Professional Documents
Culture Documents
RadiantCooledFloorsbuild PDF
RadiantCooledFloorsbuild PDF
Peter Simmonds is an associate mechanical engineer and Bungane Mehlomakulu is a mechanical engineer at IBE Consulting Engineers,
Sherman Oaks, Calif. Thilo Eibert is a research engineer at Flack + Kurtz, Inc., San Francisco, Calif.
©2006 ASHRAE. THIS PREPRINT MAY NOT BE DISTRIBUTED IN PAPER OR DIGITAL FORM IN WHOLE OR IN PART. IT IS FOR DISCUSSION PURPOSES ONLY
AT THE 2006 ASHRAE WINTER MEETING. The archival version of this paper along with comments and author responses will be published in ASHRAE Transactions,
Volume 112, Part 1. ASHRAE must receive written questions or comments regarding this paper by February 3, 2006, if they are to be included in Transactions.
can be influenced by the control or balance of the radiant heat The sum of convective heat transfer qcon and longwave
exchange in a space. When a radiant cooled floor is operated radiant heat transfer ql,rad will be defined as the space energy
correctly, the surface temperature of the floor can be regulated. transfer qs (W/m2) and can be written as
Absorbing a major portion of the solar radiation entering the
space also prevents the floor from emitting thermal energy in qs = qcon + ql,rad , (2)
the form of longwave radiation back into the space and onto
where qs = space energy transfer of the radiant floor (W/m2).
other surfaces.
When incorporating a radiant system and a constant The convective heat flux and the longwave radiant heat
volume ventilating system, the ventilation system need only flux can be expressed as
be dimensioned to supply outdoor air for each person and to qcon = hcon · (tf – tair)
remove the latent and sensible loads from people, equipment,
and lighting. The radiant system is then selected to remove the ql,rad = hl,rad · (tf – tMRT) , (3)
remaining cooling loads. Simmonds (1994) has reported on
some of these designs and how effective they are in providing where
comfort climate control. hcon = convective energy exchange coefficient floor to
Since cooling surfaces make no contribution to air space (W/m2K),
renewal, the surfaces are usually operated in conjunction with
hl,rad = longwave radiant energy exchange coefficient floor
a ventilating or air-conditioning plant, which also ensures the
to space (W/m2K),
necessary dehumidification is provided. The combination of a
radiant cooled system with a natural ventilation system and tair = space air temperature (°C),
operable windows may also be possible in certain climate tMRT = surrounding surface temperature (°C), and
conditions. tf = floor surface temperature (°C).
FUNDAMENTAL CALCULATIONS
A radiant floor system exchanges thermal energy with the Longwave Radiant Energy Exchange Coefficient
space by means of convection, shortwave radiation, and long- It is assumed that all surfaces are radiantly gray, so the
wave radiation. Since an understanding of the three different
radiant heat flux between floor surface and the other surfaces
kinds of heat transfer is very important for calculating and
(according to Fanger [1972]) can be written as
optimizing a radiant floor system, this paper contains a
detailed narrative and mathematical description. N
4 4
The three different types of heat transfer of the radiant q rad = ε f ⋅ σ ⋅ T f – ∑ ε i ⋅ σ ⋅ T i ⋅ F Af – Ai , (4)
floor are: i=1
2 CH-06-2-3
The equation can now be written as Floor Cooling
Radiant heat flux can thus be calculated by using Equa- Using the method outlined above to calculate the heat flux
tion 9. Two different values are given in the literature for the between floor surface and space, the convective and the long-
Stefan-Boltzmann constant σ, 5.67 × 10–8 W/m2⋅K4 wave radiant heat fluxes have to be calculated separately. The
(ASHRAE 1996) and 5.77 × 10–8 W/m2⋅K4 (Fanger 1972). convective heat flux is calculated using the temperature differ-
ence between the floor surface and air temperature, and the
Calculating hrad for different combinations of ε and σ (see
longwave radiant heat exchange is calculated using the
Table 1) shows that with only a small amount of error, a
temperature difference between the floor surface and the
constant value of hrad = 5.5 W/m2K can be used. surrounding surface temperature. For specific calculations, as
From Table 1, using the variant calculation of hrad and well as for optimization calculation, this method should be
using Equation 8 above, Θf is calculated to be 1.05 × 108 K3. used.
For most cases involving the design of radiant floor
Convective Heat Exchange Coefficient systems and for calculating capacity, the total heat exchange
coefficient, defined in this report, can be substituted with the
The convective heat exchange is caused by the difference space heat exchange coefficient to simplify calculation. The
in density, the action of gravity, and the space air currents. The space heat exchange coefficient is defined as the combined
heat exchange coefficient between the floor surface and the air value of the convective and longwave heat exchange coeffi-
is a function of the temperature difference. In the case of only cients with a common reference temperature. Since most
natural ventilation, two different formulas are given in the comfort requirements and standards are based on the operative
literature. temperature (dry resultant temperature and some heat load
calculations are using this temperature), the operative temper-
0.31
Cooling: h con = 0.54 ⋅ ∆T ature can be used as the reference temperature (Olesen et al.
(Recknagel and Sprenger 2000) (10) 1998; ASHRAE 2004).
The space heat transfer defined in Equation 2 can be
0.31 simplified and expressed as
Cooling: h con = 0.74 ⋅ ( 1.8 ⋅ ∆T )
(ASHRAE 1996 [converted into SI Units]), (11) qs = hs · (tf – to) , (12)
where where
hcon = convective heat exchange coefficient (°C) and hs = space heat exchange coefficient (W/m2K),
∆T = temperature difference between floor surface and tf = floor surface temperature (°C), and
space air. to = operative temperature (°C).
CH-06-2-3 3
height, residential buildings, and similar buildings and spaces. Shortwave Radiation
The following space heat exchange coefficient can be used:
The radiation within a space is usually separated into two
hs = hrad + hcon (13) groups, longwave and shortwave. As described before, long-
wave radiation is that which occurs between room surfaces,
where and both its quantity and wavelength are temperature depen-
hrad = 5.5 W/m2⋅K and dent. Longwave radiation is considered within the calculation
hcov = 1.0 W/m2⋅K, of the space heat flux of the radiant floor.
The transfer of shortwave radiation within a room does
giving hs,tot = 6.5 W/m2⋅K for floor cooling.
not depend on the temperature of surfaces. Sources of short-
This value is the summation of hcon and hl,rad. This wave radiation are high-temperature surfaces such as the sun
simplification is physically correct if the air temperature of the and electric lights. Shortwave radiation on a surface will either
space and the surrounding surface temperature are the same. be absorbed or reflected from the surface or transmitted
For common applications such as office spaces, the through any glazed surface.
surface temperature of the exterior elements (wall, window, The shortwave radiation to the floor should be considered
roof) in summer are above the air temperature, while the when radiant cooled floors are used. Since the shortwave radi-
temperature of the other surfaces do not significantly deviate ation is not temperature dependent, a temperature difference
from the air temperature. For perimeter zones, this means a between the floor surface and the air or the surrounding
higher physical space heat flux needs to be calculated, but for surfaces is not necessary for heat transfer to occur. It then
the interior zones, assuming a small temperature differential follows that there is no heat exchange coefficient for the
between the air and surrounding surface is nearly correct. absorbed shortwave radiation.
From Figure 1 it follows from the first law of thermody-
Operative Temperature namics that
The operative temperature (dry resultant temperature) is
α+τ+ρ = 1, (16)
numerically the average of the air temperature tair and mean
radiant temperature trad weighted by their respective heat where
transfer coefficients. Most requirements for comfort are based
α = fraction of incident radiation absorbed, or
on the operative temperature in a space, and for heat loss calcu-
absorptance,
lations in buildings (ASHRAE 1996) the operative tempera-
ture is commonly used and known. τ = fraction of incident radiation transmitted, or
The operative temperature TO is calculated as transmittance, and
ρ = fraction of incident radiation reflected, or
hc ⋅ Ta + hr ⋅ Tr
T O = ------------------------------------- , (14) reflectance.
hc + hr
where
Ta = air temperature in reference point,
Tr = mean radiant temperature in reference point,
hc = convective heat transfer coefficient for the human
body, and
hr = radiant heat transfer coefficient for the human body.
4 CH-06-2-3
The floor surface is opaque, so the transmittance of the be treated in the same manner as shortwave radiation from the
floor surface τ = 0. For a black surface, α = 1, τ = 0, and ρ = 0 sun.
means that all shortwave radiation reaching the surface will be The consideration of the shortwave light radiation may
absorbed by the black surface. For most surfaces, absorptance optimize the radiant floor cooling system and should be
for shortwave radiation is different from emittance for long- considered if reliable values of the heat flux of the proposed
wave radiation (low-temperature radiation). No surface is lighting are known.
considered to be completely black, so α < 1 and ρ > 0 for all The specific shortwave light radiation to the floor surface
radiant floor surfaces. Table 2 provides an example of absorp- is
tion values for common materials and surfaces.
Q s, light
q el, rad = α ⋅ ------------------ , (18)
Af
Solar Radiation
The amount of shortwave solar radiation entering a room where
depends upon the orientation of the window, the properties of qel,rad = specific shortwave radiation emitted by electrical
the glazing, the shading devices, the month, and the time of light per m2 radiated floor surface (W/m2),
day. The calculation of the shortwave direct sun transmission Qs,light = shortwave electrical light radiation (W),
through the window may be completed with currently avail- Af = radiated floor area (m2), and
able computer programs such as E + TA (ROOM) and the
α = absorptance of the floor surface.
amount entering the floor surface may be estimated, depen-
dent on the percentage of furniture or equipment standing on Floor Surface Temperature
the floor area.
According to ASHRAE Standard 55-2004 (ASHRAE
The specific sun radiation to the floor surface is the direct
2004), the surface temperature of the floor for people wearing
sun transmission through the window on the floor per radiated
typical indoor footwear shall be between 18°C (65°F) and
floor area.
29°C (84°F) to minimize foot discomfort. For floors that
Q directsun people occupy with bare feet, the floor temperature will
q s, rad = α ⋅ ------------------------ (17) depend on the type of floor material (see ASHRAE 2001).
Af
ASHRAE Standard 55 recommends that a minimum floor
where surface temperature of 19°C (67°F) be used because of
temperature differences between the floor surface and occu-
qs,rad = specific shortwave sun radiation per m2 radiated pants.
floor surface (W/m2),
Qdirectsun = sun radiation through the window on the floor (W), Floor Area Covering
2 Floor areas with significant covering on the floor surface,
Af = radiated floor area (m ), and
α = absorptance of the floor surface. such as furniture, equipment, etc., have to be considered. The
covered areas, as well as areas not provided with radiant floor
Electrical Light Radiation cooling tubes, do not contribute to the cooling capacity of the
radiant floor. For example, if 10% of the floor is covered, only
Shortwave radiation from electrical light sources is not 90% of the floor may be considered for the total cooling capac-
usually taken into consideration for radiant floor calculations; ity.
however, shortwave radiation from electrical light sources can
Radiant Floor Cooling
Table 2. Absorption of Solar Radiation
(ASHRAE 1996) The specific heat flux between the floor surface and the
space, calculated by combining Equation 12 with Equations
Absorption for 17 and 18, gives
Surfaces
Solar Radiation
q c = h c, tot ⋅ ( t o – t s ) + q s, rad , (19)
Black nonmetallic surfaces such as asphalt, 0.85…0.98
carbon, slate, paint, paper where
Red brick and tile, concrete and stone, dark 0.65…0.80 qc = specific heat flux between floor surface and space
paints (W/m2),
Tile or plaster, white or light cream 0.30 … 0.50 hs,tot = 6.5 W/m2⋅K, heat exchange coefficient,
to = operative temperature (°C),
Red tile, stone, or concrete, dark paints (red, 0.65 … 0.80
tf = floor surface temperature (°C), and
brown, green,..)
qs,rad = absorbed shortwave radiation (W/m2) emitted by
White painted surfaces 0.23 … 0.49
both sun and electrical light.
CH-06-2-3 5
Using the minimum recommended floor surface temper- and the distance between the tubes within the floor construc-
ature and a summer indoor design operative temperature of tion. Because of the distance between the tubes, the floor
26°C (78.8°F) and no absorbed shortwave radiation, the maxi- surface temperature is not constant. It is recommended to
mum space cooling capacity of the radiant floor is found by select a minimal EWT equal to the supposed maximal dew-
point temperature to avoid condensation on the floor surface
q c, s = h c, tot ⋅ ( t o – t s, min ) and to guarantee the selected cooling capacity of the radiant
W W system. In addition, the EWT should be controlled by a humid-
q c, s = 6.5 -----------
2
⋅ ( 26 – 19 )K = 45.5 ------2-
m K m (20) ity control sensor.
Btu If for any reason an EWT below the space dew point is
q c, s = 14.5 --------2- . selected, the minimal possible surface temperature of the floor
hft
in areas with reduced loads must be calculated carefully.
The maximum space cooling capacity of a radiant floor Example. If the indoor air is controlled at a dry- bulb
cooling system can be assumed to be 45 W/m2(14.3 [Btu/h] ft2) temperature of 24°C (75°F) and a relative humidity
when an operative design temperature of 26°C (78.8°F) is used. of 50%, the suggested dew point is approximately
In floor areas with absorption of shortwave radiation, the cool- 13°C (55.4°F). Therefore, a minimal EWT of 13°C
ing capacity of radiant cooled floors, as shown by Simmonds (55.4°F) may be selected.
et al. (2000) and Borressen (1994), can be approximately as The combination of the radiant floor cooling system with
high as 80 W/m2 (25.4 [Btu/h]/ft2). The capacity is also depen- a natural ventilation concept requires an accurate calculation
dent on the floor construction as well as the water temperatures, of the maximum dew points within the space, considering the
described in detail in the following sections. If the floor outdoor air conditions as well as the latent loads of the space.
construction, including the floor covering, shows a high ther-
mal resistance (heavy carpet, etc.), the space cooling capacity Entering Water Temperature (EWT)
may be lower as calculated.
The EWT is a function of many aspects and decreases
If shortwave absorption through the floor is higher than
with increasing thermal resistance of the floor construction.
the steady cooling capacity of the floor, not all of the absorbed
Increasing the water temperature difference between the EWT
energy is removed from the floor, raising the surface temper-
and leaving water temperature (LWT) increases the cooling
ature of the floor. The increase in floor temperature will
capacity of the floor and increases the acceptable distance
decrease the ability of the radiant cooled floor to absorb long-
between the water tubes.
wave radiation; this is dependant on the temperature differ-
It is recommended, as a first iteration, to select an EWT
ence between the floor and the surrounding surfaces and may
equal to the dew-point temperature of the space air, but usually
result in the floor emitting longwave radiation back into the
not below 13°C (55.4°F). The water temperature difference
space and to the surrounding surfaces.
between the EWT and LWT may be selected as 5 K. With this
SELECTION GUIDE FOR fixed value and the given floor construction, it is possible to
RADIANT FLOOR COOLING SYSTEM calculate the maximum cooling capacity of the radiant floor
system.
Floor Covering If necessary, the EWT, the temperature difference
between the EWT and LWT, as well as the tube distance can
The floor covering and floor construction have a signifi- be changed to achieve maximum performance of the system.
cant influence on the radiant floor system, especially for floor Recommended temperature levels of the hydronic floor
cooling. With increasing thermal resistance of the floor cover- cooling system are listed in Table 3.
ing (carpet instead of tile) as well as the floor construction ASHRAE Handbook—Fundamentals (ASHRAE 1996)
above the tubes, the cooling capacity decreases if the entering uses the mean water temperature (MWT), which is defined as
water temperature (EWT) is kept constant. If carpet is used,
the resistance of the carpet should be as low as possible and t LWT + t EWT
t mwt = ------------------------------ , (21)
should be specified in advance. A higher resistance as calcu- 2
lated may cause a lower cooling capacity of the radiant floor where
system.
tmwt = mean water temperature, °C,
Dew Point tEWT = entering water temperature, °C, and
tLWT = leaving water temperature, °C.
The floor surface temperature of the radiant floor is lower
than the air temperature in the space. Therefore, if the surface Table 3. Recommended EWT
temperature of the floor falls below the space air dew point at and Temperature Differentials
any area, water condenses out of the air and the floor becomes
EWT 13°C to 15°C (55.4°F to 59°F)
wet. The floor surface temperature is dependent on the water
temperature at the specific area, the cooling load of this area, ∆T 3°C to 6°C (5°F to 10.8°F)
6 CH-06-2-3
Downward Losses the floor to the cooled water in the pipe will be described fully
in subsequent papers.
The downward losses may be significant if there is no
The steady-state relationship between the space air
insulation, thus increasing the thermal resistance to the space
temperature, the floor surface temperature, and the water
below the floor. The heat exchange coefficient of a cooled
supply and return temperatures was determined by applying
floor to the space below, given by the Chartered Institution of
the steady-state equations described at the beginning of this
Building Services Engineers (CIBSE), is approximately 10.5
paper.
W/m2K (1.84 Btu/h⋅ft2⋅°F). Compared to the heat exchange
For each load condition, two control strategies have been
coefficient of the radiant floor, 6.5 W/m⋅2K (1.14 Btu/
considered: constant-volume flow varying the EWT and vari-
h⋅ft2⋅°F), the value downward is significantly higher. Also, the
able-volume flow with a constant EWT.
space air temperature at the ceiling (for example, within a false
ceiling) may be higher than the air at the floor level. Constant Volume, Variable
Entering Water Temperature (EWT)
CONTROL STRATEGIES OF
RADIANT COOLED FLOORS By maintaining a constant-volume flow rate through the
radiant loop, it is possible to maintain the surface temperature
A successful control strategy for maintaining the perfor- at a constant 68°F (20°C) by varying the EWT. The radiant
mance of a radiant cooled floor is critical to achieving comfort floor pump can be provided with a single-speed motor, and the
criteria and ensuring that surface temperatures do not drop floor surface temperature can be monitored by a surface-
below acceptable levels (20°C, 68°F). mounted temperature sensor. As the space specific load and/
The performance of the radiant floor at varying load or shortwave load decreases, the surface temperature will
conditions was determined under two control methods by begin to decrease; the surface temperature can be maintained
utilizing the simplified calculation method and the space heat by allowing the EWT to increase. Figure 2 shows a plot of the
exchange coefficient described in this paper.
It is acknowledged that there will be some time delay
associated with control of the radiant floor, which is not
directly addressed in this paper. The intent of this section is to
show the overall effect of different control strategies, and addi-
tional work will be required to investigate the time responses
of each system with a dynamic model.
The performance of the radiant floor was determined for
the load conditions listed in Tables 4 and 5.
Table 4.
Table 5.
Shortwave radiation load 0 Btu/h ft2 0 Btu/h ft2 0 Btu/h ft2 0 Btu/h ft2 0 Btu/h ft2 0 Btu/h ft2
CH-06-2-3 7
surface temperature, EWT, and LWT at varying load condi- Again as expected, the delta between the EWT and LWT
tions under this control strategy. decreases with the space load. Compared with the control
As expected, as the space load decreases, so does the delta strategy shown in Figure 2, the delta for the minimum operat-
between the EWT and the LWT. ing point of a variable-volume control strategy is considerably
higher than with a constant volume, variable EWT strategy—
17°F (8.9°C) and 6°F (3.3°C), respectively. It is also worth
Variable Volume, Constant noting that the minimum operating point is considerably less
Entering Water Temperature (EWT) than 30% of the maximum, the typical lower threshold of vari-
Alternatively, it is possible to vary the volume flow rate able-speed motors.
through the radiant loop while maintaining a constant EWT. Figure 4 shows the performance of the radiant floor in the
This control strategy can be more difficult and costly to imple- absence of control under constant volume, constant EWT
ment in practice, as it requires a variable-speed motor and conditions. The figure indicates that as the space load
controls for a very small motor. It would still be possible to increases, the surface temperature rises several degrees, reduc-
track the volume flow rate against the surface temperature and ing the convective and longwave performance, both of which
adjust the flow as the specific space load changed. Figure 3 are temperature dependant. Conversely, as the space load
shows a plot of the surface temperature, EWT, and LWT at decreases, the temperature of the flow drops below the desired
varying load conditions under this control strategy. 68°F (20°C), and issues with comfort and condensation may
arise.
RESULTS
Figure 5 shows the results of various floor surface temper-
atures used in this analysis. The floor surface temperatures
were influenced by changing the entering water temperature
with a constant flow rate (see Figure 2). For a space condi-
tioned with an all-air system, the resulting floor surface
temperature is more than 88°F (31°C). This is mainly due to
shortwave radiation heating the floor and then being re-emit-
ted as longwave radiation to the space.
The remaining results show the surface temperature of the
floor held constant by using a radiant cooled floor. Each of
these floor surface temperatures are used for subsequent anal-
ysis shown in Figures 6, 7, and 8.
Figure 6 shows the resulting mean radiant temperatures
(MRTs) in the space as the floor surface temperatures are
Figure 3 Variable flow, constant EWT control strategy. varied. The MRT for the space conditioned with an all-air
Figure 4 Radiant cooled floor performance without a Figure 5 Floor surface temperatures.
control strategy.
8 CH-06-2-3
system is nearly 92°F (33.3°C); all the alternatives with radi- alternatives. The reduction in the dry resultant temperature
ant cooled floors have space MRTs of 82°F (27.8°C) or lower. from the all-air system to the radiant cooled floor alternatives
As the MRT approaches the space air temperature, the comfort provides an indication of how significantly a reduction in the
conditions will be improved. MRT (Figure 6) can affect the overall space conditions. A
With the all-air system, the direct shortwave radiation system without a radiant floor has a dry resultant temperature
entering into the space is absorbed by the floor and retrans- higher than 88°F (31.1°C), but the radiant floor alternatives all
mitted back into the space as longwave radiation. The long- have dry resultant temperatures of 82°F (27.7°C) or lower. The
wave radiant heat transfer between the floor and the lower dry resultant temperatures in the space provide an indi-
surrounding room surfaces increases the overall MRT of the cation of how the overall comfort conditions can be improved
space, further increasing the MRT. By implementing a radiant in a space as a result of using a radiant cooled floor.
cooled floor, the surface temperature of the floor is held nearly
Figure 8 shows the total sensible gains to the space, which
constant even though direct shortwave radiation is being
are a maximum of 32 (Btu/h)/ft2. The radiant floor analyzed in
absorbed.
this paper has a total capacity of 19 (Btu/h)/ft2 with the other
By absorbing the shortwave radiation and not emitting
13 (Btu/h)/ft2 cooled by the ventilation air.
longwave radiation, the radiant cooled floor reduces the MRT
of the space, as seen in Figure 6; comfort levels will also Figure 9 shows the solar load to the space for all the
improve as the MRT approaches the space air temperature. alternatives; as the radiant floor can absorb a maximum of
Figure 7 shows the dry resultant temperatures, known as 7 Btuh/ft2 of this shortwave radiation, only slightly more
the operative temperature (see Equation 15), for each of the than 2 (Btu/h)/ft2 will add heat to the space.
CH-06-2-3 9
CONCLUSIONS van Gerpen, J.H., and H.N. Shapiro. 1985. Analysis of slab
heated buildings. ASHRAE Transactions 91(2A):473–
The control strategies for the radiant floor produce the 487.
required conditioning effect to the space and at the same time
are capable of absorbing shortwave radiation and preventing Kalisperis, L.N., M. Steinman, L.H. Summers, and B. Ole-
this from being emitted back into the space as longwave radi- sen. 1990. Automated design of radiant heating systems
ation, increasing the space temperature. The results of the anal- based on thermal comfort. ASHRAE Transactions
ysis clearly show that the flow rate though the radiant floor can 96(1):1288–1295.
be maintained at a constant flow rate and the supply tempera- Kreith, F. 1969. Principles of Heat Transfer, 2d ed. Scranton,
ture varied to meet the varying load. The total cooling capabil- PA: International Textbook Company.
ities of a cooled radiant floor are on the order of 19 (Btu/h)/ft2 Leigh, S.B. 1991. An experimental study of the control of
(60 W/m2) rather than the 12 (Btu/h)/ft2 (35 W/m2) usually radiant floor heating systems: Proportional flux modula-
considered for convection-only cooling from radiant floors. tion vs. outdoor reset control with indoor temperature
The next step will be to verify the surface heat transfer coeffi- offset. ASHRAE Transactions 97(2):800–808.
cients from the floor surface to the space to enhance the accu-
Ling, M.D.F., and J.M. Deffenbaugh. 1990. Design strategies
racy of the results. The performance of the radiant floor for this
for low-temperature radiant heating systems based on
application can be used to design radiant cooled floors when
thermal comfort criteria. ASHRAE Transactions
absorbing solar radiation and to evaluate the control strategies
96(1):1296–1305.
for such a design.
MacCluer, C.R. 1991. The response of radiant heating sys-
tems controlled by outdoor reset with feedback.
ACKNOWLEDGMENT
ASHRAE Transactions 97(2):795–799.
This paper describes a steady-state analysis of a radiant MacCluer, C.R. 1989. The control of radiant slabs. ASHRAE
cooled floor and the authors recognize that there are several Journal, September.
dynamic simulation programs and routines available that
Meierhans/Olesen. 1999. Betonkernaktivierung. Velta, Nor-
accomplish a dynamic analysis of radiant cooled floors.
derstedt.
Dynamic routines have been derived by Dr. Richard Strand of
the University of Illinois at Urbana-Champaign and the Olesen, B.W. 1994. Comparative experimental study of per-
ROOM program developed by OASYS. formance of radiant flow-heating systems and wall
panel heating system under dynamic conditions.
ASHRAE Transactions 100(1):1011–1023.
REFERENCES AND BIBLIOGRAPHY
Olesen, Michel, Bonnefoi, Carli, 1998. Heat exchange coef-
ASHRAE. 1996. 1996 ASHRAE Handbook—Fundamen- ficient between floor surface and space by floor cool-
tals. Atlanta: American Society of Heating, Refrigerat- ing—Theory or a question of definition.
ing and Air-Conditioning Engineers, Inc.
Recknagel and Sprenger. 2000. aschenbuch fuer
ASHRAE. 2004. ANSI/ASHRAE Standard 55-2004, Thermal Heizung+Klima Technik. Munich: Oldenburg Verlag.
Environmental Conditions for Human Occupancy. ROOM—A method to predict thermal comfort at any point
Atlanta: American Society of Heating, Refrigerating in a space. Copyright OASYS Ltd., developed by ARUP
and Air-Conditioning Engineers, Inc. Research and Development, London, England.
Athienitis, A.K., and J.G. Shou. 1991. Control of radiant Simmonds, P. 1991. The utilization and optimization of a
heating based on the operative temperature. ASHRAE building’s thermal inertia in minimizing the overall
ASHRAE Transactions 97(2):787–794. energy use. ASHRAE Transactions 97(1):1031–1042.
Borressen, B. 1994. Using radiant floors to absorb solar radi- Simmonds, P. 1994. Control strategies for combined heating
ation (in German). Verta Congress. and cooling radiant systems. ASHRAE Transactions
Braun, J.E. 1990. Reducing energy costs and peak electrical 100(1):1031–1039.
demand through optimal control of building thermal Simmonds, P. 1993. Thermal comfort and optimal energy
storage. ASHRAE Transactions 96(2):876–888. use. ASHRAE Transactions 99(1):1037–1048.
Fanger, P.O. 1972. Thermal Comfort Analysis and Applica- Simmonds, P., W. Gaw, S. Reuss, and S. Holst. 2000. Using
tions in Environmental Engineering. New York: radiant cooled floors to condition large spaces and main-
McGraw-Hill. tain comfort conditions. ASHRAE Transactions
ISO 1984. ISO 7730, Moderate Thermal Environments— 106(1):695–701.
Determination of the PMV and PPD Indices and Speci- Welty, J.R., C.E. Wicks, and R.E. Wilson. 1969. Fundamen-
fication of the Condition for Thermal Comfort. Geneva: tals of Momentum, Heat and Mass Transfer. New York:
International Organization for Standardization. John Wiley and Sons, Inc.
10 CH-06-2-3