You are on page 1of 22

SISTEMA ROCIADORES

Fire Sprinkler Reports

for

XXX
32882

Prepared By:

EHSP
EHSP

08-08-2020

C:\Program Files (x86)\Elite\Fire 6\Projects\EJEMPLO 1..fiw sábado, 8 de agosto de 2020, 6:00 p. m.


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr SISTEMA ROCIADORES
Hell Page 2

General Project Data Report

General Data
Project Title: SISTEMA ROCIADORES Project File Name: EJEMPLO 1..fiw
Designed By: EHSP Date: 08-08-2020
Code Reference: NFPA 13 Approving Agency: FAIC
Client Name: X Phone:
Address: XXX City, State Zip Code: 32882
Company Name: EHSP Representative:
Company Address: City And State:
Phone:
Building Name: BODEGA Building Owner: SR. BODEGA
Contact at Building: Phone at Building:
Address Of Building: City, State Zip Code:

Project Data
Description Of Hazard: Sprinkler System Type:
Design Area Of Water Application: 1500 ft² Maximum Area Per Sprinkler: 130 ft²
Default Sprinkler K-Factor: 5,60 K Default Pipe Material: SCHED 10 WET STEEL
Inside Hose Stream Allowance: 0,00 gpm Outside Hose Stream Allowance: 250,00 gpm
In Rack Sprinkler Allowance: 0,00 gpm

Sprinkler Specifications
Make: TYCO Model: TY-B
Size: 1/2" Temperature Rating: 165 F

Water Supply Test Data


Source Of Information:
Test Hydrant ID: Date Of Test:

Hydrant Elevation: 0 ft Static Pressure: 50,00 psi


Test Flow Rate: 650,00 gpm Test Residual Pressure: 45,00 psi
Calculated System Flow Rate: 504,65 gpm Calculated Inflow Residual Pressure: 26,86 psi
Available Residual Pressure At
46,87 psi
System Flow:

Calculation Project Data


Calculation Mode: Demand
HMD Minimum Residual Pressure: 7,00 psi Minimum Desired Flow Density: 0,15 gpm/ft²
Number Of Active Nodes: 67
Number Of Active Pipes: 74 Number Of Inactive Pipes: 0
Number Of Active Sprinklers: 13 Number Of Inactive Sprinklers: 0

C:\Program Files (x86)\Elite\Fire 6\Projects\EJEMPLO 1..fiw sábado, 8 de agosto de 2020, 6:01 p. m.


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr SISTEMA ROCIADORES
Hell Page 3

Fire Sprinkler Input Data

Node Input Data


Sprinkler Pressure Node Elev (ft) Non-Sprinkler
Area Group
Node Node Description KFactor (K) Estimate (psi) Branch Non- Flow (gpm)
Branch Dia.
No. Branch Description Branch Len. Branch Stnd Stnd Fittings Branch Sprk
(in)
(ft) Fittings (ft) KFactor (K)

No Discharge ---- N/A 14,39 19,00 0,00


1
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 15,28 19,00 0,00


3
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 17,63 17,00 0,00


5
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 17,66 17,00 0,00


6
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 17,72 17,00 0,00


7
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 17,80 17,00 0,00


8
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 17,87 17,00 0,00


9
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 17,86 17,00 0,00


10
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 17,85 17,00 0,00


11
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 17,85 17,00 0,00


12
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 16,60 19,00 0,00


14
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 16,36 19,00 0,00


17
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 15,51 19,00 0,00


22
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 15,28 19,00 0,00


24
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 15,76 17,00 0,00


26
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 15,73 17,00 0,00


28
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 15,65 17,00 0,00


29
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 15,46 17,00 0,00


32
---- 0,000 0,0 ---- 0,0 0,00

C:\Program Files (x86)\Elite\Fire 6\Projects\EJEMPLO 1..fiw sábado, 8 de agosto de 2020, 6:01 p. m.


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr SISTEMA ROCIADORES
Hell Page 4

Fire Sprinkler Input Data

Node Input Data (cont'd)


Sprinkler Pressure Node Elev (ft) Non-Sprinkler
Area Group
Node Node Description KFactor (K) Estimate (psi) Branch Non- Flow (gpm)
Branch Dia.
No. Branch Description Branch Len. Branch Stnd Stnd Fittings Branch Sprk
(in)
(ft) Fittings (ft) KFactor (K)
No Discharge ---- N/A 15,43 17,00 0,00
33
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 14,94 17,00 0,00


34
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 14,61 17,00 0,00


35
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 14,52 17,00 0,00


36
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 14,36 19,00 0,00


38
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 12,21 19,00 0,00


39
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 15,26 19,00 0,00


40
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 17,62 17,00 0,00


42
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 13,14 17,00 0,00


47
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 13,64 19,00 0,00


48
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 15,85 19,00 0,00


52
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 15,93 19,00 0,00


53
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 14,99 19,00 0,00


56
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 15,29 19,00 0,00


58
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 16,33 19,00 0,00


63
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 16,43 19,00 0,00


64
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 15,03 19,00 0,00


67
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 15,34 19,00 0,00


69
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 16,40 19,00 0,00


74
---- 0,000 0,0 ---- 0,0 0,00

C:\Program Files (x86)\Elite\Fire 6\Projects\EJEMPLO 1..fiw sábado, 8 de agosto de 2020, 6:01 p. m.


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr SISTEMA ROCIADORES
Hell Page 5

Fire Sprinkler Input Data

Node Input Data (cont'd)


Sprinkler Pressure Node Elev (ft) Non-Sprinkler
Area Group
Node Node Description KFactor (K) Estimate (psi) Branch Non- Flow (gpm)
Branch Dia.
No. Branch Description Branch Len. Branch Stnd Stnd Fittings Branch Sprk
(in)
(ft) Fittings (ft) KFactor (K)

No Discharge ---- N/A 16,50 19,00 0,00


75
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 15,19 19,00 0,00


78
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 15,48 19,00 0,00


80
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 16,49 19,00 0,00


85
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 16,58 19,00 0,00


86
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 15,26 19,00 0,00


89
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 15,50 19,00 0,00


91
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 16,36 19,00 0,00


96
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 16,59 19,00 0,00


98
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 19,10 17,00 0,00


102
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 24,83 4,70 0,00


103
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 27,19 1,00 0,00


104
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 29,37 -4,00 0,00


105
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 29,61 -4,00 0,00


108
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 29,61 -4,00 0,00


109
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 26,86 3,00 0,00


111
---- 0,000 0,0 ---- 0,0 0,00

No Discharge ---- N/A 29,71 -4,00 0,00


113
---- 0,000 0,0 ---- 0,0 0,00

Sprinkler ---- 5,60 12,43 19,00 0,00


201
---- 0,000 0,0 ---- 0,0 0,00

C:\Program Files (x86)\Elite\Fire 6\Projects\EJEMPLO 1..fiw sábado, 8 de agosto de 2020, 6:01 p. m.


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr SISTEMA ROCIADORES
Hell Page 6

Fire Sprinkler Input Data

Node Input Data (cont'd)


Sprinkler Pressure Node Elev (ft) Non-Sprinkler
Area Group
Node Node Description KFactor (K) Estimate (psi) Branch Non- Flow (gpm)
Branch Dia.
No. Branch Description Branch Len. Branch Stnd Stnd Fittings Branch Sprk
(in)
(ft) Fittings (ft) KFactor (K)
Sprinkler ---- 5,60 12,38 19,00 0,00
202
---- 0,000 0,0 ---- 0,0 0,00

Sprinkler ---- 5,60 12,18 19,00 0,00


203
---- 0,000 0,0 ---- 0,0 0,00

Sprinkler ---- 5,60 12,12 19,00 0,00


204
---- 0,000 0,0 ---- 0,0 0,00

Sprinkler ---- 5,60 13,73 19,00 0,00


205
---- 0,000 0,0 ---- 0,0 0,00

Sprinkler ---- 5,60 12,15 19,00 0,00


206
---- 0,000 0,0 ---- 0,0 0,00

Sprinkler ---- 5,60 12,09 19,00 0,00


207
---- 0,000 0,0 ---- 0,0 0,00

Sprinkler ---- 5,60 13,64 19,00 0,00


208
---- 0,000 0,0 ---- 0,0 0,00

Sprinkler ---- 5,60 12,18 19,00 0,00


209
---- 0,000 0,0 ---- 0,0 0,00

Sprinkler ---- 5,60 12,12 19,00 0,00


210
---- 0,000 0,0 ---- 0,0 0,00

Sprinkler ---- 5,60 13,03 19,00 0,00


211
---- 0,000 0,0 ---- 0,0 0,00

Sprinkler ---- 5,60 11,68 19,00 0,00


212
---- 0,000 0,0 ---- 0,0 0,00

Sprinkler ---- 5,60 10,25 19,00 0,00


213
---- 0,000 0,0 ---- 0,0 0,00

C:\Program Files (x86)\Elite\Fire 6\Projects\EJEMPLO 1..fiw sábado, 8 de agosto de 2020, 6:01 p. m.


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr SISTEMA ROCIADORES
Hell Page 7

Fire Sprinkler Input Data

Pipe Input Data


Nominal Nominal Fitting Total CFactor
Beg. End. Type Fitting
Pipe Description Diameter Length Length Length (gpm/inch-
Node Node Group Data
(inch) (feet) (feet) (feet) psi)

111 113 PVC, CLASS 200 6,000 0 2ET 5,00 87,50 92,50 150

113 109 PVC, CLASS 200 6,000 0 4E 770,00 84,40 854,40 150

109 108 PVC, CLASS 200 6,000 0 50,00 0,00 50,00 150

108 113 PVC, CLASS 200 6,000 0 80,00 0,00 80,00 150

108 105 PVC, CLASS 200 6,000 0 ET 56,00 66,40 122,40 150

105 104 PVC, CLASS 200 6,000 0 5,00 0,00 5,00 150

104 103 SCHED 10 WET STEEL 4,000 0 BC 3,75 45,00 48,75 120

103 102 SCHED 10 WET STEEL 4,000 0 E 12,50 13,00 25,50 120

102 9 SCHED 10 WET STEEL 4,000 0 ET 40,00 39,00 79,00 120

9 10 SCHED 10 WET STEEL 4,000 0 4,00 0,00 4,00 120

9 8 SCHED 10 WET STEEL 4,000 0 8,00 0,00 8,00 120

29 32 SCHED 10 WET STEEL 2,500 0 12,00 0,00 12,00 120

10 86 SCHED 10 WET STEEL 1,500 0 2T 2,00 20,00 22,00 120

86 85 SCHED 10 WET STEEL 1,500 0 5,00 0,00 5,00 120

85 80 SCHED 10 WET STEEL 1,500 0 54,00 0,00 54,00 120

80 78 SCHED 10 WET STEEL 1,500 0 15,80 0,00 15,80 120

78 29 SCHED 10 WET STEEL 1,500 0 2T 2,00 20,00 22,00 120

10 11 SCHED 10 WET STEEL 4,000 0 12,30 0,00 12,30 120

11 98 SCHED 10 WET STEEL 1,500 0 2T 2,00 20,00 22,00 120

29 28 SCHED 10 WET STEEL 2,500 0 12,30 0,00 12,30 120

28 89 SCHED 10 WET STEEL 1,500 0 2T 2,00 20,00 22,00 120

98 96 SCHED 10 WET STEEL 1,500 0 13,20 0,00 13,20 120

96 91 SCHED 10 WET STEEL 1,500 0 48,50 0,00 48,50 120

91 89 SCHED 10 WET STEEL 1,500 0 13,20 0,00 13,20 120

11 12 SCHED 10 WET STEEL 4,000 0 12,60 0,00 12,60 120

28 26 SCHED 10 WET STEEL 2,500 0 12,60 0,00 12,60 120

12 14 SCHED 10 WET STEEL 1,500 0 2T 2,00 20,00 22,00 120

26 24 SCHED 10 WET STEEL 1,500 0 2T 2,00 20,00 22,00 120

C:\Program Files (x86)\Elite\Fire 6\Projects\EJEMPLO 1..fiw sábado, 8 de agosto de 2020, 6:01 p. m.


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr SISTEMA ROCIADORES
Hell Page 8

Fire Sprinkler Input Data

Pipe Input Data (cont'd)


Nominal Nominal Fitting Total CFactor
Beg. End. Type Fitting
Pipe Description Diameter Length Length Length (gpm/inch-
Node Node Group Data
(inch) (feet) (feet) (feet) psi)
14 17 SCHED 10 WET STEEL 1,500 0 13,20 0,00 13,20 120

17 22 SCHED 10 WET STEEL 1,500 0 48,50 0,00 48,50 120

22 24 SCHED 10 WET STEEL 1,500 0 13,20 0,00 13,20 120

8 75 SCHED 10 WET STEEL 1,500 0 2T 2,00 20,00 22,00 120

32 67 SCHED 10 WET STEEL 1,500 0 2T 2,00 20,00 22,00 120

75 74 SCHED 10 WET STEEL 1,500 0 5,00 0,00 5,00 120

74 69 SCHED 10 WET STEEL 1,500 0 54,00 0,00 54,00 120

69 67 SCHED 10 WET STEEL 1,500 0 15,80 0,00 15,80 120

8 7 SCHED 10 WET STEEL 4,000 0 12,00 0,00 12,00 120

32 33 SCHED 10 WET STEEL 4,000 0 12,00 0,00 12,00 120

7 64 SCHED 10 WET STEEL 1,500 0 2T 2,00 20,00 22,00 120

33 56 SCHED 10 WET STEEL 1,500 0 2T 2,00 20,00 22,00 120

64 63 SCHED 10 WET STEEL 1,500 0 5,00 0,00 5,00 120

63 58 SCHED 10 WET STEEL 1,500 0 54,00 0,00 54,00 120

58 56 SCHED 10 WET STEEL 1,500 0 15,80 0,00 15,80 120

7 6 SCHED 10 WET STEEL 4,000 0 12,00 0,00 12,00 120

33 34 SCHED 10 WET STEEL 2,500 0 12,00 0,00 12,00 120

6 53 SCHED 10 WET STEEL 1,500 0 2T 2,00 20,00 22,00 120

34 48 SCHED 10 WET STEEL 1,500 0 2T 2,00 20,00 22,00 120

53 52 SCHED 10 WET STEEL 1,500 0 2,00 0,00 2,00 120

52 205 SCHED 10 WET STEEL 1,500 0 54,00 0,00 54,00 120

205 208 SCHED 10 WET STEEL 1,500 0 10,80 0,00 10,80 120

208 48 SCHED 10 WET STEEL 1,500 0 5,00 0,00 5,00 120

48 211 SCHED 10 WET STEEL 1,000 0 5,80 0,00 5,80 120

6 5 SCHED 10 WET STEEL 4,000 0 12,30 0,00 12,30 120

34 35 SCHED 10 WET STEEL 2,500 0 12,30 0,00 12,30 120

5 3 SCHED 10 WET STEEL 1,500 0 2T 2,00 20,00 22,00 120

35 47 SCHED 10 WET STEEL 1,500 0 2T 2,00 20,00 22,00 120

3 1 SCHED 10 WET STEEL 1,500 0 13,20 0,00 13,20 120

C:\Program Files (x86)\Elite\Fire 6\Projects\EJEMPLO 1..fiw sábado, 8 de agosto de 2020, 6:01 p. m.


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr SISTEMA ROCIADORES
Hell Page 9

Fire Sprinkler Input Data

Pipe Input Data (cont'd)


Nominal Nominal Fitting Total CFactor
Beg. End. Type Fitting
Pipe Description Diameter Length Length Length (gpm/inch-
Node Node Group Data
(inch) (feet) (feet) (feet) psi)

1 201 SCHED 10 WET STEEL 1,500 0 29,10 0,00 29,10 120

201 203 SCHED 10 WET STEEL 1,500 0 9,70 0,00 9,70 120

203 206 SCHED 10 WET STEEL 1,500 0 9,70 0,00 9,70 120

206 209 SCHED 10 WET STEEL 1,500 0 9,70 0,00 9,70 120

209 47 SCHED 10 WET STEEL 1,500 0 3,50 0,00 3,50 120

47 212 SCHED 10 WET STEEL 1,000 0 6,25 0,00 6,25 120

5 42 SCHED 10 WET STEEL 4,000 0 12,60 0,00 12,60 120

35 36 SCHED 10 WET STEEL 2,500 0 12,60 0,00 12,60 120

42 40 SCHED 10 WET STEEL 1,500 0 2T 2,00 20,00 22,00 120

36 39 SCHED 10 WET STEEL 1,500 0 2T 2,00 20,00 22,00 120

40 38 SCHED 10 WET STEEL 1,500 0 13,20 0,00 13,20 120

38 202 SCHED 10 WET STEEL 1,500 0 29,10 0,00 29,10 120

202 204 SCHED 10 WET STEEL 1,500 0 9,70 0,00 9,70 120

204 207 SCHED 10 WET STEEL 1,500 0 9,70 0,00 9,70 120

207 210 SCHED 10 WET STEEL 1,500 0 9,70 0,00 9,70 120

210 39 SCHED 10 WET STEEL 1,500 0 3,50 0,00 3,50 120

39 213 SCHED 10 WET STEEL 1,000 0 6,25 0,00 6,25 120

C:\Program Files (x86)\Elite\Fire 6\Projects\EJEMPLO 1..fiw sábado, 8 de agosto de 2020, 6:01 p. m.


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr SISTEMA ROCIADORES
Hell Page 10

Fire Sprinkler Output Data

Overall Node Groupings Output Data


Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)

1 3 0 -48,54 0,00 0,00 0,00 14,39 -0,00029


1 201 0 48,54

3 1 0 48,54 0,00 0,00 0,00 15,28 0,00002


3 5 0 -48,54

5 3 0 48,54 0,00 0,00 0,00 17,63 -0,00009


5 6 0 -97,36
5 42 0 48,82

6 5 0 97,36 0,00 0,00 0,00 17,66 -0,00009


6 7 0 -133,66
6 53 0 36,30

7 6 0 133,66 0,00 0,00 0,00 17,72 0,00001


7 8 0 -158,34
7 64 0 24,68

8 7 0 158,34 0,00 0,00 0,00 17,80 -0,00005


8 9 0 -183,29
8 75 0 24,95

9 8 0 183,29 0,00 0,00 0,00 17,87 0,00056


9 102 0 -254,65
9 10 0 71,36

10 9 0 -71,36 0,00 0,00 0,00 17,86 -0,00008


10 86 0 24,23
10 11 0 47,12

11 10 0 -47,12 0,00 0,00 0,00 17,85 -0,00004


11 98 0 23,64
11 12 0 23,48

12 11 0 -23,48 0,00 0,00 0,00 17,85 -0,00007


12 14 0 23,48

14 12 0 -23,48 0,00 0,00 0,00 16,60 0,00001


14 17 0 23,48

17 14 0 -23,48 0,00 0,00 0,00 16,36 -0,00002


17 22 0 23,48

22 17 0 -23,48 0,00 0,00 0,00 15,51 0,00002


22 24 0 23,48

24 22 0 -23,48 0,00 0,00 0,00 15,28 -0,00001


24 26 0 23,48

26 24 0 -23,48 0,00 0,00 0,00 15,76 0,00004


26 28 0 23,48

28 26 0 -23,48 0,00 0,00 0,00 15,73 0,00000


28 29 0 47,12
28 89 0 -23,64

C:\Program Files (x86)\Elite\Fire 6\Projects\EJEMPLO 1..fiw sábado, 8 de agosto de 2020, 6:01 p. m.


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr SISTEMA ROCIADORES
Hell Page 11

Fire Sprinkler Output Data

Overall Node Groupings Output Data (cont'd)


Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)
29 28 0 -47,12 0,00 0,00 0,00 15,65 0,00001
29 32 0 71,36
29 78 0 -24,23

32 29 0 -71,36 0,00 0,00 0,00 15,46 0,00012


32 67 0 -24,95
32 33 0 96,31

33 32 0 -96,31 0,00 0,00 0,00 15,43 -0,00017


33 56 0 -24,68
33 34 0 120,99

34 33 0 -120,99 0,00 0,00 0,00 14,94 -0,00126


34 48 0 24,88
34 35 0 96,11

35 34 0 -96,11 0,00 0,00 0,00 14,61 -0,00069


35 47 0 48,26
35 36 0 47,84

36 35 0 -47,84 0,00 0,00 0,00 14,52 -0,00018


36 39 0 47,84

38 40 0 -48,82 0,00 0,00 0,00 14,36 -0,00028


38 202 0 48,82

39 36 0 -47,84 0,00 0,00 0,00 12,21 -0,33040


39 210 0 28,75
39 213 0 18,76

40 38 0 48,82 0,00 0,00 0,00 15,26 0,00001


40 42 0 -48,82

42 5 0 -48,82 0,00 0,00 0,00 17,62 -0,00014


42 40 0 48,82

47 35 0 -48,26 0,00 0,00 0,00 13,14 0,00010


47 209 0 29,26
47 212 0 19,01

48 34 0 -24,88 0,00 0,00 0,00 13,64 -0,00061


48 208 0 4,81
48 211 0 20,07

52 53 0 -36,30 0,00 0,00 0,00 15,85 -0,00009


52 205 0 36,30

53 6 0 -36,30 0,00 0,00 0,00 15,93 0,00006


53 52 0 36,30

56 33 0 24,68 0,00 0,00 0,00 14,99 -0,00001


56 58 0 -24,68

58 56 0 24,68 0,00 0,00 0,00 15,29 0,00002


58 63 0 -24,68

63 58 0 24,68 0,00 0,00 0,00 16,33 -0,00004

C:\Program Files (x86)\Elite\Fire 6\Projects\EJEMPLO 1..fiw sábado, 8 de agosto de 2020, 6:01 p. m.


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr SISTEMA ROCIADORES
Hell Page 12

Fire Sprinkler Output Data

Overall Node Groupings Output Data (cont'd)


Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)
63 64 0 -24,68

64 7 0 -24,68 0,00 0,00 0,00 16,43 0,00002


64 63 0 24,68

67 32 0 24,95 0,00 0,00 0,00 15,03 -0,00001


67 69 0 -24,95

69 67 0 24,95 0,00 0,00 0,00 15,34 0,00002


69 74 0 -24,95

74 69 0 24,95 0,00 0,00 0,00 16,40 -0,00004


74 75 0 -24,95

75 8 0 -24,95 0,00 0,00 0,00 16,50 0,00002


75 74 0 24,95

78 29 0 24,23 0,00 0,00 0,00 15,19 -0,00001


78 80 0 -24,23

80 78 0 24,23 0,00 0,00 0,00 15,48 0,00002


80 85 0 -24,23

85 80 0 24,23 0,00 0,00 0,00 16,49 -0,00004


85 86 0 -24,23

86 10 0 -24,23 0,00 0,00 0,00 16,58 0,00002


86 85 0 24,23

89 28 0 23,64 0,00 0,00 0,00 15,26 -0,00001


89 91 0 -23,64

91 89 0 23,64 0,00 0,00 0,00 15,50 0,00002


91 96 0 -23,64

96 91 0 23,64 0,00 0,00 0,00 16,36 -0,00002


96 98 0 -23,64

98 11 0 -23,64 0,00 0,00 0,00 16,59 0,00001


98 96 0 23,64

102 9 0 254,65 0,00 0,00 0,00 19,10 -0,00019


102 103 0 -254,65

103 102 0 254,65 0,00 0,00 0,00 24,83 0,00010


103 104 0 -254,65

104 103 0 254,65 0,00 0,00 0,00 27,19 -0,00068


104 105 0 -254,65

105 104 0 254,65 0,00 0,00 0,00 29,37 0,00048


105 108 0 -254,65

108 105 0 254,65 0,00 0,00 0,00 29,61 -0,00023


108 109 0 -54,07
108 113 0 -200,58

C:\Program Files (x86)\Elite\Fire 6\Projects\EJEMPLO 1..fiw sábado, 8 de agosto de 2020, 6:01 p. m.


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr SISTEMA ROCIADORES
Hell Page 13

Fire Sprinkler Output Data

Overall Node Groupings Output Data (cont'd)


Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)
109 108 0 54,07 0,00 0,00 0,00 29,61 0,00009
109 113 0 -54,07

111 113 0 254,65 0,00 0,00 -254,65 26,86

113 108 0 200,58 0,00 0,00 0,00 29,71 0,00009


113 109 0 54,07
113 111 0 -254,65

201 1 0 -48,54 19,75 0,00 0,00 12,43 0,14362


201 203 0 28,94

202 38 0 -48,82 19,70 0,00 0,00 12,38 0,14946


202 204 0 29,27

203 201 0 -28,94 19,55 0,00 0,00 12,18 0,14000


203 206 0 9,53

204 202 0 -29,27 19,50 0,00 0,00 12,12 0,14635


204 207 0 9,92

205 52 0 -36,30 20,75 0,00 0,00 13,73 0,15633


205 208 0 15,71

206 203 0 -9,53 19,52 0,00 0,00 12,15 0,13961


206 209 0 -9,85

207 204 0 -9,92 19,47 0,00 0,00 12,09 0,14662


207 210 0 -9,40

208 48 0 -4,81 20,68 0,00 0,00 13,64 0,15741


208 205 0 -15,71

209 47 0 -29,26 19,55 0,00 0,00 12,18 0,14022


209 206 0 9,85

210 39 0 -28,75 19,49 0,00 0,00 12,12 0,14693


210 207 0 9,40

211 48 0 -20,07 20,21 0,00 0,00 13,03 0,14468

212 47 0 -19,01 19,14 0,00 0,00 11,68 0,13382

213 39 0 -18,76 17,93 0,00 0,00 10,25 0,83923

C:\Program Files (x86)\Elite\Fire 6\Projects\EJEMPLO 1..fiw sábado, 8 de agosto de 2020, 6:01 p. m.


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr SISTEMA ROCIADORES
Hell Page 14

Fire Sprinkler Output Data

Overall Pipe Output Data


q (gpm) F. L./ft Pipe-Len.
Beg. Nodal Spk/Hose Residual Nom. Dia. PF-(psi)
Elevation Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. PE-(psi)
(feet) Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) C-Value PT-(psi)
(fps) Type-Grp (ft)

1 0,00 19,00 0,00 14,39 1,50 19,75 0,06736 29,10 1,960


201 5,60 19,00 19,75 12,43 1,682 48,54 ----- 0,00 0,000
SCHED 10 WET STEEL 120 7,01 0 29,10 1,960

3 0,00 19,00 0,00 15,28 1,50 0,00 0,06736 13,20 0,889


1 0,00 19,00 0,00 14,39 1,682 48,54 ----- 0,00 0,000
SCHED 10 WET STEEL 120 7,01 0 13,20 0,889

5 0,00 17,00 0,00 17,63 1,50 0,00 0,06736 2,00 1,482


3 0,00 19,00 0,00 15,28 1,682 48,54 2T 20,00 0,866
SCHED 10 WET STEEL 120 7,01 0 22,00 2,348

5 0,00 17,00 0,00 17,63 4,00 0,00 0,00074 12,60 0,009


42 0,00 17,00 0,00 17,62 4,260 48,82 ----- 0,00 0,000
SCHED 10 WET STEEL 120 1,10 0 12,60 0,009

6 0,00 17,00 0,00 17,66 4,00 0,00 0,00264 12,30 0,033


5 0,00 17,00 0,00 17,63 4,260 97,36 ----- 0,00 0,000
SCHED 10 WET STEEL 120 2,19 0 12,30 0,033

6 0,00 17,00 0,00 17,66 1,50 0,00 0,03935 2,00 0,866


53 0,00 19,00 0,00 15,93 1,682 36,30 2T 20,00 0,866
SCHED 10 WET STEEL 120 5,24 0 22,00 1,732

7 0,00 17,00 0,00 17,72 4,00 0,00 0,00475 12,00 0,057


6 0,00 17,00 0,00 17,66 4,260 133,66 ----- 0,00 0,000
SCHED 10 WET STEEL 120 3,01 0 12,00 0,057

7 0,00 17,00 0,00 17,72 1,50 0,00 0,01927 2,00 0,424


64 0,00 19,00 0,00 16,43 1,682 24,68 2T 20,00 0,866
SCHED 10 WET STEEL 120 3,56 0 22,00 1,290

8 0,00 17,00 0,00 17,80 4,00 0,00 0,00650 12,00 0,078


7 0,00 17,00 0,00 17,72 4,260 158,34 ----- 0,00 0,000
SCHED 10 WET STEEL 120 3,56 0 12,00 0,078

8 0,00 17,00 0,00 17,80 1,50 0,00 0,01967 2,00 0,433


75 0,00 19,00 0,00 16,50 1,682 24,95 2T 20,00 0,866
SCHED 10 WET STEEL 120 3,60 0 22,00 1,299

9 0,00 17,00 0,00 17,87 4,00 0,00 0,00852 8,00 0,068


8 0,00 17,00 0,00 17,80 4,260 183,29 ----- 0,00 0,000
SCHED 10 WET STEEL 120 4,13 0 8,00 0,068

9 0,00 17,00 0,00 17,87 4,00 0,00 0,00149 4,00 0,006


10 0,00 17,00 0,00 17,86 4,260 71,36 ----- 0,00 0,000
SCHED 10 WET STEEL 120 1,61 0 4,00 0,006

10 0,00 17,00 0,00 17,86 1,50 0,00 0,01863 2,00 0,410


86 0,00 19,00 0,00 16,58 1,682 24,23 2T 20,00 0,866
SCHED 10 WET STEEL 120 3,50 0 22,00 1,276

C:\Program Files (x86)\Elite\Fire 6\Projects\EJEMPLO 1..fiw sábado, 8 de agosto de 2020, 6:01 p. m.


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr SISTEMA ROCIADORES
Hell Page 15

Fire Sprinkler Output Data

Overall Pipe Output Data (cont'd)


q (gpm) F. L./ft Pipe-Len.
Beg. Nodal Spk/Hose Residual Nom. Dia. PF-(psi)
Elevation Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. PE-(psi)
(feet) Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) C-Value PT-(psi)
(fps) Type-Grp (ft)

10 0,00 17,00 0,00 17,86 4,00 0,00 0,00069 12,30 0,008


11 0,00 17,00 0,00 17,85 4,260 47,12 ----- 0,00 0,000
SCHED 10 WET STEEL 120 1,06 0 12,30 0,008

11 0,00 17,00 0,00 17,85 1,50 0,00 0,01780 2,00 0,392


98 0,00 19,00 0,00 16,59 1,682 23,64 2T 20,00 0,866
SCHED 10 WET STEEL 120 3,41 0 22,00 1,258

11 0,00 17,00 0,00 17,85 4,00 0,00 0,00019 12,60 0,002


12 0,00 17,00 0,00 17,85 4,260 23,48 ----- 0,00 0,000
SCHED 10 WET STEEL 120 0,53 0 12,60 0,002

12 0,00 17,00 0,00 17,85 1,50 0,00 0,01757 2,00 0,387


14 0,00 19,00 0,00 16,60 1,682 23,48 2T 20,00 0,866
SCHED 10 WET STEEL 120 3,39 0 22,00 1,253

14 0,00 19,00 0,00 16,60 1,50 0,00 0,01757 13,20 0,232


17 0,00 19,00 0,00 16,36 1,682 23,48 ----- 0,00 0,000
SCHED 10 WET STEEL 120 3,39 0 13,20 0,232

17 0,00 19,00 0,00 16,36 1,50 0,00 0,01757 48,50 0,852


22 0,00 19,00 0,00 15,51 1,682 23,48 ----- 0,00 0,000
SCHED 10 WET STEEL 120 3,39 0 48,50 0,852

22 0,00 19,00 0,00 15,51 1,50 0,00 0,01757 13,20 0,232


24 0,00 19,00 0,00 15,28 1,682 23,48 ----- 0,00 0,000
SCHED 10 WET STEEL 120 3,39 0 13,20 0,232

26 0,00 17,00 0,00 15,76 1,50 0,00 0,01757 2,00 0,387


24 0,00 19,00 0,00 15,28 1,682 23,48 2T 20,00 -0,866
SCHED 10 WET STEEL 120 3,39 0 22,00 -0,479

28 0,00 17,00 0,00 15,73 2,50 23,48 0,00197 12,60 0,025


26 0,00 17,00 0,00 15,76 2,635 23,48 ----- 0,00 0,000
SCHED 10 WET STEEL 120 1,38 0 12,60 0,025

29 0,00 17,00 0,00 15,65 2,50 47,12 0,00716 12,30 0,088


28 0,00 17,00 0,00 15,73 2,635 47,12 ----- 0,00 0,000
SCHED 10 WET STEEL 120 2,77 0 12,30 0,088

29 0,00 17,00 0,00 15,65 2,50 71,36 0,01544 12,00 0,185


32 0,00 17,00 0,00 15,46 2,635 71,36 ----- 0,00 0,000
SCHED 10 WET STEEL 120 4,20 0 12,00 0,185

32 0,00 17,00 0,00 15,46 4,00 96,31 0,00259 12,00 0,031


33 0,00 17,00 0,00 15,43 4,260 96,31 ----- 0,00 0,000
SCHED 10 WET STEEL 120 2,17 0 12,00 0,031

33 0,00 17,00 0,00 15,43 2,50 0,00 0,04100 12,00 0,492


34 0,00 17,00 0,00 14,94 2,635 120,99 ----- 0,00 0,000
SCHED 10 WET STEEL 120 7,12 0 12,00 0,492

C:\Program Files (x86)\Elite\Fire 6\Projects\EJEMPLO 1..fiw sábado, 8 de agosto de 2020, 6:01 p. m.


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr SISTEMA ROCIADORES
Hell Page 16

Fire Sprinkler Output Data

Overall Pipe Output Data (cont'd)


q (gpm) F. L./ft Pipe-Len.
Beg. Nodal Spk/Hose Residual Nom. Dia. PF-(psi)
Elevation Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. PE-(psi)
(feet) Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) C-Value PT-(psi)
(fps) Type-Grp (ft)

34 0,00 17,00 0,00 14,94 1,50 0,00 0,01957 2,00 0,430


48 0,00 19,00 0,00 13,64 1,682 24,88 2T 20,00 0,866
SCHED 10 WET STEEL 120 3,59 0 22,00 1,296

34 0,00 17,00 0,00 14,94 2,50 0,00 0,02678 12,30 0,329


35 0,00 17,00 0,00 14,61 2,635 96,11 ----- 0,00 0,000
SCHED 10 WET STEEL 120 5,65 0 12,30 0,329

35 0,00 17,00 0,00 14,61 1,50 0,00 0,06665 2,00 1,466


47 0,00 17,00 0,00 13,14 1,682 48,26 2T 20,00 0,000
SCHED 10 WET STEEL 120 6,97 0 22,00 1,466

35 0,00 17,00 0,00 14,61 2,50 0,00 0,00737 12,60 0,093


36 0,00 17,00 0,00 14,52 2,635 47,84 ----- 0,00 0,000
SCHED 10 WET STEEL 120 2,81 0 12,60 0,093

36 0,00 17,00 0,00 14,52 1,50 0,00 0,06558 2,00 1,443


39 0,00 19,00 0,00 12,21 1,682 47,84 2T 20,00 0,866
SCHED 10 WET STEEL 120 6,91 0 22,00 2,309

38 0,00 19,00 0,00 14,36 1,50 19,70 0,06808 29,10 1,981


202 5,60 19,00 19,70 12,38 1,682 48,82 ----- 0,00 0,000
SCHED 10 WET STEEL 120 7,05 0 29,10 1,981

210 5,60 19,00 19,49 12,12 1,50 19,49 0,02556 3,50 0,089
39 0,00 19,00 0,00 12,21 1,682 28,75 ----- 0,00 0,000
SCHED 10 WET STEEL 120 4,15 0 3,50 0,089

39 0,00 19,00 0,00 12,21 1,00 17,93 0,31378 6,25 1,961


213 5,60 19,00 17,93 10,25 1,097 18,76 ----- 0,00 0,000
SCHED 10 WET STEEL 120 6,37 0 6,25 1,961

40 0,00 19,00 0,00 15,26 1,50 0,00 0,06808 13,20 0,899


38 0,00 19,00 0,00 14,36 1,682 48,82 ----- 0,00 0,000
SCHED 10 WET STEEL 120 7,05 0 13,20 0,899

42 0,00 17,00 0,00 17,62 1,50 0,00 0,06808 2,00 1,498


40 0,00 19,00 0,00 15,26 1,682 48,82 2T 20,00 0,866
SCHED 10 WET STEEL 120 7,05 0 22,00 2,364

209 5,60 19,00 19,55 12,18 1,50 19,55 0,02640 3,50 0,092
47 0,00 17,00 0,00 13,14 1,682 29,26 ----- 0,00 0,866
SCHED 10 WET STEEL 120 4,22 0 3,50 0,958

47 0,00 17,00 0,00 13,14 1,00 19,14 0,09527 6,25 0,595


212 5,60 19,00 19,14 11,68 1,097 19,01 ----- 0,00 0,866
SCHED 10 WET STEEL 120 6,45 0 6,25 1,461

208 5,60 19,00 20,68 13,64 1,50 4,81 0,00094 5,00 0,005
48 0,00 19,00 0,00 13,64 1,682 4,81 ----- 0,00 0,000
SCHED 10 WET STEEL 120 0,69 0 5,00 0,005

C:\Program Files (x86)\Elite\Fire 6\Projects\EJEMPLO 1..fiw sábado, 8 de agosto de 2020, 6:01 p. m.


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr SISTEMA ROCIADORES
Hell Page 17

Fire Sprinkler Output Data

Overall Pipe Output Data (cont'd)


q (gpm) F. L./ft Pipe-Len.
Beg. Nodal Spk/Hose Residual Nom. Dia. PF-(psi)
Elevation Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. PE-(psi)
(feet) Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) C-Value PT-(psi)
(fps) Type-Grp (ft)

48 0,00 19,00 0,00 13,64 1,00 20,21 0,10538 5,80 0,611


211 5,60 19,00 20,21 13,03 1,097 20,07 ----- 0,00 0,000
SCHED 10 WET STEEL 120 6,81 0 5,80 0,611

52 0,00 19,00 0,00 15,85 1,50 20,75 0,03935 54,00 2,125


205 5,60 19,00 20,75 13,73 1,682 36,30 ----- 0,00 0,000
SCHED 10 WET STEEL 120 5,24 0 54,00 2,125

53 0,00 19,00 0,00 15,93 1,50 0,00 0,03935 2,00 0,079


52 0,00 19,00 0,00 15,85 1,682 36,30 ----- 0,00 0,000
SCHED 10 WET STEEL 120 5,24 0 2,00 0,079

33 0,00 17,00 0,00 15,43 1,50 24,68 0,01927 2,00 0,424


56 0,00 19,00 0,00 14,99 1,682 24,68 2T 20,00 -0,866
SCHED 10 WET STEEL 120 3,56 0 22,00 -0,442

58 0,00 19,00 0,00 15,29 1,50 0,00 0,01927 15,80 0,304


56 0,00 19,00 0,00 14,99 1,682 24,68 ----- 0,00 0,000
SCHED 10 WET STEEL 120 3,56 0 15,80 0,304

63 0,00 19,00 0,00 16,33 1,50 0,00 0,01927 54,00 1,041


58 0,00 19,00 0,00 15,29 1,682 24,68 ----- 0,00 0,000
SCHED 10 WET STEEL 120 3,56 0 54,00 1,041

64 0,00 19,00 0,00 16,43 1,50 0,00 0,01927 5,00 0,096


63 0,00 19,00 0,00 16,33 1,682 24,68 ----- 0,00 0,000
SCHED 10 WET STEEL 120 3,56 0 5,00 0,096

32 0,00 17,00 0,00 15,46 1,50 24,95 0,01967 2,00 0,433


67 0,00 19,00 0,00 15,03 1,682 24,95 2T 20,00 -0,866
SCHED 10 WET STEEL 120 3,60 0 22,00 -0,433

69 0,00 19,00 0,00 15,34 1,50 0,00 0,01967 15,80 0,311


67 0,00 19,00 0,00 15,03 1,682 24,95 ----- 0,00 0,000
SCHED 10 WET STEEL 120 3,60 0 15,80 0,311

74 0,00 19,00 0,00 16,40 1,50 0,00 0,01967 54,00 1,062


69 0,00 19,00 0,00 15,34 1,682 24,95 ----- 0,00 0,000
SCHED 10 WET STEEL 120 3,60 0 54,00 1,062

75 0,00 19,00 0,00 16,50 1,50 0,00 0,01967 5,00 0,098


74 0,00 19,00 0,00 16,40 1,682 24,95 ----- 0,00 0,000
SCHED 10 WET STEEL 120 3,60 0 5,00 0,098

78 0,00 19,00 0,00 15,19 1,50 24,23 0,01863 2,00 0,410


29 0,00 17,00 0,00 15,65 1,682 24,23 2T 20,00 -0,866
SCHED 10 WET STEEL 120 3,50 0 22,00 -0,456

80 0,00 19,00 0,00 15,48 1,50 0,00 0,01863 15,80 0,294


78 0,00 19,00 0,00 15,19 1,682 24,23 ----- 0,00 0,000
SCHED 10 WET STEEL 120 3,50 0 15,80 0,294

C:\Program Files (x86)\Elite\Fire 6\Projects\EJEMPLO 1..fiw sábado, 8 de agosto de 2020, 6:01 p. m.


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr SISTEMA ROCIADORES
Hell Page 18

Fire Sprinkler Output Data

Overall Pipe Output Data (cont'd)


q (gpm) F. L./ft Pipe-Len.
Beg. Nodal Spk/Hose Residual Nom. Dia. PF-(psi)
Elevation Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. PE-(psi)
(feet) Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) C-Value PT-(psi)
(fps) Type-Grp (ft)

85 0,00 19,00 0,00 16,49 1,50 0,00 0,01863 54,00 1,006


80 0,00 19,00 0,00 15,48 1,682 24,23 ----- 0,00 0,000
SCHED 10 WET STEEL 120 3,50 0 54,00 1,006

86 0,00 19,00 0,00 16,58 1,50 0,00 0,01863 5,00 0,093


85 0,00 19,00 0,00 16,49 1,682 24,23 ----- 0,00 0,000
SCHED 10 WET STEEL 120 3,50 0 5,00 0,093

28 0,00 17,00 0,00 15,73 1,50 23,64 0,01780 2,00 0,392


89 0,00 19,00 0,00 15,26 1,682 23,64 2T 20,00 -0,866
SCHED 10 WET STEEL 120 3,41 0 22,00 -0,474

91 0,00 19,00 0,00 15,50 1,50 0,00 0,01780 13,20 0,235


89 0,00 19,00 0,00 15,26 1,682 23,64 ----- 0,00 0,000
SCHED 10 WET STEEL 120 3,41 0 13,20 0,235

96 0,00 19,00 0,00 16,36 1,50 0,00 0,01780 48,50 0,863


91 0,00 19,00 0,00 15,50 1,682 23,64 ----- 0,00 0,000
SCHED 10 WET STEEL 120 3,41 0 48,50 0,863

98 0,00 19,00 0,00 16,59 1,50 0,00 0,01780 13,20 0,235


96 0,00 19,00 0,00 16,36 1,682 23,64 ----- 0,00 0,000
SCHED 10 WET STEEL 120 3,41 0 13,20 0,235

102 0,00 17,00 0,00 19,10 4,00 0,00 0,01566 40,00 1,237
9 0,00 17,00 0,00 17,87 4,260 254,65 ET 39,00 0,000
SCHED 10 WET STEEL 120 5,73 0 79,00 1,237

103 0,00 4,70 0,00 24,83 4,00 0,00 0,01566 12,50 0,399
102 0,00 17,00 0,00 19,10 4,260 254,65 E 13,00 5,326
SCHED 10 WET STEEL 120 5,73 0 25,50 5,725

104 0,00 1,00 0,00 27,19 4,00 0,00 0,01566 3,75 0,763
103 0,00 4,70 0,00 24,83 4,260 254,65 BC 45,00 1,602
SCHED 10 WET STEEL 120 5,73 0 48,75 2,365

105 0,00 -4,00 0,00 29,37 6,00 0,00 0,00197 5,00 0,010
104 0,00 1,00 0,00 27,19 5,993 254,65 ----- 0,00 2,165
PVC, CLASS 200 150 2,90 0 5,00 2,175

108 0,00 -4,00 0,00 29,61 6,00 0,00 0,00197 56,00 0,241
105 0,00 -4,00 0,00 29,37 5,993 254,65 ET 66,40 0,000
PVC, CLASS 200 150 2,90 0 122,40 0,241

109 0,00 -4,00 0,00 29,61 6,00 54,07 0,00011 50,00 0,006
108 0,00 -4,00 0,00 29,61 5,993 54,07 ----- 0,00 0,000
PVC, CLASS 200 150 0,62 0 50,00 0,006

111 0,00 3,00 0,00 26,86 6,00 0,00 0,00197 5,00 0,182
113 0,00 -4,00 0,00 29,71 5,993 254,65 2ET 87,50 -3,031
PVC, CLASS 200 150 2,90 0 92,50 -2,849

C:\Program Files (x86)\Elite\Fire 6\Projects\EJEMPLO 1..fiw sábado, 8 de agosto de 2020, 6:01 p. m.


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr SISTEMA ROCIADORES
Hell Page 19

Fire Sprinkler Output Data

Overall Pipe Output Data (cont'd)


q (gpm) F. L./ft Pipe-Len.
Beg. Nodal Spk/Hose Residual Nom. Dia. PF-(psi)
Elevation Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. PE-(psi)
(feet) Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) C-Value PT-(psi)
(fps) Type-Grp (ft)

108 0,00 -4,00 0,00 29,61 6,00 200,58 0,00126 80,00 0,101
113 0,00 -4,00 0,00 29,71 5,993 200,58 ----- 0,00 0,000
PVC, CLASS 200 150 2,28 0 80,00 0,101

113 0,00 -4,00 0,00 29,71 6,00 0,00 0,00011 770,00 0,096
109 0,00 -4,00 0,00 29,61 5,993 54,07 4E 84,40 0,000
PVC, CLASS 200 150 0,62 0 854,40 0,096

201 5,60 19,00 19,75 12,43 1,50 19,55 0,02587 9,70 0,251
203 5,60 19,00 19,55 12,18 1,682 28,94 ----- 0,00 0,000
SCHED 10 WET STEEL 120 4,18 0 9,70 0,251

202 5,60 19,00 19,70 12,38 1,50 19,50 0,02642 9,70 0,256
204 5,60 19,00 19,50 12,12 1,682 29,27 ----- 0,00 0,000
SCHED 10 WET STEEL 120 4,23 0 9,70 0,256

203 5,60 19,00 19,55 12,18 1,50 9,53 0,00331 9,70 0,032
206 5,60 19,00 19,52 12,15 1,682 9,53 ----- 0,00 0,000
SCHED 10 WET STEEL 120 1,38 0 9,70 0,032

204 5,60 19,00 19,50 12,12 1,50 9,92 0,00357 9,70 0,035
207 5,60 19,00 19,47 12,09 1,682 9,92 ----- 0,00 0,000
SCHED 10 WET STEEL 120 1,43 0 9,70 0,035

205 5,60 19,00 20,75 13,73 1,50 15,71 0,00836 10,80 0,090
208 5,60 19,00 20,68 13,64 1,682 15,71 ----- 0,00 0,000
SCHED 10 WET STEEL 120 2,27 0 10,80 0,090

206 5,60 19,00 19,52 12,15 1,50 9,85 0,00352 9,70 0,034
209 5,60 19,00 19,55 12,18 1,682 9,85 ----- 0,00 0,000
SCHED 10 WET STEEL 120 1,42 0 9,70 0,034

207 5,60 19,00 19,47 12,09 1,50 9,40 0,00323 9,70 0,031
210 5,60 19,00 19,49 12,12 1,682 9,40 ----- 0,00 0,000
SCHED 10 WET STEEL 120 1,36 0 9,70 0,031

C:\Program Files (x86)\Elite\Fire 6\Projects\EJEMPLO 1..fiw sábado, 8 de agosto de 2020, 6:01 p. m.


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr SISTEMA ROCIADORES
Hell Page 20

Fire Sprinkler Output Data

Overall Sprinkler Output Data


Flowing Sprinkler Residual Flowing Sprinkler
Area Group Sprinkler Flowing Area
Sprinkler Elevation Pressure Density Discharge
Code KFactor (K) (ft²)
Node No. (feet) (psi) (gpm/ft²) (gpm)

201 5,60 19,00 12,43 119,50 0,165 19,75


Sub Totals For Non-Group 119,50 0,165 19,75

202 5,60 19,00 12,38 119,50 0,165 19,70


Sub Totals For Non-Group 119,50 0,165 19,70

203 5,60 19,00 12,18 119,50 0,164 19,55


Sub Totals For Non-Group 119,50 0,164 19,55

204 5,60 19,00 12,12 119,50 0,163 19,50


Sub Totals For Non-Group 119,50 0,163 19,50

205 5,60 19,00 13,73 130,00 0,160 20,75


Sub Totals For Non-Group 130,00 0,160 20,75

206 5,60 19,00 12,15 119,50 0,163 19,52


Sub Totals For Non-Group 119,50 0,163 19,52

207 5,60 19,00 12,09 119,50 0,163 19,47


Sub Totals For Non-Group 119,50 0,163 19,47

208 5,60 19,00 13,64 130,00 0,159 20,68


Sub Totals For Non-Group 130,00 0,159 20,68

209 5,60 19,00 12,18 119,50 0,164 19,55


Sub Totals For Non-Group 119,50 0,164 19,55

210 5,60 19,00 12,12 119,50 0,163 19,49


Sub Totals For Non-Group 119,50 0,163 19,49

211 5,60 19,00 13,03 130,00 0,155 20,21


Sub Totals For Non-Group 130,00 0,155 20,21

212 5,60 19,00 11,68 119,50 0,160 19,14


Sub Totals For Non-Group 119,50 0,160 19,14

213 5,60 19,00 10,25 119,50 0,150 17,93


Sub Totals For Non-Group 119,50 0,150 17,93

Totals For All Groups 1585,00 0,161 255,22

C:\Program Files (x86)\Elite\Fire 6\Projects\EJEMPLO 1..fiw sábado, 8 de agosto de 2020, 6:01 p. m.


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr SISTEMA ROCIADORES
Hell Page 21

Fire Sprinkler Output Summary

Hydraulically Most Demanding Sprinkler Node


HMD Sprinkler Node Number: 213
HMD Actual Residual Pressure: 10,25 psi
HMD Actual GPM: 17,93 gpm

Sprinkler Summary
Sprinkler System Type:
Specified Area Of Application: 1500,00 ft²
Minimum Desired Density: 0,150 gpm/ft²
Application Average Density: 0,170 gpm/ft²
Application Average Area Per Sprinkler: 115,38 ft²
Sprinkler Flow: 255,22 gpm
Average Sprinkler Flow: 19,63 gpm

Flow Velocity And Imbalance Summary


Maximum Flow Velocity ( In Pipe 33 - 34 ) 7,12 ft/sec
Maximum Velocity Pressure ( In Pipe 33 - 34 ) 0,34 psi

Allowable Maximum Nodal Pressure Imbalance: 1,0000 psi


Actual Maximum Nodal Pressure Imbalance: 0,3628 psi
Actual Average Nodal Pressure Imbalance: 0,2488 psi
Actual Maximum Nodal Flow Imbalance: 0,8392 gpm
Actual Average Nodal Flow Imbalance: 0,0436 gpm

Overall Network Summary


Number Of Unique Pipe Sections: 74
Number Of Flowing Sprinklers: 13

Pipe System Water Volume: 1623,88 gal

Sprinkler Flow: 255,22 gpm


Non-Sprinkler Flow: 0,00 gpm
Demand Flow Excluding Exterior Hose Flow: 255,22 gpm
Exterior Hose Flow: 250,00 gpm

Minimum Required Residual Pressure At System Inflow


26,86 psi
Node:
Demand Flow At System Inflow Node: 504,65 gpm

C:\Program Files (x86)\Elite\Fire 6\Projects\EJEMPLO 1..fiw sábado, 8 de agosto de 2020, 6:01 p. m.


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr SISTEMA ROCIADORES
Hell Page 22

Fire Sprinkler Output Data

Hydraulic Supply/Demand Graph

100

90

80

70
Pressure psi

60

50
50
45

40 39

30

20

10

0
1 2 3 4 5 6 7 8 9 10
Flowrate(x100) gpm

Supply Curve Data


Static Pressure: 50 psi
Test Residual Pressure: 45 psi
Test Flow Rate: 650 gpm

Demand Curve Data


Calculated Residual Pressure: 26,86 psi
Calculated Flow Rate: 504,65 gpm
Exterior Hose Flow: 250,00 gpm
Excess Available Residual Pressure At Calculated Flow: 20,01 psi
Pressure Required For First Sprinkler Downstream From Inflow Node To Flow: 6,93 psi

C:\Program Files (x86)\Elite\Fire 6\Projects\EJEMPLO 1..fiw sábado, 8 de agosto de 2020, 6:01 p. m.

You might also like