTROL] menu, CALIBRATION is required.
1. Make sure of connectors between door inverter and motor check the direction of
rotation of the motor while the door is being opened. If the direction of rotation is counter
clockwise, phase.order of motor and inverter is correct. If it is clockwise, change U.V.W
phase.order to U.W.V phase.order.
2 . Make sure of the value of measured speed in [01_MONITOR/01_BASIC/02_FBK
RPM] connect the jumper of CON2 in inverter control board to 1.2 or 2.3 in order that
the value of [02_FBK RPM Rpm] is positive while the door is being opened.
1. Make sure connections of Open limit switch and Close limit switch are correct OPL
LED is ON when the door is opened fully and CLL LED is ON when the door is closed
fully in a state of correct connections.
2. The parameter can not be changed with a fully opened door. Do the calibration with a
fully closed door or in the middle of opening/closing (OLS OFF and CLS OFF).
Process of Calibration
5.1 Data
5.1.1 Monitor/01_BASIC MENU
27_USE_CAN OFF ON ON ON .
No
28_Reserved . . 0 0 . modification
01
CONTROL 29_Belt_Slip_MM 100 3000 100 100 mm
30_CLS2CLL_MM . . * * mm
31_Total_Length . . * * mm
32_Calibration 0 1 0 0 .
35_Door_Type CO SO CO CO .
Note)
UH Type and UM Type have different door mechanism and control programs and therefore are
not compatible use the correct type to your door system.
Figure 1 While the door is being opened, the pattern of speed & signals
Figure 2 While the door is being closed, the pattern of speed & signals
(HIDC.INT7I.UH type)
01_DAC_Ch1_SLT
02_DAC_Ch1_Max
03_DAC_Ch2_SLT
07_DAC_Ch4_SLT
02_
INTERFACE 08_DAC_Ch4_Max
No
09_Reserved . . . .
modified
10_Error Clear OFF ON OFF .