PRESENTATION-IECEx05-CoPC-SYED-FADZIL-SOCIAL MEDIA PDF
PRESENTATION-IECEx05-CoPC-SYED-FADZIL-SOCIAL MEDIA PDF
of Personnel Competence
(CoPC) for Explosive
Atmospheres
Assessment Requirements
4
Competency comprises:
• Knowledge
• Skills
• Recent and Relevant Training (Off
and On the Job), that enable safe
working on or near Ex equipment
• The Scheme has been established to
provide a consistent approach to the
assessment of the Competence of
Personnel.
Philosophy of • It assesses the individual – not an
the IECEx CoPC organisation.
• Independent of training to remove
conflict so not concerned with how the
knowledge and skills are obtained.
Certification of Personnel Competence for Explosive
Atmosphere
Rules / Guidance
• IECEx 05 – Rules of Procedure.
• IECEx 05A – Guidance / Instructions for Applicants to obtain CoPC.
OD (Operational Documents)
• OD 501, Assessment Procedures for IECEx acceptance of ExCBs for the purpose of issuing
and maintaining IECEx CoPC.
Standards
Typical reference documents used, please check applicable unit of competency required
Scope of Authorisation
Summary of Prerequisite Units and Recommended
General Competence
Examples of Units of Competence to be gained
Some Units Need Practical Assessment
• Unit Ex 002 : Zone classification in Gas and in Dust area.
• Unit Ex 003 : Installation of equipment as ‘d’ enclosure, ‘e’ terminal box and intrinsic
safety barriers by following wiring diagram.
• Unit Ex 004 : Maintenance of installation by doing the preparation, check and reporting.
• Unit Ex 005 : Repair of a motor.
• Unit Ex 006 : Installation testing by doing the preparation, testing and reporting.
• Unit Ex 007 : Visual inspections by doing the preparation, conducting visual inspections
and reporting.
• Unit Ex 008 : Detailed inspections by doing the preparation, conducting detailed
inspections and reporting.
• Unit Ex 009 : Installation design by interpreting area classification, selecting equipment
and wiring systems and checking equipment certification for suitability.
• Unit Ex 010 : Audit inspection by doing all previous practical assessment.
Unit Ex 000: Basic knowledge and awareness
to enter a site that includes a classified
hazardous area
SCOPE PREREQUISITES
• Safety obligations. • This unit would be used in relation to any job
• Basic knowledge of persons entering a site function that may be performed in or associated
that has been classified hazardous area. with hazardous area.
• Nature of hazardous areas. • Does not require any specific prerequisites.
• Limitations on devices that may be taken
into a hazardous area.
• OHS responsibilities and procedures related
to hazardous areas.
• Does not include requirements for ensuring
the explosion protection aspects of plant
and machinery.
Unit Ex 001: Apply basic principles of
protection in explosive atmospheres
SCOPE PREREQUISITES
• Covers basic principles of protection in • No minimum level of technical education
explosive atmospheres of plant and applicable.
machinery. • Shall be assessed in combination with, or after
• This unit of competence is based on various gaining other competence required by a given
parts of IEC 60079 series. industry or enterprise for plant or machinery
operation or installations, maintenance or
service functions.
Unit Ex 002: Perform classification of
hazardous areas
SCOPE PREREQUISITES
• Covers knowledge and skills to classify areas • Degree, diploma or equivalent in a technical
where explosive hazards may exist. subject.
• Requires ability to gather and analyse data • Should be carried out by those who
relative to explosion hazards, determine the understand the relevance and significance of
extent of risk and establish and document properties of flammable materials and those
zones. who are familiar with the process and the
• Based on IEC 60079-10-1 and IEC 60079-10-2 equipment along with the safety, electrical,
and any other relevant standard. mechanical and other qualified engineering
personnel.
Unit Ex 003: Install explosion-protected
equipment and wiring systems
SCOPE PREREQUISITES
• Covers the explosion-protection aspects for • Technical education relevant to the application,
installing explosion-protected and through documents such as College Certificates
associated equipment and wiring systems. and Vocational qualifications etc.
• Requires the ability to match equipment • Minimum 3 years experience in industrial
with that specified for a given location, electrical installation practice.
work safely, and to installation Standards • For Responsible Person minimum 3 years
and complete the necessary installation experience in Ex industrial electrical installation
documentation. practice.
• Assessment is based on IEC 60079-14 and • Assessed either concurrently with or after Unit
any other relevant standards. Ex 001.
• Installation all types of protection shall be
understood.
Unit Ex 004: Maintain equipment in explosive
atmospheres
SCOPE PREREQUISITES
• Covers explosion-protection aspects for • Technical education relevant to the
maintaining explosion-protected and application, through documents such as
associated equipment and wiring systems College Certificates and Trade Credentials etc.
including plant maintenance. • Minimum 3 years experience in industrial
• Ability to develop and manage maintenance maintenance practice.
programs incorporating strategies for • For Responsible Person minimum 3 years
inspections, repair / overhaul / replacement experience in Ex maintenance practice.
of components and recording of outcomes.
• Assessed either concurrently with or after
• Based on IEC 60079-17 and any other Unit Ex 001.
relevant standards.
Unit Ex 005: Overhaul and repair of explosion-
protected equipment
SCOPE PREREQUISITES
• Covers the explosion-protection aspects of • Technical education relevant to the
overhauling and repairing explosion-protected application, through documents such as
equipment. College Certificates and Trade Credentials
• Operative requires ability to identify / select etc.
authorized components, follow specifications • For Operative minimum 3 years experience
and complete documentation. in the overhaul and repair of general
• Responsible Person requires ability to establish electrical, electronic and / or mechanical
/ document the level of work required, equipment relevant to the scope
arranging for overhaul/repair to be carried • For Responsible Person minimum 3 years
out, verify compliance of overhauled/repaired experience in the servicing of Ex electrical,
equipment and complete the documentation. electronic and/or mechanical equipment
• Based on IEC 60079-19 and any other relevant relevant to the scope of the unit of
standards. competence being applied
Unit Ex 006: Test electrical installations in or
associated with explosive atmospheres
SCOPE PREREQUISITES
• Covers testing electrical installations for • Technical education relevant to the
explosive atmospheres. application, through documents such as
• Requires ability to select, prepare and use College Certificates and Trade Credentials
appropriate testing devices, work safely and to etc.
Standards and to interpret and record test • Minimum 3 years experience in industrial
results. electrical installation practice.
• Based on IEC 60079-14 and any other relevant • Assessed either concurrently with or after
standards that may apply. Unit Ex 001.
Unit Ex 007: Perform visual and close inspection of electrical
installations in or associated with explosive atmospheres
SCOPE PREREQUISITES
• Covers evaluating the completeness of verification • Technical education relevant to the
dossier and compliance of the explosion- application, through documents such as
protected aspects of the electrical installations. College Certificates and Trade Credentials
• Requires ability to work safely in a hazardous area, etc.
evaluate a verification dossier, identify explosion- • For Operative a minimum 3 years experience
protected equipment with their certification and in industrial electrical installation practice.
specified location, inspect an installation for • For Responsible Person a minimum 3 years
compliance and report and act on inspection experience in Ex electrical installation.
results. practice relevant to the scope of the unit of
• Based on IEC 60079-14 and IEC 60079-17 and any competence being applied for taking into
other relevant standards that may apply. account the scope limitations.
• Assessed either concurrently with or after
Unit Ex 001.
Unit Ex 008: Perform detailed inspection of electrical
installations in or associated with explosive atmospheres
SCOPE PREREQUISITES
• Covers explosion-protection aspects of • Technical education relevant to the
conducting initial, periodic and sample application, through documents such as
audit inspections of explosion-protected College Certificates and Trade Credentials
equipment and installations. etc.
• Requires the ability to audit a verification • For an operative a minimum 3 years
dossier, work safely in a hazardous area, experience in general electrical installation
inspect against Standards and report and practice.
act on inspection results. • For a responsible person a minimum 3 years
• Based on IEC 60079-14 and IEC 60079-17 experience in Hazardous Area installation
and any other relevant standards that may practice.
apply. • Assessed either concurrently with or after
Unit Ex 001.
Unit Ex 009: Design electrical installation in or associated with
explosive atmospheres
SCOPE PREREQUISITES
• Covers the explosion-protection aspects • Technical education relevant to the
of designing electrical power, control application, through documents such as
and instrumentation systems and Degree, Diploma and College
installations. Certificates etc.
• Requires ability to establish design • Minimum 3 years experience in general
briefs and to pursue economical and electrical installation design or
effective explosion-protection design supervised Hazardous Area installation
solutions. design.
• Based on IEC 60079-14 and any other • Assessed either concurrently with or after
relevant standards that may apply. Unit Ex 001.
Unit Ex 010: Perform audit inspection of electrical installations
in or associated with explosive atmospheres
SCOPE PREREQUISITES
• Covers the explosion-protection aspects of • Technical education relevant to the application,
conducting an audit of an electrical installation. through documents such as Degree, Diploma,
• Requires the ability to verify whether an College Certificates, Trade Credentials etc.
installation complies with the relevant • Minimum 3 years experience in general
hazardous area Standards for that installation electrical installation or inspection practice.
and includes the verification of design and • Minimum of 2 years experience in Hazardous
certification documentation (verification Area electrical installation inspection practice.
dossier), maintenance, overhaul and repair,
• Assessed either concurrently with or after
work safety, inspection against Standards and
Units Ex 002, Ex 008 and Ex 009.
reporting of audit results.
• Based on IEC 60079-14 and IEC 60079-17 and
any other relevant standards that may apply.
Summary of essential knowledge and associated skills for each
Unit of Competence
Applicant Checklist Description
• All pages of the application form completed (including payment information and
selected schedule).
• Valid e-mail address included.
• Valid telephone number included.
• Resume with details of work experience associated with Hazardous Areas and
Non-Hazardous Areas. Please provide details of employer(s) or client(s) for
verification.
• Letter of Current Employment.
• Copy of Degree / Diploma / Certificate.
• Copy of training records related to Hazardous Areas.
• Copy of Government issue Identification Document e.g. Mykad, International
Passport etc. Please cross, with the word -IECEX COPC-
NOTE :
All documentation such as resume, certificates, identification document etc to be reviewed /
endorsed / certified by current employer, notary public or commissioner of oaths (pesuruhjaya
sumpah).
CERTIFICATION PROCESS
Applicant Checklist Description
Inquiry • Quotation
• Complete
Application +
supporting
Payment documents
• Education,
Documents
Qualification,
validation Experience, Training
< 2 weeks
• Acceptance of
Exam application
notification
> 1 month • Exam schedule
Assessment
2 ~ 3 weeks
Independent
Review &
CER
Online
Certificate
Overall Assessment for Certification
Ex05
IECEx Scheme
for Certification
of Personnel
Competence for
Explosive
Atmospheres
IECEx CoPC ID Card
United Nations Endorsement of IECEx
New United Nations Publication,
March 2011 endorsing IEC TC 31
Standards + IECEx as world’s best
practice.
Full Text
http://www.unece.org/press/pr2011/11trade_p03e.htm
IECEx On-Line CoC System
https://t.me/MyIECEx
Thank you for