E l e c t r i c a l e n e r g y s u p p ly

Energy distribution
conditions (continued)
Frequency (Hz) Voltage
Household Commercial Industrial
Country and tolerance tolerance
voltage (V) voltage (V) voltage (V)
(%) (%)
Lebanon 50 220 380/220 380/220 ±10
380
Lybian 50 ±1 220 220/380 ±10
11 kV
Lithuania 50 ±1 400/230 400/230 400/230 ±10
Luxembourg 50 ±0.0 400/230 400/230 65 kV • 20 kV +6/-10
Macedonia 50 380/220 • 220 380/220 • 220 10 kV • 6.6 kV • 380/220 Not available
63 kV • 35 kV • 30 kV
Low voltage: ±7
Madagascar 50 ±2 220/110 • 380/220 220/110 • 380/220 20 kV • 15 kV
Hight voltage: ±5
5.5 kV • 380/220
240
Malaysia 50 ±1 415/240 415/240 +5/-10
415/240
220
Mali 50 220 • 380/220 Not available Not available
380/220
Malta 50 ±2 230 400/230 11 kV • 400/230 +10/-6
Martinique 50 230 230/400V • 230 230/400 • 20 kV -10/+6
Mauritania 50 380/220 380/220 15 kV • 380/220 ±10
Mauritius 50 ±1 230 400/230 400/230 ±6
13.8 kV • 13.2 kV
Mexico 60 ±0.2 220/127 • 220 • 120 220/127 • 220 • 120 ±10
480/277 • 220/127
225 kV • 150 kV
Morocco 50 ±5 380/220 380/220 ±10
60 kV • 22 kV
25 kV • 20 kV • 12 kV
Netherlands 50 ±10 400/230 • 230 400/230 ±10
10 kV • 230/400
New Zealand 50 ±1.5 400/230 • 230 400/230 • 230 11 kV • 400/230 ±6
15 kV • 11 kV
Nigeria 50 ±1 230 • 220 400/230 • 380/220 ±5
400/230 • 380/220
Norway 50 ±1 400/230 400/230 400/230 • 690 ±10
Pakistan 50 230 400/230 • 230 400/230 ±5
Paraguay 50 ±5 220 380/220 • 220 22 kV • 380/220 ±5
Peru 60 ±6 220 220 20 kV • 10 kV • 220 ±5
50 +0.2/-0.5 1 kV • 690/400
Poland 230 400/230 +6/-10
50 +0.4/-1 400/230 • 6.3 kV
60 kV • 30 kV • 15 kV 60 kV • 30 kV • 15 kV
Portugal 50 ±1 400/230 • 230 60 ±10
10 kV • 400/230 • 230 10 kV • 400/230 • 230
Qatar 50 ±1 240 415/240 33 kV • 66 kV • 132 kV ±5
660/380
Romania 50 ±0.5 230 440/230 ±10
400/230
660/380/220 660/380/220
Russia 50 ±0.2 380/220 • 220 +10/-20
380/220/127 380/220/127
Rwanda 50 ±1 220 380/220 15 kV • 6.6 kV • 380/220 ±5
Saudi Arabia 60 ±0.3 220/127 220/127 13.8 kV • 380/220 ±5
Senegal 50 ±5 220 380/220 • 220/127 90 kV • 30 kV • 6.6 kV ±10
230/400 230/440
Serbia 50 10 kV • 6.6 kV • 230/400 ±10
LV Rationalized VOLTAGES

230 230
Singapore 50 ±1 400/230 • 230 400/230 22 kV • 6.6 kV • 400/230 ±6
Slovakia 50 ±0.5 230/030 230/400 230/400 ±10
35 kV • 20 kV • 10 kV • 6 kV
+6/-10 for
Slovenia 50 ±0.1 230/400 230/400 3.3 kV • 1000V • 660V
400/230
500V • 400/230
440/220 • 220/110
Somalia 50 230 • 220 • 110 440/220 • 220/110 ±10
230
11 kV • 6.6 kV • 3.3 kV
433/250 • 400/230 11 kV • 6.6 kV • 3.3 kV
South Africa 50 ±2.5 433/250 • 400/230 ±10
380/220 • 220 500 • 380/220
380/220
25 kV • 20 kV • 15 kV
380/220 • 220
Spain 50 ±0.5 380/220 • 220/127 11 kV • 10 kV • 6 kV ±7
220/127 • 127
3 kV • 380/220