2. Safeties: 8) Entering and leaving-fluid temperature.

Unit shall be equipped with thermistors and all 9) Evaporator and condenser pressure.

necessary components in conjunction with the 10) Electronic expansion valve positions.

control system to provide the unit with the 11) All set points.
following protections:
12) Time of day.
a. Loss of refrigerant charge.
74
b. Reverse rotation.
b. Display module, in conjunction with the
c. Low chilled fluid temperature.
microprocessor must also be capable of
d. Low oil pressure (each compressor circuit). displaying the output results of a service test.

e. Voltage imbalance. Service test shall verify operation of every

f. Ground current fault. switch, thermistor, and compressor before

g. Thermal overload. chiller is started. User shall be able to force

h. High pressure. each output device.

i. Electrical overload. c. Diagnostics shall include the ability to review

j. Loss of phase. a list of the 20 most recent alarms with clear

k. Current imbalance. language descriptions of the alarm event.

l. Loss of flow. Display of alarm codes without the ability

3. Diagnostics: for clear language descriptions shall be

a. The display module shall be capable of prohibited.


indicating the safety lockout condition by
d. An alarm history buffer shall allow the user
displaying the information in clear language at
to store no less than 20 alarm events with
the display. Information included for display
clear language descriptions, time and date
shall be:
stamp event entry.
1) Compressor lockout.
H. Operating Characteristics:
2) Loss of charge.
Unit shall be capable of starting up with 95 F (35
3) Low fluid flow.
C)
4) Low oil pressure.
entering fluid temperature to the cooler.
5) Cooler freeze protection.
I. Electrical Requirements:
6) High or low suction superheat.
1. Unit primary electrical power supply shall
7) Thermistor malfunction. enter
the unit at a single location (some units have 5. Temperature Reset Sensor:

multiple power poles). Unit shall reset leaving chilled fluid temperature

2. Unit shall operate on 3-phase power at the based on outdoor ambient temperature or
voltage shown in the equipment schedule.
space temperature when this sensor is installed.
3. Control voltage shall be 115-v (60 Hz) or 230-
* 6. Brine Option:
v
Unit shall be factory modified to start and
(50 Hz), single-phase, separate power supply.
operate at leaving chilled fluid temperatures of
4. Unit shall be shipped with factory control and
between 15 F (–9 C) and 40 F (4.4 C).
power wiring installed.
* 7. Minimum Load Control:
J. Special Features:
Unit shall be equipped with factory (or field)
Certain standard features are not applicable
installed, microprocessor-controlled, minimum
when
load control that shall permit unit operation
the features designated by * are specified. For
assistance in amending the specifications, down to 10% of full capacity.
contact your
8. Multi-Chiller Control:
local Carrier Sales office.
Control shall enable management of multiple
* 1. Wye-Delta Starter:
parallel chillers (up to 8) or two (2) chillers in
Unit shall have a factory-installed, Wye-Delta
series in a single system.
starter to minimize electrical inrush current.
9. Minus-One-Pass Cooler:
2. Sound Reduction Enclosure:
Factory-installed option shall reduce pressure
Unit shall have field-installed sound reduction
drop for high flow applications. Shall also
enclosure which covers the entire unit to muffle
provide same end inlet and outlet for
compressor noise.
076-106 sizes and opposite end inlet for 116-
3. Vibration Isolation:
271 sizes.
Unit shall be supplied with rubber-in-shear
10. Plus-One-Pass Cooler:
vibration isolators for field installation.
Factory-installed option shall enhance low
4. Control Power Transformer: temperature brine performance.
Unit shall be supplied with a field-installed 11. Suction Service Valves:
transformer that will supply control circuit
power Unit shall be supplied with factory-installed
suction service valves.
from the main unit power supply.
12. Cooler Head Insulation:
Unit shall be supplied with field-installed cooler

insulation that shall cover the cooler heads.

13. Energy Management Module:

A factory or field installed module shall provide

the following energy management capabilities:

4 to 20 mA signals for leaving fluid temperature

reset, cooling set point reset or demand limit

control; 2-point demand limit control (from 0 to

100%) activated by a remote contact closure;

and discrete input for “Ice Done” indication for

ice storage system interface.