Date: March 23, 2010  
 
Notice: Engineering Technical Bulletin – ETB 006 Clarke Fire Protection Products  
  
Alternator / Water Pump Belt Tensioning Procedure  
Effective immediately, all manually tensioned belts are to be checked with the Burroughs BT‐33‐73F belt 
tension gauge. After setting initial belt tension and tightening alternator/idler pulley hardware, inspect belt 
tension. Depress ball handle and insert gauge hook below belt as shown in figure below.  
 

 
Once the belt is hooked, release the ball handle quickly with a snapping action. Verify belt tension is within 
tolerance ranges below. If belt tension is outside tolerance range, loosen hardware, adjust tension, tighten 
hardware and recheck belt tension until within tolerance range.  
 
Belt Type  Clarke P/N Ref.  Tension Range (lbf) 
  C07816   
  C071086   
  C071087   
Single 8 Multi‐V   C071006  70‐80 
groove belt  C071043 
C071192 
C071132 
C071033 
  C07734   
Single 4 & 6 Multi‐V  C071088  60‐70 
groove belt  C071475   
C071476   
  C07833   
  C071124   
Dual 4 Multi‐V  C071125   
groove belt  C071126  60‐70 
(matched set)  C071044 
C071127 
C071128 
 

C133431 RevA