You are on page 1of 8

The “Tipping” Point of High Turndown Ratios | Gasmaster Industries Ltd.

Page 1 of 8

The “Tipping” Point of High


Turndown Ratios
How much of a good thing is too much?

Boilers used for domestic water and space heating are one of the highest
energy consumers in residential and commercial facilities. After the global
energy crisis in the 1970s, higher fuel prices prompted the search for solutions
to reduce energy consumption. Back then, conventional steam boilers were
the only option available. However, these boilers were very inefficient (due in
part to the unrecovered latent heat losses from the fuel combustion process)
which eventually led to the advanced development of high efficiency
condensing boilers.

Ideally, condensing boilers would operate as designed – condensing as


expected and delivering the highest efficiency possible. However, in reality,
external variables create unwanted problems, affecting the boiler’s efficiency.
To ensure that condensing boilers are operating at maximum efficiency,
effective controls and operation become crucial. The load on a boiler
constantly fluctuates depending on the weather conditions, occupancy rate,
internal heat gains, and other variables. Therefore, effective boiler control can
significantly affect energy use that may have resulted in system inefficiencies,
increased utility costs, unit downtime and costly unscheduled maintenance.

https://www.gasmaster.ca/articles/turndown-ratios/ 2020-01-16
The “Tipping” Point of High Turndown Ratios | Gasmaster Industries Ltd. Page 2 of 8

In the past, boilers were designed with only one mode of operation – on/off
burner control. As innovation was added into boiler designs, manufacturers
began offering units with multiple firing rates followed by units that could
modulate seamlessly between a fixed low and high fire rate based on
requirements. This reduces the number of on/off cycles resulting in increased
efficiency. On start-up and shutdown, the boiler goes through a pre-purge and
post-purge cycle that would result in heat losses affecting the boiler efficiency
– the extent of these losses depend on boiler construction, type of
application, and design of the system. How far the modulation goes from full
fire rate is determined by the turndown ratio.

Boiler Turndown Ratio


The turndown ratio is defined as the ratio of the maximum fuel input rate to
the minimum fuel input rate of a modulating burner. It is used to help
determine how low a boiler can modulate before it turns off. Boiler turndown
is important for fuel savings—especially during low-load conditions and also
reduces the wear of burner components.

Example: if a 2,000,000 Btu boiler has a 5 to 1 turndown it is capable of


modulating from 2,000,000 Btu to 400,000 Btu.

The larger the turndown the closer the modulation can adjust to the required
heat load, however, flame stability becomes more difficult in lower turn down
as less fuel and air within the same sized combustion chamber become less
stable due to lowering the combustion chamber pressure. This is when
manufacturers have no other choice but to increase the excess air within the
given combustion process to maintain stability. To understand why this is
done, let’s look closely at the boiler combustion process.

Combustion Process
Boilers generate hot gases by combusting a fuel in the presence of air and
then transferring the thermal energy from the hot gases to water. The
combustion process is, therefore, an important factor in the efficient
operation of a boiler. Stable combustion conditions require the correct
amounts of fuel and air. In theory, there is a specific amount of air required to

https://www.gasmaster.ca/articles/turndown-ratios/ 2020-01-16
The “Tipping” Point of High Turndown Ratios | Gasmaster Industries Ltd. Page 3 of 8

completely burn a given amount of fuel for combustion. This type of


theoretical complete combustion is called the stoichiometric combustion. In
practice, however, burning conditions are never ideal. Therefore, more air
than ideal “excess air” must be supplied to burn the fuel completely. Figure 1
shows the key gas measurements relating to the ideal combustion
stoichiometry.

Figure 1: Key gas measurements relating to the ideal combustion stoichiometry

In boiler combustion, if excess air is not added to the process, unburned fuel,
soot, smoke, and carbon monoxide exhaust will create additional emissions
and surface fouling. From a safety perspective, accurately controlling excess
air reduces flame instability and other boiler hazards. The challenge presents
itself at the lower end of the firing range. In general, as the firing rate of a
boiler decreases, there is a corresponding increase in excess air
requirements, leading to lower efficiencies at the lower end of the firing
range. Boiler manufacturers usually provide boiler efficiency curves over
several firing rates (e.g. 100%, 75%, 50%, 25%) based on laboratory results.
These curves, however, rarely go below 10% of the firing rate (10:1 turndown
ratio) and if they do, it should be important to take note of the excess air
levels. So how does this relate to the turndown ratio?

https://www.gasmaster.ca/articles/turndown-ratios/ 2020-01-16
The “Tipping” Point of High Turndown Ratios | Gasmaster Industries Ltd. Page 4 of 8

Effect of Excess Air on the Dewpoint Temperature


As seen in Figure 1, one of the main combustion by-products is carbon dioxide
(CO2). While adding excess air lowers the combustion efficiency, the effects are
even more unfavourable when operating condensing boilers. As excess air is
added to the combustion process, to maintain stability, CO2 production
reduces, which is the case at a reduced firing rate. This would result in a
reduction in the dew point temperature at which condensing of the
combustion gases can occur, as shown in Figure 2. As the excess air level
increases, the flue gas dew point decreases. A typical excess air level for a
natural gas-fired condensing boiler is around 5% O2 (or 30% excess air) which
produces approx. 9% CO2. This correlates to a flue gas dewpoint of 130°F.

Figure 2: CO2 correlation to the dewpoint temperature (Source: ASHRAE)

The return water temperature relative to this flue gas dew point is the most
essential factor in achieving condensing efficiency as shown in Figure 3.
Therefore, in order to begin achieving condensing performance, the return
water temperature must be below 130°F. If additional excess air is added with
the goal of improving turndown, the return water temperature will be altered.
By increasing the excess air level as required, which produces approx. 6% CO2,
in this example, the flue gas dew point now drops to 116°F. In order to achieve
the same level of condensing performance, the return water must be below
116°F. At a reduced firing rate, the demand on the heating system will be low.
This would suggest that, at a constant pump speed, the return water

https://www.gasmaster.ca/articles/turndown-ratios/ 2020-01-16
The “Tipping” Point of High Turndown Ratios | Gasmaster Industries Ltd. Page 5 of 8

temperature will increase resulting in the boiler operating outside of the


condensing zone – lowered efficiency.

Figure 3: Boiler efficiency vs. inlet water temperature

Condensing boilers achieve high efficiencies by recovering the latent heat


(approx. 10 – 12% available) from the combustion process. Based on the
observations from the effects of excess air on the dew point temperature,
closing the window of condensing (condensing mode) would mean eliminating
the opportunity to achieve the highest efficiency possible.

Putting It All Together


More excess air is required for lower firing rates to maintain flame stability
and reduce harmful emissions. However, up to a certain point, there is an
efficiency penalty as a result of the addition of excess air (see Figure 1). We
have seen that higher excess air makes it harder for the boiler to produce the
condensate that is the result of the higher energy recovery. And that’s the
heart of the problem. High excess air equals low dew point and that equals
less condensing hours in a heating season and therefore lower efficiency.

It is critical to understand that excess air must be increased to achieve a high


turndown and the result is that the flue gas dew point is decreased, making it
more difficult, if not impossible, to condense. By trying to save energy with a
very high turndown on each boiler, we actually move further away from the
flue gas dew point, which dramatically decreases a condensing boiler’s

https://www.gasmaster.ca/articles/turndown-ratios/ 2020-01-16
The “Tipping” Point of High Turndown Ratios | Gasmaster Industries Ltd. Page 6 of 8

efficiency. If the combustion is consistent overall firing rates, then you can
determine the combustion efficiency and dew point of the combustion gases
will remain consistent. It is therefore important to request for the combustion
efficiency curves at the specific turndown ratios.

Let’s look at a more practical example, a hot water system with 10 boilers each
with a 20:1 turndown ratio would result in a 200:1 turndown ratio of the entire
system. Is this really necessary? How much turndown is too much? There have
not been many published studies evaluating the performance of high
turndown ratios and determining an actual turndown “sweet spot” for
condensing boilers. Johnston Boiler Company conducted a study in 2003 to
compare the energy losses and resulting impact on the boiler efficiency
between a boiler operating at 4:1 and 10:1 turndown ratio [1]. The result from
the study indicated that there was no significant advantage of operating a 10:1
versus a 4:1 boiler turndown based on the insignificant differences in the
energy losses and boiler efficiency.

Another study by Dunphy Combustion Ltd was also conducted to determine


the effects of turndown ratio on the fuel costs [2]. The results showed that
there was significant fuel cost savings (> 15%) when operating at 5:1 turndown
versus a lower turndown ratio. However, as the turndown ratio is increased
from 5:1 to 10:1, the fuel cost savings become less significant (<2%). The cost of
a 5:1 turndown ratio burner is on average 20% less than a 10:1 burner. It would,
therefore, be more beneficial to find alternate solutions to meet partial load
demands instead of very high turndown ratio boilers given the higher costs
and insignificant savings at the very high turndown ratios.

Alternate Solutions to Partial Load Demands


During low-load conditions, it is essential to have sufficient turndown to
accurately match the base load without wasteful cycling. But the boilers also
need to be running in their most efficient state — at or near their minimum
modulation, i.e. part-load. As seen earlier, system dynamics dictate how often
boilers actually condense based on return-water temperature, which will
reduce as system loads increase with more energy consumed from the circuit.

https://www.gasmaster.ca/articles/turndown-ratios/ 2020-01-16
The “Tipping” Point of High Turndown Ratios | Gasmaster Industries Ltd. Page 7 of 8

These are some of the more common solutions to meet these part-load
demands:

Multiple Boilers
A modular approach enables the increasing load to be met by more boilers
operating at part-load conditions, which, if coinciding with favourable system
temperatures, will allow high part-load condensing performance from the
boiler plant. As system demands increase, boiler load will increase towards
full capacity. At this point system return temperatures should be low, and the
boilers will continue to operate in condensing condition, delivering an
efficient energy supply. It also provides a level of redundancy in case of
equipment failures.

Buffer Tanks
Short cycling during low load conditions reduces the boiler’s thermal
efficiency. It also increases emissions, increases maintenance and shortens
equipment life. Another way to avoid short cycling is to provide adequate
thermal mass within the heating system. Because of its excellent heat storage
characteristics, adding water to the system is the best way to increase its
thermal mass. The device that contains this water is often called a buffer tank,
because it “buffers” (e.g., helps protect) the heat source against the
undesirable effects of short cycling. This will eventually result in a reduction in
the wear and tear of the burner components.

Therefore, instead of installing a boiler with a very large turndown ratio –


which may eventually lead to reduced efficiencies, flame instability, and
ignition issues at a reduced firing rate, implementing these options in a
system will ensure excellent performance throughout each boiler’s firing
range at a reasonable turndown ratio.

Acknowledgments
1. Johnston Technical Brief, Efficiency Comparison: 4:1 Turndown & 10:1
Turndown, Johnston Boiler Company, 3/17/03

https://www.gasmaster.ca/articles/turndown-ratios/ 2020-01-16
The “Tipping” Point of High Turndown Ratios | Gasmaster Industries Ltd. Page 8 of 8

2. Dunphy Combustion Ltd, “Energy centre management – Key checks and


measures,”
http://www.dunphy.co.uk/docs/company/energy_mgt_guide.pdf
3. Kevin Carpenter, Chris Schmidt, Energy & Resource Solutions, Kelly Kissock,
University of Dayton, “Common Boiler Excess Air Trends and Strategies to
Optimize Efficiency,” 2008 ACEEE Summer Study on Energy Efficiency in
Buildings.
4. Department of Energy (DOE). 2007. Energy Tips – Process Heating. DOE/GO-
102007-2483. Washington, DC: U.S. Department of Energy, Office of Energy
Efficiency and Renewable Energy.
5. Sean Lobdell and Brian Huibregtse, “Effects of Ultra-High Turndown in
Hydronic Boilers,” Cleaver-Brooks, January 2014
6. Mark Norris, “Ramping up System Performance;” HPAC Magazine, Apr. 2014
7. David Connors, “Boiler modulation – is better?” HPAC Magazine, Feb. 2018

Interested in learning more?


CONTACT US

 }
Share Print page

This website uses cookies. By continuing to use this website, you consent to
Okay, got it.
our use of these cookies.

https://www.gasmaster.ca/articles/turndown-ratios/ 2020-01-16

You might also like