You are on page 1of 11

USER’S 

MANUAL 
SCR MONITOR BOARD 
(Also known as “Watchdog”) 

 
EU‐10258 
Inventory Number:  EUU‐7‐102583000 
 
 
 
DYNAPOWER COMPANY LLC 
85 Meadowland Drive 
South Burlington, VT 
USA   05403 
Phone: 1‐802‐860‐7200 
Fax:  1‐802‐864‐3782 

SCR Monitor Board User’s Manual – Watchdog – EUU‐7‐102583000 2013 Rev 1 
 

The DYNAPOWER EUU‐7‐102583000 (EU‐10258) SCR Monitor has 

Been designed to detect an SCR short circuit and shut down DYNAPOWER 

Electronic control circuits once a fault condition occurs. 

         

Original File Name: 2580A0M.DOC 

January, 2013 

SCR Monitor Board User’s Manual – Watchdog – EUU‐7‐102583000 2013 Rev 1 
 
 

CONTENTS 

1 ...............................................................................................................................................  Specifications 

2   ....................................................................................................................................  General Description 

3   ................................................................................................................................  Functional Description 

4   ...................................................................................................................................  Field Test Procedure 

5   ………………………………………………………………………………………………… Drawing Insert Showing Connections 

SCR Monitor Board User’s Manual – Watchdog – EUU‐7‐102583000 2013 Rev 1 
 
 

1.   SPECIFICATIONS 

Input Power  .................................................................................... 115 Vac, 50/60 Hz       45mAAC nominal  

Input Signals .................................................................  0‐32VAC 6‐Phase Star Rectifier Connection Bi‐Polar 

Input Resistance  ............................................................................................................................ 3300 Ohm 

Input VAC Isolation ..............................................................................  7500VAC Peak for 1 Second @ 60HZ 

SCR Monitor Board User’s Manual – Watchdog – EUU‐7‐102583000 2013 Rev 1 
 
 

  2.   GENERAL DESCRIPTION 

The DYNAPOWER EU‐10258 SCR Monitor Board has been designed to detect a short circuit SCR 

device and Inhibit DYNAPOWER electronic control circuits using a +7.5 to 11.5VDC output signal 

(depending on impedance.) The output comes from TB2‐9.  The maximum current available is 

150mA. The INHB terminal TB2‐8 goes high when a fault is detected. 

Output circuitry is shown in figure #1  

+15

R21
200, 0.5W

Q2
2N2222A
D13
TB2
8
INHB
1N4148
R20
1K

TB2 GND
9
 

                                                               Figure #1 

SCR Monitor Board User’s Manual – Watchdog – EUU‐7‐102583000 2013 Rev 1 
 
The DYNAPOWER EU‐10258 SCR Monitor Board has been designed to indicate a fault and 

signal the DYNAPOWER TOUCHPAD.  

The TOUCHPAD indicator output is an isolated open collector output; with a 30VPeak inverse 

voltage. It has 150mA output maximum. The typical voltage is 15V from the touchpad. INH+ is 

pulled to ground when a fault is detected. 

Details of the circuitry are shown in figure #2 

Q1
IRF531
1

U20
4N35
2

TB2
4
INH+

D19
1N4148

TB2
5
INH-
 

                                                                              Figure #2 

SCR Monitor Board User’s Manual – Watchdog – EUU‐7‐102583000 2013 Rev 1 
 
 

The dry relay contact is used to open the source power of the rectifier (Main contactor). Its 

contact is rated at 8A @ 250VAC. An MOV is incorporated at the board level to capture the 

inductive kick related to opening an inductive load.   See figure #3 

K1
TB2
6
C

MOV1
V250LA2

TB2
7
NO
 

                                                                     Figure #3 

The reset input (TB2‐3) needs to energize with 120VAC for the board to run. Typically, it is 

connected to TB2‐6 on the downstream side of the 120VAC control power.  See figure #4 

 
1

RST TB2 R4
6
3 22k 2W
U7
4N35
2

- +
BR1

WO6M C1
.22

                                                                                    Figure #4 

SCR Monitor Board User’s Manual – Watchdog – EUU‐7‐102583000 2013 Rev 1 
 
 

   

4.   FIELD TEST PROCEDURE 

No field adjustments are necessary.  To bench test board, use lab test fixture and document 
named “SCR Monitor Board Test fixture.doc”  

FIELD TEST PROCEDURE: 

 Install board in rectifier. Energize unit. All LEDS should be illuminated. 

 Start unit.   ALL LED’s should flicker. 

 Remove one of the wires from TB1‐4 through TB1‐9. SCR monitor board should trip off 
rectifier; indicate touchpad (if installed) and RED LED indicator for wire removed should 
stay illuminated. 

NOTE:   Removing common anode/cathode wire will not trip unit off. 

 Re‐install wire.  

 Cycle power to the rectifier.  

NOTE:  SCR Monitor Board will not reset until power is cycled to the board.  

 Re‐start rectifier and repeat previous step until all six transformer voltages have been 
checked. 

SCR Monitor Board User’s Manual – Watchdog – EUU‐7‐102583000 2013 Rev 1 
 
FUNCTIONAL DESCRIPTION 
 
1.0  Summary 
 
The SCR Monitor Board detects and annunciates a short circuit failure of any one of the 
six  SCRs  used  in  a  six‐pulse  SECONDARY  SCR  rectifier.    The  circuit  board  also  initiates 
rectifier shutdown in response to a shorted SCR; thus, preventing subsequent failures of 
the surviving SCRs which might otherwise result from the excessive currents created by 
the  initial  fault.    Shutdown  is  accomplished  through  an  on‐board  relay  whose  N.O. 
contacts  are  wired  in  series  with  the  holding  contact  for  the  main  contactor.    An  SCR 
fault  will  cause  this  relay  to  drop  out  which,  in  turn,  will  cause  the  main  contactor  to 
drop out. 
 
The  SCR  Monitor  also  produces  a  gate‐inhibit  signal  in  response  to  an  SCR  fault.    This 
signal is applied to terminals 11 and 6 of the C.A.T. board (#12 and #18 on 65C, and 65D 
board)  removing  gate‐drive  voltage  from  all  the  SCRs.    This  gate  inhibit  function  is 
necessary to provide an immediate shut off of the surviving SCRs; therefore,  protecting 
those devices during the relatively long time required for the main contactor to drop out 
once power to the coil is interrupted (50 ms or more). 
 
 
2.0  Detailed Description 
 
2.1  Rectifier Shutdown 
 
  Each  SCR  is  monitored  by  means  of  a  wire  connected  to  its  anode  and  terminated  on 
this circuit board.  The board detects the absence of a reverse blocking voltage across 
anode‐cathode of the SCR (indicating a short circuit from anode to cathode).  Within 23 
ms of the failure, the holding current through the interlock relay coil on this board will 
be  interrupted.    Relay  dropout  time  is  20  ms,  so  the  holding  circuit  for  the  main 
contactor will be interrupted 43 ms following the detection of a fault.  The drop out time 
of the main contactor must then be added t this 43 ms resulting in a total time lapse of 
approximately 90 to 150 ms between detection of an SCR fault and the interruption of 
AC power to the input of the rectifier. 
 
2.2  Gate Inhibit Function 
 
  To protect surviving SCRs during the relatively long interval between fault Detection and 
power interruption, a gate‐inhibit signal of 7.5 volts (with a 1k load) is produced at 
terminals TB2‐8 (+) and TB2‐9 (com) with 23 ms of the fault detection. A gate‐inhibit 
signal of 11.5V (with a 10K load) is produced at terminal TB2‐8(+) and TB2‐9(com) these 

SCR Monitor Board User’s Manual – Watchdog – EUU‐7‐102583000 2013 Rev 1 
 
terminals are wired to the inhibit terminals of the control electronics to initiate an 
immediate gate inhibit ensuring that surviving SCRs are shut down within 1 ½ power 
cycles following the fault. 

The time window of 23 ms is used rather than 16.7 ms (one period) to avoid nuisance 
shutdowns which might be caused by large electrical transients in the system. 
 
2.3   Failure Localization 
 
  The failed SCR is identified by one of six LEDs mounted on the circuit board.  Because 
this board is powered independently from a 115 VAC source, the LED will remain lit even 
though the main power to the rectifier is shut down following fault detection. 
 
  The LED associated with the failed SCR will remain lit until an attempt is made to restart 
the unit.  If the failed SCR has not been replaced, current tot the coil of the contactor 
will be interrupted within 150 ms after the START pushbutton is pressed even if finger 
pressure  is  maintained  on  the  START  pushbutton.    This  is  an  improvement  over  the 
original version.   
 
  If the failed SCR has been replaced, the unit will self‐reset and start normally. 
 
  In normal operation, all LEDs will flash at a 60 Hz rate while the rectifier is on and will be 
lit steadily while the rectifier is off. 
 
3.0  Fail‐Safe Aspects 
 
(a)  Failure of the 115 VAC power supply to the board or of the on‐board DC 
power  supply  will  cause  the  on‐board  relay  to  drop  out  initiating 
shutdown.   
 
(b)  Disconnecting  or  breaking  any  of  the  wires  to  the  A‐F  terminals 
connected  to  the  SCR  anodes  will  cause  the  on‐board  relay  to  drop  out 
initiating shutdown. 
 
(c)  A short‐circuit across TB2‐B and TB2‐9 (gate‐inhibit) circuit will prevent a 
gate‐inhibit  signal  from  being  sent  to  the  SCR  drive  electronics  but  will 
not prevent the on‐board relay from dropping out in response to a fault. 
                 
NOTE:  The "gate inhibit" function on the SCR drive electronics requires a 
positive voltage to inhibit the SCR gates and, thus, is not fail‐safe. 

(d)  In the latest design revision, the protection circuit cannot be defeated by 
maintaining pressure on the START pushbutton.  Current to the coil of the 
main  contactor  will  be  interrupted  within  150  ms  after  the  START 
pushbutton is pressed if one or more SCR has failed.

SCR Monitor Board User’s Manual – Watchdog – EUU‐7‐102583000 2013 Rev 1 
 
  5.   CONNECTION DRAWING 

SCR Monitor Board User’s Manual – Watchdog – EUU‐7‐102583000 2013 Rev 1 
 

You might also like