LOAD SCHEDULE OF WATER FALL PUMP DISTRIBUTION BOARD LOAD SCHEDULE OF PACKAGE SUBSTATION @ ZONE N
CIRCUIT CONNECTED MCB CABLE CABLE VOLTAGE DROP % VOLTAGE CIRCUIT CONNECTED MAIN BREAKER CABLE CABLE % VOLTAGE
WARNING TAPE LOAD DESCRIPTION LOAD DESCRIPTION
NAME LOAD KW RATE SIZE LENGTH @ END OF CABLE DROP NAME LOAD KW RATING SIZE LENGTH DROP
GARDEN LIGHTING 150 AF 4c x 300mm² 1.1 % ELECTRICAL
WATER FALL PUMP P-1 4.56 KW 20 AT 4c x 10mm² 16 M. 0.46 V 0.12 % GLP - N2 29.75 KW 173 M.
A-A1 COMPACTED BY LAYERS PANEL AL
GARDEN LIGHTING GLP - N3 25.75 KW 100 AF 4c x 300mm² 1.8 % ZONE N-O2a AREA
WATER FALL PUMP P-2 12.35 KW 40 AT 4c x 25mm² 128 M. 4.17 V 1.09 % 365 M.
PANEL AL
FILL MATERIAL P - 2-3 8.36 KW 32 AT 4c x 10mm² 86 M. 4.6 V 1.21 % WATER FALL PUMP WF - DB 49.80 KW 125 AT 4c x 300mm² 140 M. 1.17 % WATERFALLS / WATER CHANNEL ELECTRICAL
WATER FALL PUMPS
DISTRIBUTION BOARD AL POWER SUPPLY LAYOUT
AS-BUILT
WATER FALL PUMP P - 3-4 4.56 KW 20 AT 4c x 10mm² 19 M. 0.55 V 0.14 % SPARE - 1 SP - 1 20 KW 100 AF -- -- --
20 CM THICK SAND WATER FALL PUMP P-5 4.56 KW 20 AT 4c x 16mm² 178 M. 3.27 V 0.86 %
WATER CIRCULATION TOTAL CONNECTED LOAD
P-6 26.8 KW 80 AT 4c x 50mm² 207 M. 8.29 V 2.18 % DEMAND FACTOR : 0.90 MAXIMUM DEMAND : 95 KW
DIRECT BURRIED CABLE PUMP = 105.30 KW
SPARE - 1 SP - 1 3.8 KW 20 AT -- -- -- --
10 CM THICK SAND BED
TOTAL CONNECTED LOAD
DEMAND FACTOR : 0.80 MAXIMUM DEMAND : 39.84 KW
= 49.80 KW
SUB MAIN CABLE TYPICAL SECTION DETAIL
NTS