Introduction
Background
Control System Overview

Introduction
In 41 Cooper Square, the boilers and chillers supply primary water used to heat or cool the building. However, the water
supplied by these systems is not directly routed to the radiative copper piping. Instead, a secondary flow of water is used
throughout the network of radiant panels. In the case of heating, plate and frame heat exchangers are used to transfer
heat from the primary hot water (from the boiler) to a secondary flow that supplies hot water to the radiant panels for
heating. In order to cool the building, heat is rejected from the secondary flow to the primary chilled water supplied by the
chillers. Both the heating and cooling systems have their own heat exchanger, which supplies hot and cold secondary
flows that are routed to specified locations throughout the building. Figure 1 is a photograph of a chiller-side heat
exchanger and Figure 2 is general schematic of a heat exchanger with temperatures typical of the heating mode.

Figure 1. Heat exchanger for chiller Figure 2. Schematic of heat exchanger for boiler system.
system.

Background
Plate and Frame Heat Exchangers:

1 of 5 2/13/2019, 17:46
There are many different types of heat exchangers, all utilizing different geometric configurations in order to achieve
different design objectives. In a plate and frame heat exchanger, a series of parallel plates are joined together with
equidistant gaps between them. Each of the two working fluids is passed through alternating chambers, maximizing the
surface area over which heat can be transferred via conduction through the metal plates. This flow pattern is shown in
Figure 3, provided by a manufacturer of industrial heat exchangers similar to those used in 41 Cooper Square.

Figure 3. Plate and Frame Heat Exchanger


Flow. [1]

The two fluids in the heat exchanger are never mixed, creating two completely independent flows. Using plate and frame
heat exchangers has the advantage of allowing the boiler (or the chiller’s evaporator) pressure to remain relatively low, as
the primary flow does not have to be routed throughout the building’s radiant panels. Additionally, the secondary flow can
more easily be routed to different parts of the building in response to changing cooling and heating demands without
affecting the operation of the boiler (or chiller).

Figure 4. BMS Primary and Radiant Hot Water Heat Exchanger Panel.

The secondary flow is circulated throughout the building’s radiant panels using the two pumps labeled 'HWP1’ and ‘HWP2’
shown in Figure 4. These pumps both are controlled by Variable Frequency Drives (VFDs) that allow the BMS to regulate
the flow rate produced by each pump. The BMS adjusts the flow produced by the pumps to maintain a differential pressure
of 15 psi in the secondary water loop (as measured by the differential pressure sensor Figure 4) [2].

2 of 5 2/13/2019, 17:46
The heat exchanger used in the building’s cooling system (Figure 5) uses primary chilled water from the chiller (or from the
absorption chiller in the cogeneration plant or from the water-side free cooling plate and frame heat exchanger) to cool
secondary chilled water flow for use in the radiant panels. To avoid condensation, the BMS monitors the secondary chilled
water supply temperature, indoor air temperature, and humidity. The radiant panel surface temperature is set to the
greater of 3°F above dew point or 55°F to avoid condensation.

Figure 5. BMS Primary and Radiant Chilled Water Heat Exchanger Panel.

The flow produced by the pumps is routed to individual radiant panels using a large array of valves. Three way-valves in
each room are individually controlled by the BMS to switch between allowing hot and cold secondary flow to enter the
radiant panels. At the outlet of the radiant panels in every room, there are two servo valves, one for the hot and cold
secondary return flows. By adjusting the position of these outlet servo valves, the flow rate through the radiant panels can
be controlled while keeping the hot and cold secondary flows separate. The BMS panel of Figure 6 below shows the three-
way valve that controls the radiant water inlet flow, and the two servo valves regulating the outlet flow in a classroom
(505).

3 of 5 2/13/2019, 17:46
Figure 6. BMS Radiant Panel and Air Damper for Room 505.

Control System Overview

The purpose of the heat exchanger is to produce secondary water flow at a specified temperature. The secondary flow
rate is controlled as a function of differential pressure in the secondary flow loop. For example, if heating demand in the
building increases, more radiant panels will be opened, and the differential pressure in the secondary hot water loop will
fall due to the effective decrease in flow resistance. A differential pressure sensor detects this decrease in pressure (or
"head"), and the BMS responds by increasing the operating speed of the secondary hot water pumps to increase flow rate
and maintain a constant differential pressure of 15 psi in the secondary loop [2]. With the secondary flow rate controlled as
a function of differential pressure, the controlled (or process) variable in the heat exchanger system is the secondary
flow output temperature.

Figure 7. Heat exchanger schematic depicting servo valve to


directly control primary flow.

As shown in Figure 7, the boiler nominally provides primary flow at 180 °F (82 °C) [3]. The primary hot water flow rate
through the heat exchanger is modulated via the servo valve (the controlled device, or actuator). By modulating the
primary mass flow rate (the controlled agent), the secondary flow temperature can be controlled. For example, if the BMS
(the controller)detects that the secondary flow temperature is too low to meet current heating demands, the mass flow
rate of primary hot water through the heat exchanger will be increased via the servo valve. By increasing the primary flow
rate, there will be a greater mass of hot water in the heat exchanger at any given time, allowing more heat to be
transferred from the primary flow to the secondary flow. The increase in heat transfer causes the secondary flow
temperature to rise, making the secondary water temperature hotter in order to meet the higher heating load. Lowering
the primary flow rate would have the opposite result, decreasing the secondary flow temperature.

The secondary flow exit temperature is controlled through modulation of the primary mass flow rate. It should be noted,
however, that this mass flow rate modulation would also affect the exit temperature of the primary flow. By increasing the
primary mass flow rate, more heat transfer will occur, but the primary flow itself will exit at a higher temperature. As the hot
primary flow passes through the heat exchanger more rapidly, it does not remain in contact with the cool secondary flow
long enough to experience a large temperature drop. It is counterintuitive for this higher exit temperature to result in
greater heat transfer, but physical laws (the enthalpy of water at these operating ranges) dictate that mass flow rate, not
fluid temperature, has a dominant effect on heat transfer processes.

Since the primary flow comes out of the heat exchanger at a higher temperature at these high flow rates, it will require less
fuel to be heated back to the 180 °F set point in the boiler. The BMS takes this information into consideration, determining
primary flow rates that will produce secondary flow at the necessary temperature to meet thermal loads, while minimizing
fuel consumption in the boilers by maximizing the primary flow’s exit temperature from the heat exchanger [2].

Variable Frequency Drive: Device that modulates the frequency of the current input to an AC motor (usually driving a
pump or fan) in order to control the motor’s speed and power consumption.

4 of 5 2/13/2019, 17:46
Enthalpy: The sum of a fluid’s potential and flow energy. This measure of flow energy is covered thoroughly in
Thermodynamics and Heat Transfer.

[1] http://www.dhtnet.com/plate_frame_heat_exchangers_as.htm

[2] Gruzen Sampton, Sequence of Operation – The New Academic Building of Cooper Union, Morphosis Architects, Los
Angeles, CA, Rep. 15959, June 2005. p. 20.

[3] GMP Energy Report – The New Academic Building of Cooper Union, IBE Consulting Engineers, Camarillo, CA, 2006,
p. 16.