ILLUMINATION CALCULATION

AVERAGE ILLUMINATION CALCULATION SHEET


4TH FLOOR
ROOM CLASSIFICATION: CLASSROOM (1,2,3)

LENGTH: 8.35m HCC: 0 ρC: 80%


WIDTH: 6.7m HRC: 3.2 ρW: 50%
HEIGHT: 4m HFC: 0.8 ρF: 20%

I. D A T A

1. AVERAGE MAINTAINED ILLUMINANCE: 500 lux


2. LUMINAIRE DATA:
ITEM NO. 27
2 X 60W, 230V, 60Hz
COOL WHITE, PORCELAIN-ENAMELED REFECTOR
3. AREA ATMOSPHERE: VERY CLEAN
4. ROOM SURFACE REFLECTANCES:
CEILING: 80% WALL: 50% FLOOR: 20%
5. OPERATING CHARACTERISTIC: 10hrs/starting/day
6. CLEANING CYCLE: 12 MONTHS
II. C A L C U L A T I O N

8.35+6.7
1. CCR ¿ (5)(0)=0
8.35∗6.7
8.35.5+ 6.7
RCR= (5)(3.2)=4.30
8.35∗6.7
8.35+6.7
FCR= ( 5 )( 0.8)=1.08
48.35∗6.7

2. OBTAIN EFFECTIVE CEILING CAVITY REFLECTANCE, ρCC


% BASE REFLECTANCE = 80%
% WALL REFLECTANCE = 50%
CCR =0
ρCC = 80%
3. OBTAIN EFFECTIVE FLOOR CAVITY REFLECTANCE, ρFC
% BASE REFLECTANCE = 20%
% WALL REFLECTANDCE = 50%
FCR =1.08
ρFC = 19.6%
4. OBTAIN COEFFICIENT OF UTILIZATION, CU
ρCC = 80%
ρW = 50%
RCR = 4.30
CU = 28.6%
BY INTERPOLATION, SOLVE CU
RCR CU
4 .58
4.40 CU
5 .0.52
5. ROOM SURFACE DIRT DEPRECIATION FACTOR, RSDD
THE LIGHT DISTRIBUTION IS CLASSIFIED AS SEMI-DIRECT
EXPECTED DIRT DEPRECIATION FACTOR IS 8%

RCR = 4.30
RSDD = 94.7%
BY INTERPOLATION, SOLVE RSDD
RCR
4 95
4.30 RSDD
5 94
RSDD = 94.7%
6. LAMP LUMEN DEPRECIATIO FACTOR, LLD
BY INTERPOLATION:
6−10 87−RSDD
=
6−12 87−86
LLD = 86.33%
7. LAMP BURN OUT, LBO
LBO = 100%

8. ILLUMINANCE DIRT DEPRECIATION FACTOR, LDD


-AT ANNUALY CLAENING CYCLE, VERY CLEAN ATMOSPHERE MAINTENANCE
CATEGORY II
LDD = 97%
9. LIGHT LOSS FACTOR, LLF
LLF = (RSDD) (LLD) (LBO) (LDD)
= (94.7%) (86.33%) (100%) (97%)
LLF = 79.30%

10. TOTAL NUMBER OF LUMINAIRES, N

(ILLUMINANCE) (AREA)
N=
(LUMENS/LUMINAIRE) (CU)(LLF)
500∗8.35∗6.7
=
8300∗.7930∗.562
= 7.56
N = 8 LUMINAIRES

11. FORMATION / SPACING OF LUMINAIRE

LX N 8.35 X 8
C=

N

W
8
=
6.7 √=3.16=4

R= = =2
C 4

W 6.7
XW = = =3.35
R 2

L 8.35
XL = = =2.09
C 4

WHERE:
C = NO. OF COLUMNS OF LUMINAIRES ALONG THE WIDTH OF THE ROOM.
R = NO. OF ROWS OF LUMINAIRES ALONG THE LENGTH OF THE ROOM.
XW = SPACING BETWEEN LUMINAIRES ALONG THE LENGTH OF THE
ROOM.
XL = SPACING BETWEEN LUMINAIRES ALONG THE WIDTH OF THE ROOM.

12. ACTUAL ILLUMINATION


LUMENS
( )(CU )(LLF)(N ) 8300 X 0.562 X 0.7930 X 8
ILL = LUMINAIRE =
8.35∗6.7
AREA

= 528.95 LUX
LENGTH: 8.35 m
WIDTH: 6.7 m
NO. OF LUMINAIRES: 8
X L= 2.0875 m
Xw = 3.35 m
AVERAGE ILLUMINATION CALCULATION SHEET

ROOM CLASSIFICATION: CLASSROOM (4)

LENGTH: 7.98m HCC: 0 ρC: 80%


WIDTH: 7.75m HRC: 4 ρW: 50%
HEIGHT: 4m HFC: 0 8 ρF: 20%

I. D A T A

1. AVERAGE MAINTAINED ILLUMINANCE: 500 lux


2. LUMINAIRE DATA:
ITEM NO. 27
2 X 60W, 230V, 60Hz
COOL WHITE, PORCELAIN-ENAMELED REFECTOR
3. AREA ATMOSPHERE: VERY CLEAN
4. ROOM SURFACE REFLECTANCES:
CEILING: 80% WALL: 50% FLOOR: 20%
5. OPERATING CHARACTERISTIC: 10hrs/starting/day
6. CLEANING CYCLE: 12 MONTHS
II. C A L C U L A T I O N
8.35+6.7
1. CCR ¿ (5)(0)=0
8.35∗6.7
8.35.5+ 6.7
RCR= (5)(3.2)=4.30
8.35∗6.7
8.35+6.7
FCR= ( 5 )( 0.8)=1.08
48.35∗6.7
2. OBTAIN EFFECTIVE CEILING CAVITY REFLECTANCE, ρCC
% BASE REFLECTANCE = 80%
% WALL REFLECTANCE = 50%
CCR =0
ρCC = 80%
3. OBTAIN EFFECTIVE FLOOR CAVITY REFLECTANCE, ρFC
% BASE REFLECTANCE = 20%
% WALL REFLECTANDCE = 50%
FCR =1.08
ρFC = 19.6%
4. OBTAIN COEFFICIENT OF UTILIZATION, CU
ρCC = 80%
ρW = 50%
RCR = 4.30
CU = 28.6%
BY INTERPOLATION, SOLVE CU
RCR CU
4 .58
4.40 CU
5 .0.52

5. ROOM SURFACE DIRT DEPRECIATION FACTOR, RSDD


THE LIGHT DISTRIBUTION IS CLASSIFIED AS SEMI-DIRECT
EXPECTED DIRT DEPRECIATION FACTOR IS 8%

RCR = 4.30
RSDD = 94.93%
BY INTERPOLATION, SOLVE RSDD
RCR
4 95
4.07 RSDD
5 94
RSDD = 94.7%
6. LAMP LUMEN DEPRECIATIO FACTOR, LLD
BY INTERPOLATION:
6−10 87−RSDD
=
6−12 87−86
LLD = 86.33%
7. LAMP BURN OUT, LBO
LBO = 100%

8. ILLUMINANCE DIRT DEPRECIATION FACTOR, LDD


-AT ANNUALY CLAENING CYCLE, VERY CLEAN ATMOSPHERE MAINTENANCE
CATEGORY II
LDD = 97%
9. LIGHT LOSS FACTOR, LLF
LLF = (RSDD) (LLD) (LBO) (LDD)
= (94%) (86.33%) (100%) (97%)
LLF = 79.5%

10. TOTAL NUMBER OF LUMINAIRES, N

(ILLUMINANCE) (AREA)
N=
(LUMENS/LUMINAIRE) (CU)(LLF)
500∗7.98∗7.75
=
8300∗.795∗.576
= 8.13
N = 8 LUMINAIRES

11. FORMATION / SPACING OF LUMINAIRE

LX N 7.98 X 8
C=

N

W
8
=
7.75 √=2.87=2

R= = =4
C 2

W 7,75
XW = = =1.9375 m
R 4

L 7.98
XL = = =3.99 m
C 2

WHERE:
C = NO. OF COLUMNS OF LUMINAIRES ALONG THE WIDTH OF THE ROOM.
R = NO. OF ROWS OF LUMINAIRES ALONG THE LENGTH OF THE ROOM.
XW = SPACING BETWEEN LUMINAIRES ALONG THE LENGTH OF THE
ROOM.
XL = SPACING BETWEEN LUMINAIRES ALONG THE WIDTH OF THE ROOM.

12. ACTUAL ILLUMINATION


LUMENS
( )(CU )(LLF)(N ) 8300 X 0.576 X 0.7950 X 8
ILL = LUMINAIRE =
7.98∗7.75
AREA

= 504.285 LUX
LENGTH: 7.98 m
WIDTH: 7.75 m
NO. OF LUMINAIRES: 8
X L= 3.99 m
Xw = 1.9375 m
AVERAGE ILLUMINATION CALCULATION SHEET

ROOM CLASSIFICATION: CLASSROOM (5,6,7)

LENGTH: 7.66m HCC: 0 ρC: 80%


WIDTH: 7.22m HRC: 4 ρW: 50%
HEIGHT: 4m HFC: 0 8 ρF: 20%

I. D A T A

1. AVERAGE MAINTAINED ILLUMINANCE: 500 lux


2. LUMINAIRE DATA:
ITEM NO. 27
2 X 60W, 230V, 60Hz
COOL WHITE, PORCELAIN-ENAMELED REFECTOR
3. ATMOSPHERE: VERY CLEAN
4. ROOM SURFACE REFLECTANCES:
CEILING: 80% WALL: 50% FLOOR: 20%
5. OPERATING CHARACTERISTIC: 10hrs/starting/day
6. CLEANING CYCLE: 12 MONTHS
II. C A L C U L A T I O N
7.66+7.22
1. CCR ¿ (5)(0)=0
7.66∗7.22
7.66+7.22
RCR= (5)(3.2)=4.30
7.66∗7.22
8.35+6.7
FCR= ( 5 )( 0.8)=1.08
48.35∗6.7
2. OBTAIN EFFECTIVE CEILING CAVITY REFLECTANCE, ρCC
% BASE REFLECTANCE = 80%
% WALL REFLECTANCE = 50%
CCR =0
ρCC = 80%
3. OBTAIN EFFECTIVE FLOOR CAVITY REFLECTANCE, ρFC
% BASE REFLECTANCE = 20%
% WALL REFLECTANDCE = 50%
FCR =1.08
ρFC = 19.62%
4. OBTAIN COEFFICIENT OF UTILIZATION, CU
ρCC = 80%
ρW = 50%
RCR = 4.30
CU = 0.562
BY INTERPOLATION, SOLVE CU
RCR CU
4 .58
4.40 CU
5 0.562

5. ROOM SURFACE DIRT DEPRECIATION FACTOR, RSDD


THE LIGHT DISTRIBUTION IS CLASSIFIED AS SEMI-DIRECT
EXPECTED DIRT DEPRECIATION FACTOR IS 8%

RCR = 4.30
RSDD = 94.7%
BY INTERPOLATION, SOLVE RSDD
RCR
4 95
4.30 RSDD
5 94
RSDD = 94.7%
6. LAMP LUMEN DEPRECIATIO FACTOR, LLD
BY INTERPOLATION:
6−10 87−RSDD
=
6−12 87−86
LLD = 86.33%
7. LAMP BURN OUT, LBO
LBO = 100%

8. ILLUMINANCE DIRT DEPRECIATION FACTOR, LDD


-AT ANNUALY CLAENING CYCLE, VERY CLEAN ATMOSPHERE MAINTENANCE
CATEGORY II
LDD = 97%

9. LIGHT LOSS FACTOR, LLF


LLF = (RSDD) (LLD) (LBO) (LDD)
= (94.7%) (86.33%) (100%) (97%)
LLF = 79.30%

10. TOTAL NUMBER OF LUMINAIRES, N

(ILLUMINANCE) (AREA)
N=
(LUMENS/LUMINAIRE) (CU)(LLF)
500∗7.66∗7.22
=
8300∗.7930∗.562
= 7.47
N = 8 LUMINAIRES

11. FORMATION / SPACING OF LUMINAIRE

LX N 7.66 X 8
C=
N

W
8
=
7.22 √
=2.91=2

R= = =4
C 2

W 7.22
XW = = =1.805 m
R 4

L 7.66
XL = = =3.83 m
C 2

WHERE:
C = NO. OF COLUMNS OF LUMINAIRES ALONG THE WIDTH OF THE ROOM.
R = NO. OF ROWS OF LUMINAIRES ALONG THE LENGTH OF THE ROOM.
XW = SPACING BETWEEN LUMINAIRES ALONG THE LENGTH OF THE
ROOM.
XL = SPACING BETWEEN LUMINAIRES ALONG THE WIDTH OF THE ROOM.

12. ACTUAL ILLUMINATION


LUMENS
( )(CU )(LLF)(N ) 8300 X 0.562 X 0.7930 X 8
ILL = LUMINAIRE =
7.66∗7.22
AREA

= 535.07 LUX
LENGTH: 7.66 m
WIDTH: 7.22 m
NO. OF LUMINAIRES: 8
X L= 3.83 m
Xw = 1.805 m
AVERAGE ILLUMINATION CALCULATION SHEET

ROOM CLASSIFICATION: HALLWAY

LENGTH: 26.8m HCC: 0 ρC: 80%


WIDTH: 3m HRC: 4 ρW: 50%
HEIGHT: 4m HFC: 0 8 ρF: 20%

I. D A T A

1. AVERAGE MAINTAINED ILLUMINANCE: 250 lux


2. LUMINAIRE DATA:
ITEM NO. 27
2 X 60W, 230V, 60Hz
COOL WHITE, PORCELAIN-ENAMELED REFECTOR
3. ATMOSPHERE: VERY CLEAN
4. ROOM SURFACE REFLECTANCES:
CEILING: 80% WALL: 50% FLOOR: 20%
5. OPERATING CHARACTERISTIC: 10hrs/starting/day
6. CLEANING CYCLE: 12 MONTHS
II. C A L C U L A T I O N
26.8+3
1. CCR ¿ (5)(0)=0
26.8∗3
26.8+3
RCR= (5)( 4)=7.41
26.8∗3
26.8+3
FCR= (5)( 0)=0
26.8∗3
2. OBTAIN EFFECTIVE CEILING CAVITY REFLECTANCE, ρCC
% BASE REFLECTANCE = 80%
% WALL REFLECTANCE = 50%
CCR =0
ρCC = 80%
3. OBTAIN EFFECTIVE FLOOR CAVITY REFLECTANCE, ρFC
% BASE REFLECTANCE = 20%
% WALL REFLECTANDCE = 50%
FCR =0
ρFC = 20%
4. OBTAIN COEFFICIENT OF UTILIZATION, CU
ρCC = 80%
ρW = 50%
RCR = 7.41
CU = 0.4095
BY INTERPOLATION, SOLVE CU
RCR CU
7 .43
7.41 CU
8 0.38

5. ROOM SURFACE DIRT DEPRECIATION FACTOR, RSDD


THE LIGHT DISTRIBUTION IS CLASSIFIED AS SEMI-DIRECT
EXPECTED DIRT DEPRECIATION FACTOR IS 8%

RCR = 7.41
RSDD = 93.295%
BY INTERPOLATION, SOLVE RSDD
RCR
6 94
7.41 RSDD
8 93
RSDD = 93.295%
6. LAMP LUMEN DEPRECIATIO FACTOR, LLD
BY INTERPOLATION:
6−10 87−RSDD
=
6−12 87−86
LLD = 86.33%
7. LAMP BURN OUT, LBO
LBO = 100%
8. ILLUMINANCE DIRT DEPRECIATION FACTOR, LDD
-AT ANNUALY CLAENING CYCLE, VERY CLEAN ATMOSPHERE MAINTENANCE
CATEGORY II
LDD = 97%
9. LIGHT LOSS FACTOR, LLF
LLF = (RSDD) (LLD) (LBO) (LDD)
= (93.29%) (86.33%) (100%) (97%)
LLF = 78.12%

10. TOTAL NUMBER OF LUMINAIRES, N

(ILLUMINANCE) (AREA)
N=
(LUMENS/LUMINAIRE) (CU)(LLF)
250∗26.8∗3
=
8300∗.7812∗.4095
= 7.57
N = 8 LUMINAIRES

11. FORMATION / SPACING OF LUMINAIRE

LX N 26.8 X 8
C=
N

W
8
=
3 √ =8.45=8

R= = =1
C 8

W 3
XW = = =3 m
R 1

L 26.8
XL = = =3.35 m
C 8

WHERE:
C = NO. OF COLUMNS OF LUMINAIRES ALONG THE WIDTH OF THE ROOM.
R = NO. OF ROWS OF LUMINAIRES ALONG THE LENGTH OF THE ROOM.
XW = SPACING BETWEEN LUMINAIRES ALONG THE LENGTH OF THE
ROOM.
XL = SPACING BETWEEN LUMINAIRES ALONG THE WIDTH OF THE ROOM.

12. ACTUAL ILLUMINATION


LUMENS
( )(CU )(LLF)(N ) 8300 X 0.4095 X 0.7812 X 8
ILL = LUMINAIRE =
26.8∗3
AREA

= 264.19 LUX

LENGTH: 26.8 m
WIDTH: 3 m
NO. OF LUMINAIRES: 8
X L= 3.35 m
Xw = 3 m
AVERAGE ILLUMINATION CALCULATION SHEET

ROOM CLASSIFICATION: HALLWAY 2

LENGTH: 7.75m HCC: 0 ρC: 80%


WIDTH: 3.6m HRC: 3.2 ρW: 50%
HEIGHT: 4m HFC: 0 ρF: 20%

I. D A T A
1. AVERAGE MAINTAINED ILLUMINANCE: 250 lux
2. LUMINAIRE DATA:
ITEM NO. 27
2 X 60W, 230V, 60Hz
COOL WHITE, PORCELAIN-ENAMELED REFECTOR
3. AREA ATMOSPHERE: VERY CLEAN
4. ROOM SURFACE REFLECTANCES:
CEILING: 80% WALL: 50% FLOOR: 20%
5. OPERATING CHARACTERISTIC: 10hrs/starting/day
6. CLEANING CYCLE: 12 MONTHS
II. C A L C U L A T I O N

7.75+ 3.6
1. CCR ¿ (5)( 0)=0
7.75∗3.6
7.75+3.6
RCR= (5)( 4)=8.14
7.75∗3.6
7.75+3.6
FCR= (5)(0)=0
7.75∗3.6
2. OBTAIN EFFECTIVE CEILING CAVITY REFLECTANCE, ρCC
% BASE REFLECTANCE = 80%
% WALL REFLECTANCE = 50%
CCR =0
ρCC = 80%
3. OBTAIN EFFECTIVE FLOOR CAVITY REFLECTANCE, ρFC
% BASE REFLECTANCE = 20%
% WALL REFLECTANDCE = 50%
FCR =0
ρFC = 20%
4. OBTAIN COEFFICIENT OF UTILIZATION, CU
ρCC = 80%
ρW = 50%
RCR = 8.14
CU = 0.3758
BY INTERPOLATION, SOLVE CU
RCR CU
8 .38
8.13 CU
9 .35

5. ROOM SURFACE DIRT DEPRECIATION FACTOR, RSDD


THE LIGHT DISTRIBUTION IS CLASSIFIED AS SEMI-DIRECT
EXPECTED DIRT DEPRECIATION FACTOR IS 8%

RCR = 8.14
RSDD = 93.29%
BY INTERPOLATION, SOLVE RSDD
RCR
6 94
8.14 RSDD
9 93
RSDD = 93.29%
6. LAMP LUMEN DEPRECIATIO FACTOR, LLD
BY INTERPOLATION:
6−10 87−RSDD
=
6−12 87−86
LLD = 86.33%
7. LAMP BURN OUT, LBO
LBO = 100%

8. ILLUMINANCE DIRT DEPRECIATION FACTOR, LDD


-AT ANNUALY CLAENING CYCLE, VERY CLEAN ATMOSPHERE MAINTENANCE
CATEGORY II
LDD = 97%
9. LIGHT LOSS FACTOR, LLF
LLF = (RSDD) (LLD) (LBO) (LDD)
= (93.29%) (86.33%) (100%) (97%)
LLF = 78.12%

10. TOTAL NUMBER OF LUMINAIRES, N

(ILLUMINANCE) (AREA)
N=
(LUMENS/LUMINAIRE) (CU)(LLF)
250∗7.75∗3.6
=
8300∗.7812∗.3758
= 2.86
N = 3 LUMINAIRES
11. FORMATION / SPACING OF LUMINAIRE

LX N 7.75 X 3
C=
N

W
3
=
3.6 √=2.54=3

R= = =1
C 3

W 3.6
XW = = =3.6 m
R 1

L 7.75
XL = = =2.58 m
C 3

WHERE:
C = NO. OF COLUMNS OF LUMINAIRES ALONG THE WIDTH OF THE ROOM.
R = NO. OF ROWS OF LUMINAIRES ALONG THE LENGTH OF THE ROOM.
XW = SPACING BETWEEN LUMINAIRES ALONG THE LENGTH OF THE
ROOM.
XL = SPACING BETWEEN LUMINAIRES ALONG THE WIDTH OF THE ROOM.

12. ACTUAL ILLUMINATION


LUMENS
( )(CU )(LLF)(N ) 8300 X 0.562 X 0.7930 X 8
ILL = LUMINAIRE =
8.35∗6.7
AREA

= 528.95 LUX
LENGTH: 7.75 m
WIDTH: 3.6 m
NO. OF LUMINAIRES: 3
X L= 2.58 m
Xw = 3.6 m
AVERAGE ILLUMINATION CALCULATION SHEET
TH
5 FLOOR
ROOM CLASSIFICATION: CLASSROOM (1,2,3)

LENGTH: 8.35m HCC: 0 ρC: 80%


WIDTH: 6.7m HRC: 3.2 ρW: 50%
HEIGHT: 4m HFC: 0.8 ρF: 20%

I. D A T A

1. AVERAGE MAINTAINED ILLUMINANCE: 500 lux


2. LUMINAIRE DATA:
ITEM NO. 27
2 X 60W, 230V, 60Hz
COOL WHITE, PORCELAIN-ENAMELED REFECTOR
3. AREA ATMOSPHERE: VERY CLEAN
4. ROOM SURFACE REFLECTANCES:
CEILING: 80% WALL: 50% FLOOR: 20%
5. OPERATING CHARACTERISTIC: 10hrs/starting/day
6. CLEANING CYCLE: 12 MONTHS
II. C A L C U L A T I O N
8.35+6.7
1. CCR ¿ (5)(0)=0
8.35∗6.7
8.35.5+ 6.7
RCR= (5)(3.2)=4.30
8.35∗6.7
8.35+6.7
FCR= ( 5 )( 0.8)=1.08
48.35∗6.7
2. OBTAIN EFFECTIVE CEILING CAVITY REFLECTANCE, ρCC
% BASE REFLECTANCE = 80%
% WALL REFLECTANCE = 50%
CCR =0
ρCC = 80%
3. OBTAIN EFFECTIVE FLOOR CAVITY REFLECTANCE, ρFC
% BASE REFLECTANCE = 20%
% WALL REFLECTANDCE = 50%
FCR =1.08
ρFC = 19.6%
4. OBTAIN COEFFICIENT OF UTILIZATION, CU
ρCC = 80%
ρW = 50%
RCR = 4.30
CU = 28.6%
BY INTERPOLATION, SOLVE CU
RCR CU
4 .58
4.40 CU
5 .0.52

5. ROOM SURFACE DIRT DEPRECIATION FACTOR, RSDD


THE LIGHT DISTRIBUTION IS CLASSIFIED AS SEMI-DIRECT
EXPECTED DIRT DEPRECIATION FACTOR IS 8%

RCR = 4.30
RSDD = 94.7%
BY INTERPOLATION, SOLVE RSDD
RCR
4 95
4.30 RSDD
5 94
RSDD = 94.7%
6. LAMP LUMEN DEPRECIATIO FACTOR, LLD
BY INTERPOLATION:
6−10 87−RSDD
=
6−12 87−86
LLD = 86.33%
7. LAMP BURN OUT, LBO
LBO = 100%

8. ILLUMINANCE DIRT DEPRECIATION FACTOR, LDD


-AT ANNUALY CLAENING CYCLE, VERY CLEAN ATMOSPHERE MAINTENANCE
CATEGORY II
LDD = 97%
9. LIGHT LOSS FACTOR, LLF
LLF = (RSDD) (LLD) (LBO) (LDD)
= (94.7%) (86.33%) (100%) (97%)
LLF = 79.30

10. TOTAL NUMBER OF LUMINAIRES, N

(ILLUMINANCE) (AREA)
N=
(LUMENS/LUMINAIRE) (CU)(LLF)
500∗8.35∗6.7
=
8300∗.7930∗.562
= 7.56
N = 8 LUMINAIRES
11. FORMATION / SPACING OF LUMINAIRE

LX N 8.35 X 8
C=
N

W
8
=
6.7 √=3.16=4

R= = =2
C 4

W 6.7
XW = = =3.35
R 2

L 8.35
XL = = =2.09
C 4

WHERE:
C = NO. OF COLUMNS OF LUMINAIRES ALONG THE WIDTH OF THE ROOM.
R = NO. OF ROWS OF LUMINAIRES ALONG THE LENGTH OF THE ROOM.
XW = SPACING BETWEEN LUMINAIRES ALONG THE LENGTH OF THE
ROOM.
XL = SPACING BETWEEN LUMINAIRES ALONG THE WIDTH OF THE ROOM.

12. ACTUAL ILLUMINATION


LUMENS
( )(CU )(LLF)(N ) 8300 X 0.562 X 0.7930 X 8
ILL = LUMINAIRE =
8.35∗6.7
AREA

= 528.95 LUX
LENGTH: 8.35 m
WIDTH: 6.7 m
NO. OF LUMINAIRES: 8
X L= 2.0875 m
Xw = 3.35 m
AVERAGE ILLUMINATION CALCULATION SHEET

ROOM CLASSIFICATION: CLASSROOM (4)

LENGTH: 7.98m HCC: 0 ρC: 80%


WIDTH: 7.75m HRC: 4 ρW: 50%
HEIGHT: 4m HFC: 0 8 ρF: 20%

I. D A T A

1. AVERAGE MAINTAINED ILLUMINANCE: 500 lux


2. LUMINAIRE DATA:
ITEM NO. 27
2 X 60W, 230V, 60Hz
COOL WHITE, PORCELAIN-ENAMELED REFECTOR
3. AREA ATMOSPHERE: VERY CLEAN
4. ROOM SURFACE REFLECTANCES:
CEILING: 80% WALL: 50% FLOOR: 20%
5. OPERATING CHARACTERISTIC: 10hrs/starting/day
6. CLEANING CYCLE: 12 MONTHS
II. C A L C U L A T I O N
8.35+6.7
1. CCR ¿ (5)(0)=0
8.35∗6.7
8.35.5+ 6.7
RCR= (5)(3.2)=4.30
8.35∗6.7
8.35+6.7
FCR= ( 5 )( 0.8)=1.08
48.35∗6.7
2. OBTAIN EFFECTIVE CEILING CAVITY REFLECTANCE, ρCC
% BASE REFLECTANCE = 80%
% WALL REFLECTANCE = 50%
CCR =0
ρCC = 80%
3. OBTAIN EFFECTIVE FLOOR CAVITY REFLECTANCE, ρFC
% BASE REFLECTANCE = 20%
% WALL REFLECTANDCE = 50%
FCR =1.08
ρFC = 19.6%
4. OBTAIN COEFFICIENT OF UTILIZATION, CU
ρCC = 80%
ρW = 50%
RCR = 4.30
CU = 28.6%
BY INTERPOLATION, SOLVE CU
RCR CU
4 .58
4.40 CU
5 .0.52

5. ROOM SURFACE DIRT DEPRECIATION FACTOR, RSDD


THE LIGHT DISTRIBUTION IS CLASSIFIED AS SEMI-DIRECT
EXPECTED DIRT DEPRECIATION FACTOR IS 8%

RCR = 4.30
RSDD = 94.93%
BY INTERPOLATION, SOLVE RSDD
RCR
4 95
4.07 RSDD
5 94
RSDD = 94.7%
6. LAMP LUMEN DEPRECIATIO FACTOR, LLD
BY INTERPOLATION:
6−10 87−RSDD
=
6−12 87−86
LLD = 86.33%
7. LAMP BURN OUT, LBO
LBO = 100%

8. ILLUMINANCE DIRT DEPRECIATION FACTOR, LDD


-AT ANNUALY CLAENING CYCLE, VERY CLEAN ATMOSPHERE MAINTENANCE
CATEGORY II
LDD = 97%
9. LIGHT LOSS FACTOR, LLF
LLF = (RSDD) (LLD) (LBO) (LDD)
= (94%) (86.33%) (100%) (97%)
LLF = 79.5%

10. TOTAL NUMBER OF LUMINAIRES, N

(ILLUMINANCE) (AREA)
N=
(LUMENS/LUMINAIRE) (CU)(LLF)
500∗7.98∗7.75
=
8300∗.795∗.576
= 8.13
N = 8 LUMINAIRES

11. FORMATION / SPACING OF LUMINAIRE

LX N 7.98 X 8
C=
N

W
8
=
7.75 √
=2.87=2

R= = =4
C 2

W 7,75
XW = = =1.9375 m
R 4

L 7.98
XL = = =3.99 m
C 2

WHERE:
C = NO. OF COLUMNS OF LUMINAIRES ALONG THE WIDTH OF THE ROOM.
R = NO. OF ROWS OF LUMINAIRES ALONG THE LENGTH OF THE ROOM.
XW = SPACING BETWEEN LUMINAIRES ALONG THE LENGTH OF THE
ROOM.
XL = SPACING BETWEEN LUMINAIRES ALONG THE WIDTH OF THE ROOM.

12. ACTUAL ILLUMINATION


LUMENS
( )(CU )(LLF)(N ) 8300 X 0.576 X 0.7950 X 8
ILL = LUMINAIRE =
7.98∗7.75
AREA

= 504.285 LUX
LENGTH: 7.98 m
WIDTH: 7.75 m
NO. OF LUMINAIRES: 8
X L= 3.99 m
Xw = 1.9375 m
AVERAGE ILLUMINATION CALCULATION SHEET

ROOM CLASSIFICATION: CLASSROOM (5,6,7)

LENGTH: 7.66m HCC: 0 ρC: 80%


WIDTH: 7.22m HRC: 4 ρW: 50%
HEIGHT: 4m HFC: 0 8 ρF: 20%

I. D A T A

1. AVERAGE MAINTAINED ILLUMINANCE: 500 lux


2. LUMINAIRE DATA:
ITEM NO. 27
2 X 60W, 230V, 60Hz
COOL WHITE, PORCELAIN-ENAMELED REFECTOR
3. ATMOSPHERE: VERY CLEAN
4. ROOM SURFACE REFLECTANCES:
CEILING: 80% WALL: 50% FLOOR: 20%
5. OPERATING CHARACTERISTIC: 10hrs/starting/day
6. CLEANING CYCLE: 12 MONTHS
II. C A L C U L A T I O N
7.66+7.22
1. CCR ¿ (5)(0)=0
7.66∗7.22
7.66+7.22
RCR= (5)(3.2)=4.30
7.66∗7.22
8.35+6.7
FCR= ( 5 )( 0.8)=1.08
48.35∗6.7
2. OBTAIN EFFECTIVE CEILING CAVITY REFLECTANCE, ρCC
% BASE REFLECTANCE = 80%
% WALL REFLECTANCE = 50%
CCR =0
ρCC = 80%
3. OBTAIN EFFECTIVE FLOOR CAVITY REFLECTANCE, ρFC
% BASE REFLECTANCE = 20%
% WALL REFLECTANDCE = 50%
FCR =1.08
ρFC = 19.62%
4. OBTAIN COEFFICIENT OF UTILIZATION, CU
ρCC = 80%
ρW = 50%
RCR = 4.30
CU = 0.562
BY INTERPOLATION, SOLVE CU
RCR CU
4 .58
4.40 CU
5 0.562

5. ROOM SURFACE DIRT DEPRECIATION FACTOR, RSDD


THE LIGHT DISTRIBUTION IS CLASSIFIED AS SEMI-DIRECT
EXPECTED DIRT DEPRECIATION FACTOR IS 8%

RCR = 4.30
RSDD = 94.7%
BY INTERPOLATION, SOLVE RSDD
RCR
4 95
4.30 RSDD
5 94
RSDD = 94.7%
6. LAMP LUMEN DEPRECIATIO FACTOR, LLD
BY INTERPOLATION:
6−10 87−RSDD
=
6−12 87−86
LLD = 86.33%
7. LAMP BURN OUT, LBO
LBO = 100%

8. ILLUMINANCE DIRT DEPRECIATION FACTOR, LDD


-AT ANNUALY CLAENING CYCLE, VERY CLEAN ATMOSPHERE MAINTENANCE
CATEGORY II
LDD = 97%

9. LIGHT LOSS FACTOR, LLF


LLF = (RSDD) (LLD) (LBO) (LDD)
= (94.7%) (86.33%) (100%) (97%)
LLF = 79.30%

10. TOTAL NUMBER OF LUMINAIRES, N

(ILLUMINANCE) (AREA)
N=
(LUMENS/LUMINAIRE) (CU)(LLF)
500∗7.66∗7.22
=
8300∗.7930∗.562
= 7.47
N = 8 LUMINAIRES

11. FORMATION / SPACING OF LUMINAIRE

LX N 7.66 X 8
C=
N

W
8
=
7.22 √
=2.91=2

R= = =4
C 2

W 7.22
XW = = =1.805 m
R 4

L 7.66
XL = = =3.83 m
C 2

WHERE:
C = NO. OF COLUMNS OF LUMINAIRES ALONG THE WIDTH OF THE ROOM.
R = NO. OF ROWS OF LUMINAIRES ALONG THE LENGTH OF THE ROOM.
XW = SPACING BETWEEN LUMINAIRES ALONG THE LENGTH OF THE
ROOM.
XL = SPACING BETWEEN LUMINAIRES ALONG THE WIDTH OF THE ROOM.

12. ACTUAL ILLUMINATION


LUMENS
( )(CU )(LLF)(N ) 8300 X 0.562 X 0.7930 X 8
ILL = LUMINAIRE =
7.66∗7.22
AREA

= 535.07 LUX
LENGTH: 7.66 m
WIDTH: 7.22 m
NO. OF LUMINAIRES: 8
X L= 3.83 m
Xw = 1.805 m
AVERAGE ILLUMINATION CALCULATION SHEET

ROOM CLASSIFICATION: HALLWAY

LENGTH: 26.8m HCC: 0 ρC: 80%


WIDTH: 3m HRC: 4 ρW: 50%
HEIGHT: 4m HFC: 0 8 ρF: 20%

I. D A T A

1. AVERAGE MAINTAINED ILLUMINANCE: 250 lux


2. LUMINAIRE DATA:
ITEM NO. 27
2 X 60W, 230V, 60Hz
COOL WHITE, PORCELAIN-ENAMELED REFECTOR
3. ATMOSPHERE: VERY CLEAN
4. ROOM SURFACE REFLECTANCES:
CEILING: 80% WALL: 50% FLOOR: 20%
5. OPERATING CHARACTERISTIC: 10hrs/starting/day
6. CLEANING CYCLE: 12 MONTHS
II. C A L C U L A T I O N
26.8+3
1. CCR ¿ (5)(0)=0
26.8∗3
26.8+3
RCR= (5)( 4)=7.41
26.8∗3
26.8+3
FCR= (5)( 0)=0
26.8∗3
2. OBTAIN EFFECTIVE CEILING CAVITY REFLECTANCE, ρCC
% BASE REFLECTANCE = 80%
% WALL REFLECTANCE = 50%
CCR =0
ρCC = 80%
3. OBTAIN EFFECTIVE FLOOR CAVITY REFLECTANCE, ρFC
% BASE REFLECTANCE = 20%
% WALL REFLECTANDCE = 50%
FCR =0
ρFC = 20%
4. OBTAIN COEFFICIENT OF UTILIZATION, CU
ρCC = 80%
ρW = 50%
RCR = 7.41
CU = 0.4095
BY INTERPOLATION, SOLVE CU
RCR CU
7 .43
7.41 CU
8 0.38

5. ROOM SURFACE DIRT DEPRECIATION FACTOR, RSDD


THE LIGHT DISTRIBUTION IS CLASSIFIED AS SEMI-DIRECT
EXPECTED DIRT DEPRECIATION FACTOR IS 8%

RCR = 7.41
RSDD = 93.295%
BY INTERPOLATION, SOLVE RSDD
RCR
6 94
7.41 RSDD
8 93
RSDD = 93.295%
6. LAMP LUMEN DEPRECIATIO FACTOR, LLD
BY INTERPOLATION:
6−10 87−RSDD
=
6−12 87−86
LLD = 86.33%
7. LAMP BURN OUT, LBO
LBO = 100%

8. ILLUMINANCE DIRT DEPRECIATION FACTOR, LDD


-AT ANNUALY CLAENING CYCLE, VERY CLEAN ATMOSPHERE MAINTENANCE
CATEGORY II
LDD = 97%
9. LIGHT LOSS FACTOR, LLF
LLF = (RSDD) (LLD) (LBO) (LDD)
= (93.29%) (86.33%) (100%) (97%)
LLF = 78.12%

10. TOTAL NUMBER OF LUMINAIRES, N

(ILLUMINANCE) (AREA)
N=
(LUMENS/LUMINAIRE) (CU)(LLF)
250∗26.8∗3
=
8300∗.7812∗.4095
= 7.57
N = 8 LUMINAIRES

11. FORMATION / SPACING OF LUMINAIRE

LX N 26.8 X 8
C=

N

W
8
=
3 √ =8.45=8

R= = =1
C 8

W 3
XW = = =3 m
R 1

L 26.8
XL = = =3.35 m
C 8

WHERE:
C = NO. OF COLUMNS OF LUMINAIRES ALONG THE WIDTH OF THE ROOM.
R = NO. OF ROWS OF LUMINAIRES ALONG THE LENGTH OF THE ROOM.
XW = SPACING BETWEEN LUMINAIRES ALONG THE LENGTH OF THE
ROOM.
XL = SPACING BETWEEN LUMINAIRES ALONG THE WIDTH OF THE ROOM.
12. ACTUAL ILLUMINATION
LUMENS
( )(CU )(LLF)(N ) 8300 X 0.4095 X 0.7812 X 8
ILL = LUMINAIRE =
26.8∗3
AREA

= 264.19 LUX

LENGTH: 26.8 m
WIDTH: 3 m
NO. OF LUMINAIRES: 8
X L= 3.35 m
Xw = 3 m
AVERAGE ILLUMINATION CALCULATION SHEET

ROOM CLASSIFICATION: HALLWAY 2

LENGTH: 7.75m HCC: 0 ρC: 80%


WIDTH: 3.6m HRC: 3.2 ρW: 50%
HEIGHT: 4m HFC: 0 ρF: 20%
I. D A T A

1. AVERAGE MAINTAINED ILLUMINANCE: 250 lux


2. LUMINAIRE DATA:
ITEM NO. 27
2 X 60W, 230V, 60Hz
COOL WHITE, PORCELAIN-ENAMELED REFECTOR
3. AREA ATMOSPHERE: VERY CLEAN
4. ROOM SURFACE REFLECTANCES:
CEILING: 80% WALL: 50% FLOOR: 20%
5. OPERATING CHARACTERISTIC: 10hrs/starting/day
6. CLEANING CYCLE: 12 MONTHS
II. C A L C U L A T I O N
7.75+ 3.6
1. CCR ¿ (5)( 0)=0
7.75∗3.6
7.75+3.6
RCR= (5)( 4)=8.14
7.75∗3.6
7.75+3.6
FCR= (5)(0)=0
7.75∗3.6
2. OBTAIN EFFECTIVE CEILING CAVITY REFLECTANCE, ρCC
% BASE REFLECTANCE = 80%
% WALL REFLECTANCE = 50%
CCR =0
ρCC = 80%
3. OBTAIN EFFECTIVE FLOOR CAVITY REFLECTANCE, ρFC
% BASE REFLECTANCE = 20%
% WALL REFLECTANDCE = 50%
FCR =0
ρFC = 20%
4. OBTAIN COEFFICIENT OF UTILIZATION, CU
ρCC = 80%
ρW = 50%
RCR = 8.14
CU = 0.3758
BY INTERPOLATION, SOLVE CU
RCR CU
8 .38
8.13 CU
9 .35

5. ROOM SURFACE DIRT DEPRECIATION FACTOR, RSDD


THE LIGHT DISTRIBUTION IS CLASSIFIED AS SEMI-DIRECT
EXPECTED DIRT DEPRECIATION FACTOR IS 8%

RCR = 8.14
RSDD = 93.29%
BY INTERPOLATION, SOLVE RSDD
RCR
6 94
8.14 RSDD
9 93
RSDD = 93.29%
6. LAMP LUMEN DEPRECIATIO FACTOR, LLD
BY INTERPOLATION:
6−10 87−RSDD
=
6−12 87−86
LLD = 86.33%
7. LAMP BURN OUT, LBO
LBO = 100%

8. ILLUMINANCE DIRT DEPRECIATION FACTOR, LDD


-AT ANNUALY CLAENING CYCLE, VERY CLEAN ATMOSPHERE MAINTENANCE
CATEGORY II
LDD = 97%
9. LIGHT LOSS FACTOR, LLF
LLF = (RSDD) (LLD) (LBO) (LDD)
= (93.29%) (86.33%) (100%) (97%)
LLF = 78.12%

10. TOTAL NUMBER OF LUMINAIRES, N

(ILLUMINANCE) (AREA)
N=
(LUMENS/LUMINAIRE) (CU)(LLF)
250∗7.75∗3.6
=
8300∗.7812∗.3758
= 2.86
N = 3 LUMINAIRES
11. FORMATION / SPACING OF LUMINAIRE

LX N 7.75 X 3
C=
N

W
3
=
3.6 √=2.54=3

R= = =1
C 3

W 3.6
XW = = =3.6 m
R 1

L 7.75
XL = = =2.58 m
C 3

WHERE:
C = NO. OF COLUMNS OF LUMINAIRES ALONG THE WIDTH OF THE ROOM.
R = NO. OF ROWS OF LUMINAIRES ALONG THE LENGTH OF THE ROOM.
XW = SPACING BETWEEN LUMINAIRES ALONG THE LENGTH OF THE
ROOM.
XL = SPACING BETWEEN LUMINAIRES ALONG THE WIDTH OF THE ROOM.

12. ACTUAL ILLUMINATION


LUMENS
( )(CU )(LLF)(N ) 8300 X 0.562 X 0.7930 X 8
ILL = LUMINAIRE =
8.35∗6.7
AREA

= 528.95 LUX
LENGTH: 7.75 m
WIDTH: 3.6 m
NO. OF LUMINAIRES: 3
X L= 2.58 m
Xw = 3.6 m
AVERAGE ILLUMINATION CALCULATION SHEET
TH
6 FLOOR
ROOM CLASSIFICATION: CLASSROOM (1,2,3)

LENGTH: 8.35m HCC: 0 ρC: 80%


WIDTH: 6.7m HRC: 3.2 ρW: 50%
HEIGHT: 4m HFC: 0.8 ρF: 20%

I. D A T A

1. AVERAGE MAINTAINED ILLUMINANCE: 500 lux


2. LUMINAIRE DATA:
ITEM NO. 27
2 X 60W, 230V, 60Hz
COOL WHITE, PORCELAIN-ENAMELED REFECTOR
3. AREA ATMOSPHERE: VERY CLEAN
4. ROOM SURFACE REFLECTANCES:
CEILING: 80% WALL: 50% FLOOR: 20%
5. OPERATING CHARACTERISTIC: 10hrs/starting/day
6. CLEANING CYCLE: 12 MONTHS
II. C A L C U L A T I O N
8.35+6.7
1. CCR ¿ (5)(0)=0
8.35∗6.7
8.35.5+ 6.7
RCR= (5)(3.2)=4.30
8.35∗6.7
8.35+6.7
FCR= ( 5 )( 0.8)=1.08
48.35∗6.7
2. OBTAIN EFFECTIVE CEILING CAVITY REFLECTANCE, ρCC
% BASE REFLECTANCE = 80%
% WALL REFLECTANCE = 50%
CCR =0
ρCC = 80%
3. OBTAIN EFFECTIVE FLOOR CAVITY REFLECTANCE, ρFC
% BASE REFLECTANCE = 20%
% WALL REFLECTANDCE = 50%
FCR =1.08
ρFC = 19.6%
4. OBTAIN COEFFICIENT OF UTILIZATION, CU
ρCC = 80%
ρW = 50%
RCR = 4.30
CU = 28.6%
BY INTERPOLATION, SOLVE CU
RCR CU
4 .58
4.40 CU
5 .0.52

5. ROOM SURFACE DIRT DEPRECIATION FACTOR, RSDD


THE LIGHT DISTRIBUTION IS CLASSIFIED AS SEMI-DIRECT
EXPECTED DIRT DEPRECIATION FACTOR IS 8%

RCR = 4.30
RSDD = 94.7%
BY INTERPOLATION, SOLVE RSDD
RCR
4 95
4.30 RSDD
5 94
RSDD = 94.7%
6. LAMP LUMEN DEPRECIATIO FACTOR, LLD
BY INTERPOLATION:
6−10 87−RSDD
=
6−12 87−86
LLD = 86.33%
7. LAMP BURN OUT, LBO
LBO = 100%

8. ILLUMINANCE DIRT DEPRECIATION FACTOR, LDD


-AT ANNUALY CLAENING CYCLE, VERY CLEAN ATMOSPHERE MAINTENANCE
CATEGORY II
LDD = 97%
9. LIGHT LOSS FACTOR, LLF
LLF = (RSDD) (LLD) (LBO) (LDD)
= (94.7%) (86.33%) (100%) (97%)
LLF = 79.30%

10. TOTAL NUMBER OF LUMINAIRES, N

(ILLUMINANCE) (AREA)
N=
(LUMENS/LUMINAIRE) (CU)(LLF)
500∗8.35∗6.7
=
8300∗.7930∗.562
= 7.56
N = 8 LUMINAIRES
11. FORMATION / SPACING OF LUMINAIRE

LX N 8.35 X 8
C=
N

W
8
=
6.7 √=3.16=4

R= = =2
C 4

W 6.7
XW = = =3.35
R 2

L 8.35
XL = = =2.09
C 4

WHERE:
C = NO. OF COLUMNS OF LUMINAIRES ALONG THE WIDTH OF THE ROOM.
R = NO. OF ROWS OF LUMINAIRES ALONG THE LENGTH OF THE ROOM.
XW = SPACING BETWEEN LUMINAIRES ALONG THE LENGTH OF THE
ROOM.
XL = SPACING BETWEEN LUMINAIRES ALONG THE WIDTH OF THE ROOM.

12. ACTUAL ILLUMINATION


LUMENS
( )(CU )(LLF)(N ) 8300 X 0.562 X 0.7930 X 8
ILL = LUMINAIRE =
8.35∗6.7
AREA

= 528.95 LUX
LENGTH: 8.35 m
WIDTH: 6.7 m
NO. OF LUMINAIRES: 8
X L= 2.0875 m
Xw = 3.35 m
AVERAGE ILLUMINATION CALCULATION SHEET

ROOM CLASSIFICATION: CLASSROOM (4)

LENGTH: 7.98m HCC: 0 ρC: 80%


WIDTH: 7.75m HRC: 4 ρW: 50%
HEIGHT: 4m HFC: 0 8 ρF: 20%

I. D A T A
1. AVERAGE MAINTAINED ILLUMINANCE: 500 lux
2. LUMINAIRE DATA:
ITEM NO. 27
2 X 60W, 230V, 60Hz
COOL WHITE, PORCELAIN-ENAMELED REFECTOR
3. AREA ATMOSPHERE: VERY CLEAN
4. ROOM SURFACE REFLECTANCES:
CEILING: 80% WALL: 50% FLOOR: 20%
5. OPERATING CHARACTERISTIC: 10hrs/starting/day
6. CLEANING CYCLE: 12 MONTHS
II. C A L C U L A T I O N
8.35+6.7
1. CCR ¿ (5)(0)=0
8.35∗6.7
8.35.5+ 6.7
RCR= (5)(3.2)=4.30
8.35∗6.7
8.35+6.7
FCR= ( 5 )( 0.8)=1.08
48.35∗6.7
2. OBTAIN EFFECTIVE CEILING CAVITY REFLECTANCE, ρCC
% BASE REFLECTANCE = 80%
% WALL REFLECTANCE = 50%
CCR =0
ρCC = 80%
3. OBTAIN EFFECTIVE FLOOR CAVITY REFLECTANCE, ρFC
% BASE REFLECTANCE = 20%
% WALL REFLECTANDCE = 50%
FCR =1.08
ρFC = 19.6%
4. OBTAIN COEFFICIENT OF UTILIZATION, CU
ρCC = 80%
ρW = 50%
RCR = 4.30
CU = 28.6%

BY INTERPOLATION, SOLVE CU
RCR CU
4 .58
4.40 CU
5 .0.52

5. ROOM SURFACE DIRT DEPRECIATION FACTOR, RSDD


THE LIGHT DISTRIBUTION IS CLASSIFIED AS SEMI-DIRECT
EXPECTED DIRT DEPRECIATION FACTOR IS 8%

RCR = 4.30
RSDD = 94.93%
BY INTERPOLATION, SOLVE RSDD
RCR
4 95
4.07 RSDD
5 94
RSDD = 94.7%
6. LAMP LUMEN DEPRECIATIO FACTOR, LLD
BY INTERPOLATION:
6−10 87−RSDD
=
6−12 87−86
LLD = 86.33%
7. LAMP BURN OUT, LBO
LBO = 100%

8. ILLUMINANCE DIRT DEPRECIATION FACTOR, LDD


-AT ANNUALY CLAENING CYCLE, VERY CLEAN ATMOSPHERE MAINTENANCE
CATEGORY II
LDD = 97%
9. LIGHT LOSS FACTOR, LLF
LLF = (RSDD) (LLD) (LBO) (LDD)
= (94%) (86.33%) (100%) (97%)
LLF = 79.5%

10. TOTAL NUMBER OF LUMINAIRES, N

(ILLUMINANCE) (AREA)
N=
(LUMENS/LUMINAIRE) (CU)(LLF)
500∗7.98∗7.75
=
8300∗.795∗.576
= 8.13
N = 8 LUMINAIRES

11. FORMATION / SPACING OF LUMINAIRE

LX N 7.98 X 8
C=

N

W
8
=
7.75 √
=2.87=2

R= = =4
C 2

W 7,75
XW = = =1.9375 m
R 4

L 7.98
XL = = =3.99 m
C 2

WHERE:
C = NO. OF COLUMNS OF LUMINAIRES ALONG THE WIDTH OF THE ROOM.
R = NO. OF ROWS OF LUMINAIRES ALONG THE LENGTH OF THE ROOM.
XW = SPACING BETWEEN LUMINAIRES ALONG THE LENGTH OF THE
ROOM.
XL = SPACING BETWEEN LUMINAIRES ALONG THE WIDTH OF THE ROOM.

12. ACTUAL ILLUMINATION


LUMENS
( )(CU )(LLF)(N ) 8300 X 0.576 X 0.7950 X 8
ILL = LUMINAIRE =
7.98∗7.75
AREA

= 504.285 LUX
LENGTH: 7.98 m
WIDTH: 7.75 m
NO. OF LUMINAIRES: 8
X L= 3.99 m
Xw = 1.9375 m
AVERAGE ILLUMINATION CALCULATION SHEET

ROOM CLASSIFICATION: CLASSROOM (5,6,7)

LENGTH: 7.66m HCC: 0 ρC: 80%


WIDTH: 7.22m HRC: 4 ρW: 50%
HEIGHT: 4m HFC: 0 8 ρF: 20%

I. D A T A
1. AVERAGE MAINTAINED ILLUMINANCE: 500 lux
2. LUMINAIRE DATA:
ITEM NO. 27
2 X 60W, 230V, 60Hz
COOL WHITE, PORCELAIN-ENAMELED REFECTOR
3. ATMOSPHERE: VERY CLEAN
4. ROOM SURFACE REFLECTANCES:
CEILING: 80% WALL: 50% FLOOR: 20%
5. OPERATING CHARACTERISTIC: 10hrs/starting/day
6. CLEANING CYCLE: 12 MONTHS
II. C A L C U L A T I O N

7.66+7.22
1. CCR ¿ (5)(0)=0
7.66∗7.22
7.66+7.22
RCR= (5)(3.2)=4.30
7.66∗7.22
8.35+6.7
FCR= ( 5 )( 0.8)=1.08
48.35∗6.7
2. OBTAIN EFFECTIVE CEILING CAVITY REFLECTANCE, ρCC
% BASE REFLECTANCE = 80%
% WALL REFLECTANCE = 50%
CCR =0
ρCC = 80%
3. OBTAIN EFFECTIVE FLOOR CAVITY REFLECTANCE, ρFC
% BASE REFLECTANCE = 20%
% WALL REFLECTANDCE = 50%
FCR =1.08
ρFC = 19.62%
4. OBTAIN COEFFICIENT OF UTILIZATION, CU
ρCC = 80%
ρW = 50%
RCR = 4.30
CU = 0.562
BY INTERPOLATION, SOLVE CU
RCR CU
4 .58
4.40 CU
5 0.562

5. ROOM SURFACE DIRT DEPRECIATION FACTOR, RSDD


THE LIGHT DISTRIBUTION IS CLASSIFIED AS SEMI-DIRECT
EXPECTED DIRT DEPRECIATION FACTOR IS 8%

RCR = 4.30
RSDD = 94.7%
BY INTERPOLATION, SOLVE RSDD
RCR
4 95
4.30 RSDD
5 94
RSDD = 94.7%
6. LAMP LUMEN DEPRECIATIO FACTOR, LLD
BY INTERPOLATION:
6−10 87−RSDD
=
6−12 87−86
LLD = 86.33%
7. LAMP BURN OUT, LBO
LBO = 100%

8. ILLUMINANCE DIRT DEPRECIATION FACTOR, LDD


-AT ANNUALY CLAENING CYCLE, VERY CLEAN ATMOSPHERE MAINTENANCE
CATEGORY II
LDD = 97%

9. LIGHT LOSS FACTOR, LLF


LLF = (RSDD) (LLD) (LBO) (LDD)
= (94.7%) (86.33%) (100%) (97%)
LLF = 79.30%

10. TOTAL NUMBER OF LUMINAIRES, N

(ILLUMINANCE) (AREA)
N=
(LUMENS/LUMINAIRE) (CU)(LLF)
500∗7.66∗7.22
=
8300∗.7930∗.562
= 7.47
N = 8 LUMINAIRES

11. FORMATION / SPACING OF LUMINAIRE

LX N 7.66 X 8
C=
N

W
8
=
7.22 √
=2.91=2

R= = =4
C 2

W 7.22
XW = = =1.805 m
R 4

L 7.66
XL = = =3.83 m
C 2

WHERE:
C = NO. OF COLUMNS OF LUMINAIRES ALONG THE WIDTH OF THE ROOM.
R = NO. OF ROWS OF LUMINAIRES ALONG THE LENGTH OF THE ROOM.
XW = SPACING BETWEEN LUMINAIRES ALONG THE LENGTH OF THE
ROOM.
XL = SPACING BETWEEN LUMINAIRES ALONG THE WIDTH OF THE ROOM.

12. ACTUAL ILLUMINATION


LUMENS
( )(CU )(LLF)(N ) 8300 X 0.562 X 0.7930 X 8
ILL = LUMINAIRE =
7.66∗7.22
AREA

= 535.07 LUX
LENGTH: 7.66 m
WIDTH: 7.22 m
NO. OF LUMINAIRES: 8
X L= 3.83 m
Xw = 1.805 m
AVERAGE ILLUMINATION CALCULATION SHEET

ROOM CLASSIFICATION: HALLWAY

LENGTH: 26.8m HCC: 0 ρC: 80%


WIDTH: 3m HRC: 4 ρW: 50%
HEIGHT: 4m HFC: 0 8 ρF: 20%

I. D A T A

1. AVERAGE MAINTAINED ILLUMINANCE: 250 lux


2. LUMINAIRE DATA:
ITEM NO. 27
2 X 60W, 230V, 60Hz
COOL WHITE, PORCELAIN-ENAMELED REFECTOR
3. ATMOSPHERE: VERY CLEAN
4. ROOM SURFACE REFLECTANCES:
CEILING: 80% WALL: 50% FLOOR: 20%
5. OPERATING CHARACTERISTIC: 10hrs/starting/day
6. CLEANING CYCLE: 12 MONTHS
II. C A L C U L A T I O N
26.8+3
1. CCR ¿ (5)(0)=0
26.8∗3
26.8+3
RCR= (5)( 4)=7.41
26.8∗3
26.8+3
FCR= (5)( 0)=0
26.8∗3
2. OBTAIN EFFECTIVE CEILING CAVITY REFLECTANCE, ρCC
% BASE REFLECTANCE = 80%
% WALL REFLECTANCE = 50%
CCR =0
ρCC = 80%
3. OBTAIN EFFECTIVE FLOOR CAVITY REFLECTANCE, ρFC
% BASE REFLECTANCE = 20%
% WALL REFLECTANDCE = 50%
FCR =0
ρFC = 20%
4. OBTAIN COEFFICIENT OF UTILIZATION, CU
ρCC = 80%
ρW = 50%
RCR = 7.41
CU = 0.4095
BY INTERPOLATION, SOLVE CU
RCR CU
7 .43
7.41 CU
8 0.38

5. ROOM SURFACE DIRT DEPRECIATION FACTOR, RSDD


THE LIGHT DISTRIBUTION IS CLASSIFIED AS SEMI-DIRECT
EXPECTED DIRT DEPRECIATION FACTOR IS 8%

RCR = 7.41
RSDD = 93.295%
BY INTERPOLATION, SOLVE RSDD
RCR
6 94
7.41 RSDD
8 93
RSDD = 93.295%
6. LAMP LUMEN DEPRECIATIO FACTOR, LLD
BY INTERPOLATION:
6−10 87−RSDD
=
6−12 87−86
LLD = 86.33%
7. LAMP BURN OUT, LBO
LBO = 100%

8. ILLUMINANCE DIRT DEPRECIATION FACTOR, LDD


-AT ANNUALY CLAENING CYCLE, VERY CLEAN ATMOSPHERE MAINTENANCE
CATEGORY II
LDD = 97%
9. LIGHT LOSS FACTOR, LLF
LLF = (RSDD) (LLD) (LBO) (LDD)
= (93.29%) (86.33%) (100%) (97%)
LLF = 78.12%

10. TOTAL NUMBER OF LUMINAIRES, N

(ILLUMINANCE) (AREA)
N=
(LUMENS/LUMINAIRE) (CU)(LLF)
250∗26.8∗3
=
8300∗.7812∗.4095
= 7.57
N = 8 LUMINAIRES

11. FORMATION / SPACING OF LUMINAIRE

LX N 26.8 X 8
C=

N

W
8
=
3 √ =8.45=8

R= = =1
C 8

W 3
XW = = =3 m
R 1

L 26.8
XL = = =3.35 m
C 8

WHERE:
C = NO. OF COLUMNS OF LUMINAIRES ALONG THE WIDTH OF THE ROOM.
R = NO. OF ROWS OF LUMINAIRES ALONG THE LENGTH OF THE ROOM.
XW = SPACING BETWEEN LUMINAIRES ALONG THE LENGTH OF THE
ROOM.
XL = SPACING BETWEEN LUMINAIRES ALONG THE WIDTH OF THE ROOM.
12. ACTUAL ILLUMINATION
LUMENS
( )(CU )(LLF)(N ) 8300 X 0.4095 X 0.7812 X 8
ILL = LUMINAIRE =
26.8∗3
AREA

= 264.19 LUX

LENGTH: 26.8 m
WIDTH: 3 m
NO. OF LUMINAIRES: 8
X L= 3.35 m
Xw = 3 m
AVERAGE ILLUMINATION CALCULATION SHEET

ROOM CLASSIFICATION: HALLWAY 2

LENGTH: 7.75m HCC: 0 ρC: 80%


WIDTH: 3.6m HRC: 3.2 ρW: 50%
HEIGHT: 4m HFC: 0 ρF: 20%
I. D A T A
1. AVERAGE MAINTAINED ILLUMINANCE: 250 lux
2. LUMINAIRE DATA:
ITEM NO. 27
2 X 60W, 230V, 60Hz
COOL WHITE, PORCELAIN-ENAMELED REFECTOR
3. AREA ATMOSPHERE: VERY CLEAN
4. ROOM SURFACE REFLECTANCES:
CEILING: 80% WALL: 50% FLOOR: 20%
5. OPERATING CHARACTERISTIC: 10hrs/starting/day
6. CLEANING CYCLE: 12 MONTHS
II. C A L C U L A T I O N

7.75+ 3.6
1. CCR ¿ (5)( 0)=0
7.75∗3.6
7.75+3.6
RCR= (5)( 4)=8.14
7.75∗3.6
7.75+3.6
FCR= (5)(0)=0
7.75∗3.6
2. OBTAIN EFFECTIVE CEILING CAVITY REFLECTANCE, ρCC
% BASE REFLECTANCE = 80%
% WALL REFLECTANCE = 50%
CCR =0
ρCC = 80%
3. OBTAIN EFFECTIVE FLOOR CAVITY REFLECTANCE, ρFC
% BASE REFLECTANCE = 20%
% WALL REFLECTANDCE = 50%
FCR =0
ρFC = 20%
4. OBTAIN COEFFICIENT OF UTILIZATION, CU
ρCC = 80%
ρW = 50%
RCR = 8.14
CU = 0.3758
BY INTERPOLATION, SOLVE CU
RCR CU
8 .38
8.13 CU
9 .35

5. ROOM SURFACE DIRT DEPRECIATION FACTOR, RSDD


THE LIGHT DISTRIBUTION IS CLASSIFIED AS SEMI-DIRECT
EXPECTED DIRT DEPRECIATION FACTOR IS 8%

RCR = 8.14
RSDD = 93.29%
BY INTERPOLATION, SOLVE RSDD
RCR
6 94
8.14 RSDD
9 93
RSDD = 93.29%
6. LAMP LUMEN DEPRECIATIO FACTOR, LLD
BY INTERPOLATION:
6−10 87−RSDD
=
6−12 87−86
LLD = 86.33%
7. LAMP BURN OUT, LBO
LBO = 100%

8. ILLUMINANCE DIRT DEPRECIATION FACTOR, LDD


-AT ANNUALY CLAENING CYCLE, VERY CLEAN ATMOSPHERE MAINTENANCE
CATEGORY II
LDD = 97%
9. LIGHT LOSS FACTOR, LLF
LLF = (RSDD) (LLD) (LBO) (LDD)
= (93.29%) (86.33%) (100%) (97%)
LLF = 78.12%

10. TOTAL NUMBER OF LUMINAIRES, N

(ILLUMINANCE) (AREA)
N=
(LUMENS/LUMINAIRE) (CU)(LLF)
250∗7.75∗3.6
=
8300∗.7812∗.3758
= 2.86
N = 3 LUMINAIRES
11. FORMATION / SPACING OF LUMINAIRE

LX N 7.75 X 3
C=
N

W
3
=
3.6 √=2.54=3

R= = =1
C 3

W 3.6
XW = = =3.6 m
R 1

L 7.75
XL = = =2.58 m
C 3

WHERE:
C = NO. OF COLUMNS OF LUMINAIRES ALONG THE WIDTH OF THE ROOM.
R = NO. OF ROWS OF LUMINAIRES ALONG THE LENGTH OF THE ROOM.
XW = SPACING BETWEEN LUMINAIRES ALONG THE LENGTH OF THE
ROOM.
XL = SPACING BETWEEN LUMINAIRES ALONG THE WIDTH OF THE ROOM.

12. ACTUAL ILLUMINATION


LUMENS
( )(CU )(LLF)(N ) 8300 X 0.562 X 0.7930 X 8
ILL = LUMINAIRE =
8.35∗6.7
AREA

= 528.95 LUX
LENGTH: 7.75 m
WIDTH: 3.6 m
NO. OF LUMINAIRES: 3
X L= 2.58 m
Xw = 3.6 m
BRANCH CIRCUIT FOR LIGHTING, Size of the protective device:
PURPOSE OUTLET (C.O.) LP1
Use: 2 Pole, 15 AT, 60 AF, 230V, MCCB, 60 Hz.
GENERAL INFORMATION
Size of conduit, see appendix C, P1541
Circuit No. 1
Use: 15 mm dia., PVC
Number of luminaires (N): 14
GENERAL INFORMATION
Number of lamps per luminaire: 2
Circuit No. 3
Full load current or VA load: 0.26A
Number of luminaires (N): 19
Operating Voltage: 230
Number of lamps per luminaire: 8-2x60w F.L.,1-
Operating Frequency: 60 1x60w F.L.,10-40 incandescent lamp

Full load current, IL Full load current or VA load: 0.26A, 0.17A

IL = [(14) (2) (60)] / 230 = 7.3A Operating Voltage: 230

Size of the branch circuit conductor, P350 Operating Frequency: 60

Use: 2-2.00mm2, THHN, CU. Wire / 25A Full load current, IL

Size of the protective device: IL = {(8) (2) (60) / 230 + (1) (60)/230 +(10)
(40)/230} = 6.17A
Use: 2 Pole, 15 AT, 60 AF, 230V, MCCB, 60 Hz.
Size of the branch circuit conductor, P350
Size of conduit, see appendix C, P1541
Use: 2-2.00mm2, THHN, CU. Wire / 25A
Use: 15 mm dia., PVC
Size of the protective device:
GENERAL INFORMATION
Use: 2 Pole, 15 AT, 60 AF, 230V, MCCB, 60 Hz.
Circuit No. 2
Size of conduit, see appendix C, P1541
Number of luminaires (N): 17
Use: 15 mm dia., PVC
Number of lamps per luminaire: 13-2x60w F.L.,2-
1x60w F.L.,2-40 incandescent lamp GENERAL INFORMATION

Full load current or VA load: 0.26A, 0.17A Circuit No. 4

Operating Voltage: 230 Number of luminaires (N): 11

Operating Frequency: 60 Number of lamps per luminaire: 2

Full load current, IL Full load current or VA load: 0.26A

IL = [(13) (2) (60) + (2) (60) +(2) (40)] / 230 = 7.65 Operating Voltage: 230
A
Operating Frequency: 60
Size of the branch circuit conductor, P350
Full load current, IL
Use: 2-2.00mm2, THHN, CU. Wire / 25A
IL = {(11) (2x60) /230} =5.74 A
Size of the branch circuit conductor, P350 Size of the branch circuit conductor, P350

Use: 2-2.00mm2, THHN, CU. Wire / 25A Use: 2-3.5mm2, THHN, CU. Wire / 30A

Size of the protective device: Size of the protective device:

Use: 2 Pole, 15 AT, 60 AF, 230V, MCCB, 60 Hz. Use: 2 Pole, 15 AT, 60 AF, 230V, MCCB, 60 Hz.

Size of conduit, see appendix C, P1541 Size of conduit, see appendix C, P1541

Use: 15 mm dia., PVC Use: 15 mm dia., PVC

GENERAL INFORMATION GENERAL INFORMATION

Circuit No. 5 Circuit No. 7

Number of luminaires (N): 12 Number of luminaires (N): 12

Number of lamps per luminaire: 11-2x60w F.L.,1- Number of lamps per luminaire: 2
1x60w F.L.
Full load current or VA load: 0.26A
Full load current or VA load: 0.26A, 0.17a
Operating Voltage: 230
Operating Voltage: 230
Operating Frequency: 60
Operating Frequency: 60
Full load current, IL
Full load current, IL
IL = {(12) (2) (60) / 230}
IL = [(11) (2) (60) + (1) (60)] / 230 = 6A
= 6.26A
Size of the branch circuit conductor, P350
Size of the branch circuit conductor, P350
Use: 2-2.00mm2, THHN, CU. Wire / 25A
Use: 2-3.5mm2, THHN, CU. Wire / 30A
Size of the protective device:
Size of the protective device:
Use: 2 Pole, 15 AT, 60 AF, 230V, MCCB, 60 Hz.
Use: 2 Pole, 15 AT, 60 AF, 230V, MCCB, 60 Hz.
Size of conduit, see appendix C, P1541
Size of conduit, see appendix C, P1541
Use: 15 mm dia., PVC
Use: 15 mm dia., PVC
GENERAL INFORMATION
GENERAL INFORMATION
Circuit No. 6
Circuit No. 8
Number of luminaires (N): 13
Number of duplex C.O. per circuit: 5
Number of lamps per luminaire: 12-2x60w F.L.,1-
40 incandescent lamp 180VA per Duplex C.O:

Full load current or VA load: 0.26A, 0.17A Operating Voltage: 230

Operating Voltage: 230 Operating Frequency: 60

Operating Frequency: 60 Full load current, IL

Full load current, IL IL = [(5) (180)] / 230 = 3.91A

IL = [(12) (2) (60) + (1) (40)] / 230 = 6.43A Size of the branch circuit conductor, P350
Use: 2-2.00mm2, THHN, CU. Wire / 25A Use: 2 Pole, 20 AT, 60 AF, 230V, MCCB, 60 Hz.

Size of the protective device: Size of conduit, see appendix C, P1541

Use: 2 Pole, 15 AT, 60 AF, 230V, MCCB, 60 Hz. Use: 15 mm dia., PVC

Size of conduit, see appendix C, P1541 GENERAL INFORMATION

Use: 15 mm dia., PVC Circuit No. 11

GENERAL INFORMATION Number of duplex C.O. per circuit: 5-C.O.,2-


EMERGENCY LIGHT OUTLET(100W)
Circuit No. 9
180VA per Duplex C.O:
Number of duplex C.O. per circuit: 5-C.O.,1
EMERGENCY LIGHT OUTLET(100W) Operating Voltage: 230

180VA per Duplex C.O: Operating Frequency: 60

Operating Voltage: 230 Full load current, IL

Operating Frequency: 60 IL = [(5) (180) +(2) (100)] / 230 = 4.78A

Full load current, IL Size of the branch circuit conductor, P350

IL = [(5) (180) +(100)] / 230 = 4.35A Use: 2-3.5mm2, THHN, CU. Wire / 30A

Size of the branch circuit conductor, P350 Size of the protective device:

Use: 2-3.5mm2, THHN, CU. Wire / 30A Use: 2 Pole, 20 AT, 60 AF, 230V, MCCB, 60 Hz.

Size of the protective device: Size of conduit, see appendix C, P1541

Use: 2 Pole, 20 AT, 60 AF, 230V, MCCB, 60 Hz. Use: 15 mm dia., PVC

Size of conduit, see appendix C, P1541 GENERAL INFORMATION

Use: 15 mm dia., PVC Circuit No. 12

GENERAL INFORMATION Number of duplex C.O. per circuit: 5

Circuit No. 10 180VA per Duplex C.O:

Number of duplex C.O. per circuit: 5-C.O.,2- Operating Voltage: 230


EMERGENCY LIGHT OUTLET(100W)
Operating Frequency: 60
180VA per Duplex C.O:
Full load current, IL
Operating Voltage: 230
IL = [(5) (180)] / 230 = 3.91A
Operating Frequency: 60
Size of the branch circuit conductor, P350
Full load current, IL
Use: 2-3.5mm2, THHN, CU. Wire / 30A
IL = [(5) (180) +(2) (100)] / 230 = 4.78A
Size of the protective device:
Size of the branch circuit conductor, P350
Use: 2 Pole, 20 AT, 60 AF, 230V, MCCB, 60 Hz.
2
Use: 2-3.5mm , THHN, CU. Wire / 30A
Size of conduit, see appendix C, P1541
Size of the protective device:
Use: 15 mm dia., PVC
GENERAL INFORMATION

Circuit No. 13

Number of duplex C.O. per circuit: 5-C.O.,2-


EMERGENCY LIGHT OUTLET(100W)

180VA per Duplex C.O:

Operating Voltage: 230

Operating Frequency: 60

Full load current, IL

IL = [(5) (180) +(2) (100)] / 230 = 4.78A

Size of the branch circuit conductor, P350

Use: 2-3.5mm2, THHN, CU. Wire / 30A

Size of the protective device:

Use: 2 Pole, 20 AT, 60 AF, 230V, MCCB, 60 Hz.

Size of conduit, see appendix C, P1541

Use: 15 mm dia., PVC

GENERAL INFORMATION

Circuit No. 14

Number of duplex C.O. per circuit: 8-C.O.,1-


EMERGENCY LIGHT OUTLET(100W)

180VA per Duplex C.O:

Operating Voltage: 230

Operating Frequency: 60

Full load current, IL

IL = [(8) (180) +(1) (100)] / 230 = 6.7A

Size of the branch circuit conductor, P350

Use: 2-3.5mm2, THHN, CU. Wire / 30A

Size of the protective device:

Use: 2 Pole, 20 AT, 60 AF, 230V, MCCB, 60 Hz.

Size of conduit, see appendix C, P1541

Use: 15 mm dia., PVC

BRANCH CIRCUIT FOR MOTORS


PP1- ACU1 Size of the protective device:

GENERAL INFORMATION MSCP = 250 %( IFL)

Circuit No. 1 MSCP = 2.5(8) = 20 A

Type of motor: Synchronous Induction Motor Use: 2P, 30AT, 60 AF, 240V, 60Hz, MCCB

Horsepower rating: 1 HP Size of the Conduit

Number of phases: 1 Use: 15mm dia., PVC

Operating voltage: 230 GENERAL INFORMATION

Code letter: Circuit No. 3

Use: Window Type ACU Type of motor: Synchronous Induction Motor

IL = 125% ( IFL) Horsepower rating: 1 HP

=1.25 (8) Number of phases: 1

= 10 A Operating voltage: 230

Use: 2-3.5mm2, THHN, CU. Wire / 30A Code letter:

Size of the protective device: Use: Window Type ACU

MSCP = 250 %( IFL) IL = 125% ( IFL)

MSCP = 2.5(8) = 20 A =1.25 (8)

Use: 2P, 30AT, 60 AF, 240V, 60Hz, MCCB = 10 A

Size of the Conduit Use: 2-3.5mm2, THHN, CU. Wire / 30A

Use: 15mm dia., PVC Size of the protective device:

GENERAL INFORMATION MSCP = 250 %( IFL)

Circuit No. 2 MSCP = 2.5(8) = 20 A

Type of motor: Synchronous Induction Motor Use: 2P, 30AT, 60 AF, 240V, 60Hz, MCCB

Horsepower rating: 1 HP Size of the Conduit

Number of phases: 1 Use: 15mm dia., PVC

Operating voltage: 230 GENERAL INFORMATION

Code letter: Circuit No. 4

Use: Window Type ACU Type of motor: Synchronous Induction Motor

IL = 125% ( IFL) Horsepower rating: 1 HP

=1.25 (8) Number of phases: 1

= 10 A Operating voltage: 230

Use: 2-3.5mm2, THHN, CU. Wire / 30A Code letter:


Use: Window Type ACU Circuit No. 6

IL = 125% ( IFL) Type of motor: Synchronous Induction Motor

=1.25 (8) Horsepower rating: 1 HP

= 10 A Number of phases: 1

Use: 2-3.5mm2, THHN, CU. Wire / 30A Operating voltage: 230

Size of the protective device: Code letter:

MSCP = 250 %( IFL) Use: Window Type ACU

MSCP = 2.5(8) = 20 A IL = 125% ( IFL)

Use: 2P, 30AT, 60 AF, 240V, 60Hz, MCCB =1.25 (8)

Size of the Conduit = 10 A

Use: 15mm dia., PVC Use: 2-3.5mm2, THHN, CU. Wire / 30A

GENERAL INFORMATION Size of the protective device:

Circuit No. 5 MSCP = 250 %( IFL)

Type of motor: Synchronous Induction Motor MSCP = 2.5(8) = 20 A

Horsepower rating: 1 HP Use: 2P, 30AT, 60 AF, 240V, 60Hz, MCCB

Number of phases: 1 Size of the Conduit

Operating voltage: 230 Use: 15mm dia., PVC

Code letter: GENERAL INFORMATION

Use: Window Type ACU Circuit No. 7

IL = 125% ( IFL) Type of motor: Synchronous Induction Motor

=1.25 (8) Horsepower rating: 1 HP

= 10 A Number of phases: 1

Use: 2-3.5mm2, THHN, CU. Wire / 30A Operating voltage: 230

Size of the protective device: Code letter:

MSCP = 250 %( IFL) Use: Window Type ACU

MSCP = 2.5(8) = 20 A IL = 125% ( IFL)

Use: 2P, 30AT, 60 AF, 240V, 60Hz, MCCB =1.25 (8)

Size of the Conduit = 10 A

Use: 15mm dia., PVC Use: 2-3.5mm2, THHN, CU. Wire / 30A

GENERAL INFORMATION Size of the protective device:


MSCP = 250 %( IFL)

MSCP = 2.5(8) = 20 A

Use: 2P, 30AT, 60 AF, 240V, 60Hz, MCCB

Size of the Conduit

Use: 15mm dia., PVC

BRANCH CIRCUIT FOR LIGHTING,


PURPOSE OUTLET (C.O.) LP2
GENERAL INFORMATION GENERAL INFORMATION

Circuit No. 1 Circuit No. 3

Number of luminaires (N): 14 Number of luminaires (N): 19

Number of lamps per luminaire: 2 Number of lamps per luminaire: 8-2x60w F.L.,1-
1x60w F.L.,10-40 incandescent lamp
Full load current or VA load: 0.26A
Full load current or VA load: 0.26A, 0.17A
Operating Voltage: 230
Operating Voltage: 230
Operating Frequency: 60
Operating Frequency: 60
Full load current, IL
Full load current, IL
IL = [(14) (2) (60)] / 230 = 7.3A
IL = {(8) (2) (60) / 230 + (1) (60)/230 +(10)
Size of the branch circuit conductor, P350 (40)/230} = 6.17A
Use: 2-2.00mm2, THHN, CU. Wire / 25A Size of the branch circuit conductor, P350
Size of the protective device: Use: 2-2.00mm2, THHN, CU. Wire / 25A
Use: 2 Pole, 15 AT, 60 AF, 230V, MCCB, 60 Hz. Size of the protective device:
Size of conduit, see appendix C, P1541 Use: 2 Pole, 15 AT, 60 AF, 230V, MCCB, 60 Hz.
Use: 15 mm dia., PVC Size of conduit, see appendix C, P1541
GENERAL INFORMATION Use: 15 mm dia., PVC
Circuit No. 2 GENERAL INFORMATION
Number of luminaires (N): 17 Circuit No. 4
Number of lamps per luminaire: 13-2x60w F.L.,2- Number of luminaires (N): 11
1x60w F.L.,2-40 incandescent lamp
Number of lamps per luminaire: 2
Full load current or VA load: 0.26A, 0.17A
Full load current or VA load: 0.26A
Operating Voltage: 230
Operating Voltage: 230
Operating Frequency: 60
Operating Frequency: 60
Full load current, IL
Full load current, IL
IL = [(13) (2) (60) + (2) (60) +(2) (40)] / 230 = 7.65
A IL = {(11) (2x60) /230} =5.74 A

Size of the branch circuit conductor, P350 Size of the branch circuit conductor, P350

Use: 2-2.00mm2, THHN, CU. Wire / 25A Use: 2-2.00mm2, THHN, CU. Wire / 25A

Size of the protective device: Size of the protective device:

Use: 2 Pole, 15 AT, 60 AF, 230V, MCCB, 60 Hz. Use: 2 Pole, 15 AT, 60 AF, 230V, MCCB, 60 Hz.

Size of conduit, see appendix C, P1541 Size of conduit, see appendix C, P1541

Use: 15 mm dia., PVC Use: 15 mm dia., PVC


GENERAL INFORMATION GENERAL INFORMATION

Circuit No. 5 Circuit No. 7

Number of luminaires (N): 12 Number of luminaires (N): 12

Number of lamps per luminaire: 11-2x60w F.L.,1- Number of lamps per luminaire: 2
1x60w F.L.
Full load current or VA load: 0.26A
Full load current or VA load: 0.26A, 0.17a
Operating Voltage: 230
Operating Voltage: 230
Operating Frequency: 60
Operating Frequency: 60
Full load current, IL
Full load current, IL
IL = {(12) (2) (60) / 230}
IL = [(11) (2) (60) + (1) (60)] / 230 = 6A
= 6.26A
Size of the branch circuit conductor, P350
Size of the branch circuit conductor, P350
2
Use: 2-2.00mm , THHN, CU. Wire / 25A
Use: 2-3.5mm2, THHN, CU. Wire / 30A
Size of the protective device:
Size of the protective device:
Use: 2 Pole, 15 AT, 60 AF, 230V, MCCB, 60 Hz.
Use: 2 Pole, 15 AT, 60 AF, 230V, MCCB, 60 Hz.
Size of conduit, see appendix C, P1541
Size of conduit, see appendix C, P1541
Use: 15 mm dia., PVC
Use: 15 mm dia., PVC
GENERAL INFORMATION
GENERAL INFORMATION
Circuit No. 6
Circuit No. 8
Number of luminaires (N): 13
Number of duplex C.O. per circuit: 5
Number of lamps per luminaire: 12-2x60w F.L.,1-
40 incandescent lamp 180VA per Duplex C.O:

Full load current or VA load: 0.26A, 0.17A Operating Voltage: 230

Operating Voltage: 230 Operating Frequency: 60

Operating Frequency: 60 Full load current, IL

Full load current, IL IL = [(5) (180)] / 230 = 3.91A

IL = [(12) (2) (60) + (1) (40)] / 230 = 6.43A Size of the branch circuit conductor, P350

Size of the branch circuit conductor, P350 Use: 2-2.00mm2, THHN, CU. Wire / 25A

Use: 2-3.5mm2, THHN, CU. Wire / 30A Size of the protective device:

Size of the protective device: Use: 2 Pole, 15 AT, 60 AF, 230V, MCCB, 60 Hz.

Use: 2 Pole, 15 AT, 60 AF, 230V, MCCB, 60 Hz. Size of conduit, see appendix C, P1541

Size of conduit, see appendix C, P1541 Use: 15 mm dia., PVC

Use: 15 mm dia., PVC GENERAL INFORMATION


Circuit No. 9 Number of duplex C.O. per circuit: 5-C.O.,2-
EMERGENCY LIGHT OUTLET(100W)
Number of duplex C.O. per circuit: 5-C.O.,1
EMERGENCY LIGHT OUTLET(100W) 180VA per Duplex C.O:

180VA per Duplex C.O: Operating Voltage: 230

Operating Voltage: 230 Operating Frequency: 60

Operating Frequency: 60 Full load current, IL

Full load current, IL IL = [(5) (180) +(2) (100)] / 230 = 4.78A

IL = [(5) (180) +(100)] / 230 = 4.35A Size of the branch circuit conductor, P350

Size of the branch circuit conductor, P350 Use: 2-3.5mm2, THHN, CU. Wire / 30A

Use: 2-3.5mm2, THHN, CU. Wire / 30A Size of the protective device:

Size of the protective device: Use: 2 Pole, 20 AT, 60 AF, 230V, MCCB, 60 Hz.

Use: 2 Pole, 20 AT, 60 AF, 230V, MCCB, 60 Hz. Size of conduit, see appendix C, P1541

Size of conduit, see appendix C, P1541 Use: 15 mm dia., PVC

Use: 15 mm dia., PVC GENERAL INFORMATION

GENERAL INFORMATION Circuit No. 12

Circuit No. 10 Number of duplex C.O. per circuit: 5

Number of duplex C.O. per circuit: 5-C.O.,2- 180VA per Duplex C.O:
EMERGENCY LIGHT OUTLET(100W)
Operating Voltage: 230
180VA per Duplex C.O:
Operating Frequency: 60
Operating Voltage: 230
Full load current, IL
Operating Frequency: 60
IL = [(5) (180)] / 230 = 3.91A
Full load current, IL
Size of the branch circuit conductor, P350
IL = [(5) (180) +(2) (100)] / 230 = 4.78A
Use: 2-3.5mm2, THHN, CU. Wire / 30A
Size of the branch circuit conductor, P350
Size of the protective device:
2
Use: 2-3.5mm , THHN, CU. Wire / 30A
Use: 2 Pole, 20 AT, 60 AF, 230V, MCCB, 60 Hz.
Size of the protective device:
Size of conduit, see appendix C, P1541
Use: 2 Pole, 20 AT, 60 AF, 230V, MCCB, 60 Hz.
Use: 15 mm dia., PVC
Size of conduit, see appendix C, P1541
GENERAL INFORMATION
Use: 15 mm dia., PVC
Circuit No. 13
GENERAL INFORMATION
Number of duplex C.O. per circuit: 5-C.O.,2-
Circuit No. 11 EMERGENCY LIGHT OUTLET(100W)

180VA per Duplex C.O:


Operating Voltage: 230

Operating Frequency: 60

Full load current, IL

IL = [(5) (180) +(2) (100)] / 230 = 4.78A

Size of the branch circuit conductor, P350

Use: 2-3.5mm2, THHN, CU. Wire / 30A

Size of the protective device:

Use: 2 Pole, 20 AT, 60 AF, 230V, MCCB, 60 Hz.

Size of conduit, see appendix C, P1541

Use: 15 mm dia., PVC

GENERAL INFORMATION

Circuit No. 14

Number of duplex C.O. per circuit: 8-C.O.,1-


EMERGENCY LIGHT OUTLET(100W)

180VA per Duplex C.O:

Operating Voltage: 230

Operating Frequency: 60

Full load current, IL

IL = [(8) (180) +(1) (100)] / 230 = 6.7A

Size of the branch circuit conductor, P350

Use: 2-3.5mm2, THHN, CU. Wire / 30A

Size of the protective device:

Use: 2 Pole, 20 AT, 60 AF, 230V, MCCB, 60 Hz.

Size of conduit, see appendix C, P1541

Use: 15 mm dia., PVC

BRANCH CIRCUIT FOR MOTORS

PP2- ACU2

GENERAL INFORMATION

Circuit No. 1

Type of motor: Synchronous Induction Motor

Horsepower rating: 1 HP
Number of phases: 1 Use: 15mm dia., PVC

Operating voltage: 230 GENERAL INFORMATION

Code letter: Circuit No. 3

Use: Window Type ACU Type of motor: Synchronous Induction Motor

IL = 125% ( IFL) Horsepower rating: 1 HP

=1.25 (8) Number of phases: 1

= 10 A Operating voltage: 230

Use: 2-3.5mm2, THHN, CU. Wire / 30A Code letter:

Size of the protective device: Use: Window Type ACU

MSCP = 250 %( IFL) IL = 125% ( IFL)

MSCP = 2.5(8) = 20 A =1.25 (8)

Use: 2P, 30AT, 60 AF, 240V, 60Hz, MCCB = 10 A

Size of the Conduit Use: 2-3.5mm2, THHN, CU. Wire / 30A

Use: 15mm dia., PVC Size of the protective device:

GENERAL INFORMATION MSCP = 250 %( IFL)

Circuit No. 2 MSCP = 2.5(8) = 20 A

Type of motor: Synchronous Induction Motor Use: 2P, 30AT, 60 AF, 240V, 60Hz, MCCB

Horsepower rating: 1 HP Size of the Conduit

Number of phases: 1 Use: 15mm dia., PVC

Operating voltage: 230 GENERAL INFORMATION

Code letter: Circuit No. 4

Use: Window Type ACU Type of motor: Synchronous Induction Motor

IL = 125% ( IFL) Horsepower rating: 1 HP

=1.25 (8) Number of phases: 1

= 10 A Operating voltage: 230

Use: 2-3.5mm2, THHN, CU. Wire / 30A Code letter:

Size of the protective device: Use: Window Type ACU

MSCP = 250 %( IFL) IL = 125% ( IFL)

MSCP = 2.5(8) = 20 A =1.25 (8)

Use: 2P, 30AT, 60 AF, 240V, 60Hz, MCCB = 10 A

Size of the Conduit Use: 2-3.5mm2, THHN, CU. Wire / 30A


Size of the protective device: Code letter:

MSCP = 250 %( IFL) Use: Window Type ACU

MSCP = 2.5(8) = 20 A IL = 125% ( IFL)

Use: 2P, 30AT, 60 AF, 240V, 60Hz, MCCB =1.25 (8)

Size of the Conduit = 10 A

Use: 15mm dia., PVC Use: 2-3.5mm2, THHN, CU. Wire / 30A

GENERAL INFORMATION Size of the protective device:

Circuit No. 5 MSCP = 250 %( IFL)

Type of motor: Synchronous Induction Motor MSCP = 2.5(8) = 20 A

Horsepower rating: 1 HP Use: 2P, 30AT, 60 AF, 240V, 60Hz, MCCB

Number of phases: 1 Size of the Conduit

Operating voltage: 230 Use: 15mm dia., PVC

Code letter: GENERAL INFORMATION

Use: Window Type ACU Circuit No. 7

IL = 125% ( IFL) Type of motor: Synchronous Induction Motor

=1.25 (8) Horsepower rating: 1 HP

= 10 A Number of phases: 1

Use: 2-3.5mm2, THHN, CU. Wire / 30A Operating voltage: 230

Size of the protective device: Code letter:

MSCP = 250 %( IFL) Use: Window Type ACU

MSCP = 2.5(8) = 20 A IL = 125% ( IFL)

Use: 2P, 30AT, 60 AF, 240V, 60Hz, MCCB =1.25 (8)

Size of the Conduit = 10 A

Use: 15mm dia., PVC Use: 2-3.5mm2, THHN, CU. Wire / 30A

GENERAL INFORMATION Size of the protective device:

Circuit No. 6 MSCP = 250 %( IFL)

Type of motor: Synchronous Induction Motor MSCP = 2.5(8) = 20 A

Horsepower rating: 1 HP Use: 2P, 30AT, 60 AF, 240V, 60Hz, MCCB

Number of phases: 1 Size of the Conduit

Operating voltage: 230 Use: 15mm dia., PVC


BRANCH CIRCUIT FOR LIGHTING,
PURPOSE OUTLET (C.O.) LP3

GENERAL INFORMATION

Circuit No. 1

Number of luminaires (N): 14

Number of lamps per luminaire: 2

Full load current or VA load: 0.26A


Operating Voltage: 230 Full load current or VA load: 0.26A, 0.17A

Operating Frequency: 60 Operating Voltage: 230

Full load current, IL Operating Frequency: 60

IL = [(14) (2) (60)] / 230 = 7.3A Full load current, IL

Size of the branch circuit conductor, P350 IL = {(8) (2) (60) / 230 + (1) (60)/230 +(10)
(40)/230} = 6.17A
Use: 2-2.00mm2, THHN, CU. Wire / 25A
Size of the branch circuit conductor, P350
Size of the protective device:
Use: 2-2.00mm2, THHN, CU. Wire / 25A
Use: 2 Pole, 15 AT, 60 AF, 230V, MCCB, 60 Hz.
Size of the protective device:
Size of conduit, see appendix C, P1541
Use: 2 Pole, 15 AT, 60 AF, 230V, MCCB, 60 Hz.
Use: 15 mm dia., PVC
Size of conduit, see appendix C, P1541
GENERAL INFORMATION
Use: 15 mm dia., PVC
Circuit No. 2
GENERAL INFORMATION
Number of luminaires (N): 17
Circuit No. 4
Number of lamps per luminaire: 13-2x60w F.L.,2-
1x60w F.L.,2-40 incandescent lamp Number of luminaires (N): 11

Full load current or VA load: 0.26A, 0.17A Number of lamps per luminaire: 2

Operating Voltage: 230 Full load current or VA load: 0.26A

Operating Frequency: 60 Operating Voltage: 230

Full load current, IL Operating Frequency: 60

IL = [(13) (2) (60) + (2) (60) +(2) (40)] / 230 = 7.65 Full load current, IL
A
IL = {(11) (2x60) /230} =5.74 A
Size of the branch circuit conductor, P350
Size of the branch circuit conductor, P350
Use: 2-2.00mm2, THHN, CU. Wire / 25A
Use: 2-2.00mm2, THHN, CU. Wire / 25A
Size of the protective device:
Size of the protective device:
Use: 2 Pole, 15 AT, 60 AF, 230V, MCCB, 60 Hz.
Use: 2 Pole, 15 AT, 60 AF, 230V, MCCB, 60 Hz.
Size of conduit, see appendix C, P1541
Size of conduit, see appendix C, P1541
Use: 15 mm dia., PVC
Use: 15 mm dia., PVC
GENERAL INFORMATION
GENERAL INFORMATION
Circuit No. 3
Circuit No. 5
Number of luminaires (N): 19
Number of luminaires (N): 12
Number of lamps per luminaire: 8-2x60w F.L.,1-
1x60w F.L.,10-40 incandescent lamp Number of lamps per luminaire: 11-2x60w F.L.,1-
1x60w F.L.
Full load current or VA load: 0.26A, 0.17a Operating Voltage: 230

Operating Voltage: 230 Operating Frequency: 60

Operating Frequency: 60 Full load current, IL

Full load current, IL IL = {(12) (2) (60) / 230}

IL = [(11) (2) (60) + (1) (60)] / 230 = 6A = 6.26A

Size of the branch circuit conductor, P350 Size of the branch circuit conductor, P350

Use: 2-2.00mm2, THHN, CU. Wire / 25A Use: 2-3.5mm2, THHN, CU. Wire / 30A

Size of the protective device: Size of the protective device:

Use: 2 Pole, 15 AT, 60 AF, 230V, MCCB, 60 Hz. Use: 2 Pole, 15 AT, 60 AF, 230V, MCCB, 60 Hz.

Size of conduit, see appendix C, P1541 Size of conduit, see appendix C, P1541

Use: 15 mm dia., PVC Use: 15 mm dia., PVC

GENERAL INFORMATION GENERAL INFORMATION

Circuit No. 6 Circuit No. 8

Number of luminaires (N): 13 Number of duplex C.O. per circuit: 5

Number of lamps per luminaire: 12-2x60w F.L.,1- 180VA per Duplex C.O:
40 incandescent lamp
Operating Voltage: 230
Full load current or VA load: 0.26A, 0.17A
Operating Frequency: 60
Operating Voltage: 230
Full load current, IL
Operating Frequency: 60
IL = [(5) (180)] / 230 = 3.91A
Full load current, IL
Size of the branch circuit conductor, P350
IL = [(12) (2) (60) + (1) (40)] / 230 = 6.43A
Use: 2-2.00mm2, THHN, CU. Wire / 25A
Size of the branch circuit conductor, P350
Size of the protective device:
Use: 2-3.5mm2, THHN, CU. Wire / 30A
Use: 2 Pole, 15 AT, 60 AF, 230V, MCCB, 60 Hz.
Size of the protective device:
Size of conduit, see appendix C, P1541
Use: 2 Pole, 15 AT, 60 AF, 230V, MCCB, 60 Hz.
Use: 15 mm dia., PVC
Size of conduit, see appendix C, P1541
GENERAL INFORMATION
Use: 15 mm dia., PVC
Circuit No. 9
GENERAL INFORMATION
Number of duplex C.O. per circuit: 5-C.O.,1
Circuit No. 7 EMERGENCY LIGHT OUTLET(100W)

Number of luminaires (N): 12 180VA per Duplex C.O:

Number of lamps per luminaire: 2 Operating Voltage: 230

Full load current or VA load: 0.26A Operating Frequency: 60


Full load current, IL Size of the branch circuit conductor, P350

IL = [(5) (180) +(100)] / 230 = 4.35A Use: 2-3.5mm2, THHN, CU. Wire / 30A

Size of the branch circuit conductor, P350 Size of the protective device:

Use: 2-3.5mm2, THHN, CU. Wire / 30A Use: 2 Pole, 20 AT, 60 AF, 230V, MCCB, 60 Hz.

Size of the protective device: Size of conduit, see appendix C, P1541

Use: 2 Pole, 20 AT, 60 AF, 230V, MCCB, 60 Hz. Use: 15 mm dia., PVC

Size of conduit, see appendix C, P1541 GENERAL INFORMATION

Use: 15 mm dia., PVC Circuit No. 12

GENERAL INFORMATION Number of duplex C.O. per circuit: 5

Circuit No. 10 180VA per Duplex C.O:

Number of duplex C.O. per circuit: 5-C.O.,2- Operating Voltage: 230


EMERGENCY LIGHT OUTLET(100W)
Operating Frequency: 60
180VA per Duplex C.O:
Full load current, IL
Operating Voltage: 230
IL = [(5) (180)] / 230 = 3.91A
Operating Frequency: 60
Size of the branch circuit conductor, P350
Full load current, IL
Use: 2-3.5mm2, THHN, CU. Wire / 30A
IL = [(5) (180) +(2) (100)] / 230 = 4.78A
Size of the protective device:
Size of the branch circuit conductor, P350
Use: 2 Pole, 20 AT, 60 AF, 230V, MCCB, 60 Hz.
Use: 2-3.5mm2, THHN, CU. Wire / 30A
Size of conduit, see appendix C, P1541
Size of the protective device:
Use: 15 mm dia., PVC
Use: 2 Pole, 20 AT, 60 AF, 230V, MCCB, 60 Hz.
GENERAL INFORMATION
Size of conduit, see appendix C, P1541
Circuit No. 13
Use: 15 mm dia., PVC
Number of duplex C.O. per circuit: 5-C.O.,2-
GENERAL INFORMATION EMERGENCY LIGHT OUTLET(100W)

Circuit No. 11 180VA per Duplex C.O:

Number of duplex C.O. per circuit: 5-C.O.,2- Operating Voltage: 230


EMERGENCY LIGHT OUTLET(100W)
Operating Frequency: 60
180VA per Duplex C.O:
Full load current, IL
Operating Voltage: 230
IL = [(5) (180) +(2) (100)] / 230 = 4.78A
Operating Frequency: 60
Size of the branch circuit conductor, P350
Full load current, IL
Use: 2-3.5mm2, THHN, CU. Wire / 30A
IL = [(5) (180) +(2) (100)] / 230 = 4.78A
Size of the protective device:
Use: 2 Pole, 20 AT, 60 AF, 230V, MCCB, 60 Hz.

Size of conduit, see appendix C, P1541

Use: 15 mm dia., PVC

GENERAL INFORMATION

Circuit No. 14

Number of duplex C.O. per circuit: 8-C.O.,1-


EMERGENCY LIGHT OUTLET(100W)

180VA per Duplex C.O:

Operating Voltage: 230

Operating Frequency: 60

Full load current, IL

IL = [(8) (180) +(1) (100)] / 230 = 6.7A

Size of the branch circuit conductor, P350

Use: 2-3.5mm2, THHN, CU. Wire / 30A

Size of the protective device:

Use: 2 Pole, 20 AT, 60 AF, 230V, MCCB, 60 Hz.

Size of conduit, see appendix C, P1541

Use: 15 mm dia., PVC

BRANCH CIRCUIT FOR MOTORS

PP3- ACU3

GENERAL INFORMATION

Circuit No. 1

Type of motor: Synchronous Induction Motor

Horsepower rating: 1 HP

Number of phases: 1

Operating voltage: 230

Code letter:

Use: Window Type ACU

IL = 125% ( IFL)

=1.25 (8)

= 10 A
Use: 2-3.5mm2, THHN, CU. Wire / 30A Code letter:

Size of the protective device: Use: Window Type ACU

MSCP = 250 %( IFL) IL = 125% ( IFL)

MSCP = 2.5(8) = 20 A =1.25 (8)

Use: 2P, 30AT, 60 AF, 240V, 60Hz, MCCB = 10 A

Size of the Conduit Use: 2-3.5mm2, THHN, CU. Wire / 30A

Use: 15mm dia., PVC Size of the protective device:

GENERAL INFORMATION MSCP = 250 %( IFL)

Circuit No. 2 MSCP = 2.5(8) = 20 A

Type of motor: Synchronous Induction Motor Use: 2P, 30AT, 60 AF, 240V, 60Hz, MCCB

Horsepower rating: 1 HP Size of the Conduit

Number of phases: 1 Use: 15mm dia., PVC

Operating voltage: 230 GENERAL INFORMATION

Code letter: Circuit No. 4

Use: Window Type ACU Type of motor: Synchronous Induction Motor

IL = 125% ( IFL) Horsepower rating: 1 HP

=1.25 (8) Number of phases: 1

= 10 A Operating voltage: 230

Use: 2-3.5mm2, THHN, CU. Wire / 30A Code letter:

Size of the protective device: Use: Window Type ACU

MSCP = 250 %( IFL) IL = 125% ( IFL)

MSCP = 2.5(8) = 20 A =1.25 (8)

Use: 2P, 30AT, 60 AF, 240V, 60Hz, MCCB = 10 A

Size of the Conduit Use: 2-3.5mm2, THHN, CU. Wire / 30A

Use: 15mm dia., PVC Size of the protective device:

GENERAL INFORMATION MSCP = 250 %( IFL)

Circuit No. 3 MSCP = 2.5(8) = 20 A

Type of motor: Synchronous Induction Motor Use: 2P, 30AT, 60 AF, 240V, 60Hz, MCCB

Horsepower rating: 1 HP Size of the Conduit

Number of phases: 1 Use: 15mm dia., PVC

Operating voltage: 230 GENERAL INFORMATION


Circuit No. 5 MSCP = 250 %( IFL)

Type of motor: Synchronous Induction Motor MSCP = 2.5(8) = 20 A

Horsepower rating: 1 HP Use: 2P, 30AT, 60 AF, 240V, 60Hz, MCCB

Number of phases: 1 Size of the Conduit

Operating voltage: 230 Use: 15mm dia., PVC

Code letter: GENERAL INFORMATION

Use: Window Type ACU Circuit No. 7

IL = 125% ( IFL) Type of motor: Synchronous Induction Motor

=1.25 (8) Horsepower rating: 1 HP

= 10 A Number of phases: 1

Use: 2-3.5mm2, THHN, CU. Wire / 30A Operating voltage: 230

Size of the protective device: Code letter:

MSCP = 250 %( IFL) Use: Window Type ACU

MSCP = 2.5(8) = 20 A IL = 125% ( IFL)

Use: 2P, 30AT, 60 AF, 240V, 60Hz, MCCB =1.25 (8)

Size of the Conduit = 10 A

Use: 15mm dia., PVC Use: 2-3.5mm2, THHN, CU. Wire / 30A

GENERAL INFORMATION Size of the protective device:

Circuit No. 6 MSCP = 250 %( IFL)

Type of motor: Synchronous Induction Motor MSCP = 2.5(8) = 20 A

Horsepower rating: 1 HP Use: 2P, 30AT, 60 AF, 240V, 60Hz, MCCB

Number of phases: 1 Size of the Conduit

Operating voltage: 230 Use: 15mm dia., PVC

Code letter:

Use: Window Type ACU

IL = 125% ( IFL)

=1.25 (8)

= 10 A

Use: 2-3.5mm2, THHN, CU. Wire / 30A

Size of the protective device:


PERCENT UNBALANCE

PERCENT UNBALANCE
PANEL CODE: LP 1-230 V 4TH FLOOR

TOTAL PHASE CURRENTS:


AB = 35.38 AMPERES
BC = 35.56 AMPERES
CA = 33.9 AMPERES

COMPUTATION:
∅ AB +∅ BC+ ∅ C A
AVERAGE LOADING =
3
35.38+35.56+33.9
=
3
= 34.61 AMPERES
DEVIATION OF PHASE AB = ∅ AB−AVERAGE LOADING

= 35.38 – 34.61
= 0.77 AMPERES
DEVIATION OF PHASE BC = ∅ BC− AVERAGE LOADING

= 35.56 – 34.61
= 0.65 AMPERES
DEVIATION OF PHASE BC = ∅ CA− AVERAGE LOADING

= 33.9 – 34.61
= -0.71 AMPERES
THERRFORE, THE MAXIMUM DEVIATION OCCURS ON PHASE CA.

NOTE: % UNBALANCE MUST NOT EXCEED 10%

MAXIMUM DEVIATION
%UNBALANCE = *100%
AVERAGE LOADING

0.71
%UNBALANCE = *100%
34.61

= 2.05 %, ACCEPTABLE

PERCENT UNBALANCE
TH
PANEL CODE: PP1 ACU1, 5 FLOOR

TOTAL PHASE CURRENTS:


AB = 24 AMPERES
BC = 22.52 AMPERES
CA = 22.52 AMPERES

COMPUTATION:
∅ AB +∅ BC+ ∅ C A
AVERAGE LOADING =
3

24+22.52+22.52
=
3
= 23.01 AMPERES
DEVIATION OF PHASE AB = ∅ AB−AVERAGE LOADING

= 24 – 23.01
= 0.99 AMPERES
DEVIATION OF PHASE BC = ∅ BC − AVERAGE LOADING

= 22.52 – 23.01
= - 0.49 AMPERES
DEVIATION OF PHASE BC = ∅ CA− AVERAGE LOADING

= 22.52 – 23.01
= - 0.49 AMPERES
THERRFORE, THE MAXIMUM DEVIATION OCCURS ON PHASE AB.

NOTE: % UNBALANCE MUST NOT EXCEED 10%

MAXIMUM DEVIATION
%UNBALANCE = *100%
AVERAGE LOADING

0.99
%UNBALANCE = *100%
23.01

= 4.3 %, ACCEPTABLE

PERCENT UNBALANCE
PANEL CODE: LP 2-230 V, 5TH FLOOR

TOTAL PHASE CURRENTS:


AB = 35.38 AMPERES
BC = 35.56 AMPERES
CA = 33.9 AMPERES
COMPUTATION:
∅ AB +∅ BC+ ∅ C A
AVERAGE LOADING =
3

35.38+35.56+33.9
=
3
= 34.61 AMPERES
DEVIATION OF PHASE AB = ∅ AB−AVERAGE LOADING

= 35.38 – 34.61
= 0.77 AMPERES
DEVIATION OF PHASE BC = ∅ BC − AVERAGE LOADING

= 35.56 – 34.61
= 0.65 AMPERES
DEVIATION OF PHASE BC = ∅ CA− AVERAGE LOADING

= 33.9 – 34.61
= -0.71 AMPERES
THERRFORE, THE MAXIMUM DEVIATION OCCURS ON PHASE CA.

NOTE: % UNBALANCE MUST NOT EXCEED 10%

MAXIMUM DEVIATION
%UNBALANCE = *100%
AVERAGE LOADING

0.71
%UNBALANCE = *100%
34.61

= 2.05 %, ACCEPTABLE

PERCENT UNBALANCE
PANEL CODE: PP2 ACU2, 5TH FLOOR

TOTAL PHASE CURRENTS:


AB = 24 AMPERES
BC = 22.52 AMPERES
CA = 22.52 AMPERES

COMPUTATION:
∅ AB +∅ BC+ ∅ C A
AVERAGE LOADING =
3

24+22.52+22.52
=
3
= 23.01 AMPERES
DEVIATION OF PHASE AB = ∅ AB−AVERAGE LOADING

= 24 – 23.01
= 0.99 AMPERES
DEVIATION OF PHASE BC = ∅ BC − AVERAGE LOADING

= 22.52 – 23.01
= - 0.49 AMPERES
DEVIATION OF PHASE BC = ∅ CA− AVERAGE LOADING

= 22.52 – 23.01
= - 0.49 AMPERES
THERRFORE, THE MAXIMUM DEVIATION OCCURS ON PHASE AB.

NOTE: % UNBALANCE MUST NOT EXCEED 10%

MAXIMUM DEVIATION
%UNBALANCE = *100%
AVERAGE LOADING

0.99
%UNBALANCE = *100%
23.01

= 4.3 %, ACCEPTABLE

PERCENT UNBALANCE
PANEL CODE: LP 3-230 V 6TH FLOOR
TOTAL PHASE CURRENTS:
AB = 35.38 AMPERES
BC = 35.56 AMPERES
CA = 33.9 AMPERES

COMPUTATION:
∅ AB +∅ BC+ ∅ C A
AVERAGE LOADING =
3

35.38+35.56+33.9
=
3
= 34.61 AMPERES
DEVIATION OF PHASE AB = ∅ AB−AVERAGE LOADING

= 35.38 – 34.61
= 0.77 AMPERES
DEVIATION OF PHASE BC = ∅ BC − AVERAGE LOADING

= 35.56 – 34.61
= 0.65 AMPERES
DEVIATION OF PHASE BC = ∅ CA− AVERAGE LOADING

= 33.9 – 34.61
= -0.71 AMPERES
THERRFORE, THE MAXIMUM DEVIATION OCCURS ON PHASE CA.

NOTE: % UNBALANCE MUST NOT EXCEED 10%

MAXIMUM DEVIATION
%UNBALANCE = *100%
AVERAGE LOADING

0.71
%UNBALANCE = *100%
34.61

= 2.05 %, ACCEPTABLE

PERCENT UNBALANCE
PANEL CODE: PP1 ACU1, 6TH FLOOR

TOTAL PHASE CURRENTS:


AB = 24 AMPERES
BC = 22.52 AMPERES
CA = 22.52 AMPERES

COMPUTATION:
∅ AB +∅ BC+ ∅ C A
AVERAGE LOADING =
3

24+22.52+22.52
=
3
= 23.01 AMPERES
DEVIATION OF PHASE AB = ∅ AB−AVERAGE LOADING

= 24 – 23.01
= 0.99 AMPERES
DEVIATION OF PHASE BC = ∅ BC − AVERAGE LOADING

= 22.52 – 23.01
= - 0.49 AMPERES
DEVIATION OF PHASE BC = ∅ CA− AVERAGE LOADING

= 22.52 – 23.01
= - 0.49 AMPERES
THERRFORE, THE MAXIMUM DEVIATION OCCURS ON PHASE AB.

NOTE: % UNBALANCE MUST NOT EXCEED 10%

MAXIMUM DEVIATION
%UNBALANCE = *100%
AVERAGE LOADING

0.99
%UNBALANCE = *100%
23.01

= 4.3 %, ACCEPTABLE
SIZING OF THE MAIN FEEDER
SIZING OF THE MAIN FEEDER PROTECTIVE DEVICE AND MAIN FEEDER CONDUCTOR
CALCULATION

PANEL CODE: LP-1-230 V

SIZE OF THE FEEDER CONDUCTOR: TABLE 3.10.1.16, PAGE 250

IFL = √3 (IФMAX)

= √3 [35.56]

= 61.59 A

Use: 3 – 22mm2, THHN, CU. Wire/90A

G.C 1-5.5mm2, THHN, CU. Wire

MAIN FEEDER PROTECTIVE DEVICE: FROM ARTICLE 2.40.1.6 SECTION A, PAGE 169

IFL = √3 [35.56]

= 61.59A

Use: 3P, 60AT, 60 AF, 230V, MCCB, 60Hz

SIZE OF THE CONDUIT: FROM TABLE C2, PAGE 1545

Use: 32mm. diameter, PVC

SIZING OF THE MAIN FEEDER PROTECTIVE DEVICE AND MAIN FEEDER CONDUCTOR
CALCULATION

PANEL CODE: PP1-230 V

SIZE OF THE FEEDER CONDUCTOR: TABLE 3.10.1.16, PAGE 250

IFL = √3 (25%(IFL OF THE BIGGEST MOTOR) + IФMAX)

= √3 [0.25(8) + 24]

= 45.03 A

Use: 3 – 14mm2, THHN, CU. Wire/70A

G.C 1-5.5 mm2, THHN, CU. Wire

MAIN FEEDER PROTECTIVE DEVICE: FROM ARTICLE 2.40.1.6 SECTION A, PAGE 169

IFL = √3 [0.25(8) + 24]

= 45.03A

Use: 3P, 60 AT, 60 AF, 230V, MCCB, 60Hz

SIZE OF THE CONDUIT: FROM TABLE C2, PAGE 1545

Use: 25mm. diameter, PVC


SIZING OF THE MAIN FEEDER PROTECTIVE DEVICE AND MAIN FEEDER CONDUCTOR
CALCULATION

PANEL CODE: LP-2-230 V

SIZE OF THE FEEDER CONDUCTOR: TABLE 3.10.1.16, PAGE 250

IFL = √3 (IФMAX)

= √3 [35.56]

= 61.59 A

Use: 3 – 22mm2, THHN, CU. Wire/90A

G.C 1-5.5mm2, THHN, CU. Wire

MAIN FEEDER PROTECTIVE DEVICE: FROM ARTICLE 2.40.1.6 SECTION A, PAGE 169

IFL = √3 [35.56]

= 61.59A

Use: 3P, 60AT, 60 AF, 230V, MCCB, 60Hz

SIZE OF THE CONDUIT: FROM TABLE C2, PAGE 1545

Use: 32mm. diameter, PVC

SIZING OF THE MAIN FEEDER PROTECTIVE DEVICE AND MAIN FEEDER CONDUCTOR
CALCULATION

PANEL CODE: PP2-230 V

SIZE OF THE FEEDER CONDUCTOR: TABLE 3.10.1.16, PAGE 250

IFL = √3 (25%(IFL OF THE BIGGEST MOTOR) + IФMAX)

= √3 [0.25(8) + 24]

= 45.03 A

Use: 3 – 14mm2, THHN, CU. Wire/70A

G.C 1-5.5 mm2, THHN, CU. Wire

MAIN FEEDER PROTECTIVE DEVICE: FROM ARTICLE 2.40.1.6 SECTION A, PAGE 169

IFL = √3 [0.25(8) + 24]

= 45.03A

Use: 3P, 60 AT, 60 AF, 230V, MCCB, 60Hz

SIZE OF THE CONDUIT: FROM TABLE C2, PAGE 1545

Use: 25mm. diameter, PVC


SIZING OF THE MAIN FEEDER PROTECTIVE DEVICE AND MAIN FEEDER CONDUCTOR
CALCULATION

PANEL CODE: LP-3-230 V

SIZE OF THE FEEDER CONDUCTOR: TABLE 3.10.1.16, PAGE 250

IFL = √3 (IФMAX)

= √3 [35.56]

= 61.59 A

Use: 3 – 22mm2, THHN, CU. Wire/90A

G.C 1-5.5mm2, THHN, CU. Wire

MAIN FEEDER PROTECTIVE DEVICE: FROM ARTICLE 2.40.1.6 SECTION A, PAGE 169

IFL = √3 [35.56]

= 61.59A

Use: 3P, 60AT, 60 AF, 230V, MCCB, 60Hz

SIZE OF THE CONDUIT: FROM TABLE C2, PAGE 1545

Use: 32mm. diameter, PVC

SIZING OF THE MAIN FEEDER PROTECTIVE DEVICE AND MAIN FEEDER CONDUCTOR
CALCULATION

PANEL CODE: PP3-230 V

SIZE OF THE FEEDER CONDUCTOR: TABLE 3.10.1.16, PAGE 250

IFL = √3 (25%(IFL OF THE BIGGEST MOTOR) + IФMAX)

= √3 [0.25(8) + 24]

= 45.03 A

Use: 3 – 14mm2, THHN, CU. Wire/70A

G.C 1-5.5 mm2, THHN, CU. Wire

MAIN FEEDER PROTECTIVE DEVICE: FROM ARTICLE 2.40.1.6 SECTION A, PAGE 169

IFL = √3 [0.25(8) + 24]

= 45.03A

Use: 3P, 60 AT, 60 AF, 230V, MCCB, 60Hz

SIZE OF THE CONDUIT: FROM TABLE C2, PAGE 1545

Use: 25mm. diameter, PVC

SIZE OF THE MAIN FEEDER & MAIN PROTECTIVE TOTAL FULL LOAD CURRENT, IFL
IFL = IFL LP-1-230V + IFL LP-2-230V + IFL LP-3-230V + IFL PP-1-230V + IFL PP-2-230V + IFL PP-3-230V

= 61.59 A + 61.59 A + 61.59 A + 45.03A + 45.03A + 45.03A

= 319. 86 A

BY PARALLELING:

319.86 A
I= =106.62 A
3
SIZE OF THE MAIN FEEDER AND CONDUCTOR, TABLE 3.10.1.16, PAGE 350

USE: 3 – 38mm2, THW COPPER WIRE, STRANDED/125 AMPERE

USE: 1 – 8.0mm2 GROUNDING CONDUCTOR

SIZE OF THE CONDUIT (RIGID METAL), FROM TABLE C8(A), PAGE 1569

USE: 50mm DIAMETER RMC CONDUIT

OVERCURRENT PROTECTION: FROM ARTICLE 2.40.1.6 SECTION A, PAGE 169

USE: 3P – 100 AT, 120AF, MCCB, 240V,60Hz, KAIC


SIZING OF THE TRANSFORMER
SIZING OF THE TRANSFORMER

KVA3ФLP-1 = 3(230) (IФMAX)/1000

= 3(230) (35.56)/1000

= 24.5364 KVA

KVA3ФLP-2 = 3(230) (IФMAX)/1000

= 3(230) (35.56)/1000

= 24.5364 KVA

KVA3ФLP-2 = 3(230) (IФMAX)/1000

= 3(230) (35.56)/1000

= 24.5364 KVA

KVA3ФPP-1 = 3(230) (IФMAX)/1000

= 3(230) (24)/1000

= 16.56 KVA

KVA3ФPP-2 = 3(230) (IФMAX)/1000

= 3(230) (24)/1000

= 16.56 KVA

KVA3ФPP-3 = 3(230) (IФMAX)/1000

= 3(230) (24)/1000

= 16.56 KVA

KVATOTAL = 24.5364(3) + 16.56(3)


= 123.2892 KVA

KVARATING PER PHASE = 123.2892/3

= 41.0964 KVA

LOAD GROWTH AT 125%

KVARATING PER PHASE = (1.25*41.0964)

= 51.3705 KVA

USE: 3 UNITS, SINGLE PHASE, 50KVA, 7620/230 V, DOUBLE BUSHING

3 (50,000 )
IFL =
√ 3(230)
= 376.532 AMPERES

SIZE OF THE CURRENT TRANSFORMER

USE: 3 – CT HAVING 400:5 A TRANSFORMER RATIO


VOLTAGE DROP

VOLTAGE DROP CALCULATION


A. GENERAL INFORMATION
FARTHEST LOAD: ACU – CIRCUIT 7
DISTANCE FROM THE PANELBOARD: 30 METERS
SIZE OF WIRE USED: 2-3.5mm2(12AWG) THHN, COPPER WIRE

B. LOAD DESCRIPTION
TYPE OF LOAD: AIR CONDITIONING UNIT
NO. OF PHASE: SINGLE PHASE MOTOR
FULL LOAD CURRENT: 8 AMPERES
TRANSIENT CURRENT: 48 AMPERES
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 HZ.
POWER FACTOR: 0.8 LAGGING
TRANSIENT POWER FACTOR: 0.62 LAGGING
C. VOLTAGE DROP

RESISTANCE ∈OHMS
RL = ( KILOMETER
¿(CABLE LENGTH )
1000 m
6.6 OHMS
RL = (30 m)
1000 m
RL= 0.198 ohms
REACTANCE ∈OHMS
XL = ( KILOMETER
(CABLE LENGTH )
1000 m
0.223OHMS
XL = (30 m)
1000 m
XL = 0.00669 ohms

ZL =0.198 + j0.00669 ohms

VOLTAGE DROP @ STEADY STATE (VDS < 5%)


POWER FACTOR = 0.8 LAGGING

IL = 8 ∠ - 36.87 A
VR = VS – VD; VD = IL * ZL

VR = 230 ∠ 0– (7.4 ∠ - 36.87) (0.198 + j0.00669) = 228.70 ∠ 0.227 ° V

VS−VR
% VD = ∗100 %
VS
230−228.70
% VD = ∗100 %
230
% VD = 0.5652 %

VOLTAGE DROP @ TRANSIENT STATE (VDS < 10%)


POWER FACTOR = 0.62 LAGGING
IL = 48 ∠ - 51.68 ° A

VR = VS – VD; VD = IL * ZL
VR = 230 ∠ 0– (48 ∠ - 51.68) (0.198 + j0.00669) = 222.27 ∠ 1.4 ° V

VS−VR
% VD = ∗100 %
VS
230−222.27
% VD = ∗100 %
230
% VD = 3.36 %
SCHEDULE OF LOADS
SINGLE LINE DIAGRAM