GPR 330 - 50 Hz

Output Ratings Ratings and Performance Data


Voltage, Frequency Prime Standby Engine Make & Model: Perkins / 1506A-E88TAG5
400 Volt, 50 Hz 300 kVA / 240 kW 330 kVA / 264 kW Alternator Make & Model: Stamford / S4L1D-D41
Standard Reference Conditions: Genpower / GNP 315S W12/4
The output power ratings that are given above are achieved at Control Panel Make & Model: ComAp / AMF25
standard reference conditions.
-Air Inlet Temperature: 25°C
Base Frame Heavy Duty Fabricated Steel
-Altitude: 100 meters Engine Speed rpm 1500
-Relative Humidity: 30%
Frequency Hz 50
Genpower Generator Sets have the compliance against the reference
standards that are given below: Fuel Tank Capacity, w/o Canopy (Canopy) lt. 680 (468)
TS ISO 8528, ISO 8528, BS5000, ISO 3046, IEC 60034, NEMA MG-1.22. 50% 33,0
The options for voltage rates at 50 Hz and 60 Hz are given below. The
desired alternative output voltage rate could be achieved by using the Fuel Consumption 75% Lt/h 48,0
matching connection types for the desired voltage with the related 100% 65,0
alternator output connection terminals
For 50 Hz: General Features
200/115V - 220/110V - 220/127V - 230/115V - 380/220 V 400/230V - ● Tropical type radiator, fan, belt and enclosures.
415/240V
For 60 Hz. ● Vibration dampers.
208/120V - 220/127V - 240/139V - 380/220V - 440/254V-480/277V ● Open type gensets industrial type exhaust silencer.
Prime Power
It is the continuous operation mode of the generator under variable ● AMF control panel.
load where there is no main power. The average of the variable load ● Built-in type fuel tank chassis.
should not exceed %80 of the prime power rating of the generator.
The generator should be not operated more than maximum one hour
● Mechanical fuel level indicator
under %10 overload of the prime power rating in a 12-hours of ● Battery pack and cable set.
operation.
● The original engine oil, fuel, dry type air filter.
Standby:
It is the variable work load mode of the generator as a back-up power Options
supply to the main power. The stand-by power is the maximum
Contact your supplier for non-standard requests.
allowable power. The operation under overload is not permitted.
The maximum annual operation period is limited with 500 working ● The generator output breaker (MCCB)
hours ● External type transfer switch (ATS)
● Dual operating systems
● Low water level switch
Canopy ● Fuel tank heating and insulation systems
● Easy lifting and moving ● Single-and double-axle trailer
● Metal parts are coated with electrostatic polyester coated, ● Synchronous systems
powder painted ● Private quiet cabins (cabins SSC)
● 25-30 dbA series, Heat-insulated exhaust system. ● Private hospital type and juicy exhaust systems
● Acoustic insulation with rot*proof, moisture-repellent ● Mobile vehicle applications
and non-flammable material (per DIN 4102 A2) ● Arep or PMG alternator application
● Double swinging doors for ease of service
Engine Technical Data Fuel System
No. of Cylinders 6 Fuel Filter Type Replaceable Element
Alignment In Line Recommended Fuel Class A2 Diesel
Cycle 4 Stroke Fuel Consumption Lt/h
Induction Turbocharged AAC* Prime 110% 100% 75% 50%
Bore / Stroke 112 / 149 50 Hz 73,0 65,0 48,0 33,0
Compression Ratio 16.1:1
Displacement Lt 8,8
Cooling Method Water Standby 100% 75% 50%
Governing Type Electronic 50 Hz 73,0 55,0 37,0
Governing Class ISO 8528-G2
Moment of Inertia kg m² ( Ib/in²) 1,95 (6657) Note: Based on diesel fuel with a specific gravity of 0.85 and conforming to
Electrical System Voltage / Ground 24 V / Negative BS2869, Class A2
Charger Amps Amps. 45 Cooling System
* AAC : Air to air charge cooled Cooling System Capacity Lt. 35
Performance Water Pump Type Centrifugal
Engine Speed rpm 1500 Heat Rejected to Water & Lube Oil
Gross Engine Power kW (Hp) kW ( BTU/min)
Prime 267 (358) Prime 123 (6995)
Standby 293 (393) Standby 132 (7807)
BMEP kPA ( Psi) Heat Radiation to Room
Prime 2318 (336) kW ( BTU/min)
Standby 2540 (368) Prime 27,6 (1570)
Standby 29,8 (1695)
Air Systems Radiator Fan Load kW ( Hp) 10 (13,4)
Air Filter Type Replaceable Element Radiator Cooling Airflow m³/dak. (Cfm) 609 (21507)
Combustion Air Flow m³/min (cfm) External Restriction to Cooling Airflow Pa (inH2O)
125 (0,5)
50 Hz Note: Designed to operate in ambient conditions up to 50°C .
Prime 18,3 (648)
Standby 19,7 (696) Exhaust System
Max. Combustion Air Intake Restriction: kPa (in H2O) Silencer Type Industrial
4,0 (16) Pressure Drop Across Silencer system 5,0
Silencer Noise Reduction Level db/A 16
Lubrication System Maximum Allowable Back Pressure 10,0
Oil Filter Type Spin-On, Full Flow Exhaust Gas Flow m³/min (Cfm)
Total Oil Capacity: Lt. 41,0 Prime 44,1 (1558)
Oil Pan Lt. 39,0 Standby 48 (1685)
Oil Type API CI4 Exhaust Gas Temperature °C
Oil Cooler Ok. Prime 500
Oil Cooling Method Water Standby 540

Alternator Alternator
Make and Model Stamford / S4L1D-D41 Make and Model Genpower / GNP 315S W12/4
Cont. Power 400 V - 310 kVA Cont. Power 400 V - 325 kVA
Efficiency % 93,0 Efficiency % 93,0
AVR Model AS440 AVR Model SX440

Alternator General Information Alternator Performance Data


No. of Bearings Single bearing Overspeed rpm 2250
Insulation Class: H Short Circuit -
Winding Pitch Code: 2/3 Total Harmonic content No Load <%1,5
Wires 12 Wave Form NEMA = TIF 50%
Ingress Protection Rating IP-23 R.F.I Radio Interference VDE 875
Excitation System Self - Excited Shunt type Cooling Air m³/sec. 0,80
Voltage Regulation ±%1 Radiant Heat kW (BTU min) 18,5 (1052)
Reaktans Xd 2,85
Standards:
BS EN 60034, BS5000, VDE 0530, NEMA MG1-32, IEC34, CSA X'd 0,18
X"d 0,130
Motor Starting Capability kVA* 520
* Based on 30% voltage dip at 0 power factor.
Control Panel
Automatic Type Control Panel, Standard Equipment Manual Type Control Panel, Standard Equipment
● ComAp AMF 25 control panel
● Control relay
● System protection insurance
● Emergency stop button
● Suitable for the power generator output breaker (TMS), optional
● ComAp AMF 25 control panel ● The load output terminal (canopy types)
● Battery charger 12V/5A
● Isıtıcı tüp sürmek için 9 A kontaktör.
● 9A contactor to drive the heater tube
● Control relay
● System protection insurance
● Emergency stop button
● 2 pieces suitable for the power generator contactor (ATS), optional
● The load output terminal (canopy types)

ComAp AMF 25 Control Panel


● Support of engines equipped with ECU (J1939 interface)
● Comprehensive diagnostic messages; SPN/FMI codes; KWP2000 support
● Automatic or manual start/stop of the genset
● Push buttons for simple control, lamp test
● Graphic back-lit LCD display 128x64 pixels
● 6 LED indicators
● Parameters adjustable via keyboard or PC
● Mains measurements 50/60 Hz, V ( 3 phase)
● Generator measurements 50/60 Hz, V , A ( 3 phase), kW , kVAr , kWh
● 3 phase Generator protections
- Over-/under voltage
● Configurable analog inputs - Over-/under frequency
● Selectable protections alarm / shutdown -Current/voltage asymmetry
● Battery voltage, engine speed (pick-up) measurement - Overcurrent/overload
● Configurable programmable binary inputs and outputs ● 3 phase AMF function
● Warm-up and cooling functions - Over-/under frequency
● Generator and Mains control with feedback and return timer - Over-/under voltage
● Modem communication support - Voltage asymmetry
● Sealed to IP65

The control panel via the LCD display the following measures are followed.
● Engine Monitoring: ● Alternator monitoring:
-Oil pressure gauge -3 phase Voltmeter (3 phase + neutral)
-Cooling water temperature indicator (Temperature gauge) -3 Phase ammeter
-Fuel level indicator (Electronic float if applicable) -Frequency
-Battery voltage indicator -kW meter, kVAr meter
-J1939 engine parameters (EC, electronic motors) -kWh and kVArh energy meter
● Statistics ● Network monitoring:
-Working Hours -3 phase Voltmeter (3 phase + neutral)
-The number-starter -Frequency
-Emergency stop number
-Maintenance time
-Event records retention
Dimensions and Weights

A=740
B=1021
C=1250
D=4350
E=1812
F=1600
G=2993
H=5360
K=1004
L=694
Open Type Canopy Type Recommended concrete foundation base
WidthxLengthxHeight. (mm)
1410x3500x2280 1600x4350x2600 Width x Length: 2500 x 4500 mm
Dry weight (kg) 2555 3485 Concrete: © Class B. A. 300 doses of concrete
Iron: 2 row Q8-12 mm thin ribbed mesh, grid iron.