1. The Tertiary winding used as a path for the Zero sequence current during
secondary loaded with unbalanced load. Normally the primary neutral point
would not be connected with system ground. Tertiary winding one DELTA point
is connected with system ground which is prevent the shifting of secondary
neutral point and the voltages become unsymmetrical during unbalanced load
condition. Other wise the zero sequence current will flow through the secondary
neutral connected with Transformer Tank and tank will get heat up.
2. When an external Earth Fault occurs, the resulting zero sequence currents
flow through the OPEN DELTA winding to ground.This prevents the zero
sequence currents from flowing through the Transformer. This also prevents
abnormal DIFFERENTIAL RELAY operation of the Transformer for external
faults.
4. Some times this winding is used as a station supply and surge arrester are used
to prevent the surges from the load side.