CONTENTS

CONTENTS

INSTALLATION CABLES
– General information about cables . . . . . . . . . . . . 3 SIGNAL CABLES
– Electrical properties. . . . . . . . . . . . . . . . . . . . 4 – LON CABLING
– Identification of insulated conductors . . . . . . . . . . 5 – Distributed data system of building technology . . . . . 57
– Notes and symbols . . . . . . . . . . . . . . . . . . . . 6 – LONAK 2 x 1,3 and LONAK ARM 2 x 1,3 . . . . . . . 58
– LONAK 2 x 2 x 0,8 and LONAK 2 x 2 x 0,65. . . . . . 59
– KLM . . . . . . . . . . . . . . . . . . . . . . 60
INSTALLATION CABLES – KLMA . . . . . . . . . . . . . . . . . . . . . . 61
– ML H07V-U . . . . . . . . . . . . . . . . . . . . . . . 7 – MMSA . . . . . . . . . . . . . . . . . . . . . . 62
– MK 90 H07V2-R . . . . . . . . . . . . . . . . . . . . . 8 – MMVDMA (MMPMA) . . . . . . . . . . . . . . . . . . 63
MKEM 90 H07V2-K . . . . . . . . . . . . . . . . . . . 10
– MMJ . . . . . . . . . . . . . . . . . . . . . . 12
– MPLM . . . . . . . . . . . . . . . . . . . . . . 14 DATA CABLES
– MKEMP . . . . . . . . . . . . . . . . . . . . . . 15 – Generic cabling systems
– MJAM . . . . . . . . . . . . . . . . . . . . . . 16 – General . . . . . . . . . . . . . . . . . . . . . . 64
– MJAM ARM . . . . . . . . . . . . . . . . . . . . . . 18 – Standards . . . . . . . . . . . . . . . . . . . . . . 64
– Screening . . . . . . . . . . . . . . . . . . . . . . 64
– Application and transmission classes . . . . . . . . . 64
POWER CABLES 0,6/1 kV – Recommendations . . . . . . . . . . . . . . . . . . . 64
– MCMK . . . . . . . . . . . . . . . . . . . . . . 20 – Data transmission cables . . . . . . . . . . . . . . . . 64
– MCMK . . . . . . . . . . . . . . . . . . . . . . 22 – Generic cabling construction . . . . . . . . . . . . . . 65
– AMCMK . . . . . . . . . . . . . . . . . . . . . . 24 – Atm . . . . . . . . . . . . . . . . . . . . . . 65
– MCCMK . . . . . . . . . . . . . . . . . . . . . . 26 – Meaning of the symbols . . . . . . . . . . . . . . . . 65
– Generic cabling cable type . . . . . . . . . . . . . . . 66
– The colour system of the conductors. . . . . . . . . . 66
CONTROL CABLES – Compliance statement . . . . . . . . . . . . . . . . . 67
– MMO . . . . . . . . . . . . . . . . . . . . . . 29 – UC 300 S 24 4P/ UC 300 DS 24 2 x 4P . . . . . . . . 68
– MCMO . . . . . . . . . . . . . . . . . . . . . . 30 – UC 300 24 4P/ UC 300 D 24 2 x 4P . . . . . . . . . . 70
– UC 400 S 24 4P/ UC 400 DS 24 4P . . . . . . . . . . 72
– UC 400 24 4P/ UC 400 D 24 2 x 4P . . . . . . . . . . 74
JUMPER WIRES – UC 600 SS 23/ 1 4P FRNC and
– MKJE 90 H05V2-U, MKJ 90 H05V2-K, UC 1200 SS 22 4P FRNC . . . . . . . . . . . . . . . . 76
– MKJT 90 H05V2-K . . . . . . . . . . . . . . . . . . . 32 – SUPERCAT . . . . . . . . . . . . . . . . . . . . . . 78
– MKEMT 90 H07V2-K . . . . . . . . . . . . . . . . . . 35
– MVJ 8 kV . . . . . . . . . . . . . . . . . . . . . . 36
FIBRE OPTIC CABLES
FIBRE OPTIC ACCESSORIES
FLEXIBLE CORDS
– MST H03VH-H . . . . . . . . . . . . . . . . . . . . . . 37 – Fibre optic cables in premises data networks . . . . . . 80
– MSO H03VVH2-F . . . . . . . . . . . . . . . . . . . . 38 – General
– MSOY H03VV-F . . . . . . . . . . . . . . . . . . . . . 39 – Type coding of optical fibre cables . . . . . . . . . . . 81
– MSK H05VV-F . . . . . . . . . . . . . . . . . . . . . . 40 – Colour coding system of optical fibre cables. . . . . . 81
– Optical fiber types . . . . . . . . . . . . . . . . . . . 81
– Different constructions of optical fibre cables . . . . . 82
INSTRUMENTATION CABLES – Optical fibre cables of NK Cables for different
– General: applications . . . . . . . . . . . . . . . . . . . . . . 82
– Data transmission cables . . . . . . . . . . . . . . . . 42 – Fymsu-term . . . . . . . . . . . . . . . . . . . . . . 83
– Electrical properties. . . . . . . . . . . . . . . . . . . 42 – Connectorised riser cables . . . . . . . . . . . . . . . 83
– Selection of the cable type . . . . . . . . . . . . . . . 43 – Distribution panels and cabinets . . . . . . . . . . . . 83
– Industrial networks . . . . . . . . . . . . . . . . . . . 44
– Symmetrical halogen-free instrumentation cables . . . 44 – Data and instrumentation cable
– Optical fibre cables in industry . . . . . . . . . . . . . 45 DATAJAMAK . . . . . . . . . . . . . . . . . . . . . . 84
– Wiring and installation cables
KLVMAAM, KLVMAM . . . . . . . . . . . . . . . . . . 86
INSTRUMENTATION CABLES
– JAMAK . . . . . . . . . . . . . . . . . . . . . . 46 CATV/ RG CABLES
– JAMAK ARM . . . . . . . . . . . . . . . . . . . . . . 47 – TELLU 13 . . . . . . . . . . . . . . . . . . . . . . 87
– JAMAK-C . . . . . . . . . . . . . . . . . . . . . . 48 – RG 58, (50 Ω), RG 59, (75 Ω) . . . . . . . . . . . . . 88
– NOMAK . . . . . . . . . . . . . . . . . . . . . . 50 – RG 213, RG 214, RG 223 (50 Ω) . . . . . . . . . . . . 89
– NOMAK-E . . . . . . . . . . . . . . . . . . . . . . 51
– FKAR-PG . . . . . . . . . . . . . . . . . . . . . . 52
– KLAM . . . . . . . . . . . . . . . . . . . . . . 53 CABLE DRUMS
– RD- . . . . . . . . . . . . . . . . . . . . . . 54 – Maximum length of cable per drum, in meters . . . . . . 90
– RD-Y(St)Y . . . . . . . . . . . . . . . . . . . . . . 55 – Dimensions and weights . . . . . . . . . . . . . . . . . 91
– JAMAK & JAMAK ARM JOINTIG . . . . . . . . . . . 56

2
GENERAL INFORMATION ABOUT CABLES

CATALOGUE INFORMATION INSTALLATION OF THE CABLE ON


The dimensions and weights are rounded nominal
THE DRUM
values. Installation of a cable onto cable drum as well as
The letters “D” and “A” appearing in the product winding to another drum must be done in the manner
specifications indicate: depicted below.
D = nominal overall diameter
A = cable’s total copper cross-section
Bold printing indicates an item normally kept in stock

APPLICATION
The harmonization document HD 516 (Guide to use of
low-voltage harmonized cables) provides a guide to
the proposed safe use of harmonized electric cables
according to HD 21.

Cables should be selected so that they are suitable for


the operating conditions.

Examples of operating conditions are:


- voltage
- overcurrent
- protective measures
- grouping of cables
- method of installation
- accessibility

Cables should be selected so that they are suitable for any


external influences which may exist.

Examples of external influences are:


- ambient temperature; minimum and maximum CE SYMBOL
- precence of rain, steam or accumulation of water
- precense of corrosive, chemical or polluting The CE symbol on cable packages indicates
substances compliance with the EU’s low-voltage directive.
- mechanical stresses (impact, tension, compression,
sharp edges)
- fauna (such as rodents) STANDARDS
- flora (such as mould)
- radiation (such as sunlight) The cables in the catalogue are manufactured
according to valid Finnish SFS standards or
international CENELEC standards.
LINYL™ The independent and controlled quality labels,
the symbol and the pan-European symbol,
Plastic-insulated conductors, ML, MK, MKEM and indicate that the cables have been tested and certified.
plastic-sheated cables MMJ as well as plastic-sheated
control cables MMO are coated with the Linyl plastic
compound. The Linyl conpound makes the cable very slick ISO 9001 QUALITY SYSTEM
and nearly frictionless, and thus requires only
one-fifth of the pulling force of an ordinary cable when The Quality Management System of Draka NK Cables Ltd
drawn in ducts. As a result of this “frictionlessness”, has been approved by Lloyd’s Register Quality Assurance
it is no longer necessary to use lubricants, which can be Ltd to ISO 9001 and 14001:1994 Quality Management
detrimental to plastics. Installation is easier, faster, lighter System Standard.
and considerably more economical and reliable.

3
ELECTRICAL PROPERTIES

RATED VOLTAGE Current ratings for flexible cables


(PVC cables according to HD 21)
The rated voltage of cables is marked Uo/U, where:
- Uo = rated voltage between the conductor and earth HD 516 Table 7a
or metallic screen
- U = rated voltage between conductors.
Cross-section of Current rating Current rating
conductors 2 cores load 3 cores load
mm2 A A
DIRECT CURRENT RESISTANCE OF
0,75 6 6
CONDUCTORS 1,0 10 10
1,5 16 16
The catalogue lists for each cable, the maximum direct
current resistance values for the conductor at 2,5 25 20
4 32 25
a temperature of +20 °C, permitted by the construction
standard.The current in a conductor heats up
the conductor. The rise in temperature increases Assumptions for table are:
the conductor’s resistance. The following table shows - Conductor temperature in PVC-insulated cables
some pre-calculated correction factors for the direct +70 °C.
current resistance of copper conductor: - Ambient air temperature +30 °C.

Conductor temperature °C Correction factor


20 1,0 Table for control cables.
40 1,079
60 1,157
70 1,196 The maximum permissible continuous
80 1,236 current load in amperes for PVC-insulated control cable
90 1,275 Uo/U=450/750 V installed in open air.

Number of Copper conductor cross-section


conductors with mm2
CABLES CURRENT CARRYING load
CAPACITY
0,75 1,5 2,5
Current carrying capacities of installation cables are given
4 – – 20
in HD 384.5.523 (or IEC 364-5-523): 7 8 13 16
Electrical installation of buildings section 523: 12 7 11 13
Current carrying capacities. 19 6 9 11
27 5 8 10
Current rating tables are based on the requirements of 37 4 7 9
the maximum permissible conductor temperatures in 48 4 6 –
continuous use and assumed installation conditions.
The correction factors must be used when the conditions Assumptions for table are:
differ from the installation conditions assumed in - Conductor temperature +70 °C
the current rating tables. - Ambient air temperature +25 °C

4
IDENTIFICATION OF INSULATED
CONDUCTORS

PREVIOUS AND NEW STANDARD, ABBREVIATIONS OF COLOURS


HD 308 S2 APPEARING IN CATALOGUE
(on drum, reel or coil labels)
MMJ, MJAM and MPLM
HD 308 S2 MU = BK Black
Previous New SI = BU Blue
KEVI = GNYE Green/yellow
2-wires RU = BN Brown
VA = WH White
PU = RD Red
N-system

3-wires KE = YE Yellow
ORA = OG Orange
4-wires HA = GY Grey

5-wires CONTROL CABLES


Conductors in control cables are of the same colour
Previous New (black ) and consecutively numbered starting from
the centre of the cable.
3-wires

SHEATH MARKINGS
S-ystem

4-wires
The following embossed or colour markings are marked
4-wires*
on the outer sheath of installation, power and control
cables used in fixed installations
- manufacturer’s code
5-wires - type designation, number and cross-section of
conductors, identification letters of the insulation
*Only for 1,5 and 2,5 mm2 cables colours, and rated voltage
MSK, MSO and MSOY - manufacturer’s internal code
- continuous meter marking
- SGS FIMKO certification mark
HD 308 S2
Previous New Example:
NK CABLES MMJ 5x2,5 mm2 S 300/500 V 24AS45
2-wires 00001

Previous New CERTIFICATIONS


N-system

3-wires SGS FIMKO -cerfified

4-wires
HAR -marked

5-wires
Russian Certification Standard

MCMK and MCCMK


HD 308 S2
Previous New

3-wires
S-ystem

4-wires

5-wires

5
NOTES AND SYMBOLS

SYMBOLS EAN CODE


The EAN number (European Article Number) will be
APPLICATION adopted in addition to the national electrical article
number. It is formed from the national electrical article
number as follows:
MAXIMUM TEMPERATURE
64 (= Finland’s country code)
100 (= manufacturer code applied for by
LOWEST TEMPERATURE Finnish Electrical Wholesalers’ Federation SSTL)
04 067 22 (= SSTL’s electrical number)
2 (control number calculated
BENDING RADIUS according to the EAN regulation)

Example. MMJ 3x1,5 S coil 64 100 04 067 22-2


N N TENSILE STRESS

VOLTAGE

STANDARD

CERTIFICATIONS

IDENTIFICATION OF CORES

CONSTRUCTION

SELF-EXTINGUISHING IEC 332-1

SELF-EXTINGUISHING IEC 332-3

ELECTROMAGNETIC COMPATIBILITY

HALOGENFREE

FIRE-RESISTANT IEC 331

NOTE

See more info


www.drakankc.fi all these
cables you find in NK Club.

6
INSTALLATION CABLES

Plastic-insulated conductor
ML H07V-U
Solid conductor

APPLICATION
N N
Maximum permissible tensile stress
during installation: Ax50 N/mm²
For fixed installation in a conduit, and for wiring in
appliances, switchgear and controlgear with
a maximum voltage of 1000 V (a.c.) or a maximum of RATED VOLTAGE
750 V (d.c.) to earth.
Uo/U = 450/750 V
Current carrying capacities according to HD 384.5.523
(or IEC 364-5-523): “Electrical installation of buildings” STANDARD
-section 523: Current carrying capacities.
SFS 5523 and CENELEC HD 21
Maximum permissible temperature of conductor:
– in continuous use +70 °C
– in short circuit (max. 5 s) +160 °C

Lowest recommended handling


temperature: -25 °C

Minimum recommended bending radius: Self-extinguishing IEC 332-1


– during installation 8xD
– in a final installation if bent only once 3xD

CONSTRUCTION
Insulation Lead-free Linyl PVC,
Conductor Annealed copper wire core identification by colours

1,5 mm2
Cross-section of conductor
and colour mm² 1,5 VA 1,5 RU 1,5 MU 1,5 SI 1,5 KEVI
EAN code (SSTL code) 64 100+
coil 04 008 00-3 04 008 02-7 04 008 03-4 04 008 07-2 04 008 08-9
Nominal overall diameter mm 2,7 2,7 2,7 2,7 2,7
Total weight kg/km 20 20 20 20 20
Direct current resistance of
conductorat+20 °C max. Ω/km 12,1 12,1 12,1 12,1 12,1
Standard delivery length m 200 200 200 200 200
2
2,5 mm
Cross-section of conductor and
colour mm² 2,5 VA 2,5 RU 2,5 MU 2,5 SI 2,5 KEVI
EAN code (SSTL code) 64 100+
coil 04 008 20-1 04 008 22-5 04 008 23-2 04 008 27-0 04 008 28-7
Nominal overall diameter mm 3,3 3,3 3,3 3,3 3,3
Total weight kg/km 31 31 31 31 31
Direct current resistance of
conductorat+20 °C max. Ω/km 7,41 7,41 7,41 7,41 7,41
Standard delivery length m 200 200 200 200 200
Coil = shrink-wrapped coil

7
INSTALLATION CABLES

Plastic-insulated conductor
MK 90 H07V2-R
Stranded conductor

APPLICATION RATED VOLTAGE


For permanent installation in a conduit, and for wiring Uo/U = 450/750 V
in appliances, switchgear and controlgear with
a maximum voltage of 1000 V (a.c.) or a maximum of
750 V (d.c.) to earth.
STANDARD

Current carrying capacities according to HD 384.5.523 SFS 5523 and CENELEC HD 21


(or IEC 364-5-523): “Electrical installation of buildings”
-section 523: Current carrying capacities.

Maximum permissible temperature of conductor:


- in continuous use +90 °C
- in a short circuit (max. 5 s) +160 °C

Lowest recommended handling


temperature: -25 °C

Minimum recommended bending radius:


- during installation 8xD
- in a final installation if bent only once 3xD

Maximum permissible tensile stress Self-extinguishing IEC 332-1


N N during installation Ax50 N/mm²

CONSTRUCTION
Conductor Annealed copper wires, stranded Insulation Lead-free Linyl PVC, core identification
by colours

1,5 mm2 2,5 mm2


Cross-section of conductor and
colour mm² 1,5 RU 1,5 MU 1,5 SI 1,5 KEVI 2,5 RU 2,5 MU 2,5 SI 2,5 KEVI
EAN code (SSTL code) 64 100+
coil 04 017 04-3 04 017 03-6 04 017 05-0 04 017 02-9 04 017 08-1 04 017 07-4 04 017 09-8 04 017 06-7
Nominal overall diameter mm 3,0 3,0 3,0 3,0 3,7 3,7 3,7 3,7
Total weight kg/km 22 22 22 22 35 35 35 35
Direct current resistance of
conductorat+20 °C max. Ω/km 12,1 12,1 12,1 12,1 7,41 7,41 7,41 7,41
Standard delivery length m 250 250 250 250 200 200 200 200
Coil = shrink-wrapped coil

8
INSTALLATION CABLES

Plastic-insulated conductor
MK90 H07V2-R
Stranded conductor

Cross-section of conductor and


colour mm² 4 MU 4 SI 4 KEVI 6 RU 6 MU 6 SI 6 KEVI
EAN code (SSTL code) 64 100+ 04 017 11-91 04 017 13-5 04 017 10-4 04 017 16-6 04 017 15-9 04 017 17-3 04 017 14-2
Nominal overall diameter mm 4,2 4,2 4,2 4,8 4,8 4,8 4,8
Total weight kg/km 52 52 52 70 70 70 70
Direct current resistance of
conductorat+20 °C max. Ω/km 4,61 4,61 4,61 3,08 3,08 3,08 3,08
Standard delivery length
coil m 150 150 150 100 100 100 100

Cross-section of conductor and


colour mm² 10 MU 10 SI 10 KEVI 16 MU 16 SI 16 KEVI
EAN code (SSTL code) 64 100+ 04 017 19-5 04 017 20-3 04 017 18-0 04 017 22-7 04 017 23-4 04 017 21-0
Nominal overall diameter mm 6,1 6,1 6,1 7,2 7,2 7,2
Total weight kg/km 115 115 115 175 175 175
Direct current resistance of
conductorat+20 °C max. Ω/km 1,83 1,83 1,83 1,15 1,15 1,15
Standard delivery length
coil m 100 100 100 100 100 100

Cross-section of conductor and


colour mm² 25 MU 25 SI 25 KEVI 35 MU 35 SI 35 KEVI
EAN code (SSTL code) 64 100+ 04 022 14-6 04 022 15-3 04 022 16-0 04 522 22-6 04 522 23-3 04 522 27-1
Nominal overall diameter mm 8,9 8,9 8,9 10,0 10,0 10,0
Total weight kg/km 270 270 270 370 370 370
Direct current resistance of
conductorat+20 °C max. Ω/km 0,727 0,727 0,727 0,524 0,524 0,524
Standard delivery length
coil m 100 100 100
drum m 500/6C 500/6C 500/6C

Cross-section of conductor and


colour mm² 50 MU 50 SI 50 KEVI 70 KEVI 95 KEVI 120 KEVI
EAN code (SSTL code) 64 100+ 04 522 33-2 04 522 37-0 04 522 38-7 04 022 48-6 04 022 58-0 04 022 66-5
Nominal overall diameter mm 11,7 11,7 11,7 13,4 16,0 18
Total weight kg/km 510 510 510 710 1000 1200
Direct current resistance of
conductorat+20 °C max. Ω/km 0,387 0,387 0,387 0,268 0,193 0,153
Standard delivery length
drum m 200/6C 200/6C 200/6C 200/6C 500/8E 800/11G
Coil = shrink-wrapped coil

9
INSTALLATION CABLES

Plastic-insulated conductor
MKEM 90 H07V2-K
Flexible conductor

APPLICATION RATED VOLTAGE


For fixed installation in a conduit, and for wiring in Uo/U = 450/750 V
appliances, switchgear and controlgear with
a maximum voltage of 1000 V (a.c.) or a maximum of
750 V (d.c.) to earth.
STANDARD

Current carrying capacities according to HD 384.5.523 SFS 5523 and CENELEC HD 21


(or IEC 364-5-523): “Electrical installation of buildings”
-section 523: Current carrying capacities.

Maximum permissible temperature of conductor:


- in continuous use +90 °C
- in a short circuit (max. 5 s) +160 °C

Lowest recommended handling


temperature: – 25 °C

Minimum recommended bending radius:


- during installation 8xD
- in a final installation if bent only once 3xD

Maximum permissible tensile stress Self-extinguishing IEC 332-1


N N during installation Ax50 N/mm²

CONSTRUCTION
Conductor Annealed copper wires, stranded Insulation Lead-free Linyl PVC, core identification
flexible by colours

Cross-section of conductor and


colour mm² 1,5 RU 1,5 MU 1,5 SI 1,5 KEVI 2,5 RU 2,5 MU 2,5 SI 2,5 KEVI
EAN code (SSTL code) 64 100+ 04 031 02-5 04 031 03-2 04 031 07-0 04 031 08-7 04 031 22-3 04 031 23-0 04 031 27-8 04 031 28-5
Nominal overall diameter mm 3,0 3,0 3,0 3,0 3,6 3,6 3,6 3,6
Total weight kg/km 21 21 21 21 32 32 32 32
Direct current resistance of
conductor at+20 °C max. Ω/km 13,3 13,3 13,3 13,3 7,98 7,98 7,98 7,98
Standard delivery length
coil m 250 250 250 250 200 200 200 200

10
INSTALLATION CABLES

Plastic-insulated conductor
MKEM 90 H07V2-K
Flexible conductor

Cross-section of conductor and


colour mm² 4 MU 4 SI 4 KEVI 6 MU 6 SI 6 KEVI
EAN code (SSTL code) 64 100+ 04 031 43-8 04 031 47-6 04 031 48-3 04 031 63-6 04 031 67-4 04 031 68-1
Nominal overall diameter mm 4,1 4,1 4,1 5,0 5,0 5,0
Total weight kg/km 45 45 45 70 70 70
Direct current resistance of
conductorat+20 °C max. Ω/km 4,95 4,95 4,95 3,30 3,30 3,30
Standard delivery length , coil m 100 100 100 100 100 100

Cross-section of conductor and


colour mm² 10 MU 10 SI 10 KEVI 16 MU 16 SI 16 KEVI
EAN code (SSTL code) 64 100+ 04 031 83-4 04 031 87-2 04 031 88-9 04 032 03-9 04 032 07-7 04 032 08-4
Nominal overall diameter mm 6,5 6,5 6,5 7,6 7,6 7,6
Total weight kg/km 115 115 115 170 170 170
Direct current resistance of
conductorat+20 °C max. Ω/km 1,91 1,91 1,91 1,21 1,21 1,21
Standard delivery length, coil m 100 100 100 100 100 100

Cross-section of conductor and


colour mm² 25 MU 25 SI 25 KEVI 35 MU 35 SI 35 KEVI
EAN code (SSTL code) 64 100+ 04 032 13-8 04 032 17-6 04 032 18-3 04 532 23-2 04 532 27-0 04 532 28-7
Nominal overall diameter mm 9,4 9,4 9,4 11,0 11,0 11,0
Total weight kg/km 270 270 270 370 370 370
Direct current resistance of
conductorat+20 °C max. Ω/km 0,780 0,780 0,780 0,554 0,554 0,554
Standard delivery length
coil m 100 100 100
drum m 500/6C 500/6C 500/6C

Cross-section of conductor and


colour mm² 50 MU 50 SI 50 KEVI 70 MU 70 SI 70 KEVI
EAN code (SSTL code) 64 100+ 04 532 33-1 04 532 37-9 04 532 38-6 04 532 43-0 04 532 47-8 04 532 48-5
Nominal overall diameter mm 13,0 13,0 13,0 13,0 15,0 15,0
Total weight kg/km 520 520 520 730 730 730
Direct current resistance of
conductorat+20 °C max. Ω/km 0,386 0,386 0,386 0,272 0,272 0,272
Standard delivery length, drum m 200/6C 200/6C 200/6C 200/6C 200/6C 200/6C

Cross-section of conductor and


colour mm² 95 MU 95 SI 120 MU 150 MU 240 MU
EAN code (SSTL code) 64 100+ 04 032 53-4 04 032 57-2 04 032 63-3 04 032 73-2 04 032 93-0
Nominal overall diameter mm 17,5 17,5 19 22 27
Total weight kg/km 940 940 1200 1450 2400
Direct current resistance of
conductorat+20 °C max. Ω/km 0,206 0,206 0,161 0,129 0,0801
Standard delivery length, drum m 200/7E 200/7E 200/7E 200/7E 450/11G

11
INSTALLATION CABLES

Plastic-sheathed cable
MMJ

APPLICATION RATED VOLTAGE


For fixed surface or flush-mounted installations, Uo/U = 300/500 V, 1,5 mm² and 2,5 mm²
indoors and outdoors. Uo/U = 450/750 V, 6 mm² ... 25 mm²
- Suitable for installation in a slot covered with plaster

- Not for installation directly in ground nor directly in


STANDARD
concrete without protective ducting.
- Not for installations subject to electrical interference SFS 2091 and SFS 5524
(see MCCMK and MJAM).
- Direct sunlight may change colour of sheath

Current carrying capacities according to HD 384.5.523


(or IEC 364-5-523): “Electrical installation of buildings” CORE IDENTIFICATION
-section 523: Current carrying capacities.
N-system S-ystem
Maximum permissible temperature of conductor:
- in continuous use +70 °C 2-wires 3-wires
- in a short circuit (max. 5 s) +160 °C
3-wires 4-wires
Lowest recommended handling
temperature: -15 °C
4-wires 4-wires*
Minimum recommended bending radius:
- during installation 10xD 5-wires 5-wires
- in a final installation if bent only once 3xD

Maximum permissible tensile stress Self-extinguishing IEC 332-1


N N during installation Ax50 N/mm²
*Only for 1,5 and 2,5 mm2 cables

CONSTRUCTION
Conductor Annealed copper 1,5 and 2,5 mm², solid Filling Filling compound
6...25 mm², stranded Sheath White, leadfree Linyl PVC
Insulation Leadfree PVC, core identification by colours - marked by meters

WITH PROTECTIVE CONDUCTOR


Number of conductors and
cross-section nxmm² 3 x 1,5 S 3 x 2,5 S 3x6S 3 x 10 S
EAN code (SSTL code)
(coil) 64 100+ 04 067 22-2 04 067 23-9 04 067 25-3 –
(reel) 64 100+ 04 567 72-2 04 567 73-9 – –
(drum) 64 100+ 04 567 22-7 04 567 23-4 04 567 25-8 04 067 26-0
Nominal overall diameter mm 8,8 10,0 14,1 17,1
Total weight kg/km 130 180 350 540
Direct current resistance of
conductor at +20 °C.max. Ω/km 12,1 7,41 3,08 1,83
Standard delivery length
coil m 100 100 50 –
reel m 300 200 – –
drum m 1000/K7 1000/K7 500/K8 400/K8

12
INSTALLATION CABLES

Plastic-sheathed cable
MMJ

WITH PROTECTIVE CONDUCTOR


Number of conductors and
cross-section nxmm² 4 x 1,5 S 4 x 2,5 S 4x6S 4 x 10 S 4 x 16 S
EAN code (SSTL code)
(coil) 64 100+ 04 067 32-1 04 067 33-8 – – –
(reel) 64 100+ 04 567 82-1 – – – –
(drum) 64 100+ 04 567 32-6 04 567 33-3 04 567 35-7 04 067 36-4 04 567 37-1
Nominal overall diameter mm 9,6 11,0 15,3 18,8 21,0
Total weight kg/km 155 220 430 670 940
Direct current resistance of
conductor at +20 °C.max. Ω/km 12,1 7,41 3,08 1,83 1,15
Standard delivery length
coil m 100 100 – – –
reel m 250 – – – –
drum m 1000/K7 750/K7 500/K8 400/K8 250/K8
WITH PROTECTIVE CONDUCTOR
Number of conductors and
cross-section nxmm² 5 x 1,5 S 5 x 2,5 S 5x6S 5 x 10 S 5 x 16 S 5 x 25 S
EAN code (SSTL code)
(coil) 64 100+ 04 067 42-0 04 067 43-7 – – – –
(reel) 64 100+ 04 567 92-0 04 567 93-7 – – – –
(drum) 64 100+ 04 567 42-5 04 567 43-2 04 567 45-6 04 067 46-8 04 067 47-5 04 067 48-2
Nominal overall diameter mm 10,3 11,8 16,6 21,0 23,0 31,0
Total weight kg/km 180 260 510 830 1200 1900
Direct current resistance of
conductor at +20 °C.max. Ω/km 12,1 7,41 3,08 1,83 1,15 0,727
Standard delivery length
coil m 100 50 – – – –
reel m 200 150 – – – –
drum m 1000/K7 750/K8 500/K8 250/K8 250/K9 250/K11

WITHOUT PROTECTIVE CONDUCTOR


Number of conductors and
cross-section nxmm² 2 x 1,5 N 2 x 2,5 N 3 x 1,5 N 4 x 1,5 N 5 x 1,5 N
EAN code (SSTL code)
(coil) 64 100+ 04 064 12-2 04 064 13-9 04 064 22-1 04 064 32-0 04 064 42-9
(drum) 64 100+ 04 564-12-7 04 564 13-4 04 564 22-6 04 564 32-5 04 564 42-4
Nominal overall diameter mm 8,4 9,6 8,8 9,6 10,3
Total weight kg/km 105 150 130 155 180
Direct current resistance of
conductor at +20 °C.max. Ω/km 12,1 7,41 12,1 12,1 12,1
Standard delivery length
coil m 100 100 100 100 100
drum m 1000/K7 1000/K7 1000/K7 1000/K7 1000/K7

13
INSTALLATION CABLES

Surface installation cable NOTKA™


MPLM

APPLICATION RATED VOLTAGE


For fixed surface installation indoors. Uo/U = 300/500 V

Current carrying capacities according to HD 384.5.523


(or IEC 364-5-523): “Electrical installation of buildings”
STANDARD
-section 523: Current carrying capacities.
SS 424 02 19-2
Maximum permissible temperature of conductor:
- in continuous use +70 °C
- in a short circuit (max. 5 s) +160 °C

Lowest recommended handling CORE IDENTIFICATION


temperature: –15 °C
N-system S-ystem
Minimum recommended bending radius:
- during installation 10xD 2-wires 3-wires
- in a final installation if bent only once 3xD
3-wires
Maximum permissible tensile stress
N N during installation Ax50 N/mm²
4-wires

5-wires

Self-extinguishing IEC 332-1

CONSTRUCTION
Conductor Annealed copper wire Drain wire Tinned copper wires
Insulation PVC, core identification by colours Metal sheath Longitudinal aluminium tape
Filling Filling compound Sheath White PVC

WITHOUT
WITH PROTECTIVE CONDUCTOR PROTECTIVE
CONDUCTOR
Number of conductors and
cross-section nxmm² 3 x 1,5/1 S 3 x 2,5/1 S 4 x 1,5/1 S 5 x 1,5/1 S 2 x 1,5/1 N 3 x 1,5/1 N
EAN code (SSTL code) 64 100+ 04 055 26-7 04 055 27-4 04 055 36-6 04 055 46-5 04 055 11-3 04 055 23-6
Nominal overall diameter mm 8,5 9,8 9,2 10,0 8,0 8,5
Total weight kg/km 130 185 165 185 110 130
Direct current resistance of
conductor at +20 °C.max. Ω/km 12,1 7,41 12,1 12,1 12,1 12,1
Standard delivery length
coil m 50 50 50 50 50 50

14
INSTALLATION CABLES

Cable for lamp-posts


MKEMP
Flexible conductor

APPLICATION RATED VOLTAGE


For fixed installation mainly as a connecting cable for Uo/U = 450/750 V
post mounted luminaires.

Maximum permissible temperature of conductor:


STANDARDI
- in continuous use +70 °C
- in a short circuit (max. 5 s) +160 °C SFS 5523 and SFS 2091

Lowest recommended
handling temperature: -25 °C

Minimum recommended bending radius:


- during cable pulling 10xD
- in a final installation if bent only once 3xD

Maximum permissible tensile stress: Ax50 N/mm²


N N
Self-extinguishing IEC 332-1

CONSTRUCTION
Conductor Annealed copper wires, Sheath PVC
stranded flexible
Insulation PVC

Cross-section of conductors
and colour mm² 2,5 MU 2,5 SI 2,5 KEVI
EAN code (SSTL code) 64 100+ 04 034 03-3 04 034 07-1 04 034 08-8
Nominal overall diameter mm 8,0 8,0 8,0
Total weight kg/km 82 82 82
Direct current resistance of
conductor at +20 °C max. Ω/km 7,98 7,98 7,98
Standard delivery length
coil m 100 100 100

15
INSTALLATION CABLES

Metal sheathed cable


MJAM™

APPLICATION RATED VOLTAGE


Cable for the control, measuring and signal circuits of Uo/U = 450/750 V
electrical equipment and feeder cable for electronic
equipment for fixed surface and flush-mounted
installations, indoors and outdoors.
STANDARD

The lapped Al-PE laminate forms a good screen against SS 4240219


electrical interference and the laminate
combined with the PE-sheath forms a good moisture
barrier.

Current carrying capacities according to HD 384.5.523 CORE IDENTIFICATION


(or IEC 364-5-523): “Electrical installation of buildings”
S-ystem
-section 523: Current carrying capacities.

Maximum permissible temperature of conductor: 3-wires


- in continuous use +70 °C
- in a short circuit (max. 5 s) +160 °C
4-wires
Lowest recommended
handling temperature: –15 °C
4-wires*

Minimum recommended bending radius:


- during installation 12xD 5-wires
- in a final installation if bent only once 8xD

Maximum permissible tensile stress *Only for 1,5 and 2,5 mm2 cables
N N during installation Ax50 N/mm² Control cables 7...19 wires; numbers

Self-extinguishing IEC 332-1

Electromagnetic compatibility

16
INSTALLATION CABLES

Metal sheathed cable


MJAM™

CONSTRUCTION
Conductor Annealed copper: Filling Filling compound
1,5 and 2,5 mm2 solid Metallic screen AI-PE laminate and drain wire,
6 and 10 mm2 stranded 1,0 mm²
Insulation Leadfree PVC, core identification by Sheath White PE/leadfree PVC
colours and/or numbers - marked by meters

WITH PROTECTIVE CONDUCTOR


Number of conductors and
cross-section nxmm² 3 x 1,5 S 3 x 2,5 S 3x6S
EAN code (SSTL code) 64 100+ 04 130 01-8 04 130 02-5 04 130 04-9
Nominal overall diameter mm 10 11,5 15
Total weight kg/km 145 200 360
Direct current resistance of
conductor at +20 °C.max. Ω/km 12,1 7,41 3,08
Standard delivery length
drum m 500/K6 500/K7 250/K8

WITH PROTECTIVE CONDUCTOR


Number of conductors and
cross-section nxmm² 5 x 1,5 S 5 x 2,5 S 5x6S
EAN code (SSTL code) 64 100+ 04 130 07-0 04 130 08-7 04 130 10-0
Nominal overall diameter mm 11,5 13 18
Total weight kg/km 200 280 520
Direct current resistance of
conductor at +20 °C.max. Ω/km 12,1 7,41 3,08
Standard delivery length
drum m 500/K7 500/K7 250/K8
WITHOUT PROTECTIVE CONDUCTOR
Number of conductors and
cross-section nxmm² 7 x 1,5 12 x 1,5 19 x 1,5
EAN code (SSTL code) 64 100+ 04 130 15-5 04 130 18-6 04 130 20-9
Nominal overall diameter mm 12,5 16 19
Total weight kg/km 250 380 550
Direct current resistance of
conductor at +20 °C.max. Ω/km 12,1 12,1 12,1
Standard delivery length
drum m 400/K7 400/K8 400/K9
Electrical properties
Capacitance between
two adjacent conductors
at +20 °C and 50 Hz nF/km 130...160 130...160 130...160
Capacity to earth of
one conductor
at +20 °C and 50 Hz nF/km 210...280 210...280 210...280

17
INSTALLATION CABLES

Armoured metal-sheathed cable


MJAM™ARM

APPLICATION RATED VOLTAGE


Cable for the control, measuring and signal circuits of Uo/U = 450/750 V
electrical equipment and feeder cable for electronic
equipment for fixed surface and flush-mounted
installations, indoors and outdoors.
STANDARD

The armouring and the lapped AI-PE laminate forms SFS 5247 and SS 4240219
a good mechanical, electrical and electromagnetical
shield for the cable, and the laminate combined with the
PE-sheath forms a good moisture barrier.

Current carrying capacities according to HD 384.5.523 CORE IDENTIFICATION


(or IEC 364-5-523): “Electrical installation of buildings”
S-ystem
-section 523: Current carrying capacities.

Maximum permissible temperature of conductor: 3-wires


- in continuous use +70 °C
- in a short circuit (max. 5 s) +160 °C
4-wires
Lowest recommended
handling temperature: -15 °C
4-wires*
Minimum recommended bending radius:
- during installation 12xD
- in a final installation if bent only once 8xD 5-wires

Maximum permissible tensile stress


N N during installation Ax50 N/mm² *Only for 1,5 and 2,5 mm2 cables
Control cables 7...19 wires; numbers

Self-extinguishing IEC 332-1

Electromagnetic compatibility

18
INSTALLATION CABLES

Armoured metal-sheathed cable


MJAM™ARM

CONSTRUCTION
Conductor Annealed copper: Metallic screen AI-PE laminate and
1,5 and 2,5 mm2 solid drain wire, 1,0 mm²
6 and 10 mm2 stranded Sheath White PE/leadfree PVC
Insulation Leadfree PVC, core identification by Armouring Two zinc-coated steel tapes
colours and/or numbers Sheath Black leadfree PVC
Filling Filling compound - marked by meters

WITH PROTECTIVE CONDUCTORS


Number of conductors and
cross-section nxmm² 3 x 1,5 S 3 x 2,5 S
EAN code (SSTL code) 64 100+ 04 130 51-3 04 130 52-0
Nominal overall diameter mm 13 15
Total weight kg/km 290 360
Direct current resistance of
conductor at +20 °C.max. Ω/km 12,1 7,41
Standard delivery length
drum m 300/6C 300/7E

WITH PROTECTIVE CONDUCTORS


Number of conductors and
cross-section nxmm² 5 x 1,5 S 5 x 2,5 S
EAN code (SSTL code) 64 100+ 04 130 57-5 04 130 58-2
Nominal overall diameter mm 15 17
Total weight kg/km 360 460
Direct current resistance of
conductor at +20 °C.max. Ω/km 12,1 7,41
Standard delivery length
drum m 300/7E 300/8E

WITHOUT PROTECTIVE CONDUCTORS


Number of conductors and
cross-section nxmm² 7 x 1,5 7 x 2,5 12 x 1,5 19 x 1,5
EAN code (SSTL code) 64 100+ 04 130 65-0 04 130 66-7 04 130 68-1 04 130 70-4
Nominal overall diameter mm 16 18 20 23
Total weight kg/km 430 560 610 820
Direct current resistance of
conductor at +20 °C.max. Ω/km 12,1 7,41 12,1 12,1
Standard delivery length
drum m 400/8E 400/9E 400/11G 400/11G
Electrical properties
Capacitance between
two adjacent conductors
at +20 °C and 50 Hz nF/km 130...160 130...160 130...160 130...160
Capacity to earth of
one conductor
at +20 °C and 50 Hz nF/km 210...280 220...290 210...280 210...280

19
POWER INSTALLATION CABLES

MCMK

APPLICATION RATED VOLTAGE


For fixed installation indoors, outdoors and Uo/U = 0,6/1 kV Um = 1,2 kV
underground as well as in building structures,
e.g. directly in concrete.
STANDARD
Not for installations subject to severe electrical
interference (see MCCMK and MJAM). SFS 4880, HD 603-3F S1, IEC 60502-1

Current carrying capacities according to HD 384.5.523


(or IEC 364-5-523): “Electrical installation of buildings”
-section 523: Current carrying capacities.
CORE IDENTIFICATION
Maximum permissible temperature of conductor:
- in continuous use +70 °C
- in a short circuit (max. 5 s) +160 °C
2-wires
Lowest recommended
handling temperature: –15 °C

Minimum recommended bending radius: 3-wires


- during installation 12xD
- in a final installation if bent only once 8xD

Maximum permissible tensile stress


N N during installation Ax50 N/mm² 4-wires

Electromagnetic compatibility

Self-extinguishing IEC 332-1

20
POWER INSTALLATION CABLES

MCMK

CONSTRUCTION
Conductor Annealed copper Concentric
1,5 ... 6 mm², solid conductor A layer of copper wires and an open
10 and 16 mm² , stranded helix of parallel copper wires
Insulation Leadfree PVC, core identification by Sheath Black, leadfree PVC
colours and/or numbers - marked by meters
Filling Filling compound

Number of conductors and


cross-section nxmm² 2 x 1,5/1,5 2 x 1,5/1,5 2 x 2,5/2,5 2 x 2,5/2,5 2 x 6/6 2 x 10/10 RM
EAN code (SSTL code) 64 100+ 06 021 12-3 06 021 22-2 06 021 13-0 06 021 23-9 06 021 25-3 06 021 26-0
Nominal overall diameter mm 11,5 11,5 12,3 12,3 16,2 19,0
Total weight kg/km 165 165 200 200 370 550
Direct current resistance of
conductor at +20 °C.max. Ω/km 12,1 12,1 7,41 7,41 3,08 1,83
Standard delivery length
coil m 100 100
drum m 1000/8E 1000/K9 500/K8 500/K9

Number of conductors and


cross-section nxmm² 3 x 1,5/1,5 3 x 2,5/2,5 3 x 6/6 3 x 10/10 RM 3 x 16/16 RM
EAN code (SSTL code) 64 100+ 06 021 52-9 06 021 53-6 06 021 55-0 06 021 56-7 06 021 57-4
Nominal overall diameter mm 12 13 17 20,0 23,0
Total weight kg/km 190 240 450 680 970
Direct current resistance of
conductor at +20 °C.max. Ω/km 12,1 7,41 3,08 1,83 1,15
Standard delivery length
drum m 1000/K8 1000/K9 500/K8 500/K9 500/K11

Number of conductors and


cross-section nxmm² 4 x 1,5/1,5 4 x 1,5/1,5 4 x 2,5/2,5 4 x 2,5/2,5 4 x 6/6 4 x 10/10 RM 4 x 16/16 RM
EAN code (SSTL code) 64 100+ 06 021 92-5 06 021 72-7 06 021 93-2 06 021 43-7 06 021 45-1 06 021 76-5 06 021 47-5
Nominal overall diameter mm 13 13 14 14 18,5 22 25
Total weight kg/km 210 210 270 270 520 790 1150
Direct current resistance of
conductor at +20 °C.max. Ω/km 12,1 12,1 7,41 7,41 3,08 1,83 1,15
Standard delivery length
coil m 100 100
drum m 1000/K9 1000/K9 500/K9 500/K11 500/K11

21
POWER INSTALLATION CABLES

MCMK 1kV

APPLICATION RATED VOLTAGE


For fixed installation indoors, outdoors and Uo/U = 0,6/1 kV Um = 1,2 kV
underground as well as in building structures,
e.g. directly in concrete.
STANDARD
Not for installations subject to severe electrical
interference (see MCCMK). SFS 4880, HD 603-3F S1, IEC 60502-1,
IEC 60332-3
Current carrying capacities according to HD 384.5.523
(or IEC 364-5-523): “Electrical installation of buildings”
-section 523: Current carrying capacities.

Maximum permissible temperature of conductor: CORE IDENTIFICATION


- in continuous use +70 °C
- in a short circuit (max. 5 s) +160 °C

Lowest recommended
handling temperature: –15 °C 3-wires

Minimum recommended bending radius:


- during installation 12xD
- in a final installation if bent only once 8xD 4-wires
Maximum permissible tensile stress
N N during installation Ax50 N/mm²

Self-extinguishing IEC 332-3

22
POWER INSTALLATION CABLES

MCMK 1kV

CONSTRUCTION
Conductor Compacted, annealed (AN), copper Laying up Three phase conductors
conductor 25 and 35 mm², and neutral stranded together
round 50 mm² and larger , sector PE/PEN-conductor A layer of copper wires and an
shaped open helix of copper tape
Installation Lead-free PVC, core identification Sheath Black, leadfree PVC compound
by colours

MCMK 3½
Number of conductors and
cross-section nxmm² 3 x 25/16 AN 1kV 3 x 35/16 AN 1kV 3 x 50/25 AN 1kV 3 x 70/35 AN 1kV 3 x 95/50 AN 1kV
EAN code (SSTL code) 64 100+ 06 001 30-9 06 001 31-6 06 001 32-3 06 001 33-3 06 001 34-7
Nominal overall diameter mm 25 27 28 32 36
Total weight kg/km 1450 1800 2100 2700 3600
Standard delivery length m 500 500 500 500 500
Standard delivery drum K11 K12 K12 K14 K16
Weight (gable + drum) kg 780 1000 1150 1470 2000
MCMK 3½
Number of conductors and
cross-section nxmm² 3 x 120/70 AN 1kV 3 x 150/70 AN 1kV 3 x 185/95 AN 1kV 3 x 240/120 AN 1kV
EAN code (SSTL code) 64 100+ 06 001 35-4 06 001 36-1 06 001 37-8 06 001 38-5
Nominal overall diameter mm 40 43 48 54
Total weight kg/km 4500 5500 6750 9000
Standard delivery length m 500 500 500 500
Standard delivery drum K18 K18 K20 K22
Weight (gable + drum) kg 2500 3000 3750 4950
MCMK 4½
Number of conductors and
cross-section nxmm² 4 x 25/16 AN 1kV 4 x 35/16 AN 1kV 4 x 50/25 AN 1kV 4 x 70/35 AN 1kV 4 x 95/50 AN 1kV
EAN code (SSTL code) 64 100+ 06 001 40-8 06 001 41-5 06 001 42-2 06 001 43-9 06 001 44-6
Nominal overall diameter mm 28 30 33 35 41
Total weight kg/km 1750 2200 2650 3400 4650
Standard delivery length m 500 500 500 500 500
Standard delivery drum K12 K12 K14 K16 K18
Weight (gable + drum) kg 970 1200 1450 1900 2550
MCMK 4½
Number of conductors and
cross-section nxmm² 4 x 120/70 AN 1kV 4 x 150/70 AN 1kV 4 x 185/95 AN 1kV 4 x 240/120 AN 1kV
EAN code (SSTL code) 64 100+ 06 001 45-3 06 001 46-0 06 001 47-7 06 001 48-4
Nominal overall diameter mm 44 49 55 59
Total weight kg/km 5700 7000 8700 11500
Standard delivery length m 500 500 500 500
Standard delivery drum K20 K22 K22 K24
Weight (gable + drum) kg 3200 4900 4800 6200

23
POWER INSTALLATION CABLES

AMCMK 1 kV

APPLICATION RATED VOLTAGE


For fixed installation indoors, outdoors and Uo/U = 0,6/1 kV Um = 1,2 kV
underground installation.
STANDARD
Maximum permissible temperature of conductor:
- in continuous use +70 °C SFS 4880, HD 603-3F S1, IEC 60502-1,
- in a short circuit (max. 5 s) +160 °C IEC 60332-3B

Lowest recommended
handling temperature: –15 °C
CORE IDENTIFICATION
Minimum recommended bending radius:
- during installation 12xD
- in a final installation if bent only once 8xD

N N
Maximum permissible tensile stress
during installation
3-wires

4-wires

Self-extinguishing IEC 332-1

Self-extinguishing IEC 332-3

24
POWER INSTALLATION CABLES

AMCMK 1 kV

CONSTRUCTION
Conductor Compacted, annealed (AN), aluminium Laying up Three phase conductors and
conductor 25 and 35 mm², neutral stranded together
round 50 mm² and larger , sector PE/PEN-conductor A layer of copper wires and an
shaped open helix of copper tape
Installation Lead-free PVC, core identification Sheath Black, leadfree PVC compound
by colours

AMCMK 3½
Number of conductors and
cross-section nxmm² 3 x16/10 AN 1kV 3 x 35/10 AN 1kV 3 x 70/21 AN 1kV
EAN code (SSTL code) 64 100+ 06 225 57-6 06 003 31-0 06 003 33-4
Nominal overall diameter mm 22 27 32
Total weight kg/km 600 1100 1400
Standard delivery length m 1000 500 500
Standard delivery drum K14 K12 K14
Weight (gable + drum) kg 720 650 820
AMCMK 3½
Number of conductors and
cross-section nxmm² 3 x 120/41 AN 1kV 3 x 185/57 AN 1kV 3 x 240/72 AN 1kV
EAN code (SSTL code) 64 100+ 06 003 35-8 06 003 37-2 06 003 38-9
Nominal overall diameter mm 40 47 53
Total weight kg/km 2100 3000 3900
Standard delivery length m 500 500 500
Standard delivery drum K16 K20 K22
Weight (gable + drum) kg 1250 1850 2350
AMCMK 4½
Number of conductors and
cross-section nxmm² 4 x 16/10 AN 1kV 4 x 35/16 AN 1kV 4 x 50/15 AN 1kV 4 x 70/21 AN 1kV 4 x 95/29 AN 1kV
EAN code (SSTL code) 64 100+ 06 225 77-4 06 003 41-9 06 003 42-6 06 003 43-3 06 003 44-0
Nominal overall diameter mm 23 31 32 36 41
Total weight kg/km 680 1300 1400 1800 2400
Standard delivery length m 1000 500 500 500 500
Standard delivery drum K14 K14 K14 K16 K18
Weight (gable + drum) kg 800 800 850 1100 1450
AMCMK 4½
Number of conductors and
cross-section nxmm² 4 x 120/41 AN 1kV 4 x 150/41 AN 1kV 4 x 185/57 AN 1kV 4 x 240/72 AN 1kV 4 x 300/88 AN 1kV
EAN code (SSTL code) 64 100+ 06 003 45-7 06 003 46-04 06 003 47-1 06 003 48-8 06 003 49-5
Nominal overall diameter mm 44 49 53 60 68
Total weight kg/km 2600 3100 3800 4850 6050
Standard delivery length m 500 500 500 500 250
Standard delivery drum K20 K20 K22 K24 K22
Weight (gable + drum) kg 1650 1900 2300 2900 1950

25
INTERFERENCE-PROTECTED 1 kV CABLES

MCCMK™

APPLICATION Lowest recommended


handling temperature: -15 °C
Fixed indoor, outdoor and underground installation
Minimum recommended bending radius:
where EMC-properties are required
- during installation 12xD
- in a final installation if bent only once 8xD
The EU directive 89/336/EEC on electromagnetic
compatibility (EMC) became effective on 1st Jan 1996.
Maximum permissible tensile stress
The EMC directive to electrical equipment and systems. N
N during installation Ax50 N/mm²

The equipment and systems targeted in the directive


must be constructed so that their electromagnetic
emission does not exceed a level that would affect RATED VOLTAGE
the proper operation of radio, telecommunications,
medical equipment, and other devices. The equipment
must be immune to interference so it can operate as Uo/U = 0,6/1 kV
intended.

Screening is essential in environments where high


STANDARD
frequency disturbance currents and fields exist.
Such environments include industrial facilities utilising SFS 4880, HD 603-3F S1, IEC 60502-1
frequency transformer drives. The interfering
frequencies produced by these drives can rise to
hundreds of megahertz. Therefore, the importance of
the cable’s transfer impedance grows decisively.
The smaller the cable’s transfer impedance at high CORE IDENTIFICATION
frequencies, the better the cable’s screening abilities.

Current carrying capacities according to HD 384.5.523


(or IEC 364-5-523): “Electrical installation of buildings” 3-wires
-section 523: Current carrying capacities.

Maximum permissible temperature of conductor:


- in continuous use +70 °C 4-wires
- in a short circuit (max. 5 s) +160 °C

Self-extinguishing IEC 332-1

26
INTERFERENCE-PROTECTED 1 kV CABLES

MCCMK™

CONSTRUCTION
Conductor Annealed copper Filling Filling compound
2,5 and 6 mm² solid Concentric
10 and 16 mm² stranded conductor A layer of copper wires, copper foil and
Insulation Lead-free PVC, core identification by an open helix of parallel copper wires
numbers Sheath Black, lead-free PVC
- marked by meters

Number of conductors and


cross-section nxmm² 3 x 2,5/2,5 3 x 6/6 3 x 10/10 RM 3 x 16/16 RM
EAN code (SSTL code) 64 100+ 06 020 53-9 06 020 55-3 06 020 56-0 06 020 57-7
Nominal overall diameter mm 14 18 21 24
Total weight kg/km 260 470 700 1050
Direct current resistance of
conductor at +20 °C.max. Ω/km 7,41 3,08 1,83 1,15
Bending radius m 0,16 0,22 0,25 0,3
Standard delivery length
drum m 1000/K9 1000/K11 1000/K12 1000/15G

Number of conductors and


cross-section nxmm² 4 x 2,5/2,5 4 x 6/6 4 x 10/10 RM 4 x 16/16 RM
EAN code (SSTL code) 64 100+ 06 020 73-7 06 020 75-1 06 020 76-8 06 020 77-5
Nominal overall diameter mm 14,5 19 22 25
Total weight kg/km 290 540 830 1200
Direct current resistance of
conductor at +20 °C.max. Ω/km 7,41 3,08 1,83 1,15
Bending radius m 0,18 0,23 0,27 0,3
Standard delivery length
drum m 1000/K9 1000/K11 1000/13G 1000/15G

27
28
CONTROL CABLES

Plastic-sheathed control cable


MMO

APPLICATION RATED VOLTAGE


Cable for the control, measuring and signal circuits Uo/U = 450/750 V
of electrical equipment for fixed surface and
flush-mounted installations, indoors and outdoors.
STANDARD
Direct sunlight may change colour of sheath.
SFS 3714
Maximum permissible temperature of conductor:
- in continuous use +70 °C
- in a short circuit (max. 5 s) +160 °C

Lowest recommended
handling temperature: -15 °C

Minimum recommended
bending radius:
- during installation 10xD
- in a final installation if bent only once 8xD

Maximum permissible tensile stress Self-extinguishing IEC 332-1


N N during installation : Ax50 N/mm²

CONSTRUCTION
Conductor Annealed copper wire Sheath White leadfree Linyl PVC
Insulation Black leadfree PVC, - marked by meters
core identification by numbers

Number of conductors and


cross-section nxmm² 7 x 1,5 12 x 1,5 19 x 1,5 27 x 1,5 37 x 1,5 7 x 2,5 12 x 2,5 19 x 2,5
EAN code (SSTL code) 64 100+ 04 120 22-4 04 120 23-1 04 120 24-8 04 120 25-5 04 120 26-2 04 120 33-0 04 120 34-7 04 120 35-4
Nominal overall diameter mm 12 15 18 21 24 14 18 21
Total weight kg/km 230 350 500 700 950 310 500 750
Direct current resistance of
conductor at +20 °C max. Ω/km 12,1 12,1 12,1 12,1 12,1 7,41 7,41 7,41
Standard delivery length
drum m 1000/8E 500/8E 500/8E 500/11G 500/11G 500/8E 500/8E 500/11G
Electrical properties
Capacitance between two
adjacent conductors
at +20 °C and 50 Hz nF/km 120...150 120...150 120...150 120...150 120...150 120...150 120...150 120...150

29
CONTROL CABLES

Plastic-sheathed control cable


MCMO
with concentric copper conductor

APPLICATION RATED VOLTAGE


Cable for the control, measuring and signal circuits Uo/U = 450/750 V
of electrical equipment for fixed surface and
flush-mounted installations, indoors and outdoors.
STANDARD
The concentric copper conductor forms a good
electromechanical protection and a moderate SFS 3713
protection against electrical interference.

Maximum permissible temperature of conductor:


- in continuous use +70 °C
- in a short circuit (max. 5 s) +160 °C

Lowest recommended handling


temperature: -15 °C

Minimum recommended bending radius:


- during installation 10xD
- in a final installation if bent only once 8xD

Maximum permissible tensile stress Self-extinguishing IEC 332-1


N N during installation Ax50 N/mm²

Electromagnetic compatibility

30
CONTROL CABLES

Plastic-sheathed control cable


MCMO
with concentric copper conductor

CONSTRUCTION
Conductor Annealed copper wire Concentric
Insulation Black leadfree PVC, conductor A layer of copper wires and an open
core identification by numbers helix of parallel copper wires
Filling Filling compound Sheath Black leadfree PVC

Number of conductors and


cross-section nxmm² 7 x 1,5 12 x 1,5 19 x 1,5 27 x 1,5 37 x 1,5
EAN code (SSTL code) 64 100+ 06 019 01-4 06 019 02-1 06 019 03-8 06 019 04-5 06 019 05-2
Nominal overall diameter mm 15 19 22 26 28
Total weight kg/km 350 500 680 950 1200
Direct current resistance of
conductor at +20 °C max.
conductor’s Ω/km 12,1 12,1 12,1 12,1 12,1
concentric conductor Ω/km 3,08 3,08 3,08 3,08 2,60
Standard delivery length
drum m 500/8E 400/8E 500/11G 500/11G 400/11G
Electrical properties
Capacitance between two
adjacent conductors
at +20 °C and 50 Hz nF/km 130...160 130...160 130...160 130...160 130...160
Capacity to earth of one
conductor at +20 °C and 50 Hz nF/km 200...270 200...270 200...270 200...270 200...270

Number of conductors and


cross-section nxmm² 7 x 2,5 12 x 2,5 19 x 2,5 27 x 2,5 37 x 2,5
EAN code (SSTL code) 64 100+ 06 019 21-2 06 019 22-9 06 019 23-6 06 019 24-3 06 019 25-0
Nominal overall diameter mm 18 21 25 29 32
Total weight kg/km 480 690 950 1350 1700
Direct current resistance of
conductor at +20 °C max.
conductor’s Ω/km 7,41 7,41 7,41 7,41 7,41
concentric conductor Ω/km 3,08 3,08 3,08 2,60 2,60
Standard delivery length
drum m 500/8E 500/11G 500/11G 400/11G 300/11G
Electrical properties
Capacitance between two
adjacent conductors
at +20 °C and 50 Hz nF/km 130...160 130...160 130...160 130...160 130...160
Capacity to earth of one
conductor at +20 °C and 50 Hz nF/km 210...280 210...280 210...280 210...280 210...280

31
JUMPER WIRES

Plastic-insulated jumper wires


MKJE 90 H05V2-U, MKJ 90 H05V2-K,
MKJT 90 H05V2-K

MKJE 90 H05V2-U

MKJ 90 H05V2-K

MKJT 90 H05V2-K

APPLICATION RATED VOLTAGE


For permanent installation as interior cabling in lighting Uo/U = 300/500 V
and other equipment.

Maximum permissible temperature of conductor: STANDARD


- in continuous use +90 °C
- in a short circuit (max. 5 s) +160 °C SFS 5527 = CENELEC HD 21
H05V2-U (MKJE 90)
Lowest recommended handling H05V2-K (MKJ 90, MKJT 90)
temperature: +5 °C

Minimum recommended bending radius:


- in a final installation if bent only once 2xD
Self-extinguishing IEC 332-1

32
JUMPER WIRES

Plastic-insulated jumper wires


MKJE 90 H05V2-U, MKJ 90 H05V2-K,
MKJT 90 H05V2-K

CONSTRUCTION
Conductor MKJE 90 annealed copper wire, Insulation PVC, core identification by colours
solid
MKJ 90 annealed copper wires,
stranded flexible
MKJT 90 tinned, annealed copper
wires, stranded flexible

MKJE 90 MKJE 90 MKJE 90 MKJE 90


Cross-section of conductors H05V2-U H05V2-U H05V2-U H05V2-U
and colour mm² 0,75 VA 0,75 RU 0,75 MU 0,75 SI
EAN code (SSTL code) 64 100+ 04 162 20-0 04 162 22-4 04 156 03-2 04 156 07-0
Nominal overall diameter mm 2,2 2,2 2,2 2,2
Total weight kg/km 11 11 11 11
Direct current resistance of
conductor at +20 °C max. Ω/km 24,5 24,5 24,5 24,5
Standard delivery length
spool m 500 500 500 500

MKJ 90 MKJ 90 MKJ 90 MKJ 90 MKJ 90


Cross-section of conductors H05V2-K H05V2-K H05V2-K H05V2-K H05V2-K
and colour mm² 0,75 VA 0,75 RU 0,75 MU 0,75 PU 0,75 SI
EAN code (SSTL code) 64 100+ 04 156 50-6 04 162 02-6 04 156 53-7 04 162 26-4 04 156 57-5
Nominal overall diameter mm 2,3 2,3 2,3 2,3 2,3
Total weight kg/km 11 11 11 11 11
Direct current resistance of
conductor at +20 °C max. Ω/km 26,0 26,0 26,0 26,0 26,0
Standard delivery length
spool m 500 500 500 500 500

MKJ 90 MKJ 90 MKJT 90 MKJT 90


Cross-section of conductors H05V2-K H05V2-K H05V2-K H05V2-K
and colour mm² 0,75 SI 0,75 KEVI 0,75 SI 0,75 MU
EAN code (SSTL code) 64 100+ 04 162 07-1 04 156 58-2 04 161 07-4 04 156 73-5
Nominal overall diameter mm 2,3 2,3 2,3 2,3
Total weight kg/km 11 11 11 11
Direct current resistance of
conductor at +20 °C max. Ω/km 26,0 26,0 26,7 26,7
Standard delivery length
spool m 500 500 500 500

33
JUMPER WIRES

34
JUMPER WIRES

Plastic-insulated jumper wire


MKEMT 90 H07V2-K
Tinned, flexible conductor

APPLICATION RATED VOLTAGE


For fixed installation in a conduit, and for wiring in Uo/U = 450/750 V
appliances, switchgear and controlgear with
a maximum voltage of 1000 V (a.c.) or a maximum of
750 V (d.c.) to earth. STANDARD
Maximum permissible temperature of conductor: SFS 5523 and CENELEC HD 21
- in continuous use +90 °C
- in a short circuit (max. 5 s) +160 °C

Lowest recommended
handling temperature: -25 °C

Minimum recommended Self-extinguishing IEC 332-1


bending radius:
- during installation 8xD
- in a final installation if bent only once 3xD

CONSTRUCTION
Conductor Tinned, annealed copper wires, Insulation Lead-free Linyl PVC, core identification
stranded flexible by colours

Cross-section of conductors
and colour mm² 1,5 MU 1,5 SI 1,5 KEVI 2,5 MU 2,5 SI 2,5 KEVI
EAN code (SSTL code) 64 100+ 04 031 53-7 04 031 57-5 04 031 58-2 04 031 73-5 04 031 77-3 04 031 78-0
Nominal overall diameter mm 3,1 3,1 3,1 3,7 3,7 3,7
Total weight kg/km 21 21 21 32 32 32
Direct current resistance of
conductor at +20 °C max. Ω/km 13,7 13,7 13,7 8,21 8,21 8,21
Standard delivery length
spool m 250 250 250 200 200 200

35
JUMPER WIRES

Plastic-insulated conductor
MVJ 8 kV
Flexible conductor

APPLICATION RATED VOLTAGE


For fixed installation in neon luminaires. Uo/U = 8/8 kV

Maximum permissible temperature of conductor:


- in continuous use +70 °C
STANDARD
- in a short circuit (max. 5 s) +160 °C
SFS 5680
Lowest recommended
handling temperature: -15 °C

Minimum recommended Self-extinguishing IEC 332-1


bending radius:
- during installation 8xD
- in a final installation if bent only once 4xD

CONSTRUCTION
Conductor Annealed copper wires, Insulation PVC, yellow
stranded flexible

Cross-section of conductors
and colour mm² 1,5 KE
EAN code (SSTL code) 64 100+ 04 201 03-9
Nominal overall diameter mm 6,7
Total weight kg/km 56
Direct current resistance of
conductor at +20 °C max. Ω/km 13,3
Standard delivery length
coil m 100

36
FLEXIBLE CORDS

Non-sheathed, flat, flexible, plastic-insulated cord


MST H03VH-H

APPLICATION RATED VOLTAGE


Cord for very light duty use for light portable appliences Uo/U = 300/300 V
in domestic premises, kitchens and offices.
- Not for kitchen or heating appliances
- Not for outdoor use, industrial use, agricultural use or STANDARD
for portable tools
- Not for suspending lighting fixtures SFS 5525 = CENELEC HD 21
H03VH-H
Maximum permissible temperature of conductor:
- in continuous use +40 °C
- in a short circuit (max. 5 s) +150 °C

Lowest recommended
handling temperature: +5 °C

Minimum recommended Self-extinguishing IEC 332-1


bending radius:
- in normal usage 6xD

CONSTRUCTION
Conductor Annealed copper wires, Identification
stranded flexible of conductors A longitudinal ridge on the surface of
Insulation PVC covering two parallel conductors insulation on one of the conductor’s

Number and cross-section of conductors


and insulation colour nxmm² 2 x 0,75 VA 2 x 0,75 HA 2 x 0,75 KIR 2 x 0,75 MU
EAN code (SSTL code) 64 100+ 04 171 20-2 04 171 21-9 04 171 28-8 04 171 23-3
Nominal overall diameter mm 2,8x5,6 2,8x5,6 2,8x5,6 2,8x5,6
Total weight kg/km 26 26 26 26
Direct current resistance of
conductor at +20 °C max. Ω/km 26,0 26,0 26,0 26,0
Standard delivery length
spool m 200 200 200 200

37
FLEXIBLE CORDS

Light, flat, flexible, plastic-insulated cord


MSO H03VVH2-F

APPLICATION RATED VOLTAGE


Cord for light duty use for portable appliences in Uo/U = 300/300 V
domestic premises, kitchens and offices.
- Not for kitchen or heating appliances
- Not for outdoor use, industrial use, agricultural use or STANDARD
for non domestic portable tools
SFS 5525 = CENELEC HD 21
The weight of the lighting fixture hanging from the cable H03VVH2-F
N N must not exceed 2 kg.

Maximum permissibletemperature of conductor:


- in continuous use +60 °C
- in a short circuit (max. 5 s) +150 °C CORE IDENTIFICATION
Lowest recommended N-system
handling temperature: +5 °C

Minimum recommended 2-wires


bending radius:
- in normal usage 6xD
Self-extinguishing IEC 332-1

CONSTRUCTION
Insulation PVC, core identification by colours
Conductor Annealed copper wires, stranded Sheath PVC covering two insulated and parallel
flexible conductors, flat

WITHOUT PROTECTIVE CONDUCTOR


Number and cross-section of
conductors and sheath colour nxmm² 2 x 0,75 N VA 2 x 0,75 N HA 2 x 0,75 N RU 2 x 0,75 N MU
EAN code (SSTL code) 64 100+ 04 181 20-1 04 181 21-8 04 181 22-5 04 181 23-2
Nominal overall diameter mm 3,3x5,4 3,3x5,4 3,3x5,4 3,3x5,4
Total weight kg/km 31 31 31 31
Direct current resistance of
conductor at +20 °C max. Ω/km 26,0 26,0 26,0 26,0
Standard delivery length
spool m 200 200 200 200

38
FLEXIBLE CORDS

Light, round, flexible, plastic-insulated cord


MSOY H03VV-F

APPLICATION RATED VOLTAGE


Cord for light duty use for portable appliences in Uo/U = 300/300 V
domestic premises, kitchens and offices.
- Not for kitchen or heating appliances
- Not for outdoor use, industrial use, agricultural use or
STANDARD
for non domestic portable tools
SFS 5525 = CENELEC HD 21
The weight of the lighting fixture hanging from the cable H03VV-F
N N must not exceed 2 kg.

Maximum permissibletemperature of conductor:


- in continuous use +60 °C
- in a short circuit (max. 5 s) +150 °C CORE IDENTIFICATION
Lowest recommended N-system
handling temperature: +5 °C

Minimum recommended 2-wires


bending radius:
- in normal usage 6xD
Self-extinguishing IEC 332-1

CONSTRUCTION
Conductor Annealed copper wires, stranded Insulation PVC, core identification by colours
flexible Sheath PVC covering two insulated stranded
conductors, round

WITHOUT PROTECTIVE CONDUCTOR


Number and cross-section of
conductors and sheath colour nxmm² 2 x 0,75 N VA 2 x 0,75 N MU
EAN code (SSTL code) 64 100+ 04 181 70-6 04 181 73-7
Nominal overall diameter mm 5,4 5,4
Total weight kg/km 41 41
Direct current resistance of
conductor at +20 °C max. Ω/km 26,0 26,0
Standard delivery length
spool m 100 100

39
FLEXIBLE CORDS

Flexible, plastic-insulated cord


MSK H05VV-F

APPLICATION RATED VOLTAGE


Cord for ordinary duty use for portable appliences in Uo/U = 300/500 V
domestic premises, kitchens and offices.

- For household appliences in dry and damp premises.


STANDARD
- Not for outdoor use, industrial use, agricultural use
SFS 5525 = CENELEC HD 21
The weight of a lighting fixture hanging from the cable H05VV-F
N N must not exceed 2 kg.

Maximum permissibletemperature of conductor:


- in continuous use +60 °C
- in a short circuit (max. 5 s) +150 °C CORE IDENTIFICATION
Lowest recommended
handling temperature: +5 °C N-system S-ystem

Minimum recommended
bending radius: 2-wires
3-wires
- in normal usage 6xD

4-wires

5-wires

Self-extinguishing IEC 332-1

40
FLEXIBLE CORDS

Flexible, plastic-insulated cord


MSK H05VV-F

CONSTRUCTION
Conductor Annealed copper wires, Insulation PVC, core identification by colours
stranded flexible Sheath PVC, round

WITH PROTECTIVE CONDUCTOR


Number and cross-section of
conductors and sheath colour nxmm² 3 x 0,75 S VA 3 x 1,0 S VA 3 x 1,5 S VA 4 x 0,75 S VA 4 x 1,5 S VA
EAN code (SSTL code) 64 100+ 04 197 20-2 04 197 21-9 04 197 22-6 04 197 30-1 04 197 32-5
Nominal overall diameter mm 6,6 7,0 8,3 7,2 9,3
Total weight kg/km 61 72 100 75 130
Direct current resistance of
conductor at +20 °C max. Ω/km 26,0 19,5 13,3 26,0 13,3
Standard delivery length
coil m 100 100 100 100 100
WITH PROTECTIVE CONDUCTOR
Number and cross-section of
conductors and sheath colour nxmm² 5 x 1,0 S VA 5 x 1,5 S VA 5 x 2,5 S VA 3 x 1,5 S HA
EAN code (SSTL code) 64 100+ 04 197 41-7 04 197 42-4 04 197 43-1 04 198 22-3
Nominal overall diameter mm 8,6 10,3 12,2 8,3
Total weight kg/km 110 165 250 102
Direct current resistance of
conductor at +20 °C max. Ω/km 19,5 13,3 7,98 13,3
Standard delivery length
coil m 100 100 50 100

WITHOUT PROTECTIVE CONDUCTOR


Number and cross-section of
conductors and sheath colour nxmm² 2 x 0,75 N VA 2 x 1,0 N VA 2 x 1,5 N VA
EAN code (SSTL code) 64 100+ 04 194 10-2 04 194 11-9 04 194 12-6
Nominal overall diameter mm 6,2 6,6 7,6
Total weight kg/km 51 60 80
Direct current resistance of
conductor at +20 °C max. Ω/km 26,0 19,5 13,3
Standard delivery length
coil m 100 100 100

41
GENERAL

DATA TRANSMISSION CABLES Depending on the different installation conditions,


the cables are also divided into indoor cables and outdoor
All automation cables, such as instrumentation, signal and cables. Selfextinguishing and bendability are typical
data network cables, are data transmission cables. properties of indoor cables. They are also lighter in
They are copper cables with a maximum operating construction and smaller in size than the corresponding
voltage of 75 V or optical fibre cables. outdoor cables. The service temperature range of outdoor
They transmit information in an electric or optical form. cables is wide. They are resistant to e.g. humidity, sunlight
The transmitted information may consist of speech, sound, and handling in outdoor conditions. Depending on
moving or still pictures, text, data, measuring or control the installation site, outdoor cables can also be divided
data or it may be the signal of a fire detector or into duct, buried, submarine and aerial cables.
a burglar alarm.

The transmitted signal may be analog or digital. ELECTRICAL PROPERTIES


The capacity of an analog transmission is measured by
The transmission capacity of the cable is essentially
a bandwidth which is the frequency range required to
effected by resistance, capacitance, impedance,
transmit a certain signal. In digital transmission a certain
attenuation and crosstalk.
number of signals are transmitted in a time unit and this is
called transmission speed. A certain transmission speed Resistance
corresponds to a certain bandwidth. That is why the term
bandwidth can also be used in digital transmission. Resistance is caused by the conductor to
The bandwidth required by a digital signal is always the electric current and it is dependent on the cross
wider than that of a corresponding analog signal. section and the material of the conductor,
the temperature, the signal frequency and the metals
Cable design close to the conductor.
Data transmission cables are divided into three groups: For twisted-pair cables it is given as loop resistance which
symmetrical cables, coaxial cables and optical fibre includes the effect of both the supply conductor and
cables. the return conductor. The resistance is given per unit of
conductor the length, i.e Ω /km.
a)
insulation
Capacitance
Capacitance is inertia to voltage changes between
inner conductor
the conductors of a pair. It is dependent on the diameter of
insulation
the conductors, the distance between them,
b)
the insulation, the material around the insulation and
the electric potential of the insulation.
outer conductor
The capacitance increases if the distance between
core the conductors is reduced or if the diameter of
c) the conductors increases. It is directly proportional to
shell the dielectric constant which is specific to every insulation
material. The capacitance is given per unit of the length,
i.e. nF/km.
(a) The basic structure of a symmetrical pair, (b) a coaxial
pair and (c) an optical fibre. Impedance
A symmetrical cable consist of one or several symmetrical Impedance gives the ratio of the voltage between
pairs. A pair consists of two or four identical insulated the conductors to the current carried therein. It is also
conductors which are mutually twisted into a pair. known as surge impedance or characteristic impedance.
The conductors of a pair are alike in their electric With transmission cables all these terms have the same
disposition. Symmetrical cables are either screened or meaning. The unit of impedance is ohm (Ω).
unscreened. The impedance of homogeneous pair is constant across
the whole length of the pair. The voltage and the current
A coaxial pair is the basic element of the coaxial cable. are attenuated but their ratio is constant, i.e. equal to
It consists of two conductors, an inner conductor and the impedance. The impedance is therefore one of
an outer conductor. These are different in their structure the characteristics of a pair. At low frequencies,
and electric disposition. The cylindrical outer conductor the impedance is significant only with long cables.
is concentrically around the inner conductor. For example at a frequency below 29 kHz it begins to have
significance if the cable is longer than 1,000 m.
In an optical fibre cable, the signal proceeds in the form of At a frequency of 1,000 kHz or higher, the impedance is
light along the optical fibre. The fibre, consisting of a core very important for matching. This means that
and a shell, is made from quartz glass or plastic. the impedance of the unit or component connected to
The refractive index of the core is higher than that of the pair must be equivalent to that of the pair.
the shell, and this causes a reflection when the light hits
the shell.

42
CONTENTS
Attenuation wire conductors. Most stranded conductors are tinned
to prevent corrosion.
When the signal proceeds in the pair, it loses some of its
effect, while both the voltage and the current decrease Cables are subjected to chemical loads especially in
as a function of the distance. The attenuation is given in industrial environments where they may be exposed to oil
decibels per unit of length, e.g. dB/100 m, and it is and chemical spills and corrosive gases like sulphur
affected by the diameter of the insulation, the conductance dioxide.
of the conductor and the insulation properties. The
attenuation increases with a higher frequency and at a Also high temperatures, a high relative humidity and
rising temperature. With an increase of one degree in the fire risks must be taken into account when the cable is
temperature, the increment in the attenuation is 2 ‰. selected.

Crosstalk The sheathing material has also a great significance when


air properties are considered. The most commonly used
Crosstalk appears when signals are coupled from one pair materials are polyethylene (PE) and polyvinylchloride
to another. In symmetrical cables the crosstalk arises (PVC). PVC is the most popular sheathing material in
above all because of incomplete symmetry. indoor installations because it meets the requirements of
Also the impedance matchings and coupling modes of the IEC 332-1 burning test, in which the cable is classified
the pairs play a role in crosstalk which is an undesired as self-extinguishing. A PVC-sheathed cable is not
phenomenon. For a successful signal transmission, it is self-burning and will not spread the fire. But, almost all
important to keep crosstalk within certain limits. organic matter is destroyed by fire, which is why also
In applications with great differences in the signal levels of the emission of smoke and the combustion residue of
the pairs, the cable must be especially resistant to the cable need to be taken into account. Burning PVC
crosstalk. releases chlorine and it forms with water vapour
hazardous hydrochloric acid. This is why halogen-free
cables are getting more popular (see symmetrical
SELECTION OF THE CABLE TYPE halogen-free lnstrumentation cables).

Data transmission cables are specified in great detail for And fluoroplastics are the best of all - both electrically and
a number of applications. The choice is to be made mechanically.
according to a specification or a standard. But this is not
always possible, which is why the following facts are very The maximum service temperature with ordinary PE and
useful. PVC cables is + 70 degrees Celsius.

It is important to consider the purpose for the use of The cables which are to be buried directly are generally
the cable and the service environment before the cabling armoured.
plan is made.
Screening
A cable is subjected to mechanical loads during The electromagnetic interference in the cables are
the installation. It may also be exposed to vibration, shock capacitive, inductive or caused by a radiation field.
and friction in its service environment. These can often be A galvanic coupling may also cause interference.
avoided by proper routing or by shielding the cable with
a tube. Stranded conductors are recommended for use in
difficult installation conditions, because they are easier to
bend and fatigue-resistant and will not break as easily as

JAMAK®

JAMAK® ARM

43
CONTENTS
The table below shows the types of interference and INDUSTRIAL NETWORKS
respective screening:
Industrial automation has developed rapidly in the past few
years and will develop at an accelerated speed in
Interference Cause Screening the future. Cable design follow the latest trends very
Capacitive Electric field Pair twisting,conducting closely. The existing cable designs can be used in digital
e.g. high-voltage cable metal shields fieldbuses, but also new designs are to come. Local area
networks have become a part of industrial networks.
Inductive Magnetic field Pair twisting, armouring, At the moment they are used to handle the transmission
e.g. power cable ferromagnetic screening
at the highest level of industrial networks, i.e. Between
Radiation Radiation field Pair twisting, conducting the plant computer and the process computer.
e.g. Radiotransmitter, metal shields, proper
radar, relay or transistor earthing More details must be taken into consideration in
the design of industrial automation than in office.
Galvanic E.g. incorrectly earthed The circuits are insulated The buses of industrial automation systems are intended
service network from each other and the for continuing service. It is important that the messages
ground
are absolutely faultless and the response times accurate.
Crosstalk Electromagnetic Suitable twist length Protection against interferences must be firm. This is seen
coupling between the pairshielding e.g.in the cable constructions and their routings.
different pairs of
the cable Cables have a long service life and are therefore
an important part of the industrial plant. Well-designed
cabling works for several machine generation. That is why
special attention should be paid to the design and
implementation of the cabling.
Of course price is also an important factor in
the selection of a cable. When you compare the costs of
e.g. screened and unscreened cables, the following SYMMETRICAL HALOGEN-FREE
details are important to remember: INSTRUMENTATION CABLES
— cable investments are small compared with
the equipment investments Halogenfree, HF-cables, provide better fire safety than
— failures, for example because of inadequate traditional PVC-sheathed cables. They are self-
screening, are usually detected in the service - extinguishing like PVC-sheathed cables and do not spread
not before the fire. In a fire they emit much less visibility-reducing
— replacement of a cable afterwards is expensive, smoke than PVC-sheathed cables giving people more time
time-consuming and difficult to escape from the hazardous area and also more time for
firefighting. The smoke is also less irritating and toxic. It
Ease of installation doesn’t contain harmfull hydrochloric acid or other
corrosive gases for equipment of the structures. This
The sliding properties of the cable are important for prevents smoke damages which are often larger than
installation. those caused by the fire.
The cable is easier to pull if the sheath is made of The self-extinguishing property of the halogenfree
low friction LINYL-PVC. This is the sheathing material sheathing material is based on ethylene copolymers and
used by NK Cables uses in our indoor cables. The ratings it’s substance which decomposes respond to heat with
should be observed in the installation of each cable type. cooling the cable and releasing water vapour. The result
Availability, quality and technical support are other of a protecting layer of ash is formed on the cable and
major considerations in the selection of a cable. around the cable an extinguishing shielding
atmosphere of water vapour. A disadvantage of
The following summarized questions cover most of the halogen-free material is that the sheath is less resistant
the essential details: to mechanical loads and stiffer than a PVC sheath.
1. What is the type of the cable? (Even if the type is Halogenfree cables are also supplied by NK Cables.
not known, get in touch and check if there is
a similar type.)
2. What kind of connection or coupling is used in
the system? Fire performance properties of cables
3. What is the transmission frequency or the data
transmission speed?
Property Standard
4. How many conductors or fibres are needed in
the cable? Flame retardant IEC 332-1
5. What is the impedance of the equipment? Fire retardant IEC 332-3
6. What interference is there in the environment? Fire resistant IEC 331
(See the section on screening.) Low smoke IEC 1034-1 ja IEC 1034-2
7. What is the service environment for the cables and Halogen free, IEC 754-1 ja IEC 754-2
what are they used for? Are they indoor or outdoor zero halogen (hal.quantity <5 mg/g)
cables? Is the installation fixed, semifixed or mobile?
8. Is the cable subjected to mechanical or chemical
loads?
9. Conformity to standards?

44
CONTENTS
OPTICAL FIBRE CABLES IN INDUSTRY Price of fibre optics is high but in the interference
conditions today fibre optics are also an economically
Optical fibre cables are increasingly used in industry. sensible solution. Besides it is often the only way of
This is directly proportional to the expanding data making the connection.
transmission. Optical fibre cables are used generally at
the highest level of industrial networks. There is also more Knowledge of fibre optics is not necessary for
and more needed for data transmission at the lower levels the construction of an optical fibre connection because
of the network hierarchy. The microcomputers used for there are ready-made solutions. The optical fibre
production control are often next to the production connection may be between two electric interfaces or
equipment. between two optical fibre connectors. The client must only
specify the length of the cable, the number of fibres and
The closer to the machines and equipment the data the connector suited for the equipment or the electric
transmission lines run, the greater the electromagnetic connection. Especially for short distances, it is sensible to
interference. Power transfers, electric motor fields, install ready-made harnessies in which the connectors are
thyristor controls and electric welding are some of protected against mechanical loads during the installation.
the major sources of interference. Also earth potential At long distances and with a large number of fibres,
differences and lightning may cause disturbances. the optical fibre cable should be terminated at
the installation site. This is a process that requires special
The optical fibre cable is an ideal solution for equipment and knowledge, and it may be purchased as
an environment exposed to interference. Since it is totally a service from e.g. NK Cables, together with the cable and
insensitive to electromagnetic interference, for example the terminal equipment.
the cable routing can be made in the easiest possible way.
Even potential differences are not a problem because More information about optical fibre transformers and
fibres are glass. A small attenuation will not cause cables, termination boxes and cross-connection systems
problems at long transmission distances. The large for fibre optics are found in the product catalogues
transmission capacity of the optical fibre cable can also be “Optical Telecommunications and Local Area Cables” and
utilized in the future, because the same cable system will “Accessories and Supplies for Optical Fibre Cables”.
be sufficient for future generations of computers.
Optical fibre cable does not cause sparking and its small
size is advantageous for example in routing solutions.

45
INSTRUMENTATION CABLES

Instrumentation cable
JAMAK®

APPLICATIONS Lowest recommended installation


temperature: –5 °C
— Fixed indoor — Process control
Minimum recommended bending radius:
installations — Audio systems
- during installation 15xD
— Automation — Suitable for Maxi
- during operation 10xD
— Instrumentation Termipoint connections

Suitable specially for digital and low level analog signal IDENTIFICATION
transmission. The construction gives an excellent
protection against electromagnetic interferencies. Units marked with numbers,
a-conductors are blue and b-conductors are red.
Maximum ambient temperature:
- in operation +70 °C The cable fulfils the fire condition requirements of
IEC 332-1 (Flame retardant).

CONSTRUCTION
Conductor Stranded tinned copper Shield Plastic-aluminium tape with earth
Insulation PE conductor
Unit Twisted and individually with Sheath Grey LINYL-PVC
plastic-aluminium tape shielded pair,
earth conductor and a number tape

CABLE SIZES
Number and size of
the conductors mm2 2 x( 2+1) x 0,5 4 x (2+1) x 0,5 8 x (2+1) x 0,5 12 x (2+1) x 0,5 24 x (2+1) x 0,5 48 x (2+1) x 0,5
EAN code (SSTL code) 64 100+ 02 642 52-0 02 642 54-4 02 642 58-2 02 642 62-9 02 642 64-3 02 642 68-1
Nominal diameter mm 8,0 9,5 13,0 15,0 21,0 29,0
Mass kg/km 70 110 200 280 530 1000
Delivery length m 1000/200 1000/200 1000 1000 1000 500
ELECTRICAL PROPERTIES, 20 °C
Maximum loop resistance Ω/km 81
Nominal mutual capacitance
(800 Hz) nF/km 85
Impedance, 10 MHz Ω 70 ± 10 %
Minimum insulation resistance GΩ x km 2
Velocity factor 0,66
Maximum voltage V 75
Nominal attenuation dB/100 m
frequency 9,6 kHz 0,3
frequency 19,2 kHz 0,5
frequency 64 kHz 0,7
frequency 100 kHz 0,9
frequency 200 kHz 1,6
frequency 1,0 MHz 4,5

JAMAK is also available as halogenfree (JAMAK-HF) and more effectively shielded (JAMAK-C) version.

46
INSTRUMENTATION CABLES

Instrumentation cable
JAMAK® ARM

APPLICATIONS Lowest recommended installation


temperature: –5 °C
— Fixed outdoor — Process control
Minimum recommended bending radius:
installations — Audio systems
- during installation 15xD
— Automation — Suitable for Maxi
- during operation 10xD
— Instrumentation Termipoint connections

Suitable specially for digital and low level analog signal IDENTIFICATION
transmission. The construction gives an excellent
protection against electromagnetic interference. Units marked with number tape,
a-conductors are blue and b-conductors are red.
Maximum ambient temperature:
- in operation +70 °C

CONSTRUCTION
Conductor Stranded tinned copper Shield Plastic/aluminium tape with earth
Insulation PE conductor
Unit Twisted and individually with Sheath Grey LINYL-PVC
plastic-aluminium tape shielded pair, Armouring Wrapped steel band
earth conductor and a number tape Outersheath Black PVC

CABLE SIZES
Number and size of
the conductors mm2 4 x (2+1) x 0,5 8 x (2+1) x 0,5 12 x (2+1) x 0,5 24 x (2+1) x 0,5 48 x (2+1) x 0,5
EAN code (SSTL code) 64 100+ 02 642 72-4 02 642 78-0 02 642 82-7 02 642 84-1 02 642 88-9
Nominal diameter mm 9,5 13,0 15,0 21,0 29,0
Nominal diameter mm 13,5 17,0 19,0 25,0 33,0
Mass kg/km 240 350 470 820 1420
Delivery lenght m 1000 1000 1000 1000 500
ELECTRICAL PROPERTIES
Maximum loop resistance Ω/km 81
Nominal mutual capacitance
(800 Hz) nF/km 85
Impedance, 10 MHz Ω 70 ± 10 %
Minimum insulation resistance GΩ x km 2
Velocity factor 0,66
Maximum voltage V 75
Nominal attenuation dB/100 m
frequency 9,6 kHz 0,3
frequency 19,2 kHz 0,5
frequency 64 kHz 0,7
frequency 100 kHz 0,9
frequency 200 kHz 1,6
frequency 1,0 MHz 4,5

JAMAK ARM is also available as halogenfree (JAMAK ARM-HF) and more effectively shielded (JAMAK-C-ARM) version.

47
INSTRUMENTATION CABLES

Installations which demand better EMC-properties


JAMAK®-C

USE ELECTRICAL PROPERTIES


The EMC-directive came into force 1.1.1996. EMC means Screening effectiveness of cables can be described with
Electromagnetic Compatibility. This EMC-directive is transfer impedance, unit is mΩ/m. The smaller
applied to equipment and systems, but not for the transfer impedance, the better are the EMC/shielding
components and equipment, so cables alone are outside properties of the cables.
this directive. However cables are a part of a system and it
is clear that cables with better EMC-properties are In the table below are compared ordinary JAMAK and
required. JAMAK-C, transfer impedances.

NK Cables has developed a more effectively shielded


version of instrumentation cable JAMAK called JAMAK-C Frequency Transfer impedance, nominal
MHz mΩ/m
which has better EMC-properties.
JAMAK JAMAK-C
Installations which demand better EMC-properties, where 50 2,0 0,4
instruments and systems, are expected to work despite of 100 3,0 0,3
electromagnetic disturbances and without disturbing other
instruments and systems electromagnetically.

CONSTRUCTION INSTALLATION
Double aluminium foil protection: two plastic-aluminium When the sheath is taken away, the outer plastic-
tapes and ground wire between tapes with thicker aluminium tape can also be taken away. Then comes the
aluminium tape having the metalcoating on the outside inner plastic-aluminium tape the metalcoating on the
(plastic-aluminium tape) it is possible to make a contact outside. After this it is possible to make a contact with the
with the shield in lead-throughs and connectors in shield and connector according to connector
a angle of 360°. manufactorer’s advice in a angle of 360°.

Inner
aluminium tape

Outer
aluminium tape Ground wire

The right to alterations reserved.

48
INSTRUMENTATION CABLES

Instrumentation cable
JAMAK®-C

Maximum ambient temperature: IDENTIFICATION


- in operation +70 °C
Unit marked with number tape,
Lowest recommended installation
a-conductors are blue and b-conductors are red.
temperature: –5 °C
The cable fulfils the fire condition requirements of
Minimum recommended bending radius: IEC 332-1 (Flame retardant)
- during installation 15xD
- during operation 10xD

CONSTRUCTION
Conductor Stranded tinned copper Common Two plastic-aluminium tapes and
Insulation PE a ground
Unit Twisted and individually with Shield wire between tapes
plastic-aluminium tape shielded pair, Sheath Grey LINYL-PVC
earth conductor and a number tape

CABLE SIZES
Number and size of
the conductors mm2 2 x (2+1) x 0,5 4 x (2+1) x 0,5 8 x (2+1) x 0,5 12 x (2+1) x 0,5 24 x (2+1) x 0,5 48 x (2+1) x 0,5
EAN code (SSTL code) 64 100+ 02 642 22-3 02 642 24-7 02 642 26-1 02 642 28-5 02 642 30-8 02 642 32-2
Nominal diameter mm 8,5 10,0 13,5 15,5 21,5 29,5
Mass kg/km 75 115 210 290 540 1030
Delivery lenght m 1000 1000 1000 1000 1000 500
ELECTRICAL PROPERTIES
Maximum loop resistance Ω/km 81
Nominal mutual capacitance
(800 Hz) nF/km 85
Impedance, 10 MHz Ω 70 ± 10
Minimum insulation resistance GΩ x km 2
Velocity factor 0,66
Maximum voltage V 75
Nominal attenuation dB/100 m
frequency 9,6 kHz 0,3
frequency 19,2 kHz 0,5
frequency 64 kHz 0,7
frequency 100 kHz 0,9
frequency 200 kHz 1,6
frequency 1,0 MHz 4,5

JAMAK-C is also available as halogenfree (JAMAK-C-HF) version. The right to alterations reserved.

49
INSTRUMENTATION CABLES

Instrumentation cable
NOMAK®

APPLICATIONS Minimum recommended bending radius:


- during installation 15xD
- during operation 10xD
— Fixed indoor — Process control
installations — Suitable for Maxi Termipoint
— Automation connections
— Instrumentation IDENTIFICATION
Maximum ambient temperature: Pairs marked with numbers,
- in operation +70 °C a-conductors are orange and b-conductors are white.

Lowest recommended installation The cable fulfils the fire condition requirements of
temperature: –5 °C IEC 332-1 (Flame retardant).

CONSTRUCTION
Conductor Stranded tinned copper Overall shield Plastic/aluminium tape with earth
Insulation PVC conductor
Unit Twisted pair Shealth Grey LINYL-PVC

CABLE SIZES
Number and size of
the conductors mm2 2 x 2 x 0,5 4 x 2 x 0,5 8 x 2 x 0,5 12 x 2 x 0,5 24 x 2 x 0,5 48 x 2 x 0,5
EAN code (SSTL code) 64 100+ 02 649 52-9 02 649 54-3 02 649 58-1 02 649 62-8 02 649 64-2 02 649 68-0
Nominal diameter mm 7,5 8,5 11,0 14,0 19,0 25,0
Mass kg/km 60 85 150 210 400 720
Delivery length m 1000/200 1000/200 1000 1000 1000 1000
ELECTRICAL PROPERTIES 20 °C
Maximum loop resistance Ω/km 81
Nominal mutual capacitance
(800 Hz) nF/km 90 85
Impedance, 10 MHz Ω 100 ± 10 %
Minimum insulation resistance MΩ x km 100
Velocity factor 0.60
Maximum voltage V 75
Nominal attenuation dB/100 m
frequency 9,6 kHz 0,3
frequency 19,2 kHz 0,5
frequency 64 kHz 0,7
frequency 100 kHz 0,9
frequency 200 kHz 1,5
frequency 1,0 MHz 2,9

NOMAK is also available as halogenfree (NOMAK-HF) version. The right to alterations reserved.

50
INSTRUMENTATION CABLES

Instrumentation cable
NOMAK-E®

APPLICATIONS Minimum recommended bending radius:


- during installation 15xD
— Fixed indoor — Process control - during operation 10xD
installations — Suitable for Maxi Termipoint
— Automation connections IDENTIFICATION
— Instrumentations

Maximum ambient temperature: Pair a-wire b-wire Pair a-wire b-wire


- in operation +70 °C
1 blue red 3 green brown
Lowest recommended installation
temperature: –5 °C 2 grey yellow 4 white black

Every four -pair unit marked with a number tape.

The cable fulfils the fire condition requirements of


IEC 332-1 (Flame retardant).

CONSTRUCTION
Overall Plastic/aluminium tape with
Conductor Stranded tinned copper
earth conductor shield
Insulation PVC
Shealth Grey LINYL-PVC
Unit Twisted pair

CABLE SIZES
Number and size of
the conductors mm2 2 x 2 x 0,5 4 x 2 x 0,5 8 x 2 x 0,5 12 x 2 x 0,5 24 x 2 x 0,5
EAN code (SSTL code) 64 100+ 02 649 53-6 02 649 55-0 02 649 59-8 02 649 63-5 02 649 65-9
Nominal diameter mm 7,5 8,5 11,0 14,0 19,0
Mass kg/km 60 85 150 210 400
Delivery length m 1000 1000 1000 1000 1000
ELECTRICAL PROPERTIES 20 °C
Maximum loop resistance Ω/km 81
Nominal mutual capacitance
(800 Hz) nF/km 90 85
Impedance, 10 MHz Ω 100 ± 10 %
Minimum insulation resistance MΩ x km 100
Velocity factor 0.60
Maximum voltage V 75
Nominal attenuation dB/100 m
frequency 9,6 kHz 0,3
frequency 19,2 kHz 0,5
frequency 64 kHz 0,7
frequency 100 kHz 0,9
frequency 200 kHz 1,5
frequency 1,0 MHz 2,9
NOMAK-E is also available as halogenfree (NOMAK-E-HF) version. The right to alterations reserved.

51
INSTRUMENTATION CABLES

Automation/ Istrumentation cables


FKAR-PG n x 2 x 0,5 mm2

APPLICATIONS Minimum recommended bending radius:


- during installation 15xD
— Indoor — Process control
installations — Automation
— Instrumentation STANDARD
SS 4240323
Maximum ambient temperature: SS 4241475 Class 3, (Flame retardant).
- in operation +70 °C

Lowest recommended installation


temperature: –30 °C IDENTIFICATION
- During installation -5 °C
Insulation colour: black
Each conductor with white number marking

CONSTRUCTION
Conductor Stranded tinned copper 0,5 mm2 Overall shield Plastic/aluminium foil with drain
Insulation Black PVC wire
Unit Twisted pair Shealth Grey PVC

CABLE SIZES
Type 1 x 2 x 0,5 2 x 2 x 0,5 4 x 2 x 0,5 8 x 2 x 0,5 16 x 2 x 0,5 24 x 2 x 0,5 48 x 2 x 0,5
Nominal diameter mm 6,0 9,0 10,5 14,0 18,0 21,5 29,0
Mass kg/km 56 88 125 210 370 520 980
ELECTRICAL PROPERTIES
Maximum loop resistance Ω/km 81
Minimum insulation resistance MΩ x km 100
Maximum voltage V 150/ 250
Nominal attenuation dB/100 m
frequency 9,6 kHz 0,4
frequency 19,2 kHz 0,6

52
INSTRUMENTATION CABLES

Instrumentation cable
KLAM 3 x 1,5 + 1,5

APPLICATIONS IDENTIFICATION
— Fixed indoor — Instrumentation a-conductor is blue, b-conductor is red and
installations — Automation c-conductor is white.

Suitable for long distance transmission.

Maximum ambient temperature:


- in operation +70 °C

Lowest recommended installation


temperature: –5 °C

Minimum recommended bending radius: The cable fulfils the fire condition requirements of
- during installation 15xD IEC 332-1 (Flame retardant).
- during operation 10xD

CONSTRUCTION
Conductor Stranded tinned copper Unit Twisted conductors shielded with
Insulation PVC plastic/aluminium tape, earth conductor
Sheath Grey LINYL-PVC

CABLE SIZES
Number and size of
the conductors mm2 3 x 1,5+1,5
EAN code (SSTL code) 64 100+ 02 640 03-8
Nominal diameter mm 8,5
Mass kg/km 115
Delivery length m 1000
ELECTRICAL PROPERTIES 20 °C
Maximum loop resistance Ω/km 24
Minimum insulation resistance MΩ x km 500
Maximum voltage V 75

KLAM is also available as halogenfree (KLAM-HF) version. The right to alterations reserved.

53
INSTRUMENTATION CABLES

Symmetrical data transmission cables


RD-

APPLICATION Cable description

These symmetrical data transmission cables are used in RD Y (St) Y n x 2 x 0,5


control and supervision centres for industrial units. They number of pairs x conductor cross
are suitable for fixed installation inside housing. Cables section
with reinforced or douple outer sheath can be installed Y outer sheath PVC (+70 °C)
also outdoors for direct burial. Yv reinforced outer sheath PVC
for direct burial
CONSTRUCTION Yw outer sheath heat resistant
PVC (+90 °C)
Multi-wired conductor or plain copper adapted to Yu outer sheath flame retardent PVC
Maxi-Termi-Point connection; conductor insulation (LOI s30), IEC 332-1
consists of PVC or halogen free material. Cores ar twisted YuFR outer sheath fire retardent PVC
to pairs with short loops inside a unit featuring good (LOI s30), IEC 332-3C
nearend crosstalk attenuation. Overall shielding of either H outer sheath halogen free,
aluminium laminated plastic foil or copper braid prevents IEC 332-3C
EMC interference. St static shielding (foil)
C copper braid shielding
IDENTIFICATION Y conductor insulation PVC (+70 °C)
Yw conductor insulation heat resistant
Conductors PVC (+90 °C)
H conductor insulation halogen free
Color R “Rechnerkabel”
Pair no.
a-conductor a-conductor (stranding min. 20 loops/m)
1 blue red
D DECONTIC
(registered trade mark of ABB)
2 grey yellow
3 green brown
4 white black

Every unit with number coding


Also available
Sheath colours
RD-Y(St)Y with PVC outer sheath
Grey, resp. Blue for intrinsic safe systems at inhouse RD-Y(St)Yu with special flame retardent PVC
application; black for outdoor installation outer sheath
RD-H(St)H with halogen free outer sheath
Sheath printing RD-Yw(C)Yw with heat resistant PVC outer sheath
and braided copper
Manufacturer, type coding including conductor dimension
and number of pairs, metre marking

54
INSTRUMENTATION CABLES

Symmetrical data transmission cables


RD-Y(St)Y

APPLICATIONS IDENTIFICATION
Fixed installation inside housing Color
Pair no.
a-conductor a-conductor
Maximum ambient temperature:
1 blue red
- in operating -40 °C ...+70 °C
2 grey yellow
Lowest recommended installation 3 green brown
temperature: –5 °C

Fire behaviour:
oxygen index LOI acc. To ASTM-D-2863 no limit Every unit with number coding
smoke density acc. To ASTM-D-2843 90 %
HCL emission acc. To IEC 754-1 >25 %
fire propagation acc. To IEC 332-1

CONSTRUCTION
Conductor plain copper wire, Core stranding (0+4)
0,5 mm2 /7x0,3 mm2 Ø) Shielding Al-laminated plastic foil +
Insulation PVC, Ø 1,5 mm drain wire 0,5 mm2
Stranding 2 conductors per pair Outer shealth PVC
CABLE SIZES
Pert. no C17582000 C17582100 C17582200 C17582300 C17582400 C17582500 C17582600 C17582700 C17582800
Type 2x2x0,5 4x2x0,5 8x2x0,5 12x2x0,5 16x2x0,5 24x2x0,5 32x2x0,5 48x2x0,5 96x2x0,5
Outer diameter mm 6,5 ± 0,5 9,0 ± 0,5 11,5 ± 0,5 13,0 ± 0,8 14,5 ± 0,8 17,5 ± 1,0 20,0 ± 1,0 24,0 ± 1,0 32,5 ± 1,5
Mass kg/km 65 110 190 240 300 420 570 800 1500
Cu-content 25 45 85 125 165 245 325 485 965
Bending radius mm 50 70 90 100 110 135 150 180 250
Delivery length m 4000 2000 2000 2000 2000 2000 2000 1000 500
ELECTRICAL PROPERTIES 20 °C
Maximum loop resistance Ω/km 73,6
Nominal mutual capacitance
(800 Hz) nF/km 100
4x2 nF/km 120
Minimum insulation resistance MΩ x km 100
Nominal impedance
(at 1 kHz) Ω 370
(at 1 kHz) Ω 130
Maximum voltage V 600
Test voltage (at 50 Hz, 2 min)
cond./conductor V 2000
cond./shield 2000
Nominal attenuation dB/100 m
frequency 1,0 kHz 1,2
frequency 10,0 kHz 3,0
The right to alterations reserved.

55
INSTRUMENTATION CABLES

JAMAK® & JAMAK® ARM


JOINTING

Pair shields and the common shield are spliced and The length of the splice depends on the number of
earthed by a copper conductor. It is important in the the pairs:
jointing and terminal connections that the pair shields are
insulated one from
the another, except for the common grounding point. Number of pairs 2 4 8 12 24 48

If the jointing has to be EMC protected, the shields have to Joint gap mm 280 280 280 280 400 400
be jointed all around i.e. 360°.

SPLICING
1. The sheath is stripped. The inner sheath is pulled 4. Splicing of the earth conductor of the pair shield
open by the tear-off wire.

2-12 pair

25 30 earth conductor splice


1 1
2 2 1
3 2 1
3 3 2
4 4 3 2
4 3
4
4

5. Complete pair joint


50 40 joint gap

24 and 48 pairs 1 1 1 1 1

pair insulation

2. The pair shield is opened and removed

1. cut
Note! If the jointing has to be EMC protected,
1 1 1 the shields have to be jointed all around i.e. 360°.
2. cut
1 1 1

1 6. Splicing of the inner sheath

pull off
thermal protection earth conductor splice for
the common shield
1 1 1 1 1

strip

shrink-on tube
3. Splicing of a pair

100 7. Splicing of the armouring


conductor sleeve soldering
pair sleeve copper braid

1 1 1 1

earth conductor
outer shrink-on tube inner shrink-on tube

8. Complete joint
An indoor cable is jointed without steps 6 and 7.

shrink-on tube

The right to alterations reserved.

56
LON CABLING

DISTRIBUTED DATA SYSTEMS OF


BUILDING TECHNOLOGY

LON (Local Operating Network) LON-Cabling


- LON is field bus that enables the distributed data LON-Cabling can be realized with three different conductor
systems in buildings sizes (1,3 mm, 0,8 mm and 0,65 mm).
- based on the Neuron-prosessor of Echelon Co LON-cables of NK Cables are:
- chosen by the Finnish building association as
the basis of SaMBA-project LONAK® 2 x 1,3
- LON is a building automation system which controls LONAK® ARM 2 x 1,3
lights, heating, air conditioning, electricity, security LONAK® 2 x 2 x 0,8
systems of buildings with intelligent automation systems LONAK® 2 x 2 x 0,65
- LON-net/Intelligent nodes. They use the same language,
which is Lon Talk. LON-bus is open and suitable for LON Cabling works also with Cat. 5 cables, but only with
products of different manufacturers shorter connections and smaller node amounts.
- LON-net does not need centralized control
- Applications are buildings, industry and process Readiness of LON-Cabling
automation, vehicles and small systems
- Lon Works networks is becoming the dominant standart Readiness for LON can be improved by installing
for home networking around the world. a sufficient amount of LON boxes with RJ 45 female
connectors to connect the nodes.
It is very important to plan cabling systems so that it is
possible to connect intelligent switches and nodes easily LON outlets should be installed in such amounts and at
and make solutions which work properly in the future too. such distances that a allow a readiness for LON in all
premises can be achieved.
The LON cables of NK Cables fulfil requirements of
Echelon specification, which describes cabling systems
The type of cable used as a connecting wire and its lenght
and requirements.
should be chosen according to the tranceivers and in
compliance with the allowed lengths of cable and
distances between nodes.

Cabling implemented in the right way is a basic


prerequisite for error-free and reliable data transmission
between intelligent nodes. Cabling has a great effect on
how the LON network will serve its users in the future when
it is need to change and grow.

Implementation of LON-Cabling

LON-pair
The last outlet includes terminating resistor
LON
1 2 3 4 5 6 7 8
RJ 45-female connector

LON-outlet
0,65 mm cable

Connection cable Connection cable


4-way breakout box RJ 45 - RJ 45 RJ 45 - screw connection

57
SIGNAL CABLES

Building automation cable


LONAK 2 x 1,3 and LONAK ARM 2 x 1,3

APPLICATIONS Minimum recommended bending radius:


- during installation 15xD
- during operation 10xD
— LONAK: Fixed indoor — LONAK ARM: Outdoor
installations installations
Maximum permissible tensile stress
— LON net cabling — Building automation
cabling N
N during installation: 130 N

Designed specially for LON network cabling systems.

Maximum ambient temperature:


IDENTIFICATION
- in operation +70 °C
a-conductor is white, b-conductor is blue
Lowest recommended installation
temperature: –5 °C The LONAK cable fulfils the fire condition requirements
of IEC 332-1.

CONSTRUCTION
LONAK 2 x 1,3 LONAK ARM 2 x 1,3

Conductor Stranded tinned copper Conductor Stranded tinned copper


Insulation PVC Insulation PE
Unit Twisted pair Unit Twisted pair
Sheath Grey LINYL-PVC Sheath Grey PVC
Sheath NK CABLES LONAK 2 x 1,3 Armouring Helically wrapped steel bands
marking traceability code, metre marking Outersheath Black PE

CABLE SIZES
Number and size of
the conductors mm2 2 x 1,3 2 x 1,3
EAN code (SSTL code) 64 100+ 02 649 20-8 02 649 30-7
Nominal diameter mm 7,0 10,5
Mass kg/km 65 155
Delivery length m 1000 1000
ELECTRICAL PROPERTIES 20 °C
Maximum loop resistance Ω/km 28 28
Nominal mutual capacitance nF/km 72 72
Nominal impedance Ω 82
Minimum insulation resistance MΩ x km 100 100
Velocityfactor 0,55 0,55
Maximum voltage V 75 75

LONAK is also available as halogenfree LONAK-HF version. LONAK ARM is also available as halogenfree LONAK ARM-HF version.

58
SIGNAL CABLES

Building automation cable


LONAK 2 x 2 x 0,8 and
LONAK 2 x 2 x 0,65

APPLICATIONS
N
N
Maximum permissible tensile stress
during installation:
2 x 2 x 0,8 100 N
— 2 x 2 x 0,8: Fixed indoor — 2 x 2 x 0,65: Out-
2 x 2 x 0,65 65 N
installations door installations
— LON net cabling — Building automation
cabling IDENTIFICATION
Designed specially for LON network cabling systems.
Pair Conductor
Maximum ambient temperature:
- in operation +70 °C 1 white / blue
2 white / orange
Lowest recommended installation
temperature: –5 °C

Minimum recommended bending radius: The cable fulfils the fire condition requirements of
- during installation 15xD IEC 332-1.
- during operation 10xD

CONSTRUCTION
LONAK 2 x 2 x 0,8 LONAK 2 x 2 x 0,65

Conductor Tinned copper Conductor Tinned copper


Insulation PVC Insulation PE
Unit Twisted pair Unit Twisted pair
Shield Aluminium tape and earth conductor Shield Aluminium tape and earth conductor
Sheath Grey LINYL-PVC Sheath Grey LINYL-PVC

CABLE SIZES
Number and diameter of
the conductors mm 2 x 2 x 0,8 2 x 2 x 0,65
EAN code (SSTL code) 64 100+ 02 649 38-3 02 649 36-9
Nominal diameter mm 6,5 4,5
Mass kg/km 58 32
Delivery length m 1000 1000
ELECTRICAL PROPERTIES 20 °C
Maximum loop resistance Ω/km 73 106
Nominal mutual capacitance nF/km 98 49
Minimum insulation resistance MΩ x km 100 100
Velocity factor 0,55 0,67
Resistance unbalance, max % 3
Max. capacitance unbalance pF/m 1600
Maximum voltage V 75 75

LONAK 2 x 2 x 0,8 is also available as halogenfree LONAK-HF version. The right to alterations reserved.

59
SIGNAL CABLES

Signal cable
KLM

APPLICATIONS IDENTIFICATION
— Fixed indoor — Alarm, signal and 1. Conductor blue
installations security control 2. Conductor yellow
— Building automation transmission 3. Conductor white
4. Conductor red

Maximum ambient temperature:


- in operation +70 °C

Lowest recommended installation


temperature: –5 °C

Minimum recommended bending radius: The cable fulfils the fire condition requirements of
- during installation 15xD IEC 332-1.
- during operation 10xD

CONSTRUCTION
According to SFS 2751 Unit Insulated conductors twisted together
Conductor Tinned copper Sheath Grey LINYL-PVC
Insulation PVC

CABLE SIZES
Number and diameter of
the conductors mm 2 x 0,8 4 x 0,8
EAN code (SSTL code) 64 100+ 02 910 01-8 02 910 03-2
Nominal diameters mm 4,5 5,0
Mass kg/km 25 40
Delivery length m 500 500
ELECTRICAL PROPERTIES 20 °C
Maximum conductor resistance Ω/km 36,7
Minimum insulation resistance MΩ x km 500
Maximum voltage V 75

KLM is also available as halogenfree KLM-HF version.

60
SIGNAL CABLES

Signal cable
KLMA

APPLICATIONS IDENTIFICATION
— Fixed indoor — Alarm, signal and 1. Conductor blue
installations security control 2. Conductor yellow
— Building automation transmission 3. Conductor white
4. Conductor red
Maximum ambient temperature:
- in operation +70 °C

Lowest recommended installation


temperature: –5 °C

Minimum recommended bending radius: The cable fulfils the fire condition requirements of
- during installation 15xD IEC 332-1.
- during operation 10xD

CONSTRUCTION
According to SFS 2755 Unit Twisted conductors shielded with
Conductor Tinned copper plastic-aluminium tape, earth conductor
Insulation PVC Sheath Grey LINYL-PVC

CABLE SIZES
Number and diameter of
the conductors mm 2 x 0,8+0,8 4 x 0,8+0,8
EAN code (STTL code) 64 100+ 02 920 01-7 02 920 03-1
Nominal diameters mm 4,5 5,0
Mass kg/km 30 45
Delivery length m 500 500
ELECTRICAL PROPERTIES 20 °C
Maximum conductor resistance Ω/km 36,7
Minimum insulation resistance MΩ x km 500
Maximum voltage V 75

KLMA is also available as halogenfree KLMA-HF version. The right to alterations reserved.

61
SIGNAL CABLES

Fire alarm cable


MMSA

APPLICATIONS IDENTIFICATION
— Fixed indoor — Alarm, signal and
installations security control Conductors Stranding
— Building automation transmission Number
in concentric Colour Type Make-up
Maximum ambient temperature: layer
- in operation +70 °C
1 Blue 4x 0+4
(mark colour)
Lowest recommended installation 2, 5, 8 ... yellow 12x 3+9
temperature: –5 °C 3, 6, 9... white 20x 1+7+12
4, 7, 10 brown
Minimum recommended bending radius: last red
- during installation 15xD
(direction
- during operation 10xD indication)

The cable fulfils the fire condition requirements of


IEC 332-1.

CONSTRUCTION
According to SFS 2752 Earth shield Aluminium tape on insulated conductor
Conductor Tinned copper Stranding Twisted conductors, earth conductor
Insulation PVC Sheath Grey LINYL-PVC

CABLE SIZES
Number and diameter of
the conductors mm 4 x 0,8+0,8 12 x 0,8+0,8 20 x 0,8+0,8
EAN code (SSTL code) 64 100+ 02 630 70-1 02 630 72-5 02 630 74-9
Nominal diameters mm 5,5 8,5 10,0
Mass kg/km 45 115 180
Delivery length m 1000 1000 1000
ELECTRICAL PROPERTIES 20 °C
Maximum conductor resistance Ω/km 36,7
Minimum insulation resistance MΩ x km 500
Maximum voltage V 75

The right to alterations reserved.

62
SIGNAL CABLES

Fire alarm cable


MMVDMA (MMPMA)

MMVDMA

MMPMA

APPLICATIONS IDENTIFICATION
— Fixed outdoor — Alarm, signal and
installations security control
— Building automation transmission Conductors Stranding
Number
Maximum ambient temperature: in concentric Colour Type Make-up
- in operation +70 °C layer
1 Blue 4x 0+4
Lowest recommended installation (mark colour)
temperature: –5 °C 2, 5, 8 ... yellow
3, 6, 9... white 12x 3+9
4, 7, 10 brown 20x 1+7+12
Minimum recommended bending radius: last red
- during installation 15xD
- during operation 10xD (direction
indication)

CONSTRUCTION
According to SFS 2752 Stranding Twisted conductors, earth conductor
Conductor Tinned copper Sheath Grey LINYL-PVC
Insulation PVC Armouring Steel wire armouring
Earth shield Aluminium tape on insulated conductor Outersheath Black PVC

CABLE SIZES
Number and diameter of
conductors mm 4 x 0,8+0,8 12 x 0,8+0,8 20 x 0,8+0,8
EAN code (SSTL code) 64 100+ 02 633 00-9 02 633 02-3 02 633 04-7
Nominal diameters mm 11,5 15,0 17,5
Mass kg/km 230 390 520
Delivery length m 1000 1000 1000
ELECTRICAL PROPERTIES 20 °C
Maximum conductor resistance Ω/km 36,7
Minimum insulation resistance MΩ x km 500
Maximum voltage V 75

The right to alterations reserved.

63
DATA CABLES

GENERIC CABLING SYSTEMS

GENERAL APPLICATION AND TRANSMISSION


CLASSES
Generic cabling is applied to telecommunication cabling
as a permanent part of the office to meet the expanding
needs of the user’s. It meets also the future data
Transmission Application Maximum
transmission requirements including new computers and classes frequency
relocation of the workstations on the premises
- minimizing the need for new cabling. Voice band and
A low-frequency 100 kHz
applications
The physical structure of a generic cabling system is
star-shaped. This makes the network control easier which Medium-speed
B data applications 1 MHz
is important especially now when the telecommunication
and data networks in buildings are the property of Fast data
the owner. A star-shape cable system allows to change C applications 16 MHz
the network topology from the cross-connection to a bus
Very fast data
or a ring. In a star-shape system all the active components D applications 100 MHz
can be placed together in one space which is easy to
control and can be locked and which improves data E Very fast data
applications 200 MHz
security. Also measurements and maintenance are easier
to carry out in the cross-connection area. lf one branch of Very fast data _
OPTICAL applications
the star network falls off the whole system is not paralyzed
because the faulty branch can be disconnected from the
network. A generic cabling system constructed for a certain
application consists of one or several transmission lines.
The generic cabling system is not really open until its
components are vendorindependent. They just have to
conform to the standards. When planning a cable system
it is important to consider what the openness really means RECOMMENDATIONS
and how open the non-compatible and vendor-dependent
cable systems are. — It is important to examine the building needs very
carefully, including e.g. the existing network and
the desires for more extended data transmission
STANDARDS in the future.

The European standard for the generic cabling systems — The maximum length of horizontal cabling is 90 m.
is EN 50173 which was set up on the basis of the The maximum length of cross-connection and
international ISO/IEC 11801. The corresponding standard equipment cabling is 10 m.
in the U.S. is ANSI/TIA/EIA 568-A supported by TIA and
— An optical fibre cable is recommended for local and
EIA. The EN 50173 applicable in Europe defines the
rising cabling.
different transmission line applications and classes as well
as the categories 3 and 5 for the line components. — Two double cables should be installed for each work
For example, a data network that fulfills the requirements area, in order to meet the increasing need of
of class D can be set up from components of category 5. telecommunication.
EN 50173 recommends the use of 100 Ω twisted-pair
cables in horizontal cabling.

Cat. 6 standard will be ready in 2001. DATA TRANSMISSION CABLES


Our complete range of UC cables fulfills tomorrow’s
SCREENING needs. Our new product family UC 400 is designed for
applications beyond CAT 5 with good properties.
The abbreviations UTP, FTP and STP-screening Our new development for the high-end field is UC 1000.
construction are used to refer to the cable. UTP is a cable A cable class that not only fulfills the above mentioned
where symmetrical twisted pairs are used for screening. standards, but also offers reserves, allowing base band
A FTP cable has an overall metal shield, and in a STP transmission of Gigabit-Ethernet.
cable all the pairs are screened separately. The cable type
is chosen to suit the environment where it’s used.
In Finland most of the installations are made with FTP and
UTP cables. Optical fibre cables are recommended for
local and rising cabling.
The STP may also be marked ScTP and S/STP, meaning
a construction with a pair and an overall shield.

64
DATA CABLES

CONTENTS
GENERIC CABLING CONSTRUCTION

Campus distributor
CD
Campus backbone cabling

Building distributor BD BD BD
Building backbone cabling

Floor distributor FD FD FD FD
Horizontal cabling

Telecommunication outlets TO TO TO TO TO TO

ATM
ATM, or the Asynchronous Transfer Mode, is a network
technology which use is very rapidly increasing. ATM can
be used to transfer sound, picture and data. ATM is based
on data transfer with cells of the same size which reserve
the line only for the duration of the actual transmission.

MEANING OF THE SYMBOLS


UC = Universal Cable
300 = Maximum frequency 300 MHz,
fast data applications
400, 600 = Maximum frequency 400, 600 MHz,
fast data applications
S = Screen aluminium shield
D = Double
SS = Super Screen pair foil screen
with common braid
24 = AWG-number
diameter of conductor 0,51 mm
22 = AWG-number
diameter of conductor 0,64 mm
4P = four pair
2x4P = Double
FRNC = Halogen-free material

Example. UC 300 D S 24 2x4 P

UC = Universal Cable,
300 = Maximum frequency 300 MHz,
fast data applications
D = Double
S = Screen aluminium shield
24 = AWG-number
diameter of conductor 0,51 mm
2x4P = Double

65
DATA CABLES

CONTENTS

GENERIC CABLING CABLE TYPE

Design/protection against
Cable type electromagnetic Frequency, max. MHz Classification Application
disturbancies EN 50173

Telephone network
UC 300 S 24 4P FTP Category 5/5e ISDN
Overall shield 100/125 Ethernet 10, 100 Mbit/s
Token Ring 4/16 Mbit/s
CDDI /TP-PMD
UC 300 DS 24 2 x 4P FTP Category 5/5e ATM
Overall shield
Shotgun version

Telephone network
UC 300 24 4P UTP Category 5/5e ISDN
100/125 Ethernet 100 Mbit/s
Token Ring 4/16 Mbit/s
UC 300 D 24 2 x 4P UTP Category 5/5e CDDI /TP-PMD
Shotgun version ATM
HORIZONTAL
CABLING
High Telephone network
UC 400 24 4P Performance UTP ISDN
200/250 Ethernet 100 Mbit/s
Cat 6 Token Ring 4/16 Mbit/s
UC 400 D 24 2 x 4P High CDDI /TP-PMD
Performance UTP ATM
Shotgun version Gigabit-Ethernet

High Telephone network


UC 400 S 24 2 x 4P Performance FTP ISDN
200/250 Ethernet 100 Mbit/s
Cat 6 Token Ring 4/16 Mbit/s
UC 400 DS 24 2 x 4P High CDDI /TP-PMD
Performance FTP ATM
Shotgun version Gigabit-Ethernet

Telephone network
UC 600 SS 23 4P Overall shield Cat 7 ISDN
Screened pair 600 Ethernet 100 Mbit/s
Token Ring 4/16 Mbit/s
S/STP CDDI /TP-PMD
UC 1000 SS 22 4P 1000 ATM
Gigabit-Ethernet

ISDN
BUILDING FYMSU n x 62.5/125 Fibre optic cable Ethernet 10 Mbit/s
BACKBONE (Spiral Space®) Token Ring 4/16 Mbit/s
CABLING CDDI /TP-PMD
ATM
Gigabit-Ethernet

THE COLOUR SYSTEM OF THE


CONDUCTORS
NK Cables recommend that the conductors of UC 300 The standard does not define the colour systems but, for
cables could be connected as follows: reasons of conformity, the above system is recommended.

Pair a b
1 white blue
2 white orange
3 white green
4 white brown

On the a-wire there is a stripe of the same colour as


the corresponding b-wire.

66
DATA CABLES
CONTENTS

All these new UC-cables have been tested by the EC group of Delta, and here is an example of a statement on UC 300 S.

67
DATA CABLES

Data cable, category 5, FTP


UC 300 S 24 4P / UC 300 DS 24 2 x 4P

APPLICATIONS STANDARDS
— Fixed indoor — Ethernet 100 Mbit/s EN 50173; prEN 50288-3-1
installations — Token Ring 4/16 Mbit/s ISO/IEC 11801 2rd ed
— CDDI — Telephone networks TIA/EIA 568-A
— TP-PMD — ISDN ISO 8802.3/IEEE 802.3 100 base T
— ATM — Generic cabling system

Maximum ambient temperature: IDENTIFICATION


- in operation +70 °C

Lowest recommended installation Pair Colour code Pair Colour code


temperature: –5 °C 1 white/blue 3 white/green

Minimum recommended bending radius: 2 white/orange 4 white/brown


- during installation 10xD
- during operation 5xD

Maximum permissible tensile stress On the a-wire there is a stripe of the same colour as
N N
during installation:
UC 300 S 24 4P 80 N
the corresponding b-wire.

UC 300 DS 24 2 x 4P 160 N The cable fulfils the fire condition requirements of


IEC 332-1.

UC 300 S 24 4P is available as halogenfree UC 300 DS 24 2 x 4P- FRNC-B/C version.

68
DATA CABLES

Data cable,category 5, FTP


UC 300 S 24 4P / UC 300 DS 24 2 x 4P

CONSTRUCTION
Conductor Copper wire, d = 0,51 mm Screen Plastic/aluminium tape as a overall
Insulation PE shield
Unit Twisted pair Sheath Grey PVC
Earth wire Tinned copper

CABLE SIZES

Type UC 300 S 24 4P UC 300 DS 24 2 x 4P


EAN code (STTL code) 64 100+ 02 640 01 02 640 64
Nominal diameters mm 5,8 5,8 x 11,6
Mass kg/km 36 72
Delivery length m 500 500
ELECTRICAL PROPERTIES 20 °C
Loop resistance, max Ω/km 176
Insulation recistance, min GΩ x km 2
Nominal mutual capacitance nF/km 48
Maximum capacitance
unbalance, pair to ground pF/km ≤1500
Nominal impedance Ω ƒ =1 - 100 MHz 100 ± 15
Maximum transfer impedance MΩ x m 100
Velocity factor 0,67
Maximum voltage V 75

TRANSMISSION CHARACTERISTICS ACC. TO CATEGORY 5e (at 20 °C)


Frequency Attenuation NEXT PS-NEXT ACR PS-ACR ELFEXT PS-ELFEXT Return
loss
MHz (dB/100 m) (dB) (dB) (dB/100 m) (dB/100 m) (dB/100 m) (dB/100 m) (dB)
max. nom. min. nom. min. nom. min. nom. min. nom. min. nom. min. nom. min.
1 2 1,9 65 71 62 68 63,3 69,1 60,3 66,1 64 68 61 65 23
4 3,9 3,7 56 62 53 59 52,4 58,3 49,4 55,3 52 56 49 53 23
10 6,3 6,0 50 56 47 53 44,0 50,0 41,0 47,0 44 48 41 45 23
16 8,0 7,6 47 53 44 50 39,3 45,3 36,3 42,3 40 44 37 41 23
20 9,0 8,5 46 51 43 48 36,8 43,0 33,8 40,0 38 42 35 39 23
31,2 11,4 10,7 43 49 40 46 31,5 37,9 28,5 34,9 34 38 31 35 23
62,5 16,5 15,7 38 40 35 41 21,9 28,4 18,9 25,4 28 32 25 29 23
100 21,3 19,8 35 41 32 38 14,0 21,2 11,0 18,2 24 28 21 25 23
125 22,3 40 37 17,2 14,2 26 23
155,5 24,2 38 35 13,9 10,9 24 21
175 25,7 37 34 11,6 8,6 23 20
200 27,5 36 33 9,0 6,0 22 19
250 29,2 35 32 5,8 2.8 20 17
300 32,0 34 31 1,8 -1,2 16 13

The right to alterations reserved.

69
DATA CABLES

Data cable, category 5, UTP


UC 300 24 4P / UC 300 D 24 2 x 4P

APPLICATIONS STANDARDS
— Fixed indoor — Ethernet 100 Mbit/s EN 50173; prEN 50288-3-1
installations — Token Ring 4/16 Mbit/s ISO/IEC 11801 2rd ed
— CDDI — Telephone networks TIA/EIA 568-A
— TP-PMD — ISDN ISO 8802.3/IEEE 802.3 100 base T
— ATM — Generic cabling system

Maximum ambient temperature:


- in operation +70 °C IDENTIFICATION
Lowest recommended installation
temperature: –5 °C Pair Colour code Pair Colour code
1 white/blue 3 white/green
Minimum recommended bending radius:
- during installation 10xD 2 white/orange 4 white/brown
- during operation 5xD

Maximum permissible tensile stress On the a-wire there is a stripe of the same colour as
N N
during installation:
UC 300 24 4P 80 N
the corresponding b-wire.
UC 300 D 24 2 x 4P 160 N
The cable fulfils the fire condition requirements of
IEC 332-1.

UC 300 24 4P is available as halogenfree UC 300 D 24 2 x 4P- FRNC-B/C version.

70
DATA CABLES

Data cable, category 5, UTP


UC 300 24 4P / UC 300 D 24 2 x 4P

CONSTRUCTION
Conductor Copper wire, d = 0,51 mm Unit Twisted pair
Insulation PE Sheath Grey PVC

CABLE SIZES

Type UC 300 24 4P UC 300 D 24 2 x 4P


EAN code (STTL code) 64 100+ 02 640 05 02 640 07
Nominal diameters mm 5,0 5,0 x 10,0
Mass kg/km 35 70
Delivery length m 500 500
ELECTRICAL PROPERTIES 20 °C
Loop resistance, max Ω/km 176
Insulation recistance, min GΩ x km 2
Nominal mutual capacitance nF/km 48
Maximum capacitance
unbalance, pair to ground pF/km ≤1500
Nominal impedance Ω ƒ =1 - 100 Mhz 100 ± 15
Velocity factor 0,67
Maximum voltage V 75

TRANSMISSION CHARACTERISTICS ACC. TO CATEGORY 5e (at 20 °C)


Frequency Attenuation NEXT PS-NEXT ACR PS-ACR ELFEXT PS-ELFEXT Return
loss
MHz (dB/100 m) (dB) (dB) (dB/100 m) (dB/100 m) (dB/100 m) (dB/100 m) (dB)
max. nom. min. nom. min. nom. min. nom. min. nom. min. nom. min. nom. min.
1 2 1,9 65 71 62 68 63,3 69,1 60,3 66,1 64 68 61 65 23
4 3,9 3,7 56 62 53 59 52,4 58,3 49,4 55,3 52 56 49 53 23
10 6,3 6,0 50 56 47 53 44,0 50,0 41,0 47,0 44 48 41 45 23
16 8,0 7,6 47 53 44 50 39,3 45,3 36,3 42,3 40 44 37 41 23
20 9,0 8,4 46 51 43 48 36,8 43,0 33,8 40,0 38 42 35 39 23
31,2 11,4 10,7 43 49 40 46 31,5 37,9 28,5 34,9 34 38 31 35 23
62,5 16,5 15,7 38 44 35 41 21,9 28,4 18,9 25,4 28 32 25 29 23
100 21,3 19,8 35 41 32 38 14,0 21,2 11,0 18,2 24 28 21 25 23
125 22,3 40 37 17,2 14,2 26 23
155,5 24,2 38 35 13,9 10,9 24 21
175 25,7 37 34 11,6 8,6 23 20
200 27,5 36 33 9,0 6,0 22 19
250 29,2 35 32 5,8 2,8 20 17
300 32,0 34 31 1,8 -1,2 16 13

The right to alterations reserved.

71
DATA CABLES

Data cable, category 6, STP, Patented


UC 400 S 23/1 4P/UC 400 DS 23/1 2x4P

APPLICATIONS STANDARDS
— Fixed indoor — Ethernet 10 Mbit/s, 100 Mbit/s EN 50173-1; prEN 50288-5-1
installations — Gigabit- Ethernet ISO/IEC 11801 2nd edition
— CDDI — Telephone networks TIA/EIA 568-B
— TP-PMD — ISDN ISO 8802.3/IEEE 802.3 10 base T, 100 base T
— ATM — Generic cabling system ISO 8802.5/IEEE 802.5

Maximum ambient temperature:


- in operation +70 °C
IDENTIFICATION
Lowest recommended installation
temperature: –5 °C
Pair Colour code Pair Colour code
Minimum recommended bending radius: 1 white/blue 3 white/green
- during installation 10xD
- during operation 5xD 2 white/orange 4 white/brown

Maximum permissible tensile stress


N N
during installation:
UC 400 S 23/1 4P 100 N
The cable fulfils the fire condition requirements of
IEC 332-1.
UC 400 DS 23/1 2 x 4P 200 N
Halogenfree cable fulfils the fire condition requirements
of IEC 332-3

UC 400 S 23/1 4P is available as halogenfree UC 400 S 24 4P- FRNC-B/C version.

72
DATA CABLES

Data cable, category 6, STP, Patented


UC 400 S 23/1 4P/UC 400 DS 23/1 2x4P

CONSTRUCTION
Conductor Copper wire, d=0,56 mm Earth wire Tinned copper
Insulation PE Screen Special wrapping of Al laminated foil
Unit Twisted pair Sheath Blue PVC

CABLE SIZES

Type UC 400 S 23/1 4P UC 400 DS 23/1 2x4P


EAN code (SSTL code) 64 100+ 02 640 75 02 640 76
Nominal diameters mm 6,5 6,5/13,0
Mass kg/km 41 82
Delivery length m 500 500
ELECTRICAL PROPERTIES 20 °C
Loop resistance, max Ω/km 176
Insulation resistance, min GΩ x km 2
Nominal mutual capacitance nF/km 48
Maximum capacitance
unbalance, pair to ground pF/km ≤1500
Nominal impedance Ω ƒ =1 - 100 MHz 100 ± 15
Transfer impedance, max mΩ/m 100
Velocity factor 0,78
Maximum voltage V 75

TRANSMISSION CHARACTERISTICS ACC. TO CATEGORY 6 (at 20 °C)


Frequency Attenuation NEXT PS-NEXT ACR PS-ACR ELFEXT PS-ELFEXT Return
loss
MHz (dB/100 m) (dB) (dB) (dB/100 m) (dB/100 m) (dB/100 m) (dB/100 m) (dB)
max. nom. min. nom. min. nom. min. nom. min. nom. min. nom. min. nom. min.
1 2,2 2 74 87 71 84 71,8 85,0 68,8 82,0 67 75 64 72 23
4 3,8 3,8 65 78 62 75 61,2 74,2 58,2 71,2 55 75 52 72 23
10 6,0 6,0 59 72 56 69 53,0 66,0 50,0 63,0 47 75 44 72 23
16 7,6 7,6 56 69 53 66 48,4 61,3 45,4 58,3 43 71 40 68 23
20 8,5 8,5 55 68 52 65 46,5 59,0 43,5 56,0 41 69 38 66 23
31,2 10,7 10,7 52 65 49 62 41,3 54,0 38,3 51,0 37 65 34 62 23
62,5 15,5 15,1 47 60 44 57 31,5 45,0 28,5 42,0 31 59 28 56 23
100 19,9 19,1 44 57 41 54 24,1 37,9 21,1 34,9 27 55 24 52 23
125 22,5 21,3 43 56 40 53 20,5 34,2 17,5 31,2 25 53 22 50 21
155,5 25,4 23,8 42 54 39 51 16,6 30,3 13,6 27,3 23 51 20 48 21
175 27,1 25,3 41 53 38 50 13,9 28,1 10,9 25,1 22 50 19 47 21
200 29,2 27,0 40 53 37 50 10,8 25,5 7,8 22,5 21 49 18 46 21
250 33,0 32,6 38 51 35 48 5,0 18,5 2,0 15,5 19 47 16 44 19
300 35,7 50 47 14,2 11,2 45 42
400 41,2 48 45 6,8 3,8 53 40

The right to alterations reserved.

73
DATA CABLES

Data cable, category 6, UTP (4 x 2 x 0,56 / AWG 23)


UC 400 24 4P/UC 400 D 24 2 x 4P

APPLICATIONS STANDARDS
— Fixed indoor — Ethernet 10 Mbit/s, 100 Mbit/s EN 50173; prEN 50288-6-1
installations — Gigabit- Ethernet ISO/IEC 11801 2nd edition
— CDDI — Telephone networks TIA/EIA 568-A
— TP-PMD — ISDN ISO 8802.3/IEEE 802.3 10 base T, 100 base T
— ATM — Generic cabling system ISO 8802.5/IEEE 802.5

Maximum ambient temperature:


- in operation +70 °C IDENTIFICATION
Lowest recommended installation
temperature: –5 °C Pair Colour code Pair Colour code
1 white/blue 3 white/green
Minimum recommended bending radius:
- during installation 10xD 2 white/orange 4 white/brown
- during operation 5xD

Maximum permissible tensile stress


N N during installation:
UC 400 24 4P 80 N The cable fulfils the fire condition requirements of
UC 400 D 24 2 x 4P 160 N IEC 332-1.

Halogenfree cable fulfils the fire condition requirements


of IEC 332-3

UC 400 24 4P is available as halogenfree UC 400 D 24 2 x 4P- FRNC-B/C version.

74
DATA CABLES

Data cable, category 6, UTP (4 x 2 x 0,56 / AWG 23)


UC 400 24 4P/UC 400 D 24 2 x 4P

CONSTRUCTION
Conductor Copper wire, d=0,56 mm Unit Twisted pair
Insulation PE Sheath Blue PVC

CABLE SIZES

Type UC 400 24 4P UC 400 D 24 2 x 4P


EAN code (SSTL code) 64 100+ 02 640 71 02 640 72
Nominal diameters mm 5,2 5,2/10,4
Mass kg/km 35 70
Delivery length m 500 500
ELECTRICAL PROPERTIES 20 °C
Loop resistance, max Ω/km 176
Insulation resistance, min GΩ x km 2
Nominal mutual capacitance nF/km 48
Maximum capacitance
unbalance, pair to ground pF/km ≤1500
Nominal impedance Ω ƒ =1 - 100 MHz 100 ± 15
Velocity factor 0,78
Maximum voltage V 75

TRANSMISSION CHARACTERISTICS ACC. TO CATEGORY 6 (at 20 °C)


Frequency Attenuation NEXT PS-NEXT ACR PS-ACR ELFEXT PS-ELFEXT Return
loss
MHz (dB/100 m) (dB) (dB) (dB/100 m) (dB/100 m) (dB/100 m) (dB/100 m) (dB)
max. nom. min. nom. min. nom. min. nom. min. nom. min. nom. min. nom. min.
1 2,0 1,9 74 78 71 75 72,0 76,1 69,0 73,1 67 82 65 80 23
4 3,8 3,8 65 69 62 66 61,2 65,2 58,2 62,2 55 70 53 68 23
10 6,0 6,0 59 63 56 60 53,0 57,0 50,0 54,0 47 62 45 60 23
16 7,6 7,6 56 60 53 57 48,4 52,3 45,4 49,3 43 58 41 56 23
20 8,5 8,5 55 59 52 56 46,5 50,0 43,5 47,0 41 56 39 54 23
31,2 10,7 10,7 52 56 49 53 41,3 45,0 38,3 42,0 37 52 35 50 23
62,5 15,5 15,1 47 51 44 48 31,5 36,0 28,5 33,0 31 46 29 44 23
100 19,9 19,1 44 48 41 45 24,1 28,9 21,1 25,9 27 42 25 40 23
125 22,5 21,3 43 47 40 44 20,5 25,2 17,5 22,2 25 40 23 38 21
155,5 25,4 23,8 42 45 39 42 16,6 21,3 13,6 18,3 23 38 21 36 18,8
175 27,1 25,3 41 44 38 41 13,9 19,1 10,9 16,1 22 37 20 35 18,4
200 29,2 27,0 40 44 37 41 10,8 16,5 7,8 13,5 21 36 19 34 18,0
250 33,0 33,0 38 42 36 39 5,0 9,1 2,0 6,1 20 34 17 32 17,3
300 36,1 41 38 4,8 1,8 32 30
400 41,7 39 36 -2,7 -5,7 30 28

The right to alterations reserved.

75
DATA CABLES

Data cable, category 7, STP


UC 600 SS 23/1 4P FRNC and
UC 1200 SS 22 4P FRNC

APPLICATIONS STANDARDS
— Fixed indoor — Ethernet 100 Mbit/s EIA/TIA 568A; TSB 36
installations — Gigabit-Ethernet ISO/IEC 11801 2nd ed.; JTC1 SC25 WG3 N552
— FDDI — Telephone networks EN 50173; prEN 50288-4-1
— TP-PMD — ISDN
— ATM — Generic cabling system
IDENTIFICATION
Maximum ambient temperature:
- in operation +70 °C
Pair Colour code Pair Colour code
Lowest recommended installation 1 white/blue 3 white/green
temperature: –5 °C
2 white/orange 4 white/brown
Minimum recommended bending radius:
- during installation 10xD
- during operation 5xD

Maximum permissible tensile stress


N N
during installation
UC 600 340 N The cable fulfils the fire condition requirements of
UC 1000 370 N IEC 332-3.

Halogenfree cables have better fire resistant properties.

CONSTRUCTION
UC 600 SS 23/1 4P FRNC-B UC 1200 SS 22 4P FRNC-B

Conductor Stranded tinned copper, d = 0,56 mm Conductor Stranded tinned copper, d = 0,64 mm
Insulation PE Insulation PE
Unit Twisted pair with aluminium tape Unit Twisted pair with aluminium tape
Earth Tinned copper conductor Earth Tinned copper conductor
Shield Copper wire braid as a common shield Shield Copper wire braid as a common shield
Sheath Orange, halogen-free material Sheath UC 1000 Yellow, halogen-free material

Structure PVC-sheath also. The right to alterations reserved.

76
DATA CABLES

Data cable, category 7, STP


UC 600 SS 23/1 4P FRNC and
UC 1200 SS 22 4P FRNC

CABLE SIZES
Type UC 600 SS 23/1 4P UC 1200 SS 22 4P
EAN code (SSTL code) 64 100+ 02 640 56 02 640 91
Nominal diameters mm 7,5 8,9
Mass kg/km 75 90
Delivery length m 500 500
ELECTRICAL PROPERTIES 20 °C
Loop resistance, max Ω/km 165 130
Insulation resistance, min GΩ x km 2 2
Nominal mutual capacitance nF/km 43 43
Maximum capacitance
unbalance, pair to ground pF/km ≤1200 ≤1200
Nominal impedance Ω ƒ =1 - 100 MHz 100 ± 15 ƒ =1 - 100 MHz 100 ± 15
Transfer impedance, max mΩ/m 100 100
Velocity factor 0,78 0,80
Maximum voltage V 75 75
UC 600 SS 23/1 4P FRNC: TRANSMISSION CHARACTERUSTICS ACC. TO CATEGORY 7 (at 20 °C)
Frequency Attenuation NEXT PS-NEXT ACR PS-ACR ELFEXT PS-ELFEXT Return
loss
MHz (dB/100 m) (dB) (dB) (dB/100 m) (dB/100 m) (dB/100 m) (dB/100 m) (dB)
max. nom. min. nom. min. nom. min. nom. min. nom. min. nom. min. nom. min.
1 2 2 80 90 80 87 78,0 88,0 78,0 85,0 70 80 67 77 23
4 3,7 3,7 80 90 80 87 76,3 86,3 76,3 83,3 58 80 55 77 23
10 5,9 5,9 80 90 80 87 74,1 84,1 74,1 81,1 50 80 47 77 23
16 7,4 7,4 80 90 80 87 72,6 82,6 72,6 79,6 46 76 43 73 23
20 8,3 8,3 80 90 80 87 71,7 81,7 71,7 78,7 44 74 41 71 23
31,2 10,4 10,4 80 90 75 87 69,6 79,6 64,6 76,6 40 70 37 67 23
62,5 14,9 14,9 75 90 71 87 60,1 74,8 56,1 71,8 34 64 31 61 23
100 19,0 19,0 72 87 68 84 53,0 67,7 49,0 64,7 30 60 27 57 23
125 21,4 21,3 71 85 66 82 49,6 63,9 44,6 60,9 28 58 25 55 21
155,5 24,0 23,8 70 84 65 81 46,0 60,0 41,0 57,0 26 56 23 53 21
175 25,6 25,3 69 83 64 80 43,4 57,8 38,4 54,8 25 55 22 52 21
200 27,5 27,0 68 82 63 79 40,5 55,2 35,5 52,2 24 54 21 51 21
250 31,0 30,1 66 81 62 78 35,0 50,6 31,0 47,6 22 52 19 49 19
300 34,2 33,0 65 80 60 77 30,8 46,5 25,8 43,5 20 50 17 47 19
450 42,7 42,6 63 77 58 74 20,3 34,3 15,3 31,3 17 47 14 44 19
600 50,1 49,2 61 75 56 72 10,9 25,8 5,9 22,8 14 44 11 41 19
750 55,5 73 70 17,5 14,5 42 39
UC 1200 SS 22 4P FRNC: TRANSMISSION CHARACTERUSTICS ACC. TO CATEGORY 7 (at 20 °C)
Frequency Attenuation NEXT PS-NEXT ACR PS-ACR ELFEXT PS-ELFEXT Return
loss
MHz (dB/100 m) (dB) (dB) (dB/100 m) (dB/100 m) (dB/100 m) (dB/100 m) (dB)
max. nom. min. nom. min. nom. min. nom. min. nom. min. nom. min. nom. min.
1 2 1,7 80 100 77 97 78,0 98,3 75,0 95,3 70 98 67 95 23
4 3,7 3,1 80 100 77 97 76,3 96,9 73,3 93,9 58 97 55 94 23
10 5,9 5,2 80 100 77 97 74,1 94,8 71,1 91,8 50 95 47 92 23
16 7,4 6,5 80 100 77 97 72,6 93,5 69,6 90,5 46 94 43 91 23
20 8,3 7,0 80 100 77 97 71,7 93,0 68,7 90,0 44 93 41 90 23
31,2 10,4 9,0 80 100 77 97 69,6 91,0 66,6 88,0 40 91 37 88 23
62,5 14,9 13,0 75 100 72 97 60,1 87,0 57,1 84,0 34 87 31 84 23
100 19,0 16,5 72 100 69 97 53,0 83,5 50,0 80,5 30 84 27 81 23
125 21,4 19,0 71 99 68 96 49,6 79,5 46,6 76,5 28 81 25 78 21
155,5 24,0 21,5 70 97 67 94 46,0 75,6 43,0 72,6 26 79 23 76 21
175 25,6 22,5 69 96 66 93 43,4 73,9 40,4 70,9 25 78 22 75 21
200 27,5 24,1 68 95 65 92 40,5 71,4 37,5 68,4 24 76 21 73 21
250 31,0 26,9 66 94 63 91 35,0 67,1 32,0 64,1 22 73 19 70 19
300 34,2 28,5 65 93 62 90 30,8 64,3 27,8 61,3 20 72 17 69 19
450 42,7 34,9 63 90 60 87 20,3 55,3 17,3 52,3 17 65 14 62 19
600 50,1 43,5 61 88 58 85 10,9 44,8 7,9 41,8 14 57 11 54 19
1200 58,0 85 82 27,0 24,0 42 39

77
DATA CABLES

Category 5 outdoor cable, UTP/armoured UTP


SuperCAT

APPLICATIONS STANDARDS
Aerial, duct or direct buried installations EIA/TIA 568A
ISO/IEC 11801 2nd edition; JTC1 SC25 WG3 N552
— Fixed outdoor — Ethernet 1000 Mbit/s, 100 Mbit/s EN 50173
installations — Telephone networks
— CDDI — ISDN
— TP-PMD — Generic cabling system
— ATM IDENTIFICATION

Maximum ambient temperature:


- in operation +75 °C Pair Colour code Pair Colour code
1 white/blue 3 white/green
Lowest recommended installation
temperature: –70 °C 2 white/orange 4 white/brown

Minimum recommended bending radius:


- without load ≥ 35 mm
- with load ≥ 70 mm

The right to alterations reserved.

78
DATA CABLES

Category 5 outdoor cable, UTP/armoured UTP


SuperCAT

CONSTRUCTION
Conductor Bare copper wire, d = 0,50 mm Filling Specially jelly
Insulation PE compound
Twisting 2 cores to the pair Sheath Black PVC
Cable lay up 4 pairs to the core Fylly flooded - waterproof
Tough UV and abrasion resistant jacket

Armoured UTP:
Optional aluminium or steel shielding system

CABLE SIZES

Type Supercat 5 UTP Supercat 5 armoured UTP


EAN code (SSTL code) 64 100+ 02 601 00 02 601 01
Nominal diameters mm 5,8 8,6
Mass kg/km 50 130
Delivery length m 305 305
ELECTRICAL PROPERTIES 20 °C
Loop resistance, max Ω/km ≤188
Resistance, min Ω x 100 m ≤9,38
Resistance unbalance % ≤3
Capacitance at 800 Hz pF/m 55,8
Insulation resistance
(500 V) MΩ x km ≥ 2000
Max propagation delay skew ns/100 m ≤ 45
Velocity of propagation % 69

TRANSMISSION CHARACTERUSTICS ACC. TO CATEGORY 5e (at 20 °C)


Frequency Attenuation NEXT PS-NEXT ACR PS-ACR ELFEXT PS-ELFEXT Return
loss
MHz (dB/100 m) (dB) (dB) (dB/100 m) (dB/100 m) (dB/100 m) (dB/100 m) (dB)
max. nom. min. nom. min. nom. min. nom. min. nom. min. nom. min. nom. min.
1 2,0 1,9 85,0 65,0 79 62 83,1 63,3 77,1 60,3 84,9 63,8 78,8 60,8 20,0
4 4,1 3,9 79,2 56,3 73 53,3 75,3 52,2 69,2 49,2 74,3 51,7 67,8 48,7 23
10 6,5 6,2 59 63 62,7 47,3 62,2 43,8 56,5 40,8 66,5 43,8 60,0 40,8 25,5
16 8,2 7,9 56 60 61,1 44,3 58,6 39,1 53,2 39,1 62,5 39,7 55,8 36,7 25,0
20 9,3 9,0 55 59 61,1 42,8 58,3 36,5 52,0 33,5 61,6 37,7 53,7 34,7 25,0
31,2 11,7 11,3 52 56 53,2 39,9 50,4 30,2 41,8 28,2 57,0 33,8 49,7 30,8 23,6
62,5 17,0 16,4 47 51 52,6 35,4 42,4 21,4 36,2 18,4 50,6 27,8 43,6 24,8 21,5
100 22,0 21,2 44 48 44,8 32,3 30,5 13,3 23,6 10,3 44,9 23,8 39,1 20,8 20,1

The right to alterations reserved.

79
Fibre optic cables in premises
data networks

80
GENERAL

TYPE CODING OF OPTICAL FIBRE


CABLES
An example of the cable designation Characteristics of the fibres

FYOVD2PMU 4 x 6 x SML 04S03T The attenuation of the fibre is given in tenths of decibels
per kilometre with two numbers followed by the letter
indicating the corresponding wavelength:
F =850 nm, S =1300 nm, T = 550 nm
Cable construction
Number and grouping of the fibres Example: 04S03T
Type of the fibre and the coating (0.4 dB/km at 1300 nm: 0.3 dB/km at 1550 nm)
Characteristics of the fibres
For multimode fibres also the bandwidth is given in
Cable construction hundreds of MHz km with two figures following the
First letter: attenuation value.
F = optical fibre cable
Example: 1008S (1.0 dB/km, 800 Mhz km at 300 nm)
Second letter:
Y = single loose tube construction (SPIRAL SPACE®)
Z = stranded loose tube construction
T = stranded tight buffer construction
COLOUR CODING SYSTEM OF
X = slotted core construction OPTICAL FIBRE CABLES
A colour coding system is used for identification of optical
Next letters:
fibres, fibre groups and tubes. A fibre group has normally
B = laminated O = filling compound
not more than 6 fibres, which are coloured as follows:
C = copper P = round steel wire
D = corrugated R = nonmetallic
— blue (always the first one)
H = metal (aluminium) strength member
— white
tape V = steel tape
— yellow
J = jute S = indoor installation
— green
K = messenger U = outdoor installation
— grey
wire
— red (always the last one)
L = lead
M = plastic W = submarine
The same colour coding system is adapted to the binders
over the fibre bundles.
-Y = combination cable (the last letter)

Example: FYOVD2PMU (optical fibre cable, OPTICAL FIBRE TYPES


SPIRAL SPACE® design, jelly filled, corrugated steel tape,
plastic sheath with two steel wires, for outdoor installation)

Number and grouping of the fibres


The numbers following the letter code indicate the number
of the fibre groups (i.e. tubes or bundles) and the number
of the fibres in each group.

Example: 4x6 (four groups of six fibres)


Core Cladding Primary coating
Type of the fibre and its coating
The first two letters of the code indicate the type of the The construction and the operation principle of a single-mode
fibre: fibre
SM = Single-mode fibre (10/125 µm) ITU-T G.652
GI = Multimode fibre (50/125 µm) ITU-T G.651
GK = Multimode fibre (62.5/125 µm)
GL = Multimode fibre (85/125 µm)
GN = Multimode fibre (100/140 µm)

The third letter indicates the outer diameter or the type of


the coating
L = 250 µm T = 900 µm
W = 500 µm R = Ribbon Core Cladding Primary coating

Example: MSL The construction and the operation principle of a multimode


(Single-mode fibre ITU-T G.652 with 250 µm coating) fibre

81
CONTENTS

DIFFERENT CONSTRUCTIONS OF OPTICAL FIBRE CABLES

Single loose-tube Stranded loose-tube Slotted core


FY... FZ... FX...
SPIRAL SPACE

OPTICAL FIBRE CABLES OF NK CABLES FOR DIFFERENT APPLICATIONS

SPIRAL SPACE® SPIRAL SPACE®

Duct and buried cables Indoor cables


FYOVD2PMU steel tape armoured Spiral Space FMS non-metallic jumper cables
FYO2RMU non-metallic Spiral Space cable FMMS non-metallic breakout cable
FZOMU non-metallic stranded loose tube cable FYMSU non-metallic Spiral Space cable

SPIRAL SPACE®

Indoor installation cable FLMS

Buried and duct cable FYOHB2PMU

Indoor cable FMMS

SPIRAL SPACE®

Buried and duct cable FZOMVDMU Non-metallic buried and duct cable
FYO2RMU

82
CONTENTS

FYMSU-TERM DISTRIBUTION PANELS AND


CABINETS

ORP-250

PK-100A and PK-200


CONNECTORISED RISER CABLES

FYMSU-PACK 100

PK 300

Pigtails

83
DATA CABLES

Data and instrumentation cable


DATAJAMAK

APPLICATIONS STANDARDS
— Fixed indoor — Token Ring 4/16 Mbit/s ISO 8802.3/IEEE 802.3 10 base T
installations — Telephone networks
— Ethernet 10 Mbit/s — RS 232/422/423
IDENTIFICATION
Maximum ambient temperature:
- in operation +70 °C a-conductor is white and b-conductor is orange

Lowest recommended installation The cable fufils the fire condition requirements of
temperature: –5 °C IEC 332-1.

Minimum recommended bending radius:


- during installation 10xD
- during operation 15xD

DATAJAMAK is available as halogenfree, DATAJAMAK-HF version.

84
DATA CABLES

Data and instrumentation cable


DATAJAMAK

CONSTRUCTION
Conductor Stranded tinned copper Shield Plastic-aluminium tape with earth
Insulation PE conductor
Unit Twisted and individually shielded pair Sheath Grey LINYL-PVC
with plastic-aluminium tape, earth
conductor and a number tape

CABLE SIZES
Number and size of
the conductors mm2 2 x (2+1) x 0,24 4 x (2+1) x 0,24 8 x (2+1) x 0,24
EAN code (STTL code) 64 100+ 02 642 53-7 02 642 55-1 02 642 60-5
Nominal diametersr mm 7,5 9,0 12
Mass kg/km 50 75 140
Delivery length m 1000 1000 1000
ELECTRICAL PROPERTIES 20 °C
Loop resistance, max Ω/km 165
Nominal mutual capacitance pF/m 52
Capacitance earth unbalance 1500
pair to ground 1 Khz, max pF/km
Nominal impedance Ω 100±15
Insulatio resistance, min GΩ x km 2
Velocity factor 0,7
Maximum voltage V 75
Max attenuation dB/100 m
Frequency 9,6 kHz 0,3
frequency 9,2 kHz 0,5
frequency 64 kHz 0,7
frequency 100 kHz 0,9
frequency 200 kHz 1,5
frequency 1,0 MHz 3,3
frequency 4,0 MHz 6,6
frequency 10 MHz 9,5
frequency 16 Mhz 11,5

NEXT min dB
Frequency 9,6 kHz 90
frequency 9,2 kHz 90
frequency 64 kHz 85
frequency 100 kHz 85
frequency 200 kHz 80
frequency 1,0 MHz 80
frequency 4,0 MHz 70
frequency 10 MHz 70
frequency 16 Mhz 70

DATAJAMAK is available as halogenfree, DATAJAMAK-HF version. The right to alterations reserved.

85
DATA CABLES

Installation cables for exchanges with screened pairs


KLVMAAM, KLVMAM

APPLICATIONS IDENTIFICATION
Wiring of digital exchanges and PCM equipment. a-conductor is white and b-conductor is blue
Screened groups numbered

CONSTRUCTION
KLVMAAM KLVMAM

Conductor Annealed, tinned copper wire Conductor Annealed, tinned copper wire
Insulation Cellular PE Insulation Cellular PE
Group Two insulated conductors in a pair Group Two insulated conductors in a pair
Group screen Plastic aluminium foil and ground wire Screen Plastic aluminium foil and ground wire
Collective Two layers of plastic aluminium foil and Sheath Black Linyl
screen ground wire
Sheath Grey Linyl

CABLE SIZES

KLVMAAM KLVMAM
Number and size of
the conductors mm2 2 x (2+1) x 0,4 8 x (2+1) x 0,4 16 x (2+1) x 0,4 24 x (2+1) x 0,4 2 x 0,4 x 0,4
EAN code (STTL code) 64 100+ 02 021 52-3 02 021 58-5 02 021 61-5 02 021 64-6 02 021 02-8
Nominal seath thickness mm 0,6 0,6 1,2 1,2 0,6
Nominal outer diameter mm 4 x 6,5 9,0 12,5 15,0 3,5
Nominal cable mass kg/km 30 75 160 220 14
Standard delivery length m 1000/200 1000/100 500/100 500 1000
ELECTRICAL PROPERTIES 20 °C
Characteristic impedance 1 MHz Ω 120
Nominal mutual capacitance
800 MHz nF/km 47
Minimum insulation resistance
500 V, 1 min GΩ x km 2
Attenuation
1 MHz dB/100 m 3,7
Minimum near-end crosstalk
attenuation 1 MHz dB/100 m 80

The right to alterations reserved.

86
DATA CABLES

Indoor cable for community antenna system


TELLU™ 13

APPLICATIONS Minimum recommended single bending


radius 15 mm
Indoor cable for CATV systems
Maximum permissible tensile stress
Lowest recommended installation N
N during installation 120 N
temperature: –5 °C
SFS 5711

CONSTRUCTION
Inner conductor Annealed copper wire Outer conductor Copper tape covered with
Insulation Foamed PE a copper braid
Sheath White Linyl

CABLE SIZES
Number and size of
the conductors mm2 TELLU 13 WHITE drum TELLU 13 WHITE coil
EAN code (STTL code) 64 100+ 02 821 86-4 02 321 86-9
Nominal diameter of
the inner conductor mm 1,0 1,0
Nominal diameter of
the insulated conductor mm 4,8 4,8
Nominal outer diameter mm 7,0 7,0
Mass kg/km 56 56
Delivery length m 1000 200
ELECTRICAL PROPERTIES 20 °C
Nominal loop DC-resistance Ω/km 34
Nominal capacitance pF/m 56
Characteristic impedance Ω 75 ±2
Velocity factor 80
Structural return loss, min. dB
30 - 470 MHz 18 FORMULA FOR THE
470 - 860 Mhz 16
860 - 1750 MHz 14 ATTENUATION COEFFICIENT OF
TELLU INDOOR CABLE f ≥10 MHz
Screening attenuation, min. dB 80
Max attenuation dB/100 m α = A1 f f + A2f, where
frequency 68 MHz 5,1 α = attenuation coefficient, dB/100 m
frequency 108 MHz 6,5
frequency 174 MHz 8,4 f = frequency, MHz
frequency 230 MHz 9,7
frequency 300 MHz 11,3 A1 and A2 are constants
frequency 400 MHz 13,2
frequency 470 MHz 14,5
frequency 606 MHz 16,7
frequency 790 MHz 19,5
frequency 860 MHz 20,5
frequency 1750 MHz 31,2
frequency 2050 MHz 34,4

87
DATA CABLES

Military cable
RG 58, (50 Ω), RG 59, (75 Ω)

APPLICATIONS
N
N
Maximum permissible tensile stress
during installation RG 58: 120 N
RG 59: 145 N
Indoor cable for CATV systems

Lowest recommended installation


temperature: -5 °C

CONSTRUCTION
Inner conductor Copper braid
RG 58r Stranded copper wire, tin plated RG 58r Tin plated
RG 59 Copperclad steel wire RG 59 Bare
Insulation PE Sheath Black PVC

CABLE SIZES
Type RG 58 C/U RG 59 B/U
Nominal diameter of
the inner conductor mm 0,9 0,59
Nominal outer diameter mm 5,0 6,2
Mass kg/km 40 57
Delivery length m 1000 1000
ELECTRICAL PROPERTIES 20 °C
Nominal loop DC-resistance Ω/km 50 165
Mutual capacitance pF/m 100 67
Characteristic impedance Ω 50 ±2 75 ±3
Velocity ratio % 66 66
Max attenuation dB/100 m
frequency 5 MHz 3,0 2,5
frequency 10 MHz 4,2 3,5
frequency 200 MHz 23 16
frequency 400 MHz 34,5 24
frequency 1000 MHz 60 38
Transfer impedance at 3 MHz
specified value mΩ/m 50
measurement value mΩ/m 36 36
operating voltage kVeff 1,8 2,0

88
DATA CABLES

Military cable
RG 213, RG 214, RG 223, (50 Ω)

APPLICATIONS
N N
Maximum permissible tensile stress
during installation RG 213 470 N
RG 214 730 N
Indoor cable for CATV systems
RG 223 220 N
Lowest recommended installation
temperature: -5 °C

CONSTRUCTION
Inner conductor RG 213 bare
RG 213 Stranded copper wire, RG 214, RG 223
bare 7x0,75 1st braid Silver plated
RG 214 Stranded copper wire, 2nd braid Silver plated
silver plated 7x0,75 Sheath PVC
RG 223 Copper wire, silver plated
Insulation PE

CABLE SIZES
Type RG 213 RG 214 RG 223
Nominal diameter of
the inner conductor mm 2,25 2,25 0,9
Nominal outer diameter mm 10,3 10,8 5,5
Mass kg/km 157 226 60
Delivery length m 1000 1000 1000
ELECTRICAL PROPERTIES 20 °C
DC-resistance Ω/km
inner conductor 5,7 5,7 29,1
1st braid 3,9 9,4 13,5
2nd braid 8,2 15,5
Mutual capacitance pF/m 100 100 100
Characteristic impedance Ω 50 ±2 50 ±2 50 ±2
Velocity ratio % 0,66 0,66 0,66
Max attenuation dB/100 m
frequency 60 MHz 5 6,0 18,2
frequency 80 MHz 6 7,5 15,5
frequency 200 MHz 10 11 21
frequency 400 MHz 15 17 31
frequency 1000 MHz
Transfer impedance at 3 MHz
operating voltage kVeff 4,5 4,5 1,9
test voltage kVeff 10,0 10,0 4,1

89
CABLE DRUMS

MAXIMUM LENGTH OF CABLE


PER DRUM, IN METERS
Type of drum
Diameter of cable
5C 6C 7E 8E 9F 11G 13G 15G 16L 18M 20P 22P
3 4500 7850
4 2460 4410 7250 9790
5 1570 2790 4710 6220 9000
6 1120 1950 3210 4400 6130
7 780 1410 2360 3190 4560
8 580 1080 1800 2370 3480 5720 7950
9 480 840 1460 1950 2770 4420 6280
10 390 660 1170 1490 2170 3720 5090 6930 9360
11 320 570 930 1300 1790 2960 4210 5520 7820 8260
12 260 480 800 1050 1470 2500 3530 4785 6490 7020
13 200 410 680 910 1290 2200 3020 3950 5610 5950
14 190 350 580 790 1130 1800 2590 3465 4830 5030 8420
15 150 290 500 680 990 1620 2260 3040 4150 4480 7310 8900
16 140 240 420 590 870 1410 1990 2565 3750 4000 6320 7780
17 110 230 400 500 750 1250 1750 2310 3190 3300 5740 6770
18 100 190 340 480 650 1100 1570 2070 2870 2960 4930 6170
19 100 180 320 410 560 960 1410 1840 2590 2830 4460 5630
20 150 270 340 540 930 1270 1685 2330 2510 4040 4860
21 140 260 330 460 800 1150 1480 2080 2220 3650 4410
22 140 210 320 440 710 1050 1420 1860 1960 3290 4010
23 200 210 270 370 680 960 1290 1800 1890 2960 3630
24 160 260 360 590 880 1155 1610 1670 2870 3520
25 160 210 350 570 810 1110 1430 1600 2580 3190
26 150 210 290 540 750 990 1390 1400 2310 2880
27 150 200 290 470 690 940 1230 1360 2240 2600
28 110 160 230 450 650 830 1200 1180 2000 2520
29 110 160 230 430 600 790 1050 1140 1950 2260
30 110 150 220 380 560 725 1030 1110 1730 2210
31 110 150 220 360 530 690 890 950 1690 1970
32 100 150 170 345 500 630 870 930 1490 1930
33 110 170 300 470 595 860 900 1450 1720
34 110 170 315 440 560 740 770 1420 1680
35 110 160 305 410 555 720 750 1250 1640
36 100 160 280 390 480 710 730 1220 1450
37 100 120 270 370 470 610 720 1190 1420
38 120 240 350 445 610 600 1040 1390
39 120 230 330 420 580 580 1020 1220
40 120 225 320 410 570 570 1000 1200
41 110 210 300 405 560 560 980 1180
42 110 200 280 385 480 550 840 1030
43 195 270 370 470 450 830 1010
44 175 260 355 460 440 810 990
45 170 250 320 450 430 800 970
46 165 240 325 380 420 680 840
47 160 230 310 370 420 670 820
48 150 220 290 360 410 660 810
49 145 210 280 360 400 650 800
50 140 200 275 350 320 640 790
51 135 190 270 350 310 630 670
52 180 250 280 310 520 660
53 180 240 280 300 510 650
54 170 230 270 300 510 640
55 170 220 270 300 500 630
56 160 210 270 290 490 620
57 150 210 260 290 490 520
58 150 200 260 280 400 510
59 140 195 260 210 390 510
60 140 190 200 210 390 500

90
CABLE DRUMS

DIMENSIONS AND WEIGHTS

E C A

EAN code Drum dimensions, mm Drum weight


Type of (STTL-code)
drum 64 100 + A B C D E kg
5C 99 994 05-2 500 500 250 400 55 10
6A 99 994 06-9 600 500 250 400 55 16
7E 99 994 07-6 700 610 325 500 55 20
8E 99 994 08-3 800 610 375 500 55 26
9F 99 994 09-0 900 660 425 550 82 40
11G 99 994 59-5 1100 725 500 600 82 70
13G 99 994 63-2 1300 760 600 600 82 105
15G 99 994 65-6 1500 760 700 600 82 150
16L 99 994 16-8 1600 970 800 800 82 185
18M 99 994 18-2 1800 1025 1100 850 82 260
20P 99 994 21-2 2000 1155 1100 960 82 350
22P 99 994 22-9 2200 1155 1200 960 82 445
K6 600 468 250 400 75 12
K7 700 580 325 500 75 20
K8 800 580 375 500 75 25
K9 900 630 425 550 75 34
K11 1100 762 575 650 106 55
K12 1200 982 675 850 106 90
K14 1400 982 800 850 106 115
K16 1600 1018 950 850 106 195
K18 1800 1075 1100 850 106 230

91
Draka NK Cables Ltd • Kimmeltie 1, 02110 Espoo, P.O. BOX 419, FIN-00101 Helsinki, Finland
Tel. +358 10 5661 • Telefax +358 9 682 1007
www.drakankc.fi