Professional Documents
Culture Documents
1989
ISO 8421-5:
1988
Glossary of
UDC 001.4:614.84:628.53
BS 4422-5:1989
The preparation of this British Standard was entrusted by the Fire Standards
Policy Committee (FSM/-) to Technical Committee FSM/9, upon which the
following bodies were represented:
© BSI 07-1999
Amendments issued since publication
First published November 1976
First revision May 1989 Amd. No. Date of issue Comments
Contents
Page
Committees responsible Inside front cover
National foreword ii
Introduction 1
Reference 1
Scope and field of application 1
Terms and definitions 1
Publications referred to Inside back cover
© BSI 07-1999 i
BS 4422-5:1989
National foreword
This Part of BS 4422 has been prepared under the direction of the Fire Standards
Policy Committee. It supersedes BS 4422-5:1976 which is withdrawn. This Part
is identical with ISO 8421-5:1988 “Fire protection — Vocabulary — Part 5: Smoke
control”, published by the International Organization for Standardization (ISO).
The international standard was prepared by Technical Committee ISO/TC21,
Equipment for fire protection and fire-fighting, with the active participation of
the UK.
BS 4422-5:1976 contained miscellaneous terms associated with fire, including
smoke control terms. The smoke control terms are contained in this Part of
BS 4422. The other terms defined in BS 4422-5:1976 will be contained in further
Parts of BS 4422 as it is revised. Further Parts of ISO 8421 are in preparation, as
listed in the introduction, and will be used as a basis for revision of the other Parts
of BS 4422. It is intended that the system of numbering the Parts will be the
same.
Terminology and conventions. The text of the international standard has
been approved as suitable for publication as a British Standard without
deviation. Some terminology and certain conventions are not identical with those
used in British Standards; attention is drawn especially to the following.
Wherever the words “part of ISO 8421” are used, referring to this standard, they
should be read as “Part of BS 4422”.
Cross-reference
International standard Corresponding British Standard
Additional information. The French index given in ISO 8421-5:1988 has not
been included in this Part of BS 4422; hence the reference to this index in the
clause entitled “Scope and field of application” is not relevant. Attention is also
drawn to the definition of “smoke” in BS 4422-1.
A British Standard does not purport to include all the necessary provisions of a
contract. Users of British Standards are responsible for their correct application.
Compliance with a British Standard does not of itself confer immunity
from legal obligations.
Summary of pages
This document comprises a front cover, an inside front cover, pages i and ii,
pages 1 and 2, an inside back cover and a back cover.
This standard has been updated (see copyright date) and may have had
amendments incorporated. This will be indicated in the amendment table on
the inside front cover.
ii © BSI 07-1999
BS 4422-5:1989
Introduction 5.6
mechanical smoke control
ISO 8421 will consist of the following parts, which
are being published separately: smoke control with the help of mechanical means
— Part 1: General terms and phenomena of fire; 5.7
natural smoke control
— Part 2: Structural fire protection;
smoke control mainly with the help of the buoyant
— Part 3: Fire detection and alarm; force of smoke
— Part 4: Fire extinguishing equipment;
5.8
— Part 5: Smoke control; neutral pressure plane
— Part 6: Evacuation and means of escape; level in a building at which the inside pressure is
— Part 7: Explosion detection and suppression equal to the outside pressure
means; 5.9
— Part 8: Terms specific to fire-fighting, rescue pressurization
sevices and handling hazardous materials. the establishment of a pressure difference across a
barrier to protect a stairway, lobby, escape route or
Reference room of a building from smoke penetration
ISO 8421-1, Fire protection — Vocabulary — 5.10
Part 1: General terms and phenomena of fire. roof (or ceiling) screen
vertical subdivision fitted internally to the roof (or
Scope and field of application ceiling) to create an obstacle to lateral flow of smoke
This part of ISO 8421 gives terms and definitions in and combustion gases. (Known as “smoke/draft
the field of smoke control. General terms are curtains” in the USA)
covered by ISO 8421-1. Terms are given in English 5.11
alphabetical order: a French index is provided. roof vent
NOTE In the number which designates each term, the initial see smoke vent (5.20)
Figure 5 denotes Part 5 of this International Standard.
5.12
Terms and definitions stack pressure
5.1 pressure difference caused by a temperature
air inlet; air intake difference creating an air movement within a duct,
chimney or enclosure
opening through which outdoor air is supplied
5.13
5.2 smoke zone
damper, smoke
free volume between the floor and the roof or ceiling,
movable device for smoke control, open or closed in bounded by roof or ceiling screens (see 5.10)
its normal position, which is automatically or
manually actuated 5.14
smoke control
NOTE In French a “volet” is normally closed and a “clapet” is
normally open. measures to control the spread or movement of
5.3 smoke and combustion gases during a fire within a
draught building
current of air accelerating toward a fire, supplying 5.15
air for combustion smoke control door
5.4 door set designed to reduce the rate of spread or
drift smoke movement of smoke during a fire
smoke which is no longer in a stratified condition 5.16
(see smoke layering — 5.19) smoke extraction; smoke venting
5.5 measures taken to remove smoke and hot gases
lobby ventilated from a building
protected lobby provided with means of ventilation 5.17
connected to the open air smoke extraction system
system consisting of smoke outlet, smoke extractor,
switch, etc, permanently installed in a building for
the purpose of smoke venting
© BSI 07-1999 1
BS 4422-5:1989
5.18
smoke exhaust fan
fan used to remove smoke and hot gases in the event
of fire. It may be either mobile (generally brought by
the fire brigade) or fixed (within the building)
5.19
smoke layering
stratification of smoke within a room or space
caused by thermal effects in the absence of
turbulence
5.20
smoke vent
opening in the enclosing walls or roof of a building,
intended to release heat and smoke in the event of
fire, automatically and/or manually opened
NOTE In French, there are separate terms for a wall and roof
opening.
5.21
smoke shaft
shaft provided to remove smoke in the event of fire
2 © BSI 07-1999
BS 4422-5:1989
Publications referred to
© BSI 07-1999
BS 4422-5:
1989
ISO 8421-5: BSI — British Standards Institution
1988
BSI is the independent national body responsible for preparing
British Standards. It presents the UK view on standards in Europe and at the
international level. It is incorporated by Royal Charter.
Revisions
It is the constant aim of BSI to improve the quality of our products and services.
We would be grateful if anyone finding an inaccuracy or ambiguity while using
this British Standard would inform the Secretary of the technical committee
responsible, the identity of which can be found on the inside front cover.
Tel: 020 8996 9000. Fax: 020 8996 7400.
BSI offers members an individual updating service called PLUS which ensures
that subscribers automatically receive the latest editions of standards.
Buying standards
Orders for all BSI, international and foreign standards publications should be
addressed to Customer Services. Tel: 020 8996 9001. Fax: 020 8996 7001.
Information on standards
Copyright
Copyright subsists in all BSI publications. BSI also holds the copyright, in the
UK, of the publications of the internationalstandardization bodies. Except as
permitted under the Copyright, Designs and Patents Act 1988 no extract may be
reproduced, stored in a retrieval system or transmitted in any form or by any
means – electronic, photocopying, recording or otherwise – without prior written
permission from BSI.
This does not preclude the free use, in the course of implementing the standard,
of necessary details such as symbols, and size, type or grade designations. If these
details are to be used for any other purpose than implementation then the prior
written permission of BSI must be obtained.