VARIODYN® D1
System Communication Unit SCU

• Digital audio memory for VARIODYN ® D1voice alarm


and public address system
• Cross-linkable via Ethernet
• Normconforming audio memory for alarm
and evacuation
• Can be used to log and record announcements
• Automatic temporary storage and playback of
interrupted messages
• Emergency power supply via 24 V DC
© 2009 Honeywell International Inc.

Application
The System Communication Unit The SCU can also be used to log and record announcements. These are
SCU serves as digital audio memory also saved on the hard drive and are backed up with date, time and acti-
for the VARIODYN® D1 voice alarm vation details.
Part No. 795874.G0.HO • 12/2009 • Technical information is subject to change without notice!

and public address system.


The automatic temporary storage allows announcements to be played
It is possible to record and play back which are momentarily unable to reach all targets by releasing them.
multiple audio data streams simul-
taneously. Connections
Connection to other VARIODYN® D1 • Ethernet connection 100 Mbit/s
Modules via Ethernet and is con- • Mains supply
stantly monitored. • 24 V DC emergency power supply input

Audio memory (the availability of Indicators


which is critical) for alarms and eva- • POWER-LED, HARDDISK-LED
cuation announcements occurs • ERROR-LED, STAND-ALONE-LED
according to IEC EN 60849 on
non-volatile flash-memory. Memory
capacity is approx. two hours.

Other audio files such as announce-


ments, signals or advertisements are
saved onto a hard drive. The memo-
ry capacity is approx. 1.000 hours.
795874_G0_HO_112009:Variodyn_D1_DOM4_8_4_24_032008.qxd 09.12.2009 09:55 Seite 1

DCS15 CD-Player
DCS15

UIM

DOM/
Power amplifiers

DOM/
Power amplifiers LAN TCP/IP FACP ID3000

DOM
DCS15
Configuration
via servide PC

UIM SCU
Central server
System VARIODYN-3000

DAL (Digital Audio Link) Serial Connection

© 2009 Honeywell International Inc.


DOM Digital Output Moduel DCS15 Digital Call Station
UIM Universal Interface Module SCU System Communication Unit Ethernet Fire network
FACP Fire Alarm Control Panel Direct Connection

System Overview VARIODYN® D1

Technical Data
Flash memory approx. two hours
Hard disk approx. 1.000 hours
Nominal voltage 90 V AC to 265 V AC
Nominal frequency 47 Hz to 63 Hz

Part No. 795874.G0.HO • 12/2009 • Technical information is subject to change without notice!
Current rating typ. 0.5 A @ 230 V AC
Ambient temperature -5 °C to +55 °C
Relative humidity 15 % to 90 %
Housing colour grey, similar to RAL 7016
Weight 3 kg
Dimensions (W x H x D) 483 x 44 x 360 mm/1 HE, 19"

Emergency power supply


Nominal voltage 24 V DC
Power consumption 32 W

Order information Part No.


System Communication Unit SCU 583381.22
Mounting kit 1 583703