Professional Documents
Culture Documents
Project :- 2 X 600 Sree Singaji TPP, Stage-1, Khandwa, M.P. Prepared by KAR Note No. 278-E-Dn-02
Title:-Analysis & Design of Raker Column, Pedestal Checked by UKR Revision R1
& Foundation of NDCT-II Date 22-Jul-10 Page No.
Page 122
SPECTRUM TECHNO-CONSULTANT PVT. LTD.
Project :- 2 X 600 Sree Singaji TPP, Stage-1, Khandwa, M.P. Prepared by KAR Note No. 278-E-Dn-02
Title:-Analysis & Design of Raker Column, Pedestal Checked by UKR Revision R1
& Foundation of NDCT-II Date 22-Jul-10 Page No.
Page 123
SPECTRUM TECHNO-CONSULTANT PVT. LTD.
Project :- 2 X 600 Sree Singaji TPP, Stage-1, Khandwa, M.P. Prepared by KAR Note No. 278-E-Dn-02
Title:-Analysis & Design of Raker Column, Pedestal Checked by UKR Revision R1
& Foundation of NDCT-II Date 22-Jul-10 Page No.
Page 124
SPECTRUM TECHNO-CONSULTANT PVT. LTD.
Project :- 2 X 600 Sree Singaji TPP, Stage-1, Khandwa, M.P. Prepared by KAR Note No. 278-E-Dn-02
Title:-Analysis & Design of Raker Column, Pedestal Checked by UKR Revision R1
& Foundation of NDCT-II Date 22-Jul-10 Page No.
Sample Calculation for Wind Load Calculation at height 16.941 m by Peak wind load
p1 = ∑ Fn cos nθ
p1 = 1.33297
p = 1.43 x p1 = 1.90615
Vz = k1 x k2 x k3 x Vb
= 40.53 m/s
Pz = p x 0.6 x Vb2
2
=1878.97 N/m
2
= 1.8790 kN/m
Page 125
SPECTRUM TECHNO-CONSULTANT PVT. LTD.
Project :- 2 X 600 Sree Singaji TPP, Stage-1, Khandwa, M.P. Prepared by KAR Note No. 278-E-Dn-02
Title:-Analysis & Design of Raker Column, Pedestal Checked by UKR Revision R1
& Foundation of NDCT-II Date 22-Jul-10 Page No.
Vcr = f1 x d
Sn
The calculated critical wind speed calculated is more than expected wind speed at
the site, hence the calculations for across wind loads need not be performed.
Page 126
SPECTRUM TECHNO-CONSULTANT PVT. LTD.
Project :- 2 X 600 Sree Singaji TPP, Stage-1, Khandwa, M.P. Prepared by KAR Note No. 278-E-Dn-02
Title:-Analysis & Design of Raker Column, Pedestal Checked by UKR Revision R1
& Foundation of NDCT-II Date 22-Jul-10 Page No.
Grade of Concrete M 40
2
Elastic Modulus of Concrete = Ec = 31622777 kN/m
Thickness of Shell = d = 0.25 m
Diameter of Shell at throat = 72.6 m
Radius of Shell at throat = rth = 36.3 m
2
qcr = 19.97603 kN/m
Vb = 39 m/s K1 = 1.06 K3 = 1
Gust Factor G = 1.622 Pressure increment Factor = 1.43
K2 at throat level as per table 2 of IS: 875 Part 3 = 1.196
2
Peak Wind Load Pressure = 2.097445 kN/m
2
Gust Wind Load Pressure = 2.128 kN/m
Required factor of Safety = 5
Factor of Safety = 9.386207 SAFE
Page 127
SPECTRUM TECHNO-CONSULTANT PVT. LTD.
Project :- 2 X 600 Sree Singaji TPP, Stage-1, Khandwa, M.P. Prepared by KAR Note No. 278-E-Dn-02
Title:-Analysis & Design of Raker Column, Pedestal Checked by UKR Revision R1
& Foundation of NDCT-II Date 22-Jul-10 Page No.
6.1 Calculation for Snap through Buckling according to BS 4485: Part 4 : 1996
Grade of Concrete M 40
Elastic Modulus of Concrete = Ec = 28 KN/mm2 (as defined in 7.2 of 8110: Part 2)
Thickness of Shell = d = 0.25 m
Diameter of Shell at throat = 72.6 m
Radius of Shell at throat = rth = 36.3 m
Vs = 39 m/s Sc = 1.545 Sh = 0
Smz = 1.545 Pressure increment Factor = 1
Page 128