Design of wiring lay-out for a residence and estimate the quantity of materials
Pre – Lab Questions
1. What is the difference between an isolator and Miniature Circuit Breaker?
Ans- Isolator cuts out a portion of a substation when a fault occurred. The other devices
operate without any interruption. The Circuit breaker is a device known as an
Automatic circuit breaker (ACB) or Miniature circuit breaker (MCB), which trips the entire
system if any fault occurs and thus the whole system is affected
2. How much the current in the sub circuit wiring to switch board in Hall?
Ans- There are two types of sockets in the home.
Normal: Current up to 5 Amp can be drawn. Used for TV, hair dryer, table lamp etc.
Power Socket: Current up to 15 Amp. can be drawn. Suitable for Fridge, Heater, washing
machine etc.
Socket size.
Ans- 5 PVC wires can be drawn in a 19mm PVC pipe for wiring
Experiment
Design of wiring lay-out for a residence and estimating the quantity
No.
of materials
3
Objective
1. To draw a plan for position of switches and switch boards
2. To decide the number of sub circuits
3. To draw the single line diagram and estimate the materials required
Data Given
Sl.No Light
Rooms Tube Light Points Fan Points Plug Points
. Points
1 Hall 2 1 2 2
2 Bed Room 1 1 1 1
3 Kitchen 1 1 1 1
4 Bath Room - - 1 1
5 Toilet - - 1 -
Assumptions
Height of ceiling - 3.5 m
Thickness of wall – 0.3 m
Power factor – 0.8
Power supply – single phase
PVC Conduit – concealed type
Each sub circuit – 800 watts
Plan of rsidence
Total = 18
Length calculation
For each light on wall (vertical) - 0.5 m from ceiling
For each switch board (vertical) – 2 m from ceiling
For Main Board (vertical) – 1.5 m from ceiling
For sub circuit No. -1
Description Length Total Length
Horizontal
5+6+2.5 13.5
(ceiling)
Vertical (Wall) 1.5+2+0.5+0.5 4.5
Wastage 10 % 1.8
Grand total 19.8
Say 20m
For sub circuit No. -2
Description Length Total Length
Horizontal (ceiling) 4+2+4+1.5+1.5+1.5 14.5
Vertical (Wall) 1.5+2+0.5+0.5+2+0.5+0.5 7.5
Wastage 10 % 2.2
Grand total 24.2
Say 25m
For sub circuit No. –3
Description Length Total Length
Horizontal
1+2+2 5
(ceiling)
Vertical (Wall) 1+2+0.5+0.5 4.5
Wastage 10 % 0.95
Grand total 10.45
Say 11m
PVC Pipe
For sub circuit 1 = 20m
For sub circuit 2 =25m
For sub circuit 3= 11m
Total = 56m (say- 60m)
PVC Copper wire
Length of wire 60m × 3 = 180m
Wastage = 10% = 18m
Total = 198m (say 200m)
Earth wire
Length of 14SWG earth wire = length of pvc conduit = 60m
Wastage = 10% = 6m
Total = 66m
18 8S.W.G.H.D.B.C wire 5m
Experiment – 3
Design of wiring lay-out for a residence and estimate the quantity of materials
Post – Lab Questions
1. What is the cross-sectional area of a SWG No. 14 copper wire used for earthing?
Ans- SWG (Standard wire gauge) of no.14 is 3.24sq.mm
2. How much the current carrying capacity of various PVC copper wires with respect to
its cross-sectional area?
Ans- 1. 0.75 sq mm = 15A
1. 1.00 sq mm = 19A
3. 1.50 sq mm = 24A
4. 2.5 sq mm = 32A
3. Why the multi stranded copper wire is used for wiring than single strand wire?
Ans- Due to its flexible nature and low susceptibility to cracking and metal fatigue the
multi stranded copper wire is used over single stranded wire. Hence, suitable of
bending to a greater extent.
5. What is the current capacity of SWG No.8 G.I. Wire used for earthing and mention
where it is used?
Ans- . Current capacity of SWG No.8 G.I. Wire is 25575kcmil/A. It is used for large
household appliances like central air conditioning
EVALUATION SHEET
Title of Experiment: Design of wiring lay-out for a residence and estimate the quantity of
materials
_________________________________________________________
Sl.
Maximum Marks
No Marks Split Up Marks Obtained
(40)
.
1 Pre-Lab questions 5
2 Execution of experiment 15
3 Calculation / Evaluation of Result 10
Total 40