Application
MULTICAL® type 66-C is used to measure both heating MULTICAL® type 66-CDE receives volume pulses from the
and cooling in all water based plants with flow tempera- connected flow meters and calculates the energy for
tures from 2°C to 160°C and with all flow meter sizes every predetermined water volume .
between qp 0.6 m3/h and qp 3000 m3/h.
The energy calculation includes temperature measure-
If a flow meter is installed in both the flow and return ments in flow and return as well as correction for densi-
pipes, MULTICAL® type 66-C can monitor leaks and ty and heat content according to EN 1434.
bursts in the heating/cooling system. Furthermore, leak-
MULTICAL® type 66-CDE has a battery back-up for the
ages in the tap water system can be monitored by
calculator. The meter can be supplied by either 230
means of pulses, if a water meter is connected.
VAC, 24 VAC/DC or by a 3.6 V lithium battery.
Power and water flow can be limited by means of
Data can be read either by means of optical reading
MULTICAL® type 66-C if a 3-point motor-operated valve is
placed on the front cover in accordance with EN 61 107
connected in the return pipe.
or by means of plug-in modules, which can be inserted
MULTICAL® type 66-D and type 66-E can also be used to in the calculator itself.
measure energy in open or closed systems.
Kamstrup A/S
Industrivej 28, Stilling
DK-8660 Skanderborg
TEL: +45 89 93 10 00
FAX: +45 89 93 10 01
E-MAIL: energi@kamstrup.dk
WEB: www.kamstrup.com
Calculator features
1. Display 2. Calculation
MULTICAL® is equipped with a liquid crystal display with MULTICAL® uses volume-based energy integrations,
8 numerical digits plus 3 alphanumeric characters. Dur- which means that the speed with which the calculator
ing normal operation the accumulated values for thermal calculates energy consumption is proportional to the
energy and water consumption are shown using 7 digits actual water flow. Depending on the size of the flow part,
and the relevant units of measurement using 3 alphanu- integrations are performed with intervals from 0.001 m3
meric characters (MWh, m3 etc.). to 10 m3.
If a customer number is to be displayed, up to 11 digits The water quantity and degree of cooling are multiplied
can be used, though without measuring unit. using the k-factor from EN 1434, thus ascertaining the
amount of thermal energy. The meter is very accurate,
The accumulated value for thermal energy in MWh, kWh working with energy measurements in fractions. The
or GJ is constantly displayed, the unit depends on the value displayed will, however, be rounded off. Fractions
individual programming. If the left or right front panel is remaining will be added to the next reading.
pressed, the display indicates as follows:
Heating and cooling energy is calculated in the same
1.1 MULTICAL® 66C, standard and leak manner. However, the total is stored in separate regi-
Left key Right key sters, depending on whether the temperature difference
Cooling energy Thermal energy is positive or negative. If the meter is used for combined
m3*tF Volume
m3*tR
heating and cooling installations, the cooling power and
Hour counter
TA2 T1
temperature difference will be indicated by a minus (-) in
TA3 T2 the display.
TL3 ∆t
TL3 Power
The current flow calculation, l/h or m3/h, is performed
VA Monthly peak power depending on the number of pulses generated by the
VB Year’s peak power flow meter. The display is updated every 10 sec. when
T3 Year’s peak date
P1 connecting flow meters with electronical output
Flow
P2 Peak flow (CCC=1xx), though only every 30 sec. when connecting
Customer No. Year’s peak flow mechanical flow meters with reed-switch (CCC=0xx).
Clock Info codes
Date Info counter Pulse separation (imp/l), which is determined by the
Target date CCC-program, ensures that the flow meter and the calcu-
Segment test
lator are totally compatible.
1.2 MULTICAL® 66D, open system
The actual power, kW or MW, is calculated on the basis of
Left key Right key
the current values for: water flow, differential tempe-
VA ∆-energy rature and k-factor. The display value is updated every 10
VB V1-volume
P1 V1-density
sec. as is the water flow.
P2 V1-flow
Customer No.
The peak power and peak flow are determined as the
V1-peak flow
Clock V1-power
average peak over a given period of time, typically 60
Date V2-volume min., but can be configured in the range 1...1440 min.
Target date V2-density
Qsum1 V2-flow temp.
Qsum2 t1-flow temp. 3. Measuring temperature
Segment test t2-reference temp. Prior to each temperature measurement, the calculator
t3-return
Hour counter measures two internal reference resistors, compensating
PR1 for temperature and long-term drift. The temperatures of
PR2 T1, T2 and T3 are measured several times at different
Info
Info hour counter points, thus ensuring forceful mains immunity.
The measurements are linear in the complete tempera-
1.3 MULTICAL® 66E, closed system
ture range from 0...165°C with a resolution of 0.01°C. An
Left key Right key
information code is recorded if the temperature is above
TA2 V1-energy
TA3 or below this range (see section 5).
V1-volume
TL2 V1-density
TL3 The temperature measurements are effectuated at every
V1-flow
VA V1-peak flow energy integration as well as every 10 sec. when the dis-
VB V1-power play is updated.
P1 V2-volume
P2 V2-density
Customer No. V2-flow 4. Permanent memory
Clock t1-flow temp.
Date t2-return temp. The calculator’s EEPROM is updated hourly with all the
Target date (t1-t2) accumulated values, thus ensuring minimum loss in the
Segment test Hour counter event of total power cut (concurrent failure on back-up
PR1
PR2
and primary supply). On the programmed billing date,
Info e.g. 1 June, all relevant data is saved with regard to annu-
Info hour counter al billing reading.
220 sec. after a key has been pressed, the display will
automatically revert to the accumulated thermal energy.
2
Calculator features
Additionally, the EEPROM comprises an extensive data 230 VAC, type 66-00-300-000
logger with intervals from hours to years. The data log- Supply module with galvanic separation from the net
ger’s capacity is 960 hours/60 days/36 months/15 supply. The module meets the demands of douple isola-
years. Furthermore, all changes in the info code are tion and is designed for direct net connection.
logged (see section 5), which facilitates effective trouble
shooting. NB: National installation rules and regulations must be
complied with!
7. Voltage supply The plug-in modules now available, which are listed in
MULTICAL is constructed with two separate voltage sup-
® the order specification, can be supplied together with
plies: a back-up battery, which is incorporated in the cal- the calculator or separately for retrofitting in meters that
culator top, as well as a primary supply, which is placed are already installed.
in the base of the unit.
10. Programming & verification
The primary supply is either a D-cell lithium battery or a
supply module designed for external net supply. A METERTOOL for MULTICAL® type 66-CDE is Windows®
change from one supply type to another can be carried based software, which contains all facilities necessary to
out on site without re-verification. program the calculator. When the software is used with
VERIFICATION EQUIPMENT, type 66-99-28x, the calcula-
Battery, type 66-00-200-000 tor can be tested and calibrated. See “Accessories” for
“High Capacity D-cell” lithium batteries must be used. type number of METERTOOL and VERIFICATION EQUIP-
These are very reliable and ensure safe, reliable metering MENT.
for up to 10 years, depending on the application (see
technical data). 3
Approved measuring data
Approv. authority/standard DS/EN 1434 and Accuracy EC ±(0.5 + ∆θ min/∆θ) %
DIN/EN 1434
Temperature sensors Pt500 - EN 60 751
Heat meter
Flow meter sizes θp 0.6 m3/h...3000 m3/h
Temperature range θ 10°C...160°C
Environment class A
Differential range ∆θ 3K...150K
Cooling meter
Temperature range θ 2°C...30°C
Differential range ∆θ 3K...20K
Technical data
Temperature inputs T1, T2 and T3 General data
Temperature range 0°C...165°C Accuracy, calculator ±(0.15 + 2/∆θ) %
Differential range 0K...160K Accuracy, sensors pair ±(0.4 + 4/∆θ) %
Display resolution 0.01K Voltage supply 3.65 VDC ±10%
Sensor type Pt500 - EN 60 751 Power consumpt. - idle < 35µA excl. flow meter
Back-up battery ½ AA lithium cell
Flow meter inputs V1 and V2 -lifetime 20 years with wall mounting
Input resistance > 100 kΩ
Primary battery D-cell lithium, HiCap
Pulse ON (< 0.5 V) > 0.5 msec. -lifetime 10 years with wall mounting
8 years with compact mounting
Pulse OFF (> 2.0 V) > 10 msec.
5 years with 2 flow meters
Pulse frequency < 128 Hz connected
Integration frequency < 1 Hz Net supply 230 VAC +15/-30%, 48...52 Hz
24 VAC/DC ± 30%
Material characteristics Power absorbtion < 1 W (1 VA)
Calculator top SAN
Supply back-up Integral SuperCap
PCB casing ABS which eliminates operation
stop due to power cuts up to
Connection unit PP
5 min.
Gaskets Sarlink 3150 B
Data output Passive, isolated serial data
Wall bracket PC+30% glass Req: 300 Baud,
Data: 1200 Baud
Can be converted to RS232
Type approvals
Permanent
062 TS
TS 27.01 27.01 memory EEPROM
098 Display LCD, 8+3 digits, 7 mm digit height
DS 2340 EN 1434 Optical IR head EN 61 107
General
Ambient temperature 0°C...55°C
Storage temperature -20°C...60°C
Protection class IP 54
Weight 0.4 kg, excl. flow meter
4
Order specifications
Type number 66 - o - o - o - o - o - ooo
5
Accessories
Description Type No.
IR head with 9 pole FD-sub 66-99-102
IR head with 25 pole MD-sub 66-99-107
Data cable with 9 pole FD-sub 66-99-106
Configuration number
Config. number DD - E - FF - GG - M - N
oo o oo oo o o
Display readings
Tariff type
6
Dimensional drawings
MULTICAL® panel-mounted
Panel cut-out 137 x 185 mm, ±1 mm
MULTICAL® wall-mounted
7
Tolerance band
The above diagram shows MULTICAL®'s tolerance band, compared with tolerance requirements in EN 1434,
5810-280 GB/06.2002/Rev. C1
Authorized distributor
Please contact Kamstrup A/S for information about your