You are on page 1of 10

This is an open access article published under an ACS AuthorChoice License, which permits

copying and redistribution of the article or any adaptations for non-commercial purposes.

Article

pubs.acs.org/est

Influence of the Mixing Energy Consumption Affecting Coagulation


and Floc Aggregation
Yamuna S. Vadasarukkai and Graham A. Gagnon*
Dalhousie University, Halifax, Nova Scotia B3J 1Z1, Canada
*
S Supporting Information

ABSTRACT: The operational significance of energy-intensive


rapid mixing processes remains unaddressed in coagulation
See https://pubs.acs.org/sharingguidelines for options on how to legitimately share published articles.

and flocculation of insoluble precipitates (flocs), which play an


important role in the removal of impurities from drinking
water supplies. In this study, the influence of rapid mixing and
associated mixing energy on floc aggregation was examined for
Downloaded via 103.133.141.122 on November 24, 2020 at 16:37:09 (UTC).

a surface water source characterized by a high fraction of


aquatic humic matter. Infrared spectral analyses showed that
the colloidal complexes resulting from ligand exchange
between iron and dissolved natural organic matter (DOM)
were not substantially influenced by the mixing energy input.
This signified that DOM removal by coagulation can be
achieved at lower mixing intensity, thereby reducing energy
consumption. In contrast, macroscopic investigations showed the coagulation mixing energy affected floc size distributions during
the slow mixing stage in flocculation and, to some extent, their settling characteristics. The results from analysis of floc properties
clearly showed that more mixing energy was expended than necessary in coagulation, which is typically designed at a high mixing
intensity range of 600−1000 s−1 in treatment plants. The key findings from this study have practical implications to water utilities
to strategically meet water quality goals while reducing energy demands.

1. INTRODUCTION coagulation with the plant influent. A rapid-mixing tank with


Urban water infrastructure systems require significant amounts mechanical mixers is often a conventional means to accomplish
of energy for proper operation of major processes, which may mixing process in water treatment practice.7 Rapid-mixing tanks
include water intake, conveyance, treatment, and distribution are typically designed for intense mixing with a root-mean-
systems, to deliver a safe and high-quality drinking water to square velocity gradient (G-value) of 600−1000 s−1.8 Previous
customers. Life cycle analysis (LCA) is often used to quantify studies have identified several disadvantages in this tank
energy usage at each stage1−3 as measured by energy design,7,9 stating that the practice of intense mixing in
benchmarks, such as kilowatt-hour of electricity consumed coagulation is largely unnecessary. A major shortcoming is
per unit volume of treated water. 4 Accordingly, the that a relatively large amount of energy is utilized to achieve a
predominant use of electricity is directly associated with typical design mixing intensity since the average power supplied
pumping (e.g., low lift and/or high lift pumps), which is increases with the square of the G-value. For instance, Edzwald7
connected to the pressure demands and operational character- calculated that the power requirement to achieve a typical G-
istics of water distribution networks. Ultimately, pumping value of 750 s−1 was 6.25 times greater when compared to 300
represents 60−85% of the total electricity consumption for s−1. This reflects a proportional increase in the energy cost and
surface water treatment plants.1,5 Rapid mixing in coagulation is associated carbon emissions.
described as the second largest consumer of direct energy in a Experimental investigations have supported the theory that
conventional water treatment plant.2,5 A report from the the coagulation process has a great potential for energy savings
Electric Power Research Institute (EPRI)5 estimated that rapid with regards to rapid mixing conditions, without sacrificing
mixing processes had a total electricity consumption of water quality standards.10−12 For instance, Vadasarukkai et al.11
approximately 308 kW-h/day in a representative surface water have proposed a low-mixing intensity range of 110 s−1 < G <
treatment plant with a intake of 45 million liters/day (MLD). 450 s−1 for a combined effective removal of turbidity and
In addition, the primary energy (e.g., fossil fuels, nuclear dissolved natural organic matter (DOM). Alternatively, a more
energy, renewable energy) used in the production of electricity
for the operation of these systems is associated with greenhouse Received: December 12, 2016
gas (GHG) emissions.6 Revised: January 23, 2017
In water treatment practice, high energy is expended to Accepted: February 16, 2017
ensure instantaneous dispersal of chemicals added during Published: February 16, 2017

© 2017 American Chemical Society 3480 DOI: 10.1021/acs.est.6b06281


Environ. Sci. Technol. 2017, 51, 3480−3489
Environmental Science & Technology Article

sustainable system for coagulation mixing, such as pipe and Table 1. Raw Water Quality for Kelly Lake
open channel static mixers, are now available to water plants.7
water quality parameters values
Nevertheless, there has been no study to date that examines
how energy utilized in coagulation specifically influences the pH 6.0 ± 0.3
overall aggregation of metal hydroxide precipitates. Surface turbidity 0.4 ± 0.1 NTU
hydroxyl groups on these precipitates aid in effective sorption total organic carbon 3.8 ± 0.3 mg/L
of turbidity, pathogens, inorganics, and DOM to their surfaces. dissolved organic carbon 3.6 ± 0.3 mg/L
Such precipitates can also grow into large sized aggregates UV absorbance at 254 nm 0.15 ± 0.02 cm−1
through the formation of hydroxyl bridges between metal SUVA 4.0 ± 0.2 L/mg.m
precipitates,13 collectively termed flocs. These flocs play a vital zeta potential −24 ± 0.4 mV
role in the fate and transport of contaminants incorporated in Elemental Analysis Concentration (μg/L)
their structural matrix and their removal in subsequent solid− magnesium (Mg) 556 ± 2.7
liquid separation processes. iron (Fe) 330 ± 2.4
In efforts to reduce targeted impurities from drinking water sodium (Na) 3900 ± 2.8
supplies, it is important to understand the factors that may aluminum (Al) 111 ± 1.0
affect floc aggregation. The objective of this research was to calcium (Ca) 1470 ± 11.3
understand how and to what degree the mixing energy potassium (K) 196 ± 5.4
consumed in coagulation influences the overall characteristics
of flocs, including morphology, size distributions, and settling These optimal chemical conditions were used for enhanced
characteristics. Surface analyses of flocs formed immediately coagulation in the present study to form iron-DOM floc
after the rapid mixing process (i.e., microflocs) were aggregates.
characterized using Fourier transform infrared (FT-IR) spec- All experiments were carried out at a room temperature (21
troscopy. This was performed to obtain specific information on ± 1 °C) in a 1-L square jar test beaker, fitted with a flat paddle
the mechanism of interaction(s) of sorbed constituents and the impeller (76 × 25 mm). A compact digital mixer (Cole-Parmer,
metal hydroxide precipitates. Additionally, morphology of Vernon Hills, Illinois), which had a mixing capacity ranging
microflocs formed during the rapid mixing stage was from 50 to 2500 rpm, was used to mix the water sample. The
investigated using transmission electron microscopy (TEM) equivalent G-value for the flat paddle impeller configuration
and scanning electron microscopy (SEM) combined with was determined from the laboratory velocity gradient
energy dispersive X-ray spectrometry (EDS). A digital in-line calibration chart (G-curve) of Cornwell and Bishop.15 The
holographic microscope (DIHM) was used to measure floc size solution was adjusted to the required pH (4.80 or 6.85) by
distributions during slow mixing in the flocculation stage. The adding a predetermined volume of the pH adjusting chemicals
results from the present study provide opportunities for water (i.e., 1 N NaOH or 0.2 N HNO3 solutions). All reagents used
utilities to strategically meet both water quality goals and were of analytical grade and stock solutions were prepared
energy reduction demands. In particular, it is estimated that an using deionized (DI) water.
average of 10% reduction in annual energy costs in utilities Energy calculations were based on a representative surface
across the U.S. represents a saving of more than $400 million water treatment facility, with an average flow of 120 million
annually to the water industry.14 It is anticipated that this study liters/day. eq 1 was used to calculate the daily consumption of
will contribute to the ongoing research and development in energy during the rapid mixing operation in the coagulation
implementing technologies for an effective management of process, expressed in kilowatt-hour/day. The average power
energy resources, costs, and carbon footprints. supplied to stir the mechanical mixer was calculated from the
previously determined G-value, assuming a motor efficiency of
2. MATERIALS AND METHODS 85%.7 A water temperature of 15 °C, a retention time of 20 s in
Water Quality. Source water from Kelly Lake, drawn from the rapid mixing tanks, and a power cost of $0.12 per kW-h was
the intake at the Louisbourg drinking water treatment plant used as the plant design conditions.7
(Sydney, NS, Canada), was used in this study. This raw water ⎛ G2 × Q × t × μ ⎞
× t = ⎜⎜ ⎟×t
avg m
source is characterized by an average specific ultraviolet E = Pavg
absorbance (SUVA) of 4 to 4.2 m−1 of absorbance per mg/L, η ⎟
⎝ ⎠ (1)
indicating a high fraction of aquatic humic matter. Table 1
provides a description of the general characteristics of this where Pavg is the average power supplied in a mixing tank (J/s),
source water, along with the results of elemental analysis t is the operating time period of the mixer (assumed as 24 h), G
measured using the inductively coupled plasma-mass spectrom- is the root-mean-square velocity gradient (s−1), μ is the
etry (ICP-MS) (Thermo Scientific XSeries II ICP-MS, dynamic viscosity of water (kg/m.s), η is the motor efficiency,
Waltham, Massachusetts). Qavg is the average daily plant flow rate (m3/s), and tm is the
Coagulation-Flocculation Experiment. Coagulation and mean hydraulic retention time (s).
flocculation experiments were tested at two pH conditions, a Coagulation experiments were conducted at rapid mixing
slightly acidic pH of 4.80 and a near neutral pH of 6.85, speeds ranging from 0 to 750 rpm, which gave an equivalent G-
following a procedure similar to that of Vadasarukkai et al.11 In value range from 0 to 1450 s−1. An optimized dose of ferric
that study, which used the same source water from Kelly Lake, sulfate and a calculated volume of pH adjusting chemicals were
an iron dose of 0.33 mM and 0.66 mM was determined as added at the start of the rapid mix process. Coagulation was
optimal coagulant concentration (OCC) of ferric sulfate at pHs conducted for 90 s at a specific G-value. Flocculation was
4.80 and 6.85, respectively. At the OCC, the authors showed achieved at a fixed G-value of 46 s−1 for 18 min. The energy
total organic carbon (TOC) concentration and residual consumed in the slow-mixing stage was not included in the
turbidity decreased following settling in the treated water. total energy consumption of the plant, but accounts for 103
3481 DOI: 10.1021/acs.est.6b06281
Environ. Sci. Technol. 2017, 51, 3480−3489
Environmental Science & Technology Article

kW-h/day. The operating conditions used in this study were 24 h. This allowed the water from the surface of floc structures
within the recommended standards followed in water treatment to evaporate and prevented crystallization, which occurs at
plants,8,16 except for the G-value and 90 s of mixing time high-temperature (e.g., 30−104 °C) drying.17,19 A FEI Tecnai-
specified in the coagulation experiments. The use of more than 12 TEM (Hillsboro, Oregon) equipped with a Gatan 832 CCD
one chemical (e.g., ferric sulfate, 1 N NaOH or 0.2 N HNO3 camera and Gatan Microscopy suite software was used to take
solutions) in the present case required this additional retention floc images. Duplicate samples were prepared for each analysis.
time to simulate plant conditions.8 The sample preparation was kept consistent for both the
Characterization of Micro- And Macro- Structures of electron microscopy so to produce compatible results at
Iron-DOM floc Aggregates. Rapid Mixing Stage. Analyses different mixing conditions. That is, using a 10 mL pipet, a
of the functional groups in the resulting microflocs was droplet of floc sample was carefully placed on a SEM sample
performed using an attenuated total reflectance (ATR) Fourier mount, and the sample was dried at room temperature before
transform infrared spectroscopy (FT-IR) in the mid-infrared image analysis. The samples were sputter coated with gold−
region of 4000−650 cm−1 in the absorption mode (Cary 630 palladium to prevent charge buildup on poorly conducting
ATR FT-IR, Agilent Technologies, California). An approximate samples, such as flocs in the present case. A Polaron SC7620
volume (∼200 mL) of floc aggregates was collected following mini Sputter Coater (Quorum Technologies, Lewes) with a
coagulation. The floc suspension was left undisturbed to settle plasma current of 18 mA for 120 s was used for this purpose.
for an hour in an acid-rinsed crucible while supernatant was The samples may ineffectually dissipate the resulting electron
carefully discarded using a 25 mL glass pipet. charge without such coating procedures, which can cause
Flocs contain water molecules, which can absorb a significant imaging artifacts.24 Both the elements were removed during the
portion of the infrared (IR) band due to the hydroxyl group energy dispersive X-ray spectroscopy (EDS) analysis of
(−OH). Therefore, water molecules can interfere with the elemental compositions. A Hitachi S-4700 FEG SEM (Hitachi,
spectral analysis of organic compounds (e.g., carboxylic, Tokyo) equipped with an energy dispersive X-ray spectroscope
phenolic groups of DOM), as residual water are reported to was used to provide analysis of elemental composition of
absorb strong signals at 3700−3000 cm−1 and 1700−1600 samples. Each EDS spectrum was run for at least 30 s, with an
cm−1.17 For this reason, many studies have concentrated and accelerating voltage of 20 kV and an emission current of 8.5 μA.
dried the floc samples.17−19 Fewer studies have preferred a A minimum of four EDS spectra per image was analyzed and
diffuse reflectance infrared Fourier transform (DRIFT) spec- the most representative images are presented. Each reported
troscopy for investigations of aquatic humic substances.20 Other value was calculated by averaging the elemental composition
adsorption studies have applied a thin layer of metal oxides on from various representative SEM images (4−7 images), with at
the crystal surface and then filled the ATR cell with organic acid least four EDS spectra per image.
solutions.21 In the present study, sample was oven-dried at 35− Flocculation Stage. A digital in-line holographic microscope
40 °C for at least 3 days (or until the water was evaporated (DIHM) from 4deep Inwater Imaging (Halifax, Nova Scotia,
from the sample). The oven-dried floc aggregates were gently Canada) was used to measure the dynamic growth of floc sizes
scraped and stored in a vial at 4 °C until analysis. A more during the coagulation-flocculation experiments. The micro-
specific description of the sample preparation method is scope was vertically mounted to one of the corners of the jar
illustrated in the Supporting Information (SI). beaker, minimizing any interruption to the impeller rotations.
An attenuated total reflectance flow cell with a zinc selenide Holograms of flocs were recorded continuously at 2 frames per
(Zn−Se) crystal was used for this purpose. The Happ-Genzel second (fps), and they were stored as digital bitwise images.
method was used with 200 scans at a resolution of 2 cm−1. The formation of microflocs was not recorded at coagulation
Backgrounds were taken with the crystal alone. Analysis of the G-values >450 s−1 due to bubbles formed near the sampling
spectral data was performed using optical spectroscopy software port, which can cause significant errors in size measurements.
(Spekwin32, Germany).22 Numerical reconstruction of holograms was performed to get
Transmission electron microscopy (TEM) and scanning images of floc aggregates, as described in Vadasarukkai et al.25
electron microscopy (SEM) combined with energy dispersive Equivalent circular diameter (d) of floc size was calculated from
X-ray spectrometry (EDS) were used to take images of flocs the area of the identified flocs, which was expressed as a
generated from coagulation. Approximately 20 mL sample was volume-based floc equivalent diameter.
collected from the rapid mixing stage and stored at 4 °C until Settling Properties. The treated water from the jar test
the analysis. As both electron microscopy techniques work in beaker was poured into an Imhoff cone (Wheaton, Millville,
vacuum, a large quantity of water in floc sample must be NJ) immediately after the slow stirring operation in
removed as a sample preparation step. Initial investigation of flocculation. It was allowed to settle quiescently for 24 h.
floc images identified that flocs dried at 30−45 °C were Samples were collected periodically from 10.3 cm below the
irregular flat-plates, coarse/rough textured aggregates with water surface using a wide-mouth glass pipet. Residual turbidity
sharp edges (data not shown), which may not effectively measurements were recorded using a HACH 2100AN
represent an amorphous floc precipitate commonly seen in laboratory turbidimeter (Hach Company, Loveland, Colorado).
water treatments. It was therefore concluded that the sample The volume of settleable solids was recorded at the end of the
preparation at an elevated temperature was unsuitable for the experiment. This study did not account for a drop in water level
SEM observation of floc structures. height due to the withdrawal of approximately 40 mL of water
Alternatively, Cornelissen et al.23 found the resulting damage samples during turbidity measurements, which can result in an
from drying of flocs at room temperature was not apparent at estimated 5% discrepancy for the high settling velocity and at
smaller floc sizes imaged using TEM. Therefore, a droplet of approximately a 30% discrepancy for the low settling velocity
the TEM sample was carefully placed on a 200-mesh copper values.26 The linear range of the curve was identified, and it was
grid from Electron Microscopy Sciences (Hatfield, Pennsylva- used to determine the sedimentation rate,27 as expressed in eq
nia). The grid was then allowed to dry at room temperature for 2.
3482 DOI: 10.1021/acs.est.6b06281
Environ. Sci. Technol. 2017, 51, 3480−3489
Environmental Science & Technology Article

Figure 1. TEM images of microfloc formed at a G-value of 175 s−1 for the optimal coagulant concentration of 0.33 mM of Fe and pH 4.80. Floc sizes
shown in the inset were measured using ImageJ software v1.49.

y2 − y1 distributions between the two pHs, as illustrated in Figure 2.


slope(NTU,min) =
x 2 − x1 (2) A significant difference in the variation of floc size distributions
where y1 and y2 are the values of turbidity in NTU of the linear
slope. The slope of the regression line was calculated between
the time period 0 (x1) and 30 (x2) minutes of the settling
period.

3. RESULTS AND DISCUSSION


Floc Morphology and Size Distributions at Optimal
Coagulant Concentrations (OCC). The iron to carbon ratio
(i.e., >0.8 mg Fe/mg TOC) used as OCC in the present study
resulted in a rapid growth of ferric flocs in the rapid mixing
stage itself kept at a G of 175 s−1, which was well within the
optimal operating range (i.e., 110 s−1 < G < 450 s−1) of mixing
energy input recommended for enhanced coagulation.11 This
corresponds to an energy usage of 27 kW-h/day for a 120
million liters/day representative treatment facility.
TEM micrographs in Figure 1 showed three sample
population of flocs at the nanoscale, illustrating that a variety
of floc morphologies were present at the optimal coagulant
concentration. The darker regions of the TEM images in Figure
1b and c showed dense, spheroid-like or needle-like clusters Figure 2. Illustration of floc size distributions at a flocculation mixing
that were closely packed to one another. The darker regions intensity (G-value) of 46 s−1 for the optimal coagulant concentrations.
represented a floc size of 60 to 180 nm, as shown in the insets. The displayed histogram was estimated from three replicate
According to previous microscopic investigations,28,29 the experiments at pH 4.80 and 6.85, respectively.
association of coagulant species and humic networks was
hypothesized to form similar electron-dense spots having a between the two experiments was confirmed using Levene’s
variety of shapes, including needle-like, globular or net-like test (α = 0.05; N > 30). The volume fraction of floc sizes
structures. In the present case, this network of clusters was ranged from 100 to 1000 μm at pH 4.80. The median floc
interconnected by what appear to be different sizes of granular diameter (D50) was 424 μm. At the higher iron dose (0.66
structures that were lighter in appearance. The lighter regions mM, pH 6.85), floc sizes were more variable and had a greater
were prominent near the edges of floc aggregate. Another type D50 value of 581 μm.
of floc morphology shown in Figure 1a was often seen in TEM Unlike the distinct differences in floc sizes, it was difficult to
micrographs at different scales of observation. The shape of the interpret the inherent differences in the floc morphology
aggregate can be best described as an irregular, flaky or between the two experiments because of fractal nature of floc
relatively tenuous precipitate made up of many particles of aggregates. Details on micrographs are included in the SI (i.e.,
darker and lighter shades. Few of the darker particles were Figures S2 in SI). Most of the TEM micrographs showed
closely packed, while many of them were loosely joined to one irregular, flake-like geometries at both pHs. At pH 6.85, many
another, as one can visually see from a large amount of void sections in the TEM grid had partially transparent patches of
spaces in their structure compared to Figure 1b and c. Many approximately 100 to 500 nm in size (inserts shown in Figure
larger floc aggregates observed under a different magnification S2c and S2d in SI) that resembles a sheet of fabric attached to
(e.g., Figures S2 in SI) showed similar irregular geometric the precipitate. This TEM observation may represent
resemblance to the aggregate shown in Figure 1a. This visual amorphous hydroxide precipitates favored at around neutral
observation of self-similarity in the shape of floc aggregates, pH.31
regardless of the scale of observation, is consistent with the Influence of Mixing Energy Utilized in Rapid Mixing
fractal nature of floc precipitates.23,30 on Coagulation, Flocculation, And Settling Processes.
Differences in the optimal coagulant dose at pH 4.80 and This section discusses the influence of variation in the mixing
6.85 (i.e., an iron dose of 0.33 mM vs 0.66 mM, respectively) energy consumed in coagulation on the overall characteristics
resulted in a major difference in the overall floc size of floc properties, including morphology, size distributions, and
3483 DOI: 10.1021/acs.est.6b06281
Environ. Sci. Technol. 2017, 51, 3480−3489
Environmental Science & Technology Article

their settling characteristics. Energy calculations are representa- Table 2. Peak Intensity Ratios Calculated from the Infrared
tive of a 120 million liters/day surface water treatment facility. Spectra at Various Coagulation Mixing Intensities (G-value)
a. Aggregation Behavior of Primary Particles (DOM) and the corresponding energy consumed in the coagulation
during Coagulation. Initial population has a strong influence experiments at (a) 0.33 mM of Fe and pH = 4.80 (b) 0.66
on floc size formation.32 In the present study, a major mM of Fe and pH= 6.85
constituent of primary particles was comprised of dissolved
G-values (s−1) 46 175 452 1450
organic matter (DOM), which played an important role in the
characteristics of flocs resulting from coagulation. Results from energy consumed at 120 MLD
(kW-hr/day) 2 27 183 1879
the FT-IR spectral analyses (Figure S3 in SI) showed similar
surface complexation-ligand exchange reactions between DOM Assignment of Peak Intensity Ratios: (a) 0.33 mM of Fe and pH 4.80
and iron hydroxides at both pHs, despite the differences seen in adsorbed carboxylate (υas) I1559 1.77 1.50 1.57 1.51
the floc size distributions. This phenomenon of adsorption of structural O−H I3177
DOM on to metal oxide surfaces has been demonstrated
previously in natural soil and aqueous systems.33−35 It resulted adsorbed carboxylate (υs) I1375 1.61 1.32 1.46 1.33
in similar IR peaks at 1559 and 1375 cm−1 at both the pHs in structural O−H I3177
the present study (spectral results are presented in Figure S3 in
SI). These absorption bands represented the stretching adsorbed SO4 I1039 2.46 1.72 1.99 1.71
vibrations of the carboxylate groups (i.e., COO−) adsorbed structural O−H I3177
onto the surface active hydroxyl functional groups of iron
hydroxides (i.e., Fe−OH2 and Fe−OH stretches), which has Assignment of Peak Intensity Ratios: (b) 0.66 mM of Fe and pH = 6.85
been previously noted for the adsorption process on iron adsorbed carboxylate (υas) I1558 1.29 1.44 1.34 1.32
hydroxides.36 structural O−H I3177
The adsorption of DOM on iron hydroxides were influenced
by the pKa values of functional groups in the raw water, which adsorbed carboxylate (υs) I1374 1.11 1.23 1.13 1.11
had approximate values of 2.85 and 7.03 from acid−base structural O−H I3177
titration curves (data not shown). At pH 4.80, disassociation of
protons was expected, favoring the COO− functional groups to adsorbed SO4 I1044 1.41 1.37 1.38 1.07
replace the dominant OH2 groups from surfaces of iron.37 structural O−H I3177
Therefore, an addition of a 0.33 mM of iron at pH 4.80 resulted
in a partial neutralization of the net positive charge on iron carboxylate groups (i.e., COO−) peaks 1559 and 1375 cm−1 at
hydroxide surfaces and formed insoluble iron-DOM complexes. different mixing energy inputs. This suggests iron-DOM
Alternatively, when the pH was near the pKa value of 7.03, complexes formed in the hypothesized size range of 60−180
more protons in the humic networks were disassociated, nm were less vulnerable to the coagulation G-values. In other
leading to an increase in the iron dose from 0.33 to 0.66 mM at words, it implied DOM removal by coagulation can be achieved
pH 6.85. at reduced energy consumption. This disproves the theory that
A major difference between the two pHs occurred in the intense mixing is necessary to bring about particle−particle
fingerprinting region below 1100 cm−1, which can be explained collision for effective interactions. However, a relatively large
by the adsorption behavior of sulfate. Peak et al.38 had shown standard deviation for the adsorbed sulfate peak near 1039
the spectrum of sulfate adsorbed on goethite had a sharply cm−1 was evident at both pHs. This implies that the coagulation
defined peak at 976 cm−1 for pH less than 6, forming an inner- G-values caused some changes to the shape of absorption
sphere sulfate complex with two distinctive splits formed at spectra of sulfate complexes, indicating changes in their
1055 and 1133 cm−1. These peaks were similar to the IR peaks composition.
formed at pH 4.80 in the current study at 975, 1040, and 1111 b. Microstructure and Their Interactions. A scanning
cm−1. At pH 6.85, the sharp peak at 975 cm−1 was broadened electron microscope with an energy dispersive X-ray spectros-
and shifted to 969 cm−1. Aromatic ethers, carbohydrate, and copy (SEM-EDS) analysis was used to compare the elemental
polysaccharide groups also exhibit a broad band near 1120−980 composition of flocs formed at different mixing energy inputs
cm−1 with a characteristics peak near 1034 cm−1.39 It is possible during coagulation. Although a consistent sample preparation
that sulfate may have interacted with the coadsorbed functional technique was used for both electron microscopy methods, floc
groups of DOM macromolecules and formed complexes, images taken using SEM looked significantly different from
instead of being directly incorporated on to the surface of those observed by TEM, which is likely an artifact of drying
iron hydroxides. This observation was previously described for process. This suggests that drying at room temperature resulted
enhanced adsorption of trace metals onto iron oxide surfaces in some perturbation of hydrated floc samples for SEM
through the formation of ternary complexes in the presence of observation. Cornelissen et al.23 found cryogenic freezing of the
high sulfate concentrations.40 samples can improve imaging of larger (1−100 μm) floc
The relative peak intensity ratios in Table 2 provided a particles using SEM, without the loss of structural information
quantitative comparison of IR peaks formed at different resulting from drying.
amounts of energy used in coagulation. Details on the spectral TEM images were more representative of flocs because of
comparison at different mixing energy input are included in insignificant damage caused by the drying process, which is
Figure S4 in SI. The ratios for the three prominent peaks of likely due to the small size range of flocs analyzed using TEM.23
adsorbed constituents (i.e., 1559, 1375, and 1039 cm−1) and Floc morphology can be evaluated using SEM despite the
the structural O−H vibration (i.e., 3177 cm−1) in the lattice artifacts introduced by drying. SEM images revealed qualitative
structure of flocs were calculated as I1559/I3177, I1375/I3177, and differences in floc morphology as a function of mixing
I1039/I3177. It showed a fairly constant ratio for the adsorbed condition. For instance, the SEM analysis showed the flocs
3484 DOI: 10.1021/acs.est.6b06281
Environ. Sci. Technol. 2017, 51, 3480−3489
Environmental Science & Technology Article

resulting from a low mixing energy had flat plate-like structures hydroxides), in addition to the oxygen present in organic
that were assembled in an elongated pattern. At higher mixing matter.
energies, smaller flocs composed of globular aggregates with a The EDS data, along with the FT-IR analyses, reinforces the
compact structure were observed (Figure S5 in SI). This interpretation that hydrolyzed iron species interacted with
phenomenon can be related to flocculation mixing studies.32,41 DOM macromolecules, resulting in flocs with DOM-iron
In those studies, a consistent trend of reduction in floc sizes compositions within their structure. However, the elemental
with increasing the mixing intensity was shown to form small analysis cannot confirm the nature of the interactions, which
and compact flocs. The floc samples were investigated further may require investigations using X-ray photoelectron spectros-
using EDS analysis to understand the elemental compositions copy (XPS) and/or solid-state nuclear magnetic resonance
that may have resulted in varied floc structures. (NMR) results.43 There was a marginal difference in the
The EDS analysis are semiquantitative as the elemental percentage composition of major elements present between the
compositions are normalized to 100% for the selected elements. two mixing conditions at pH 4.80. That is, carbon and oxygen
A highly irregular surface of flocs resulting from the drying were detected at slightly higher amounts in the floc samples
method may cause increased variations at specific spots and taken at 183 kW-h/day, while the percent weight of iron and
between samples. A low concentration of iron or DOM could sulfur contents was lesser when compared to floc samples taken
be due to differences in surface area (e.g., small/globular, at 2 kW-h/day. Likewise, floc aggregates formed at pH 6.85
elongated/plate-like structures), such uneven surfaces are showed similarities between the elemental compositions at 2
suggested to increase variations in electron scattering and and 183 kW-h/day (Figure 3 (bottom panel)). In this case, an
absorption due to matrix effects.42 Therefore, the EDS results increased fraction of iron (e.g., 8.3−18.2%) was observed in
were not directly compared, but it was used to evaluate the those flocs, which may have experienced more rapid
percent weight trend (e.g., increasing/decreasing) of major precipitation reaction under higher pH conditions.
elements at different mixing conditions. The EDS analysis of elemental composition of flocs
The results from the EDS analysis for coagulation experi- supported the hypothesis that the hydrolysis of iron and their
ments carried out at the mixing energy input of 2 and 183 kW- subsequent aggregation with DOM particles occurred irre-
h/day are illustrated in Figure 3. The elemental composition of spective of the mixing condition. Previous microscopic
investigations have found that iron and DOM interactions
resulted in aggregates of 60−300 nm in size28,29,44 Perikinetic
or Brownian diffusion mechanism initiated by thermal energy
was likely to control particles-coagulant collisions during
coagulation that may result in successful attachment of
particles,45 while the importance of coagulation mixing has
been related to settling characteristics of flocs.29,46 A model
proposed by Siéliéchi et al.29 has indicated that low-intensity
mixing favors small sediment volume due to intrahumic colloid
shrinkage and high-intense mixing is associated with a high
collision rate and large sediment volume.
c. Floc Size Distribution. Mixing energy input in coagulation
governed the floc growth during the slow mixing stage in
flocculation, as illustrated in Figure 4. Unless stated, the data
represents the volume fractions of floc size distributions
measured using the in-line holographic microscopy in
flocculation at 46 s−1. It was apparent that no mixing energy
during coagulation resulted in an obvious decline in the floc
size distribution at pH 4.80. On the contrary, a wide range of
floc sizes were formed at pH 6.85 even without having a proper
mixing condition in coagulation. The slow mixing energy
provided at a 103 kW-h/day in flocculation compensated for
the no mixing operation in coagulation and achieved necessary
bridging between precipitates in that case. On a similar note, a
Figure 3. Illustration of elemental composition of floc aggregates using
recent study had shown the overall water treatment perform-
SEM-EDS analysis for pH 4.80 (top panel) and 6.85 (bottom panel).
ance of a full-scale drinking water treatment plant remained
unaffected during the accidental failures of mechanical mixer in
the rapid mixing tank.10
flocs was comparable between the two mixing conditions, with For an average flow of 120 million liters/day, the energy
oxygen detected as a major element along with carbon, iron, consumed to operate at a specified designed G-values of 600−
sulfur, and sodium coexisting in their structural matrix. Even 1000 s−1 is in the range of 342−913 kW-h/day. As seen from
though EDS spectra detected appreciable percent weight of Figure 4, operating at a mixing energy >200 kW-h/day did not
aluminum (Al) in the floc samples, it was not included in the show any significant improvement in the evolution of floc sizes
analysis because aluminum was also present in the SEM sample in flocculation, in terms of median (D50) and 90th percentiles
mount. Other elements, such as calcium and magnesium, were (D90). Conversely, there was a slight drop in the median floc
detected at a low concentration. The relatively higher percent diameter at higher mixing energy. That is, the decrease in the
weight of oxygen may have been a result of iron hydrolysis (e.g., median floc size was from 375 to 275 μm at pH 4.8 and it
Fe−OH and Fe−OH2) and precipitation reactions (e.g., iron dropped from 550 to 325 μm at pH 6.85. Likewise, Pivokonsky
3485 DOI: 10.1021/acs.est.6b06281
Environ. Sci. Technol. 2017, 51, 3480−3489
Environmental Science & Technology Article

Figure 4. Variation in floc size distributions with the change in the coagulation mixing intensities (G-value) and the corresponding energy consumed
for the coagulation experiments conducted at 0.33 mM of Fe and pH 4.80 (top panel) and 0.66 mM of Fe and pH 6.85 (bottom panel).

et al.41 found for a pilot-scale set up that a shallow reduction in Floc breakage can pose an important practical problem by
the average floc diameter was observed at G ≥ 200 s−1, with the causing resuspension of impurities and increased iron
value of the slope being 0.34. This type of fragmentation of iron concentrations in settled water. An overall shift in the floc
hydroxide flocs has been previously indicated for tannery waste size distributions to the left support this theory of an increase in
samples at >170 s−1.47 the volume fractions of smaller flocs less than 100 μm in
A general trend of decrease in floc sizes occurred in the case diameter. While an increase in small flocs population with
of higher energy usage, representing aggregate breakage. This increasing mixing regimes was indicated, the size detection limit
phenomenon has been demonstrated previously, with floc of DIHM was limited to provide a quantitative estimation of
aggregates becoming more compact and homogeneous in size small flocs less than 17 μm. The size range of the DIHM was
with increasing G-values.32,41 Floc breakage could be a result of suitable to measure flocs larger than 50 μm, which are the
variations in local G-value,48,49 which was not accounted for in
major source contributing toward total surface area, volume,
the present study. High mixing energy may contain maximum
and mass of flocs.51 Further analysis, using a Malvern
local G-values several orders of magnitude higher than the
average G-value. Bridgeman et al.48 found that a 500 μm Mastersizer 300052 and/or Zetasizer nano,44 is recommended
particle was subjected to 9.4 times the average G-value of 165 to examine the small floc size distribution that may have
s−1 at every 5 s of rapid mixing. This suggests that, in the resulted at high energy usage, as carryover of these flocs can
present case, the frequency at which a floc was exposed to a pose significant challenges on downstream separation processes
maximum (peak) local velocity gradient is expected to increase (e.g., turbidity breakthrough in filters, reduced filter runtimes,
with increasing mixing energy. Further analysis, involving floc increased organic loading etc.). Recent work by Yu et al.13
size measurements are required to investigate whether suggests that broken flocs may not grow into large aggregates
shortening the mixing time is necessary to promote floc due to a net reduction in the number of active surface hydroxyl
aggregation and subsequently, improve particle removal50 at groups. This may greatly reduce the effectiveness of separation
different mixing conditions. processes in the present case.
3486 DOI: 10.1021/acs.est.6b06281
Environ. Sci. Technol. 2017, 51, 3480−3489
Environmental Science & Technology Article

d. Settling Kinetics of Flocs. Comparison of slope values in decreasing trend of residual turbidity with time indicated the
Table 3 indicated the sedimentation rates were higher for the settling process had a dampening effect on the differences in
floc characteristics due to coagulation mixing energy. In other
Table 3. Influence of the Coagulation Mixing Intensities (G- words, there was no significant difference in the settling kinetics
Value) And the Corresponding Energy Consumed on the after 60 min, particularly in the recommended mixing energy
Sedimentation Rate As Calculated from the Slope of range of 11−181 kW-h.11 The compact flocs (essentially
Turbidity-Time Regression Line smaller size particles) resulting from a higher coagulation
mixing energy were able to settle given enough time, except for
G-values (s−1) 0 24 112 452 1450
the data shown at 0 and 1879 kW-h/day. As expected, when the
energy consumed at 120 MLD 0 0.5 11 182 1879 coagulation mixing energy was at 0 kW-h/day (i.e., G = 0 s−1)
(kW-hr/day)
and 1879 kW-h/day (i.e., G = 1450 s−1), the residual turbidity
Sedimentation Rate (NTU/ (a) 0.33 mM of Fe and pH 4.80
min):a was fairly high (>2 NTU) even after a settling time of 90 min
−0.32 −0.17 −0.17 −0.10 −0.18 (at an overflow rate of 0.1 cm/min). This demonstrates that a
Sedimentation Rate (NTU/ (b) 0.66 mM of Fe and pH 6.85 minimum amount of energy is necessary to form settleable flocs
min):a and for effective separation of those aggregates from the settled
−0.52 −0.33 −0.32 −0.25 −0.61 water in the subsequent separation processes.
a
The slope of the regression line was calculated between the time
period 0 (x1) and 30 (x2) minutes of the settling period. 4. PRACTICAL IMPLICATIONS FOR WATER
TREATMENT
optimal iron dose of 0.66 mM at pH 6.85 than for 0.33 mM at
pH 4.80. This implies a faster rate of floc formation and The key findings from the present study, which was done at
bench-scale, are also critical to pilot-scale and full-scale
subsequent settling rates were achieved at the higher particle
implementations. In most treatment plants, physicochemical
concentration27 in the case of the near neutral pH. conditions related to the coagulant type and dose, temperature,
The settled water turbidity curve in Figure 5 provides a and pH are routinely optimized at laboratory-scale using jar
comparative evaluation of the effect of coagulation mixing tests and at pilot-scale. Mixing energy input associated with the
energy on the settling characteristics of flocs. An overall tank geometry, impeller types, and speed are not often

Figure 5. Influence of the coagulation mixing intensities (G-value) on settling kinetics for the coagulation experiments conducted at 0.33 mM of Fe
and pH 4.80 (top panel) and 0.66 mM of Fe and pH 6.85 (bottom panel).

3487 DOI: 10.1021/acs.est.6b06281


Environ. Sci. Technol. 2017, 51, 3480−3489
Environmental Science & Technology Article

considered for floc growth in existing testing protocols. This


shortcoming in the design of rapid mixing systems is too big to
■ AUTHOR INFORMATION
Corresponding Author
ignore in the current scenario of rising demands for energy and
*Phone: 902.494.3268; fax 902.494.3108; e-mail graham.
water and consequent carbon emissions. As shown in this
gagnon@dal.ca.
study, more mixing energy is expended in current treatment
plants than is necessary if they operate at recommended design Notes
G-values (i.e., 600−1000 s−1). In the case of a 120 MLD water The authors declare no competing financial interest.
treatment system, reducing energy consumption from a 502
kW-h/day, representing a G-value of 750 s−1, to less than 200
kW-h/day, representing a G-value of 450 s−1, would result in an
■ ACKNOWLEDGMENTS
The authors acknowledge the financial support of both NSERC
annual energy savings of nearly 170 MW-h/year without and Halifax Water through the NSERC/Halifax Water
compromising effluent water quality. That is, energy savings of Industrial Research Chair program. We acknowledge the
over 90% can be achieved depending on plant flow rate. It is Institute for Research in Materials (IRM) at Dalhousie
pertinent that stakeholders and decision-makers consider the University. We thank the technical and in-kind supports of
key results from this study to capitalize on energy efficiency Patricia Scallion (IRM, Dalhousie University) during SEM
opportunities. analysis and Dr. Ping Li (Biology Dept., Dalhousie University)
Flocs play a significant role in the transportation of dissolved in executing TEM analysis. We thank Jon-Paul Sun (Ph.D.
natural organic matter (DOM) and other impurities within Student) from the department of Physics at Dalhousie
engineered treatment systems and their removal from drinking University for allowing us to use the FTIR instrument. The
water supplies. In this study, floc characteristics for a surface authors also acknowledge the technical support of Heather
water source were investigated at two pHs from within a range Daurie at Dalhousie University’s Clean Water lab. We thank the
(pH 4−6) associated with coagulation of high color and TOC Louisbourg water treatment plant authority, Nova Scotia,
waters.53 An important inference drawn was that the mixing Canada for providing access to the water treatment for
energy did not have an influence on the iron-DOM colloidal sampling.
complexes formed in coagulation. While this phenomenon of
complexation of DOM on to the surface of metal oxide is well
documented in early mechanistic studies,33,34 it is expected the
■ REFERENCES
(1) Santana, M. V. E.; Zhang, Q.; Mihelcic, J. R. Influence of water
impact of the reported finding is applicable to other water quality on the embodied energy of drinking water treatment. Environ.
sources and coagulant types. Further investigations on the Sci. Technol. 2014, 48 (5), 3084−3091.
effect of different particle concentrations are recommended. (2) Plappally, A. K.; Lienhard, J. H. Energy requirements for water
production, treatment, end use, reclamation, and disposal. Renewable
The major difference in the overall floc size distributions
Sustainable Energy Rev. 2012, 16 (7), 4818−4848.
resulting at the optimal coagulant concentrations for the two (3) Stokes, J.; Horvath, A. Life cycle energy assessment of alternative
pHs studied would have potential implications for a number of water supply systems. Int. J. Life Cycle Assess. 2006, 11 (5), 335−343.
treatment plants. Prior investigation of the spatial distribution (4) New York State Energy Research & Development Authority.
of floc sizes at a direct filtration plant suggests large, irregular Water and Wastewater Energy Management Best Practices Handbook;
shaped floc aggregates can reduce the effective filter run New York State Energy Research & Development Authority: Albany,
times.25 The data acquired in the present study on floc sizes can NY, 2010.
(5) Electric Power Research Institute. Water & Sustainability (Vol. 4):
be calibrated to a treatment plant’s specific case by operating at U.S. Electricity Consumption for Water Supply & Treatment- The Next
a definite pH, coagulant dose, and mixing energy. For plants Half Century; Electric Power Research Institute Inc.: Palo Alto, CA,
requiring dense and pinpoint flocs, such as in a direct filtration 2002.
facility, a small standard deviation in floc sizes would be (6) Mo, W.; Wang, R.; Zimmerman, J. B. Energy-water nexus analysis
beneficial; this can be achieved at a slightly acidic pH condition. of enhanced water supply scenarios: A regional comparison of Tampa
While ferric salts based coagulation have been practiced widely Bay, Florida, and San Diego, California. Environ. Sci. Technol. 2014, 48
(10), 5883−5891.
in the pH 5s, plants that coagulate at this pH and less may
(7) Edzwald, J. K. Coagulant mixing revisited: theory and practice.
require pH adjustments of treated water prior to filtration. Aqua 2013, 62 (2), 67−77.
Alternatively, in treatment plants with clarification processes (8) American Water Works Association; American Society of Civil
(e.g., sedimentation) it may be more desirable to operate at a Engineering. Mixing, Coagulation, and Flocculation. In: Water
higher pH since this resulted in a relatively high standard Treatment Design, 5th ed.; Randtke, S. J., Horsley, M. B., Eds.;
deviation in floc size distributions which would aid in McGraw Hill, AWWA and ASCE: New York, 2012.
differential settling processes. (9) Kawamura, S. Integrated Design and Operation of Water Treatment


Facilities, 2nd ed.; John Wiley & Sons: New York, 2000.
(10) Allerdings, D.; Foerster, G.; Vasyukova, E.; Uhl, W. The
ASSOCIATED CONTENT practical influence of rapid mixing on coagulation in a full-scale water
*
S Supporting Information
treatment plant. Water Sci. Technol. 2015, 71 (4), 566−571.
(11) Vadasarukkai, Y. S.; Gagnon, G. A. Application of low-mixing
The Supporting Information is available free of charge on the energy input for the coagulation process. Water Res. 2015, 84, 333−
ACS Publications website at DOI: 10.1021/acs.est.6b06281. 341.
Five figures (FT-IR spectral data, Figure S1; TEM (12) Amirtharajah, A.; Mills, K. M. Rapid-mix design for mechanisms
of alum coagulation. J. Am. Water Works Assoc. 1982, 74 (4), 210−216.
micrographs, Figure S2; FT-IR spectral data, Figures S3 (13) Yu, W.; Gregory, J.; Graham, N. Regrowth of broken hydroxide
and S4; SEM-EDS analysis, Figure S5) addressing flocs: Effect of Added Fluoride. Environ. Sci. Technol. 2016, 50 (4),
additional experimental data are included (PDF) 1828−1833.

3488 DOI: 10.1021/acs.est.6b06281


Environ. Sci. Technol. 2017, 51, 3480−3489
Environmental Science & Technology Article

(14) U.S Environmental Protection Agency, Ensuring a Sustainable (35) Vinkler, P.; Lakatos, B.; Meisel, J. Infrared spectroscopic
Future: An Energy Management Guidebook for Wastewater and Water investigations of humic Substances and their metal-complexes.
Utilities; Environmental Protection Agency: Washington, D.C, 2008. Geoderma 1976, 15 (3), 231−242.
(15) Cornwell, D. A.; Bishop, M. M. Determining velocity-gradients (36) Rout, K.; Mohapatra, M.; Anand, S. 2-Line ferrihydrite:
in laboratory and full-scale systems. Journal American Water Works synthesis, characterization and its adsorption behaviour for removal
Association 1983, 75 (9), 470−475. of Pb(II), Cd(II), Cu(II) and Zn(II) from aqueous solutions. Dalton
(16) Ten State Standards of the Great Lakes-Upper Mississippi River Transactions 2012, 41 (11), 3302−3312.
Board of State and Provincial Public Health and Environmental (37) Liu, C., Huang, P. M. The influence of catechol humification on
Managers, Recommended Standards for Water Works; Health Research surface properties of metal oxides. In Humic Substances Structures,
Inc., Health Education Services Division: Albany, NY, 2012. Models and Functions; Ghabbour, E. A.; Davies, G., Eds.; The Royal
(17) Sari, M. A.; Chellam, S. Mechanisms of boron removal from Society of Chemistry: Cambridge, UK, 2001; pp 253−270.
hydraulic fracturing wastewater by aluminum electrocoagulation. J. (38) Peak, D.; Ford, R. G.; Sparks, D. L. An in situ ATR-FTIR
Colloid Interface Sci. 2015, 458, 103−111. investigation of sulfate bonding mechanisms on goethite. J. Colloid
(18) El Samrani, A. G.; Lartiges, B. S.; Montarges-Pelletier, E.; Interface Sci. 1999, 218 (1), 289−299.
Kazpard, V.; Barres, O.; Ghanbaja, J. Clarification of municipal sewage (39) Amir, S.; Jouraiphy, A.; Meddich, A.; El Gharous, M.;
with ferric chloride: the nature of coagulant species. Water Res. 2004, Winterton, P.; Hafidi, M. Structural study of humic acids during
38 (3), 756−768. composting of activated sludge-green waste: Elemental analysis, FTIR
(19) Goodwill, J. E.; Jiang, Y.; Reckhow, D. A.; Gikonyo, J.; and C-13 NMR. J. Hazard. Mater. 2010, 177 (1−3), 524−529.
Tobiason, J. E. Characterization of Particles from Ferrate Preoxidation. (40) Webster, J. G.; Swedlund, P. J.; Webster, K. S. Trace metal
Environ. Sci. Technol. 2015, 49 (8), 4955−4962. adsorption onto an acid mine drainage iron(III) oxy hydroxy sulfate.
(20) Niemeyer, J.; Chen, Y.; Bollag, J. M. Characterization of humic Environ. Sci. Technol. 1998, 32 (10), 1361−1368.
acids, composts, and peat by diffuse reflectance fourier-transform (41) Pivokonsky, M.; Bubakova, P.; Pivokonska, L.; Hnatukova, P.
infrared-spectroscopy. Soil Science Society of America Journal 1992, 56 The effect of global velocity gradient on the character and filterability
(1), 135−140. of aggregates formed during the coagulation/flocculation process.
(21) Guan, X.; Shang, C.; Chen, G. ATR-FTIR investigation of the Environ. Technol. 2011, 32 (12), 1355−1366.
role of phenolic groups in the interaction of some NOM model (42) McNaught, H.; Trenholm, R.; Claassen, D.; Scott, C.; Kodweis,
compounds with aluminum hydroxide. Chemosphere 2006, 65 (11), G.; Vanderford, B. J.; Rexing, D.; Wert, E. C. No-lead brass service
2074−2081. valve performance in Colorado River water. Journal American Water
(22) Menges, F. Spekwin32 - Optical Spectroscopy Software, Version Works Association. 2015, 107 (8), E416−E424.
v1.72.0; 2016; http://www.effemm2.de/spekwin/. (43) Lin, J.; Huang, C.; Dempsey, B. A.; Hu, J. Fate of hydrolyzed Al
(23) Cornelissen, A.; Burnett, M. G.; McCall, R. D.; Goddard, D. T. species in humic acid coagulation. Water Res. 2014, 56, 314−324.
The structure of hydrous flocs prepared by batch and continuous flow (44) Rahman, M. S.; Gagnon, G. A. Bench-scale evaluation of
water treatment systems and obtained by optical, electron and atomic drinking water treatment parameters on iron particles and water
force microscopy. Water Sci. Technol. 1997, 36 (4), 41−48. quality. Water Res. 2014, 48, 137−147.
(24) Fischer, E. R.; Hansen, B. T.; Nair, V.; Hoyt, F. H.; Dorward, D. (45) Benjamin, M. M.; Lawler, D. F. Water Quality Engineering:
W. Scanning Electron Microscopy. In Current Protocols in Microbiology; Physical/Chemical Treatment Processes; John Wiley & Sons: NJ, 2013.
John Wiley & Sons, Inc., 2012, DOI: 10.1002/ (46) Kan, C. C.; Huang, C. P.; Pan, J. R. S. Time requirement for
9780471729259.mc02b02s25. rapid-mixing in coagulation. Colloids Surf., A 2002, 203 (1−3), 1−9.
(25) Vadasarukkai, Y. S.; Gagnon, G. A. Characterization, fate and (47) Rossini, M.; Garrido, J. G.; Galluzzo, M. Optimization of the
transport of floc aggregates in full-scale flocculation tanks. Environ- coagulation-flocculation treatment: Influence of rapid mix parameters.
mental Science-Water Research & Technology 2016, 2 (1), 223−232. Water Res. 1999, 33 (8), 1817−1826.
(26) Wong, K. B.; Piedrahita, R. H. Settling velocity characterization (48) Bridgeman, J.; Jefferson, B.; Parsons, S. Assessing floc strength
of aquacultural solids. Aquacult. Eng. 2000, 21 (4), 233−246. using CFD to improve organics removal. Chemical Engineering Research
(27) Tassinari, B.; Conaghan, S.; Freeland, B.; Marison, I. W. & Design 2008, 86 (8A), 941−950.
Application of turbidity meters for the quantitative analysis of (49) Hopkins, D. C.; Ducoste, J. J. Characterizing flocculation under
flocculation in a jar test apparatus. J. Environ. Eng. 2015, 141 (9), heterogeneous turbulence. J. Colloid Interface Sci. 2003, 264 (1), 184−
04015015−1−04015015−8. 194.
(28) Myneni, S. C. B.; Brown, J. T.; Martinez, G. A.; Meyer-Ilse, W. (50) Garland, C.; Weber-Shirk, M.; Lion, L. W. Revisiting Hydraulic
Imaging of humic substance macromolecular structures in water and Flocculator Design for Use in Water Treatment Systems with
soils. Science 1999, 286 (5443), 1335−1337. Fluidized Floc Beds. Environ. Eng. Sci. 2016, ahead of print.
(29) Sieliechi, J. M.; Lartiges, B. S.; Kayem, G. J.; Hupont, S.; doi:10.1089/ees.2016.0174.
(51) Li, D. H.; Ganczarczyk, J. Size distribution of activated-sludge
Frochot, C.; Thieme, J.; Ghanbaja, J.; de la Caillerie, J. B. D.; Barres,
flocs. Res. J. Water Pollut. Control Fed. 1991, 63 (5), 806−814.
O.; Kamga, R.; Levitz, P.; Michot, L. J. Changes in humic acid
(52) Lee, S. Y.; Gagnon, G. A. Growth and structure of flocs
conformation during coagulation with ferric chloride: Implications for
following electrocoagulation. Sep. Purif. Technol. 2016, 163, 162−168.
drinking water treatment. Water Res. 2008, 42 (8−9), 2111−2123.
(53) Amirtharajah, A.; Dennett, K. E.; Studstill, A. Ferric chloride
(30) Gorczyca, B.; Ganczarczyk, J. Structure and porosity of alum
coagulation for removal of dissolved organic matter and trihalo-
coagulation flocs. Water Qual. Res. J. Can. 1999, 34 (4), 653−666.
methane precursors. Water Sci. Technol. 1993, 27 (11), 113−121.
(31) Duan, J. M.; Gregory, J. Coagulation by hydrolysing metal salts.
Adv. Colloid Interface Sci. 2003, 100, 475−502.
(32) Coufort, C.; Bouyer, D.; Line, A. Flocculation related to local
hydrodynamics in a Taylor-Couette reactor and in a jar. Chem. Eng. Sci.
2005, 60 (8−9), 2179−2192.
(33) Gu, B. H.; Schmitt, J.; Chen, Z.; Liang, L. Y.; Mccarthy, J. F.
Adsorption and desorption of different organic-matter fractions on
iron-oxide. Geochim. Cosmochim. Acta 1995, 59 (2), 219−229.
(34) Guan, X.; Shang, C.; Chen, G. ATR-FTIR investigation of the
role of phenolic groups in the interaction of some NOM model
compounds with aluminum hydroxide. Chemosphere 2006, 65 (11),
2074−2081.

3489 DOI: 10.1021/acs.est.6b06281


Environ. Sci. Technol. 2017, 51, 3480−3489

You might also like