T4 PV Connector
INSTALLATION MANUAL
INSTALLATION MANUAL TLIAN is a subsidiary of Canadian Solar
Component Assembly:
T4 Product Specifications:
T4 Type
Cable Outside Required Torque to Reference gap
E E
Article Picture
Diameter (OD) Lock
1 2 3 4 5 6 7 8
D D
F F
Negative
5.8mm≤OD≤6.9mm 3.0N·m~4N·m 0<gap≤1.0mm
Connector
E C E C
Positive
5.8mm≤OD≤6.9mm
D
B 3.0N·m~4N·m 0<gap≤1.0mm
D
B
Connector
MODEL NO. T O L E R A N C E S Ò » ° ã ¹« ²î D E S IG N d e s ig n _ b y d a te (3 )
m o d e l_ n u m 0 .0 0 ~ 3 0 .0 0 0 .2 0
DRAW N d ra w n _ b y d a te U N IT mm
3 0 .0 1 ~ 5 0 .0 0 0 .2 5
Negative
PART NAME
5 0 .0 1 ~ 1 0 0 .0 0 0 .3 5
C p a r t_ n a m e 1 0 0 .0 1 ~ 1 5 0 .0 0 0 .4 0 CHECKED checked_by d a te S C A L E d ra w in g _ s c Ca le
—— —— ——
D R A W IN G N O . 1 5 0 .0 1 ~ 1 8 0 .0 0 0 .4 5
A 1 8 0 .0 1 ~ 2 1 0 .0 0 0 .5 0 APPROVED a p p ro v e d _ b y d a te PAGE 1/1 A
T L -T 4 -F J 1 -1 0 1 -T U V 1
Contact
2 1 0 .0 1 ~ 2 5 0 .0 0 0 .5 5
1 A S IS S U E D ½ Ç ¶ È ¹« ²î 2
MODEL NO. T O L E R A N C E S Ò » °ã ¹« ²î D E S IG N d e s ig n _ b y d a te (3 )
m o d e l_ n u m 0 .0 0 ~ 3 0 .0 0 0 .2 0
DRAW N d ra w n _ b y d a te U N IT mm
3 0 .0 1 ~ 5 0 .0 0 0 .2 5
PART NAME
5 0 .0 1 ~ 1 0 0 .0 0 0 .3 5
p a r t_ n a m e 1 0 0 .0 1 ~ 1 5 0 .0 0 0 .4 0 CHECKED checked_by d a te S C A L E d r a w in g _ s c a le
D R A W IN G N O . 1 5 0 .0 1 ~ 1 8 0 .0 0 0 .4 5
A 1 8 0 .0 1 ~ 2 1 0 .0 0 0 .5 0 APPROVED a p p ro v e d _ b y d a te PAGE 1 /1 A
1
T L -T 4 -Z J 1 -1 0 1 -T U V 1 2 1 0 .0 1 ~ 2 5 0 .0 0 0 .5 5
A S IS S U E D ½ Ç ¶ È ¹« ²î 2
Safety Precautions:
Products must be assembled and installed by qualified personal, insuring all safety regulations
are followed. For protection against electric shock, please insure the system is not energized
during installation. Do not disconnect under load. Insure that the AC and the DC sides are both
Use only the tools and components listed in this installation man_ual. Follow the directions as
stated in this manual. Do not alter or willingly damage the product in any way.
Sealing cap must be used on disconnected connectors to prevent dust and water ingress.
Do not allow direct contact with hydrocarbon, phenol, ketone ammonia or other plastic
installation.
Disconnect Tools
1 set=2 pieces
3. Connection
To connect, attach the positive and negative
connectors to each other, until you hear a “click.”
Once connected, gently pull on them to insure a
secure connection.
4. Check connection
To check the connection, insure that you cannot
see the seal ring. The gap between the connectors
should be less than 0.5mm.
9. Make connection
INSTALLATION MANUAL TLIAN is a subsidiary of Canadian Solar
10. Disconnect
The attachment can only be disconnected by
using the disconnect tools.
INSTALLATION MANUAL TLIAN is a subsidiary of Canadian Solar
The technical descriptions herein are for reference only when using this product.