7XG3127 – RA27
Arc Fault Monitor with Linear Sensor Input
Energy Management
Restricted
7XG3127 – RA27 Description
Arc Fault Monitor with Linear Sensor Input
The 7XG3127 device can use upto 4 point sensors (7XG3130) and
Overcurrent Relays a single optical linear sensor (7XG3140), with 3 high speed
output tripping zones.
Healthy LED’s
A front panel green LED is provided to indicate when the relay is
powered up and all connected arc sensors are operating
correctly. Should any of the sensors become disconnected the
associated red supervision LED will be illuminated. Healthy
sensors will continue to operate normally.
High speed arc fault detection for metal clad air insulated
switchgear utilizing optical sensors.
Calibration Indication
The Cal LED will commence flashing if the linear sensor fails the
automatic calibrate routine.
Components
Arc Sensors
RA27
Trip IA CB
RA27
Trip Bus
Section CB &
IA CB
IA
Bus Section
CB
F1 F2
RA27 RA27
Trip F1 CB Trip F2 CB
Arc sensor models The RA27 may be configured to suit a wide range of arc flash
monitoring applications.
The configuration mode is set via a 10 position rotary switch
There are two models available:
accessible when the front panel slide switch is operated as shown
7XG3127-1 Point sensor inputs only (Upto 4 x RA30)
in figure 9. Positions 0-9 are employed for trip and sensor func-
7XG3127-2 Point Sensor inputs (Upto 4 x RA30) plus one
tion configuration.
Linear optic sensor (RA40)
The single digit configuration code required to set the function
mode is determined from matrix in Table 1
Arc sensor Operating modes
Note that the setting must be carried out with the device pow-
ered ON as the LED’s provide feedback and to allow the configu-
The RA27 has three operating modes: ration to be stored on completion of the setting process when
the slide switch is released.
1. Normal Operating Mode The device starts up in this The operating mode position can be changed using a small blade
mode when powered ON screwdriver, rotating the switch to the required position
2. Setting Display Mode
With the slide switch held up for 2s, the device enters
the display setting mode.
7XG3127-1 LED’s for trip and sensor configuration will
be displayed in accordance with Table 1
7XG3127-2 As above with alternating LED’s for linear
sensor transmission length in accordance with Table 2
3. Configuration Mode
The configuration mode is entered when a setting
change is made by the adjustment of the rotary selector
switch. When this occurs the Green arc flash monitor
LED will commence flashing, refer to configuration se-
lection indication.
Table 1
8 COMMON TRIPPING
3
7XG3127-2 Configuration Switch Setting Arc 1
Input
Trip 1
10
5
Sensor Trip 2
Common Tripping Scheme 0 1 2 3 4
Type
7
Trip 3
| | | | | 1S40
Linear Arc Input
9
Linear 7XG3140 1 1 1 1 1 Common
Number of Sen- 4
Input 1 7XG3130 0 1 1 1 2 11
sors Connected Arc 2 Trip 4
Input
Input 2 7XG3130 0 0 1 2 2 6
13
Common
ZONE TRIPPING
3
Trip 1
7XG3127-1 Configuration Switch Setting 8
Arc 1 5
Sensor ZONE 1 Trip 2
Zone Tripping Scheme 5 6 7 8 9 Input
10
Type 7
Trip 3
| | | | |
9
Input Common
7XG3130 1 1 1 2 2
Number of Sen- 1 4
11
sors Connected Trip 4
Input Arc 2
7XG3130 0 1 2 1 2 Input ZONE 2
2 6
13
Common
8 ZONE TRIPPING
7XG3127-2 Configuration Switch Setting 3
Arc 1 Trip 1
Sensor Input
10
Zone Tripping Scheme 5 6 7 8 9 5
Type ZONE 1 Trip 2
| | | | | 1S40 7
Linear Arc Input Trip 3
Linear 7XG3140 1 1 1 1 1
9
Common
Number of Sen- Input
7XG3130 1 1 1 2 2 4
sors Connected 1 11
Trip 4
Arc 2
Input Input ZONE 2
7XG3130 0 1 2 1 2 6
13
2 Common
100-300V dc
Arc Fault Sensor Linear Sensor Input
Absolute Range
75-275V ac
Mechanical Environment
Mechanical Classification
Vibration - Sinusoidal
Durability – 0.1Hz >105 operations at no load
IEC 60255-21-1 Class I
maximum repetition rate >104 operations at full load
Surge Immunity
IEC 60255-26, #7.2.7, Acceptance criterion B
Flush Panel Mount (As shown in Figure 17) Flush Panel Mount (As shown in Figure 20)
Figure 12: Panel cut out for flush mounting Terminal Block Type
TBD-R1 base Figure 13: Panel cut out for flush mounting Terminal Block Type
TBD-R2 base
Terminal Block
TBD-R1 /R2 Rear connect terminal block suitable for flush
mount relay version.
TBD-F Front connect terminal block suitable for rail
mount relay version
panel.
Note: The terminal block retention plates supplied with TBD-R2
mounting are not suitable for use with linear sensor.
8
Arc 1 3
Input Trip 1
10
5
Trip 2
1S40 7
Trip 3
Linear Arc Input
9
Common
4
11
Arc 2
Trip 4
Input
6
13
Common
1 12
Supervision
Vx 2 14 Contact
EMEA-C10159-00-7600
November 2018
www. siemens.com/energy