Experiment – 7

Design of wiring lay-out for a residence and estimate the quantity of materials
Pre – Lab Questions
1. What is the difference between an isolator and Miniature Circuit Breaker?
Ans- Isolator cuts out a portion of a substation when a fault occurred. The other devices
operate without any interruption. The Circuit breaker is a device known as an
Automatic circuit breaker (ACB) or Miniature circuit breaker (MCB), which trips the entire
system if any fault occurs and thus the whole system is affected

2. How much the current in the sub circuit wiring to switch board in Hall?
Ans- There are two types of sockets in the home.

Normal: Current up to 5 Amp can be drawn. Used for TV, hair dryer, table lamp etc.

Power Socket: Current up to 15 Amp. can be drawn. Suitable for Fridge, Heater, washing
machine etc.

Current capacity for the socket is decided by …

Wiring cable size.

Protective switch gear.

Socket size.

Total allowable power allocated by the Electric Supply Company.

3. What are the components in Main Board?


Ans. The incoming cables
Outgoing circuit conductors
Knife switch
Load break switch
Earthing Switch
Circuit Breaker
Fuses
Protection Relays

4. Draw various types of switches used in wiring.


Ans-
5. How many 1.5 mm PVC wires can be drawn in a 19 mm PVC pipe for wiring? 
2

Ans- 5 PVC wires can be drawn in a 19mm PVC pipe for wiring

6. Write the purpose of HDBC wire used in residence wiring.


Ans. Solid and stranded (classes AA and A) bare copper are suitable for overhead
transmission and distribution applications.
Stranded conductor of greater flexibility (classes B and C) are suitable for uninsulated
hook up, jumpers, and grounds in electrical construction. Soft Drawn copper is unilay
construction

Experiment
Design of wiring lay-out for a residence and estimating the quantity
No.
of materials
3

Objective
1. To draw a plan for position of switches and switch boards
2. To decide the number of sub circuits
3. To draw the single line diagram and estimate the materials required

Data Given
Sl.No Light
Rooms Tube Light Points Fan Points Plug Points
. Points
1 Hall 2 1 2 2
2 Bed Room 1 1 1 1
3 Kitchen 1 1 1 1
4 Bath Room - - 1 1
5 Toilet - - 1 -

Assumptions
Height of ceiling - 3.5 m
Thickness of wall – 0.3 m 
Power factor – 0.8 
Power supply – single phase 
PVC Conduit – concealed type
Each sub circuit – 800 watts 

Connected load calculation


Type of load Quantity Rating Total
Tube light load 4 40W 160W
Celling fan 3 60W 180W
Ordinary light point 6 60W 360W
Plug point load 5 300W 1500W
Total load for 18 point 2200W

Plan of rsidence

Lay-out for wiring arrangement


Determination and Arrangement of sub circuits
No. of sub circuits = Connected load / 800 watts
For sub circuit-1 (hall room) = 7
For sub circuit-2(bedroom and bathroom point) = 7

For sub circuit -3(kitchen room) = 4

Total = 18

Calculation of line current


Line current =   Connected load / (voltage x powerfactor)
= 2200/230×0.8
= 11.965 (say 12 Amps)

Length calculation
For each light on wall (vertical) - 0.5 m from ceiling
For each switch board (vertical) – 2 m from ceiling
For Main Board (vertical) – 1.5 m from ceiling
For sub circuit No. -1
Description Length Total Length
Horizontal
5+6+2.5 13.5
(ceiling)
Vertical (Wall) 1.5+2+0.5+0.5 4.5
Wastage 10 % 1.8
Grand total 19.8
Say 20m
For sub circuit No. -2
Description Length Total Length
Horizontal (ceiling) 4+2+4+1.5+1.5+1.5 14.5
Vertical (Wall) 1.5+2+0.5+0.5+2+0.5+0.5 7.5
Wastage 10 % 2.2
Grand total 24.2
Say 25m
For sub circuit No. –3
Description Length Total Length
Horizontal
1+2+2 5
(ceiling)
Vertical (Wall) 1+2+0.5+0.5 4.5
Wastage 10 % 0.95
Grand total 10.45
Say 11m

Total length of pvc copper conduit type =20m+25m+11m=56m (Say 60m)

Length and size of PVC pipe / copper wire / earth wire  

PVC Pipe
For sub circuit 1 = 20m
For sub circuit 2 =25m
For sub circuit 3= 11m
Total = 56m (say- 60m)
PVC Copper wire
Length of wire 60m × 3 = 180m
Wastage = 10% = 18m
Total = 198m (say 200m)
Earth wire
Length of 14SWG earth wire = length of pvc conduit = 60m

Wastage = 10% = 6m

Total = 66m

Sigle line diagram


Result
The single diagram for the given residence was done and the materials required for
the wiring was estimated.
Schedule of materials
Sl.No
Description of materials Quantity
.
1 16A,250V grade DP isolator switch 1 nos

2 4 way 250V, 6A distribution box 1 nos

3 6A, 250V, MCB 3 nos

4 PVC wires, 250V grade 1.5mm copper wire 200m

5 19mm PVC conduit pipe 60m

6 Celling fan rose PCV type 6A,240V 7 nos

7 Plug socket with switches 3 pic 5A 5 nos

8 Batten holder 250V 6 nos

9 Flush type switch 5A 250V 13 nos

10 19mm PVC conduit elbow 1 nos

11 19mm PVC conduit bend 10 nos

12 TW Boards (30×20)cm size 4 nos

13 TW Boards (15×10)cm size 1 nos

14 PVC conduit junction box

15 i) Single way 8 nos

16 ii) two way 4 nos

17 iii) three way 7 nos

18 8S.W.G.H.D.B.C wire 5m

19 Earthing set 1 nos

20 Wooden screws Req no

21 PVC insulated tape(1/2”) 1 roll


22 14S.W.G.H.D.B.C wire 66m

23 Earthing thimbles with nuts and bolts 2 nos

Experiment – 3
Design of wiring lay-out for a residence and estimate the quantity of materials
Post – Lab Questions
1. What is the cross-sectional area of a SWG No. 14 copper wire used for earthing?
Ans- SWG (Standard wire gauge) of no.14 is 3.24sq.mm

2. How much the current carrying capacity of various PVC copper wires with respect to
its cross-sectional area?
Ans- 1. 0.75 sq mm = 15A
1. 1.00 sq mm = 19A
3. 1.50 sq mm = 24A
4. 2.5 sq mm = 32A

3. Why the multi stranded copper wire is used for wiring than single strand wire?
Ans- Due to its flexible nature and low susceptibility to cracking and metal fatigue the
multi stranded copper wire is used over single stranded wire. Hence, suitable of
bending to a greater extent.

4. How to calculate the rating of MCB used in each sub circuit?


Ans- . To calculate rating of MCB, the current value should be 125% more than the
current value. For example, if current is 10A , then rating of MCB will be
125*10=12.5A

5. What is the current capacity of SWG No.8 G.I. Wire used for earthing and mention
where it is used?
Ans- . Current capacity of SWG No.8 G.I. Wire is 25575kcmil/A. It is used for large
household appliances like central air conditioning

6. List few PVC accessories used in concealed type wiring.


Ans-1. PVC wire troughs
2. PVC saddles
3. PVC couples
4. PVC conduit
5. PVC casing-capping
6. PVC insulated copper wires and jackets

SRM INSTITUTE OF SCIENCE AND TECHNOLOGY


KATTANKULATHUR
FACULTY OF ENGINEERING AND TECHNOLOGY
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING

EVALUATION SHEET

Name: CS Hritesh Kumar


Sahoo__________________________________________________________

Regn. No.: ________RA2011011010045_______________________

Class & Branch: ____Auto-A______________________

Title of Experiment: Design of wiring lay-out for a residence and estimate the quantity of
materials
_________________________________________________________

Date of Conduction: ____________________

Date of Submission: ____________________

Sl.
Maximum Marks
No Marks Split Up Marks Obtained
(40)
.
1 Pre-Lab questions 5

2 Execution of experiment 15
3 Calculation / Evaluation of Result 10

4 Post Lab questions 5

5 Online quiz /viva  5

Total 40

Signature of Staff with date

You might also like