Wiring Diagram: Generic Loop Com- Notes For Generic Loop Communicaon Wiring Diagram:

municaon Connecons for all 3000 1. Field connec on = (Used only with op onal J-Box)
Electronic, Truck and 700,800,900
2. All wiring must be installed and used in accordance with the na onal
Dispensers (only for a maximum of electrical code (NFPA #70, Automo ve and marine service code NFPA
one Diesel and one DEF). #30A), State and Local electrical codes.

Generic Loop 3. All wiring gauge is minimum required, con nuous without splicing,
stranded wire with THHN Insula on must be used. Do NOT reuse old
Personality Module
wire from an exis ng installa on.
(121982) (See Note 6)
4. Use only rigid metal conduit. Do not use PVC conduit.
(FUEL COMMUNICATION)
5. Absolutely no daisy chaining of data wires. Damage to the dispenser or
console will result. Do not connect these wires if unit is used without a
TS1 *JP1 TS2 *JP2 console.

1 2 1 2 6. The Personality Board used for Generic Loop is the same Personality
Board used for Current Loop.

7. Benne: recommends that the RS485 wires for (op onal) Card Readers
are twisted at least 3 mes per foot from the dispenser to the Interface
Generic Loop (+) Both Sides Orange 18 GA.

Generic Loop (-) Both Sides Yellow 18 GA.

Box.
* There is one shunt
across the two top pins for
7” or 10” Card Reader COMMUNICATION
JP1 and JP2 while using
(op onal)
the Generic Loop Protocol.
Not Used VAC Hot
Not Used VAC Neutral
RS485 (+) Violet 18 GA.
RS-485 Data +
Not Used RS-485 Data Common
RS485 (-) Yellow 18 GA.
RS-485 Data -

3/4” Conduit
(electronic enclosure)

Op onal Factory
Installed J-Box
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 Benne+ Pump Company

Toll Free: 800-235-7618

Telephone: 231-798-1310
(If J-Box not present wire directly to electronic enclosure.)
www.benne:pump.com
To Interface
To Interface Instr.# 135044
Box Box
Rev Level: A
(See Note 7)
Date: 6-20-17