QUALITROL 509ITM Series

QUALITROL 509ITM Series


Intelligent Transformer Monitor


Protocol Manual: DNP V3.00, Modbus, IEC 60870 &
IEC 61850 Communications
Document ID: IST-100-1 ECN-31022

www.qualitrolcorp.com
Legal

Information in this document is subject to change without notice. This document is provided to purchasers of Qualitrol
products for use in the installation, operation and servicing of such products. No other use, nor any reproduction,
distribution or the making of any derivatives of this document is authorized, without the express prior written permission of
Qualitrol.
Qualitrol endeavors to ensure the accuracy and quality of its published materials; however, no warranty, expressed or
implied, is provided. Qualitrol disclaims any responsibility or liability for any direct or indirect damages resulting from the
use of the information in this manual or products described in it. Mention of any product or brand does not constitute an
endorsement by Qualitrol of that product or brand.
This document was originally composed in English and was subsequently translated into other languages. The fidelity of
subsequent translations cannot be guaranteed. In case of conflict between the English version and another language
version, the English version takes precedence.

©2010 QUALITROL Company LLC, an ISO 9001 system certified company. All rights reserved. Information subject to change without notice.
®

All trademarks are properties of their respective companies, as noted herein. IST-104-1.

www.qualitrolcorp.com
Protocol Manual

Contents
Hardware Instructions.................................................................................... 1 
OVERVIEW ................................................................................................................ 1 
Communications for the Qualitrol 509ITM Series Transformer Monitor ............................ 1 
General .............................................................................................................................. 1 
About Qualitrol ................................................................................................................... 2 
DNP 3.0 Communications .............................................................................. 3 
Introduction .............................................................................................................. 3 
DNP V3.0 Device Profile ........................................................................................... 3 
DNP V3.0 Implementation Table.............................................................................. 6 
DNP V3.0 Point List ................................................................................................ 14 
Binary Input Points ............................................................................................................. 14 
Binary Output Status Points ............................................................................................ 16 
Counters .......................................................................................................................... 17 
Analog Inputs .................................................................................................................. 18 
Analog Output Status Points ........................................................................................... 29 
Octet Strings .................................................................................................................... 32 
Time and Date .................................................................................................................32 
Modbus Protocol .......................................................................................... 33 
General .................................................................................................................... 33 
Function Codes Supported ................................................................................... 33 
Modbus Register Map ............................................................................................ 33 
Binary Parameters ........................................................................................................... 33 
Binary Parameters ........................................................................................................... 34 
Analog Parameters .......................................................................................................... 35 
Analog Parameters .......................................................................................................... 46 
String Parameters ........................................................................................................... 49 
Analog Parameters .......................................................................................................... 52 
Analog Parameters .......................................................................................................... 54 
String Parameters ........................................................................................................... 54 
Analog Parameters .......................................................................................................... 62 
String Parameters ........................................................................................................... 63 

www.qualitrolcorp.com
Protocol Manual

Analog Parameters .......................................................................................................... 63 


Binary Parameters ........................................................................................................... 78 
Analog Parameters .......................................................................................................... 78 
String Parameters ........................................................................................................... 90 
IEC 60870-5-101 Configuration/ Interoperability Guide ............................ 92 
Introduction ............................................................................................................ 92 
Interoperability ....................................................................................................... 92 
System or device .............................................................................................................93 
Network Configuration ..................................................................................................... 93 
Physical Layer ................................................................................................................. 93 
Link Layer ........................................................................................................................ 93 
Application Layer .............................................................................................................94 
Basic Application Functions ............................................................................................ 99 
File transfer ................................................................................................................... 101 
IEC 60870-5-101 I/O DATA MAP .......................................................................... 102 
IEC 61850 COMMUNICATIONS .................................................................. 121 
Introduction .......................................................................................................... 123 

www.qualitrolcorp.com
Hardware Instructions
OVERVIEW
Communications for the Qualitrol 509ITM Series
Transformer Monitor
General
The 509ITM comes equipped with digital communication capabilities and a four-wire RS485 port
comes on the rear of the device. Optional ports; an asynchronous serial fiber optic port and/or an
Ethernet port can be ordered. (See the 509ITM configuration form when ordering). The hardware
wiring and configuring the software for the ports is explained in the 509ITM Hardware/Software
Manual IST-099-1.
The 509ITM must be configured for the proper communication protocol for each active port using the
Qualitrol ITM Manager Software package supplied with the unit (or downloaded from the Qualitrol
Web Site (www.qualitrolcorp.com). Using the software package the user can configure the 509ITM
for the appropriate protocol, baud rates, data bits, etc. for their system requirements (see the
communication window below). Once the correct parameters have been entered and loaded into the
509ITM the unit must have power cycled before these new values will take affect.

1 www.qualitrolcorp.com
About Qualitrol
Qualitrol has been a leader in supplying pressure, liquid level and temperature controls since 1945.
As an ISO 9001 System-certified company, we are committed to providing quality and reliability, both
in our products and in our service.

2 www.qualitrolcorp.com
DNP 3.0 Communications
Introduction
The purpose of this document is to describe specific configuration and interoperability information for
an implementation of the Distributed Network Protocol (DNP), Version 3.0 using the DNP 3.0 Slave
Source Code Library. This document provides information on how to communicate via the DNP 3.0
protocol.
This implementation of DNP 3.0 is fully compliant with DNP 3.0 Subset Definition Level 3, and
contains significant functionality beyond Subset Level 3.

DNP V3.0 Device Profile


The following table provides a “Device Profile Document” in the standard format defined in the DNP
3.0 Subset Definitions Document. While it is referred to in the DNP 3.0 Subset Definitions as a
“Document,” it is in fact a table, and only a component of a total interoperability guide. The table, in
combination with the Implementation Table provided in Section 0 and the Point List Tables provided
in Section 0 should provide a complete configuration/interoperability guide for communicating with a
device implanting the DNP 3.0 Slave Source Code Library.

DNP V3.0
DEVICE PROFILE DOCUMENT
Vendor Name: Qualitrol
Device Name: 509ITM
Highest DNP Level Supported: Device Function:

For Requests:
For Responses:
Level 3
Level 3
 Master
 Slave

3 www.qualitrolcorp.com
DNP V3.0
DEVICE PROFILE DOCUMENT
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels
Supported (the complete list is described in the attached table):

For static (non-change-event) object requests, request qualifier codes 07 and 08 (limited quantity), and 17 and 28 (index) are
supported. Static object requests sent with qualifiers 07, or 08, will be responded with qualifiers 00 or 01.

16-bit, 32-bit and Floating Point Analog Change Events with Time may be requested.
Analog Input Deadbands, Object 34, variations 1 through 3, are supported.
Floating Point Analog Output Status and Output Block Objects 40 and 41 are supported.
Sequential file transfer, Object 70, variations 2 through 8, are supported.
Octet String and String Event Objects 110 and 111 are supported.
Virtual Terminal Output and Event Objects 112 and 113 are supported.
Device Attribute Object 0 is supported.
Data Set Objects 85-88 are supported.
Output Event Objects 11, 13, 42 and 43 are supported.
Activate Configuration
Secure Authentication

Maximum Data Link Frame Size (octets): Maximum Application Fragment Size (octets):

Transmitted: 292 Transmitted: Configurable up to 2048


Received 292 Received 2048
Maximum Data Link Re-tries: Maximum Application Layer Re-tries:

 None  None
 Fixed  Configurable
 Configurable from 0 to 65535
Requires Data Link Layer Confirmation:

 Never
 Always
 Sometimes
 Configurable as: Never, Only for multi-frame messages, or Always
Requires Application Layer Confirmation:

 Never
 Always
 When reporting Event Data (Slave devices only)
 When sending multi-fragment responses (Slave devices only)
 Sometimes
 Configurable as: “Only when reporting event data”, or “When reporting event data or
multi-fragment messages.”

4 www.qualitrolcorp.com
DNP V3.0
DEVICE PROFILE DOCUMENT
Timeouts while waiting for:

Data Link Confirm:  None  Fixed at ____  Variable  Configurable.


Complete Appl. Fragment:  None  Fixed at ____  Variable  Configurable
Application Confirm:  None  Fixed at ____  Variable  Configurable.
Complete Appl. Response:  None  Fixed at ____  Variable  Configurable

Others: Transmission Delay, configurable


Select/Operate Arm Timeout, configurable
Need Time Interval, configurable
Application File Timeout, configurable
Unsolicited Notification Delay, configurable
Unsolicited Response Retry Delay, configurable
Unsolicited Offline Interval, configurable
Binary Change Event Scan Period, configurable
Double Bit Change Event Scan Period, configurable
Analog Change Event Scan Period, configurable
Counter Change Event Scan Period, configurable
Frozen Counter Change Event Scan Period, configurable
String Change Event Scan Period, configurable
Virtual Terminal Event Scan Period, configurable

Sends/Executes Control Operations:

WRITE Binary Outputs  Never  Always  Sometimes  Configurable


SELECT/OPERATE  Never  Always  Sometimes  Configurable
DIRECT OPERATE  Never  Always  Sometimes  Configurable
DIRECT OPERATE – NO ACK  Never  Always  Sometimes  Configurable

Count > 1  Never  Always  Sometimes  Configurable


Pulse On  Never  Always  Sometimes  Configurable
Pulse Off  Never  Always  Sometimes  Configurable
Latch On  Never  Always  Sometimes  Configurable
Latch Off  Never  Always  Sometimes  Configurable

Queue  Never  Always  Sometimes  Configurable


Clear Queue  Never  Always  Sometimes  Configurable

Attach explanation if 'Sometimes' or 'Configurable' was checked for any operation.


Reports Binary Input Change Events when no Reports time-tagged Binary Input Change Events
specific variation requested: when no specific variation requested:

 Never  Never
 Only time-tagged  Binary Input Change With Time
 Only non-time-tagged  Binary Input Change With Relative Time
 Configurable to send one or the  Configurable
other

5 www.qualitrolcorp.com
DNP V3.0
DEVICE PROFILE DOCUMENT
Sends Unsolicited Responses: Sends Static Data in Unsolicited Responses:

 Never  Never
 Configurable  When Device Restarts


Only certain objects
Sometimes (attach explanation)
 When Status Flags Change
 ENABLE/DISABLE UNSOLICITED No other options are permitted.
Function codes supported
Default Counter Object/Variation: Counters Roll Over at:

 No Counters Reported  No Counters Reported


 Configurable  Configurable (attach explanation)
 Default Object  16 Bits
Default Variation:  32 Bits
 Point-by-point list attached  Other Value: _____
 Point-by-point list attached
Sends Multi-Fragment Responses:
 Yes
 No
 Configurable

Sequential File Transfer Support:

Append File Mode  Yes No


Custom Status Code Strings Yes  No
Permissions Field  Yes No
File Events Assigned to Class  Yes No
File Events Send Immediately  Yes No
Multiple Blocks in a Fragment Yes  No
Max Number of Files Open 1

DNP V3.0 Implementation Table


The following table identifies which object variations, function codes, and qualifiers the DNP 3.0 Slave
Source Code Library supports in both request messages and in response messages. For static (non-
change-event) objects, requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with
qualifiers 00 or 01. Requests sent with qualifiers 17 or 28 will be responded with qualifiers 17 or 28.
For change-event objects, qualifiers 17 or 28 are always responded.
In the table below, text shaded as 00, 01 (start stop) indicates Subset Level 3 functionality (beyond
Subset Level 2).
In the table below, text shaded as 07, 08 (limited qty) indicates functionality beyond Subset Level 3.

6 www.qualitrolcorp.com
REQUEST RESPONSE
OBJECT
(Library will parse) (Library will respond with)
Object Variation Function Qualifier Codes Function Qualifier Codes
Description
Number Number Codes (dec) (hex) Codes (dec) (hex)
0 1-253 Device Attribute Specific 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 1)
17, 27, 28 (index)
2 (write) 00, 01 (start-stop)

0 254 Device Attribute - Non-Specific All 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Attributes Request 06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 1)
17, 27, 28 (index)
0 255 Device Attribute – List of Attribute 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Variations 06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 1)
17, 27, 28 (index)
1 0 Binary Input – Any Variation 1 (read) 00, 01 (start-stop)
22 (assign 06 (no range, or all)
class) 07, 08 (limited qty)
17, 27, 28 (index)
1 1 Binary Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(default – 06 (no range, or all) 17, 28 (index –
see note 1) see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
1 2 Binary Input with Status 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
2 0 Binary Input Change – Any Variation 1 (read) 06 (no range, or all)
07, 08 (limited qty)
2 1 Binary Input Change without Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited qty) 130 (unsol. resp)
2 2 Binary Input Change with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited qty) 130 (unsol. resp)
2 3 Binary Input Change with Relative Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
(default – 07, 08 (limited qty) 130 (unsol. resp)
see note 1)
3 0 Double Bit Input – Any Variation 1 (read) 00, 01 (start-stop)
22 (assign 06 (no range, or all)
class) 07, 08 (limited qty)
17, 27, 28 (index)
3 1 Double Bit Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(default – 06 (no range, or all) 17, 28 (index –
see note 1) see note 1)
07, 08 (limited qty)
17, 27, 28 (index)
3 2 Double Bit Input with Status 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 1)
17, 27, 28 (index)
4 0 Double Bit Input Change – Any Variation 1 (read) 06 (no range, or all)
07, 08 (limited qty)
4 1 Double Bit Input Change without Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index )
07, 08 (limited qty) 130 (unsol. resp)
4 2 Double Bit Input Change with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index )
07, 08 (limited qty) 130 (unsol. resp)
4 3 Double Bit Input Change with Relative 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index )
(default – Time 07, 08 (limited qty) 130 (unsol. resp)
see note 1)
10 0 Binary Output – Any Variation 1 (read) 00, 01 (start-stop)
22 (assign 06 (no range, or all)
class) 07, 08 (limited qty)
17, 27, 28 (index)
10 1 Binary Output 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 1)
17, 27, 28 (index)

7 www.qualitrolcorp.com
REQUEST RESPONSE
OBJECT
(Library will parse) (Library will respond with)
Object Variation Function Qualifier Codes Function Qualifier Codes
Description
Number Number Codes (dec) (hex) Codes (dec) (hex)
1 (write 00, 01 (start-stop)

10 2 Binary Output Status 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(default – 06 (no range, or all) 17, 28 (index –
see note 1) see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
11 0 Binary Output Change – Any Variation 1 (read) 06 (no range, or all)
07, 08 (limited qty)
11 1 Binary Output Change without Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index )
(default – 07, 08 (limited qty) 130 (unsol. resp)
see note 1)
11 2 Binary Output Change with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index )
07, 08 (limited qty) 130 (unsol. resp)
12 0 Control Relay Output Block 22 (assign 00, 01 (start-stop)
class) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
12 1 Control Relay Output Block 3 (select) 17, 28 (index) 129 (response) echo of request
4 (operate)
5 (direct op)
6 (dir. op, noack)
12 2 Pattern Control Block 3 (select) 7 (limited quantity) 129 (response) echo of request
4 (operate)
5 (direct op)
6 (dir. op, noack)
12 3 Pattern Mask 3 (select) 00, 01 (start- 129 (response) echo of request
4 (operate) stop)
5 (direct op)
6 (dir. op, noack)
13 0 Binary Output Command Event – Any 1 (read) 06 (no range, or all)
Variation 07, 08 (limited qty)
13 1 Binary Output Command Event without 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index )
Time 07, 08 (limited qty) 130 (unsol. resp)
13 2 Binary Output Command Event with 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index )
Time 07, 08 (limited qty) 130 (unsol. resp)
20 0 Binary Counter – Any Variation 1 (read) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)

7 (freeze) 00, 01 (start-stop)


8 (freeze noack) 06 (no range, or all)
9 (freeze clear) 07, 08 (limited qty)
10 (frz. cl. noack)
20 1 32-Bit Binary Counter (with Flag) 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
20 2 16-Bit Binary Counter (with Flag) 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
20 5 32-Bit Binary Counter without Flag 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(default – 06 (no range, or all) 17, 28 (index –
see note 1) see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
20 6 16-Bit Binary Counter without Flag 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
21 0 Frozen Counter – Any Variation 1 (read) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)

8 www.qualitrolcorp.com
REQUEST RESPONSE
OBJECT
(Library will parse) (Library will respond with)
Object Variation Function Qualifier Codes Function Qualifier Codes
Description
Number Number Codes (dec) (hex) Codes (dec) (hex)
21 1 32-Bit Frozen Counter (with Flag) 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
21 2 16-Bit Frozen Counter (with Flag) 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
21 5 32-Bit Frozen Counter with Time Of 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-
Freeze 06 (no range, or all) stop)
07, 08 (limited qty) 17, 28 (index –
17, 27, 28 (index) see note 1)

21 6 16-Bit Frozen Counter with Time Of 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-
Freeze 06 (no range, or all) stop)
07, 08 (limited qty) 17, 28 (index –
17, 27, 28 (index) see note 1)

21 9 32-Bit Frozen Counter without Flag 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(default – 06 (no range, or all) 17, 28 (index –
see note 1) see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
21 10 16-Bit Frozen Counter without Flag 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
22 0 Counter Change Event – Any Variation 1 (read) 06 (no range, or all)
07, 08 (limited qty)
22 1 32-Bit Counter Change Event without 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
(default – Time 07, 08 (limited qty) 130 (unsol. resp)
see note 1)
22 2 16-Bit Counter Change Event without 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Time 07, 08 (limited qty) 130 (unsol. resp)
22 5 32-Bit Counter Change Event with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited qty) 130 (unsol. resp)
22 6 16-Bit Counter Change Event with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited qty) 130 (unsol. resp)
23 0 Frozen Counter Event (Variation 0 is 1 (read) 06 (no range, or all)
used to request default variation) 07, 08 (limited qty)
23 1 32-Bit Frozen Counter Event 1 (read) 06 (no range, or all) 129 (response) 17,28 (index)
(default – 07, 08 (limited qty) 130 (unsol. resp)
see note 1)
23 2 16-Bit Frozen Counter Event 1 (read) 06 (no range, or all) 129 (response) 17,28 (index)
07, 08 (limited qty) 130 (unsol. resp)
23 5 32-Bit Frozen Counter Event with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited qty) 130 (unsol. resp)
23 6 16-Bit Frozen Counter Event with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited qty) 130 (unsol. resp)
30 0 Analog Input - Any Variation 1 (read) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
30 1 32-Bit Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
30 2 16-Bit Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
30 3 32-Bit Analog Input without Flag 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(default – 06 (no range, or all) 17, 28 (index –
see note 1) see note 2)
07, 08 (limited qty)
17, 27, 28 (index)

9 www.qualitrolcorp.com
REQUEST RESPONSE
OBJECT
(Library will parse) (Library will respond with)
Object Variation Function Qualifier Codes Function Qualifier Codes
Description
Number Number Codes (dec) (hex) Codes (dec) (hex)
30 4 16-Bit Analog Input without Flag 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
30 5 short floating point 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
30 6 long floating point 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 1)
17, 27, 28 (index)
32 0 Analog Change Event – Any Variation 1 (read) 06 (no range, or all)
07, 08 (limited qty)
32 1 32-Bit Analog Change Event without 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
(default – Time 07, 08 (limited qty) 130 (unsol. resp)
see note 1)
32 2 16-Bit Analog Change Event without 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Time 07, 08 (limited qty) 130 (unsol. resp)
32 3 32-Bit Analog Change Event with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited qty) 130 (unsol. resp)
32 4 16-Bit Analog Change Event with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited qty) 130 (unsol. resp)
32 5 short floating point Analog Change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Event without Time 07, 08 (limited qty) 130 (unsol. resp)
32 6 long floating point Analog Change Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
without Time 07, 08 (limited qty) 130 (unsol. resp)
32 7 short floating point Analog Change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Event with Time 07, 08 (limited qty) 130 (unsol. resp)
32 8 long floating point Analog Change Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
with Time 07, 08 (limited qty) 130 (unsol. resp)
34 0 Analog Input Deadband (Variation 0 is 1 (read) 00, 01 (start-stop)
used to request default variation) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
34 1 16 bit Analog Input Deadband 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
2 00, 01 (start-stop)
(write) 07, 08 (limited qty)
17, 27, 28 (index)
34 2 32 bit Analog Input Deadband 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(default – 06 (no range, or all) 17, 28 (index –
see note 1) see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
2 00, 01 (start-stop)
(write) 07, 08 (limited qty)
17, 27, 28 (index)
34 3 Short Floating Point Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Deadband 06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
2 00, 01 (start-stop)
(write) 07, 08 (limited qty)
17, 27, 28 (index)
40 0 Analog Output Status 1 (read) 00, 01 (start-stop)
22 (assign 06 (no range, or all)
class) 07, 08 (limited qty)
17, 27, 28 (index)
40 1 32-Bit Analog Output Status 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)

10 www.qualitrolcorp.com
REQUEST RESPONSE
OBJECT
(Library will parse) (Library will respond with)
Object Variation Function Qualifier Codes Function Qualifier Codes
Description
Number Number Codes (dec) (hex) Codes (dec) (hex)
40 2 16-Bit Analog Output Status 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(default – 06 (no range, or all) 17, 28 (index –
see note 1 see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
40 3 short floating point Analog Output Status 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
40 4 long floating point Analog Output Status 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
41 0 Analog Output Block 22 (assign 00, 01 (start-stop)
class) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
41 1 32-Bit Analog Output Block 3 (select) 17, 28 (index) 129 (response) echo of request
4 (operate) 27 (index)
5 (direct op)
6 (dir. op, noack)
41 2 16-Bit Analog Output Block 3 (select) 17, 28 (index) 129 (response) echo of request
4 (operate) 27 (index)
5 (direct op)
6 (dir. op, noack)
41 3 short floating point Analog Output Block 3 (select) 17, 27, 28 (index) 129 (response) echo of request
4 (operate)
5 (direct op)
6 (dir. op, noack)
41 4 long floating point Analog Output Block 3 (select) 17, 27, 28 (index) 129 (response) echo of request
4 (operate)
5 (direct op)
6 (dir. op, noack)
42 0 Analog Output Event – Any Variation 1 (read) 06 (no range, or all)
07, 08 (limited qty)
42 1 32-Bit Analog Output Event without 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Time 07, 08 (limited qty) 130 (unsol. resp)
42 2 16-Bit Analog Output Event without 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
(default – Time 07, 08 (limited qty) 130 (unsol. resp)
see note 1
42 3 32-Bit Analog Output Event with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited qty) 130 (unsol. resp)
42 4 16-Bit Analog Output Event with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited qty) 130 (unsol. resp)
42 5 short floating point Analog Output Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
without Time 07, 08 (limited qty) 130 (unsol. resp)
42 6 long floating point Analog Output Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
without Time 07, 08 (limited qty) 130 (unsol. resp)
42 7 short floating point Analog Output Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
with Time 07, 08 (limited qty) 130 (unsol. resp)
42 8 long floating point Analog Output Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
with Time 07, 08 (limited qty) 130 (unsol. resp)
43 0 Analog Output Command Event – Any 1 (read) 06 (no range, or all)
Variation 07, 08 (limited qty)
43 1 32-Bit Analog Output Command Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
without Time 07, 08 (limited qty) 130 (unsol. resp)
43 2 16-Bit Analog Output Command Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
(default – without Time 07, 08 (limited qty) 130 (unsol. resp)
see note 1
43 3 32-Bit Analog Output Command Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
with Time 07, 08 (limited qty) 130 (unsol. resp)
43 4 16-Bit Analog Output Command Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
with Time 07, 08 (limited qty) 130 (unsol. resp)
43 5 short floating point Analog Output 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Command Event without Time 07, 08 (limited qty) 130 (unsol. resp)

11 www.qualitrolcorp.com
REQUEST RESPONSE
OBJECT
(Library will parse) (Library will respond with)
Object Variation Function Qualifier Codes Function Qualifier Codes
Description
Number Number Codes (dec) (hex) Codes (dec) (hex)
43 6 long floating point Analog Output 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Command Event without Time 07, 08 (limited qty) 130 (unsol. resp)
43 7 short floating point Analog Output 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Command Event with Time 07, 08 (limited qty) 130 (unsol. resp)
43 8 long floating point Analog Output 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Command Event with Time 07, 08 (limited qty) 130 (unsol. resp)
50 0 Time and Date

50 1 Time and Date 1 (read) 07, (limited qty = 1) 129 (response) 07 (limited qty = 1)
(default –
see note 1)

2 (write) 07 (limited qty = 1)

50 3 Time and Date Last Recorded Time 2 07 (limited qty)


(write)

51 1 Time and Date CTO 129 (response) 07 (limited qty)


130 (unsol. resp) (qty = 1)
51 2 Unsynchronized Time and Date CTO 129 (response) 07 (limited qty)
130 (unsol. resp) (qty = 1)

52 1 Time Delay Coarse 129 (response) 07 (limited qty)


(qty = 1)
52 2 Time Delay Fine 129 (response) 07 (limited qty)
(qty = 1)
60 0 Not Defined
60 1 Class 0 Data 1 (read) 06 (no range, or all)
60 2 Class 1 Data 1 (read) 06 (no range, or all)
07, 08 (limited qty)
20 (enbl. unsol.) 06 (no range, or all)
21 (dab. unsol.)
22 (assign class)
60 3 Class 2 Data 1 (read) 06 (no range, or all)
07, 08 (limited qty)

20 (enbl. unsol.) 06 (no range, or all)


21 (dab. unsol.)
22 (assign class)
60 4 Class 3 Data 1 (read) 06 (no range, or all)
07, 08 (limited qty)
20 (enbl. unsol.) 06 (no range, or all)
21 (dab. unsol.)
22 (assign class)
70 0 File Event – Any Variation 1 06 (no range, or all)
(read) 07, 08 (limited qty)
22 (assign 06 (no range, or all)
class)

70 2 File Authentication 29 5b (free-format) 129 (response) 5B (free-format)


(authenticate)

70 3 File Command 25 5b (free-format)


(open)
27
(delete)
70 4 File Command Status 26 5b (free-format) 129 (response) 5B (free-format)
(close) 130 (unsol. resp)
30 (abort)
70 5 File Transfer 1 5b (free-format) 129 (response) 5B (free-format)
(read) 130 (unsol. resp)
2
(write)

70 6 File Transfer Status 129 (response) 5B (free-format)


130 (unsol. resp)

12 www.qualitrolcorp.com
REQUEST RESPONSE
OBJECT
(Library will parse) (Library will respond with)
Object Variation Function Qualifier Codes Function Qualifier Codes
Description
Number Number Codes (dec) (hex) Codes (dec) (hex)
70 7 File Descriptor 28 (get file 5b (free-format) 129 (response) 5B (free-format)
info) 130 (unsol. resp)
70 8 File Specification String 31(activate 5b (free-format)
config)
80 1 Internal Indications 1 (read) 00, 01 (start-stop) 129 (response) 00, 01(start-stop)

2 (write) 00 (start-stop)
(see note 3) index=4 or 7
85 0 Data Set Prototype 1 00, 01 (start-stop)
(read) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index
85 1 Data Set Prototype 1 00, 01 (start-stop) 129 (response) 5B (free-format)
(read) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index
2 (write) 5b (free-format)

86 0 Data Set Descriptor 22 (assign class) 00, 01 (start-stop)


06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index
86 1 Data Set Descriptor - Contents 1 00, 01 (start-stop) 129 (response) 5B (free-format)
(read) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index
2 (write) 5b (free-format)

86 2 Data Set Descriptor – Characteristics 1 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(read) 06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index
86 3 Data Set Descriptor – Point Index 1 00, 01 (start-stop) 129 (response) 5B (free-format)
Attributes (read) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index
2 (write) 5b (free-format)

87 0 Data Set – Present Value 1 00, 01 (start-stop)


(read) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index
87 1 Data Set – Present Value 1 00, 01 (start-stop) 129 (response) 5B (free-format)
(read) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index
2 (write) 5b (free-format)

88 0 Data Set Event 1 06 (no range, or all)


(read) 07, 08 (limited qty)

88 1 Data Set Event - Snapshot 1 06 (no range, or all) 129 (response) 5B (free-format)
(read) 07, 08 (limited qty) 130 (unsol. resp)

91 1 Activate Status 129 (response) 07 (limited qty)

110 string Octet String Object 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
length 22 (assign class) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index
2 (write) 00, 01 (start-stop)
07, 08 (limited qty)
17, 27, 28 (index)
111 string Octet String Event Object 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
length 07, 08 (limited qty) 130 (unsol. resp)

13 www.qualitrolcorp.com
REQUEST RESPONSE
OBJECT
(Library will parse) (Library will respond with)
Object Variation Function Qualifier Codes Function Qualifier Codes
Description
Number Number Codes (dec) (hex) Codes (dec) (hex)
112 string Virtual Terminal Output Block 2 (write) 00, 01 (start-stop)
length 07, 08 (limited qty)
17, 27, 28 (index)
113 string Virtual Terminal Event Data 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
length 07, 08 (limited qty) 130 (unsol. resp)
120 1 Authentication Challenge 32 (auth 5b (free-format) 131 (challenge) 5b (free-format)
challenge) 132(unsol. challenge
120 2 Authentication Reply 33 (auth reply) 5b (free-format) 129 (response) 5b (free-format)
120 3 Authentication Aggressive Mode 5b (free-format) 131 (challenge) 5b (free-format)
Request 132(unsol. challenge
120 4 Authentication Session Key Status 1 (read) 5b (free-format)
Request
120 5 Authentication Session Key Status 129 (response) 5b (free-format)
120 6 Authentication Session Key Change 129 (response) 5b (free-format)
120 7 Authentication Error 34 (auth 5b (free-format) 129 (response) 5b (free-format)
challenge)
No Object (function code only) 13 (cold restart)
No Object (function code only) 14 (warm restart)
No Object (function code only) 23 (delay meas.)
No Object (function code only) 24
(record current
time)

Note 1: A Default variation refers to the variation responded when variation 0 is requested and/or in
class 0, 1, 2, or 3 scans. Default variations are configurable; however, default settings for the
configuration parameters are indicated in the table above.
Note 2: For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request
is sent with qualifiers 17 or 28, respectively. Otherwise, static object requests sent with qualifiers 00,
01, 06, 07, or 08, will be responded with qualifiers 00 or 01. (For change-event objects, qualifiers 17
or 28 are always responded.)
Note 3: Writes of Internal Indications are only supported for index 4 or 7 (Need Time IIN1-4 or
Restart IIN1-7)

DNP V3.0 Point List


The tables below identify all the default data points provided by the implementation of the DNP 3.0
Slave Source Code Library.

Binary Input Points


The default binary input event buffer size is set to allow 100 events.

BINARY INPUT; OBJ 1; VAR 0, 1, 2


POINT POINT VARIABLE DESCRIPTION
0 RELAY 1 ENABLED 1 = ENABLED; 0 = DISABLED
1 RELAY 2 ENABLED 1 = ENABLED; 0 = DISABLED
2 RELAY 3 ENABLED 1 = ENABLED; 0 = DISABLED
3 RELAY 4 ENABLED 1 = ENABLED; 0 = DISABLED
4 RELAY 5 ENABLED 1 = ENABLED; 0 = DISABLED
5 RELAY 6 ENABLED 1 = ENABLED; 0 = DISABLED
6 RELAY 7 ENABLED 1 = ENABLED; 0 = DISABLED
7 RELAY 8 ENABLED 1 = ENABLED; 0 = DISABLED
8 RELAY 1 ACTUATED 1 = ACTUATED; 0 = NOT ACTUATED

14 www.qualitrolcorp.com
BINARY INPUT; OBJ 1; VAR 0, 1, 2
POINT POINT VARIABLE DESCRIPTION
9 RELAY 2 ACTUATED 1 = ACTUATED; 0 = NOT ACTUATED
10 RELAY 3 ACTUATED 1 = ACTUATED; 0 = NOT ACTUATED
11 RELAY 4 ACTUATED 1 = ACTUATED; 0 = NOT ACTUATED
12 RELAY 5 ACTUATED 1 = ACTUATED; 0 = NOT ACTUATED
13 RELAY 6 ACTUATED 1 = ACTUATED; 0 = NOT ACTUATED
14 RELAY 7 ACTUATED 1 = ACTUATED; 0 = NOT ACTUATED
15 RELAY 8 ACTUATED 1 = ACTUATED; 0 = NOT ACTUATED
16 SYSTEM STATUS RELAY 1 = ACTUATED; 0 = NOT ACTUATED
17 HEATER STATUS 1 = ENABLED; 0 = DISABLED
18 RELAY 1 LATCHING FEATURE 1 = ENABLED; 0 = DISABLED
19 RELAY 2 LATCHING FEATURE 1 = ENABLED; 0 = DISABLED
20 RELAY 3 LATCHING FEATURE 1 = ENABLED; 0 = DISABLED
21 RELAY 4 LATCHING FEATURE 1 = ENABLED; 0 = DISABLED
22 RELAY 5 LATCHING FEATURE 1 = ENABLED; 0 = DISABLED
23 RELAY 6 LATCHING FEATURE 1 = ENABLED; 0 = DISABLED
24 RELAY 7 LATCHING FEATURE 1 = ENABLED; 0 = DISABLED
25 RELAY 8 LATCHING FEATURE 1 = ENABLED; 0 = DISABLED
26 RELAY 1 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
27 RELAY 2 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
28 RELAY 3 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
29 RELAY 4 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
30 RELAY 5 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
31 RELAY 6 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
32 RELAY 7 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
33 RELAY 8 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
34 EVENT RECORD 1 1 = TRIGGERED; 0 = NOT TRIGGERED
35 EVENT RECORD 2 1 = TRIGGERED; 0 = NOT TRIGGERED
36 EVENT RECORD 3 1 = TRIGGERED; 0 = NOT TRIGGERED
37 EVENT RECORD 4 1 = TRIGGERED; 0 = NOT TRIGGERED
38 EVENT RECORD 5 1 = TRIGGERED; 0 = NOT TRIGGERED
39 EVENT RECORD 6 1 = TRIGGERED; 0 = NOT TRIGGERED
40 EVENT RECORD 7 1 = TRIGGERED; 0 = NOT TRIGGERED
41 EVENT RECORD 8 1 = TRIGGERED; 0 = NOT TRIGGERED
42 INPUT MODULE 1 READ ERROR 1 = ERROR DURING READ; 0 = VALID READ
43 INPUT MODULE 2 READ ERROR 1 = ERROR DURING READ; 0 = VALID READ
44 INPUT MODULE 3 READ ERROR 1 = ERROR DURING READ; 0 = VALID READ
45 INPUT MODULE 4 READ ERROR 1 = ERROR DURING READ; 0 = VALID READ
46 INPUT MODULE 5 READ ERROR 1 = ERROR DURING READ; 0 = VALID READ
47 INPUT MODULE 6 READ ERROR 1 = ERROR DURING READ; 0 = VALID READ
48 INPUT MODULE 7 READ ERROR 1 = ERROR DURING READ; 0 = VALID READ
49 INPUT MODULE 8 READ ERROR 1 = ERROR DURING READ; 0 = VALID READ
50 INPUT MODULE 1 SCALING FEATURE ENABLED 1 = ACTIVE; 0 = NOT ACTIVE
51 INPUT MODULE 2 SCALING FEATURE ENABLED 1 = ACTIVE; 0 = NOT ACTIVE
52 INPUT MODULE 3 SCALING FEATURE ENABLED 1 = ACTIVE; 0 = NOT ACTIVE
53 INPUT MODULE 4 SCALING FEATURE ENABLED 1 = ACTIVE; 0 = NOT ACTIVE
54 INPUT MODULE 5 SCALING FEATURE ENABLED 1 = ACTIVE; 0 = NOT ACTIVE
55 INPUT MODULE 6 SCALING FEATURE ENABLED 1 = ACTIVE; 0 = NOT ACTIVE

15 www.qualitrolcorp.com
BINARY INPUT; OBJ 1; VAR 0, 1, 2
POINT POINT VARIABLE DESCRIPTION
56 INPUT MODULE 7 SCALING FEATURE ENABLED 1 = ACTIVE; 0 = NOT ACTIVE
57 INPUT MODULE 8 SCALING FEATURE ENABLED 1 = ACTIVE; 0 = NOT ACTIVE
58 INPUT MODULE 9 READ ERROR 1 = ERROR DURING READ; 0 = VALID READ
59 INPUT MODULE 10 READ ERROR 1 = ERROR DURING READ; 0 = VALID READ
60 INPUT MODULE 11 READ ERROR 1 = ERROR DURING READ; 0 = VALID READ
61 INPUT MODULE 12 READ ERROR 1 = ERROR DURING READ; 0 = VALID READ
62 INPUT MODULE 13 READ ERROR 1 = ERROR DURING READ; 0 = VALID READ
63 INPUT MODULE 14 READ ERROR 1 = ERROR DURING READ; 0 = VALID READ
64 INPUT MODULE 15 READ ERROR 1 = ERROR DURING READ; 0 = VALID READ
65 INPUT MODULE 16 READ ERROR 1 = ERROR DURING READ; 0 = VALID READ
66 INPUT MODULE 9 SCALING FEATURE ENABLED 1 = ACTIVE; 0 = NOT ACTIVE
67 INPUT MODULE 10 SCALING FEATURE ENABLED 1 = ACTIVE; 0 = NOT ACTIVE
68 INPUT MODULE 11 SCALING FEATURE ENABLED 1 = ACTIVE; 0 = NOT ACTIVE
69 INPUT MODULE 12 SCALING FEATURE ENABLED 1 = ACTIVE; 0 = NOT ACTIVE
70 INPUT MODULE 13 SCALING FEATURE ENABLED 1 = ACTIVE; 0 = NOT ACTIVE
71 INPUT MODULE 14 SCALING FEATURE ENABLED 1 = ACTIVE; 0 = NOT ACTIVE
72 INPUT MODULE 15 SCALING FEATURE ENABLED 1 = ACTIVE; 0 = NOT ACTIVE
73 INPUT MODULE 16 SCALING FEATURE ENABLED 1 = ACTIVE; 0 = NOT ACTIVE

Binary Output Status Points


The following table lists the Binary Output Status Points (Object 10).
While Binary Output Status Points are included here for completeness, they are not often polled by
DNP 3.0 Masters. It is recommended that Binary Output Status points represent the most recent
DNP “commanded” value for the corresponding Control Relay Output Block point. Because many, if
not most, Control Relay Output Block points are controlled through pulse mechanisms, the value of
the output status may in fact be meaningless. Binary Output Status points are not recommended to
be included in class 0 polls.
As an alternative, it is recommended that “actual” status values of Control Relay Output Block points
be looped around and mapped as Binary Inputs. (The “actual” status value, as opposed to the
“commanded” status value, is the value of the actuated control. For example, a DNP control
command may be blocked through hardware or software mechanisms; in this case, the actual status
value would indicate the control failed because of the blocking. Looping Control Relay Output Block
actual status values as Binary Inputs has several advantages:
 it allows actual statuses to be included in class 0 polls,
 it allows change event reporting of the actual statuses, which is a more efficient and time-
accurate method of communicating control values,
 and it allows reporting of time-based information associated with controls, including any delays
before controls are actuated, and any durations if the controls are pulsed.
The default select/control buffer size is large enough to hold 10 of the largest select requests
possible.

BINARY OUTPUT; OBJ 10; VAR 0, 1, 2


POINT POINT VARIABLE DESCRIPTION
0 RELAY 1 ENABLED 1 = ENABLED; 0 = DISABLED
1 RELAY 2 ENABLED 1 = ENABLED; 0 = DISABLED
2 RELAY 3 ENABLED 1 = ENABLED; 0 = DISABLED

16 www.qualitrolcorp.com
BINARY OUTPUT; OBJ 10; VAR 0, 1, 2
POINT POINT VARIABLE DESCRIPTION
3 RELAY 4 ENABLED 1 = ENABLED; 0 = DISABLED
4 RELAY 5 ENABLED 1 = ENABLED; 0 = DISABLED
5 RELAY 6 ENABLED 1 = ENABLED; 0 = DISABLED
6 RELAY 7 ENABLED 1 = ENABLED; 0 = DISABLED
7 RELAY 8 ENABLED 1 = ENABLED; 0 = DISABLED
8 INPUT MODULE MAX/MIN RESET PULSE/RESET (1)
9 RELAY 1 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
10 RELAY 2 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
11 RELAY 3 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
12 RELAY 4 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
13 RELAY 5 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
14 RELAY 6 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
15 RELAY 7 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
16 RELAY 8 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
17 LATCHED RELAYS RESET PULSE/RESET (1)
18 COOLING MONITOR MAX/MIN RESET PULSE/RESET (1)
19 INPUT MODULE 1 ENABLED 1 = ENABLED; 0 = DISABLED
20 INPUT MODULE 2 ENABLED 1 = ENABLED; 0 = DISABLED
21 INPUT MODULE 3 ENABLED 1 = ENABLED; 0 = DISABLED
22 INPUT MODULE 4 ENABLED 1 = ENABLED; 0 = DISABLED
23 INPUT MODULE 5 ENABLED 1 = ENABLED; 0 = DISABLED
24 INPUT MODULE 6 ENABLED 1 = ENABLED; 0 = DISABLED
25 INPUT MODULE 7 ENABLED 1 = ENABLED; 0 = DISABLED
26 INPUT MODULE 8 ENABLED 1 = ENABLED; 0 = DISABLED
27 INPUT MODULE 9 ENABLED 1 = ENABLED; 0 = DISABLED
28 INPUT MODULE 10 ENABLED 1 = ENABLED; 0 = DISABLED
29 INPUT MODULE 11 ENABLED 1 = ENABLED; 0 = DISABLED
30 INPUT MODULE 12 ENABLED 1 = ENABLED; 0 = DISABLED
31 INPUT MODULE 13 ENABLED 1 = ENABLED; 0 = DISABLED
32 INPUT MODULE 14 ENABLED 1 = ENABLED; 0 = DISABLED
33 INPUT MODULE 15 ENABLED 1 = ENABLED; 0 = DISABLED
34 INPUT MODULE 16 ENABLED 1 = ENABLED; 0 = DISABLED

Counters
The following table lists both Binary Counters (Object 20) and Frozen Counters (Object 21). When a
freeze function is performed on a Binary Counter point, the frozen value is available in the
corresponding Frozen Counter point. The default Binary Counter and Frozen Counter event buffer
sizes are set to 30.

BINARY COUNTER; OBJ 20; VAR 0, 1, 2, 3, 4, 5, 6


POINT POINT VARIABLE DESCRIPTION
TRANSLIFE 1; TRANSFORMER LIFE TOTAL LIFE CONSUMPTION CALCULATED; TRANSLIFE
0 CONSUMPTION 1
TRANSLIFE 2; TRANSFORMER LIFE TOTAL LIFE CONSUMPTION CALCULATED; TRANSLIFE
1 CONSUMPTION 2
TRANSLIFE 3; TRANSFORMER LIFE TOTAL LIFE CONSUMPTION CALCULATED; TRANSLIFE
2 CONSUMPTION 3
3 TOTAL TRANSFORMER OPERATING HOURS CUMULATIVE TRANSFORMER OPERATING HOURS

17 www.qualitrolcorp.com
Analog Inputs
The following table lists Analog Inputs (Object 30). It is important to note that 16-bit and 32-bit
variations of Analog Inputs, Analog Output Control Blocks, and Analog Output Statuses are
transmitted through DNP as signed numbers.
The “Default Deadband,” and the “Default Change Event Assigned Class” columns are used to
represent the absolute amount by which the point must change before an analog change event will be
generated, and once generated in which class poll (1, 2, 3, or none) will the change event be
reported.
The default analog input event buffer size is set 30.

ANALOG INPUT; OBJ 30; VAR 0, 1, 2, 3, 4, 5, 6


POINT POINT VARIABLE DESCRIPTION
0 RELAY 1, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
1 RELAY 2, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
2 RELAY 3, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
3 RELAY 4, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
4 RELAY 5, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
5 RELAY 6, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
6 RELAY 7, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
7 RELAY 8, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
8 RELAY 1, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
9 RELAY 2, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
10 RELAY 3, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
11 RELAY 4, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
12 RELAY 5, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
13 RELAY 6, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
14 RELAY 7, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
15 RELAY 8, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX

ALL MODULES BUT CT, WINDING TEMPERATURE IF THE MODULE IS A CT, WINDING TEMPERATURE
16 INPUT MODULE 1 PRESENT VALUE OR INPUT MODULE 1 PRESENT WINDING TEMP
17 INPUT MODULE 1 MINIMUM VALUE OR INPUT MODULE 1 MINIMUM WINDING TEMP
18 INPUT MODULE 1 MAXIMUM VALUE OR INPUT MODULE 1 MAXIMUM WINDING TEMP
19 0 OR INPUT MODULE 1 PRESENT CURRENT
20 0 OR INPUT MODULE 1 MAXIMUM CURRENT
21 INPUT MODULE 2 PRESENT VALUE OR INPUT MODULE 2 PRESENT WINDING TEMP
22 INPUT MODULE 2 MINIMUM VALUE OR INPUT MODULE 2 MINIMUM WINDING TEMP
23 INPUT MODULE 2 MAXIMUM VALUE OR INPUT MODULE 2 MAXIMUM WINDING TEMP
24 0 OR INPUT MODULE 2 PRESENT CURRENT
25 0 OR INPUT MODULE 2 MAXIMUM CURRENT
26 INPUT MODULE 3 PRESENT VALUE OR INPUT MODULE 3 PRESENT WINDING TEMP
27 INPUT MODULE 3 MINIMUM VALUE OR INPUT MODULE 3 MINIMUM WINDING TEMP
28 INPUT MODULE 3 MAXIMUM VALUE OR INPUT MODULE 3 MAXIMUM WINDING TEMP
29 0 OR INPUT MODULE 3 PRESENT CURRENT
30 0 OR INPUT MODULE 3 MAXIMUM CURRENT
31 INPUT MODULE 4 PRESENT VALUE OR INPUT MODULE 4 PRESENT WINDING TEMP
32 INPUT MODULE 4 MINIMUM VALUE OR INPUT MODULE 4 MINIMUM WINDING TEMP
33 INPUT MODULE 4 MAXIMUM VALUE OR INPUT MODULE 4 MAXIMUM WINDING TEMP

18 www.qualitrolcorp.com
ANALOG INPUT; OBJ 30; VAR 0, 1, 2, 3, 4, 5, 6
POINT POINT VARIABLE DESCRIPTION
34 0 OR INPUT MODULE 4 PRESENT CURRENT
35 0 OR INPUT MODULE 4 MAXIMUM CURRENT
36 INPUT MODULE 5 PRESENT VALUE OR INPUT MODULE 5 PRESENT WINDING TEMP
37 INPUT MODULE 5 MINIMUM VALUE OR INPUT MODULE 5 MINIMUM WINDING TEMP
38 INPUT MODULE 5 MAXIMUM VALUE OR INPUT MODULE 5 MAXIMUM WINDING TEMP
39 0 OR INPUT MODULE 5 PRESENT CURRENT
40 0 OR INPUT MODULE 5 MAXIMUM CURRENT
41 INPUT MODULE 6 PRESENT VALUE OR INPUT MODULE 6 PRESENT WINDING TEMP
42 INPUT MODULE 6 MINIMUM VALUE OR INPUT MODULE 6 MINIMUM WINDING TEMP
43 INPUT MODULE 6 MAXIMUM VALUE OR INPUT MODULE 6 MAXIMUM WINDING TEMP
44 0 OR INPUT MODULE 6 PRESENT CURRENT
45 0 OR INPUT MODULE 6 MAXIMUM CURRENT
46 INPUT MODULE 7 PRESENT VALUE OR INPUT MODULE 7 PRESENT WINDING TEMP
47 INPUT MODULE 7 MINIMUM VALUE OR INPUT MODULE 7 MINIMUM WINDING TEMP
48 INPUT MODULE 7 MAXIMUM VALUE OR INPUT MODULE 7 MAXIMUM WINDING TEMP
49 0 OR INPUT MODULE 7 PRESENT CURRENT
50 0 OR INPUT MODULE 7 MAXIMUM CURRENT
51 INPUT MODULE 8 PRESENT VALUE OR INPUT MODULE 8 PRESENT WINDING TEMP
52 INPUT MODULE 8 MINIMUM VALUE OR INPUT MODULE 8 MINIMUM WINDING TEMP
53 INPUT MODULE 8 MAXIMUM VALUE OR INPUT MODULE 8 MAXIMUM WINDING TEMP
54 0 OR INPUT MODULE 8 PRESENT CURRENT
55 0 OR INPUT MODULE 8 MAXIMUM CURRENT
56 DIFFERENTIAL CALCULATION 1 PRESENT VALUE
57 DIFFERENTIAL CALCULATION 1 MINIMUM VALUE
58 DIFFERENTIAL CALCULATION 1 MAXIMUM VALUE
59 DIFFERENTIAL CALCULATION 2 PRESENT VALUE
60 DIFFERENTIAL CALCULATION 2 MINIMUM VALUE
61 DIFFERENTIAL CALCULATION 2 MAXIMUM VALUE
62 DIFFERENTIAL CALCULATION 3 PRESENT VALUE
63 DIFFERENTIAL CALCULATION 3 MINIMUM VALUE
64 DIFFERENTIAL CALCULATION 3 MAXIMUM VALUE
65 DIFFERENTIAL CALCULATION 4 PRESENT VALUE
66 DIFFERENTIAL CALCULATION 4 MINIMUM VALUE
67 DIFFERENTIAL CALCULATION 4 MAXIMUM VALUE
68 HOTTEST PRESENT WINDING TEMPERATURE OF ALL ACTIVE CT, TEMPERATURE MODULES
69 RELAY 1, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
70 RELAY 2, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
71 RELAY 3, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
72 RELAY 4, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
73 RELAY 5, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
74 RELAY 6, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
75 RELAY 7, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
76 RELAY 8, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
77 RELAY 1, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
78 RELAY 2, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
79 RELAY 3, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
80 RELAY 4, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX

19 www.qualitrolcorp.com
ANALOG INPUT; OBJ 30; VAR 0, 1, 2, 3, 4, 5, 6
POINT POINT VARIABLE DESCRIPTION
81 RELAY 5, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
82 RELAY 6, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
83 RELAY 7, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
84 RELAY 8, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
85 RELAY 1, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
86 RELAY 2, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
87 RELAY 3, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
88 RELAY 4, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
89 RELAY 5, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
90 RELAY 6, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
91 RELAY 7, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
92 RELAY 8, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
93 RELAY 1, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
94 RELAY 2, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
95 RELAY 3, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
96 RELAY 4, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
97 RELAY 5, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
98 RELAY 6, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
99 RELAY 7, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
100 RELAY 8, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
101 RELAY 1, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
102 RELAY 2, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
103 RELAY 3, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
104 RELAY 4, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
105 RELAY 5, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
106 RELAY 6, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
107 RELAY 7, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
108 RELAY 8, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
109 RELAY 1, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
110 RELAY 2, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
111 RELAY 3, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
112 RELAY 4, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
113 RELAY 5, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
114 RELAY 6, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
115 RELAY 7, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
116 RELAY 8, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
117 TRANSLIFE 1 CONSUMED LIFE FOR LAST HOUR CALCULATED CONSUMED LIFE FOR LAST HOUR
118 TRANSLIFE 1 CONSUMED LIFE FOR LAST DAY CALCULATED CONSUMED LIFE FOR LAST DAY
119 TRANSLIFE 1 REMAINING TRANSFORMER LIFE (20 YEARS - CONSUMED LIFE)
120 TL1 CRITICAL WINDING TEMP SETPOINT 1 1ST CRITICAL SPT TO CALCULATE TIME TO REACH
121 TL1 CRITICAL WINDING TEMP SETPOINT 2 2ND CRITICAL SPT TO CALCULATE TIME TO REACH
122 TL1 CRITICAL WINDING TEMP SETPOINT 3 3RD CRITICAL SPT TO CALCULATE TIME TO REACH
CALCULATED TIME TO 1ST SPT FOR GIVEN
123 TL1 TIME TO CRITICAL SETPOINT 1 CONDITIONS
CALCULATED TIME TO 2ND SPT FOR GIVEN
124 TL1 TIME TO CRITICAL SETPOINT 2 CONDITIONS
CALCULATED TIME TO 3RD SPT FOR GIVEN
125 TL1 TIME TO CRITICAL SETPOINT 3 CONDITIONS

20 www.qualitrolcorp.com
ANALOG INPUT; OBJ 30; VAR 0, 1, 2, 3, 4, 5, 6
POINT POINT VARIABLE DESCRIPTION
126 TRANSLIFE 2 CONSUMED LIFE FOR LAST HOUR CALCULATED CONSUMED LIFE FOR LAST HOUR
127 TRANSLIFE 2 CONSUMED LIFE FOR LAST DAY CALCULATED CONSUMED LIFE FOR LAST DAY
128 TRANSLIFE 2 REMAINING TRANSFORMER LIFE (20 YEARS - CONSUMED LIFE)
129 TL2 CRITICAL WINDING TEMP SETPOINT 1 1ST CRITICAL SPT TO CALCULATE TIME TO REACH
130 TL2 CRITICAL WINDING TEMP SETPOINT 2 2ND CRITICAL SPT TO CALCULATE TIME TO REACH
131 TL2 CRITICAL WINDING TEMP SETPOINT 3 3RD CRITICAL SPT TO CALCULATE TIME TO REACH
CALCULATED TIME TO 1ST SPT FOR GIVEN
132 TL2 TIME TO CRITICAL SETPOINT 1 CONDITIONS
CALCULATED TIME TO 2ND SPT FOR GIVEN
133 TL2 TIME TO CRITICAL SETPOINT 2 CONDITIONS
CALCULATED TIME TO 3RD SPT FOR GIVEN
134 TL2 TIME TO CRITICAL SETPOINT 3 CONDITIONS
135 TRANSLIFE 3 CONSUMED LIFE FOR LAST HOUR CALCULATED CONSUMED LIFE FOR LAST HOUR
136 TRANSLIFE 3 CONSUMED LIFE FOR LAST DAY CALCULATED CONSUMED LIFE FOR LAST DAY
137 TRANSLIFE 3 REMAINING TRANSFORMER LIFE (20 YEARS - CONSUMED LIFE)
138 TL3 CRITICAL WINDING TEMP SETPOINT 1 1ST CRITICAL SPT TO CALCULATE TIME TO REACH
139 TL3 CRITICAL WINDING TEMP SETPOINT 2 2ND CRITICAL SPT TO CALCULATE TIME TO REACH
140 TL3 CRITICAL WINDING TEMP SETPOINT 3 3RD CRITICAL SPT TO CALCULATE TIME TO REACH
CALCULATED TIME TO 1ST SPT FOR GIVEN
141 TL3 TIME TO CRITICAL SETPOINT 1 CONDITIONS
CALCULATED TIME TO 2ND SPT FOR GIVEN
142 TL3 TIME TO CRITICAL SETPOINT 2 CONDITIONS
CALCULATED TIME TO 3RD SPT FOR GIVEN
143 TL3 TIME TO CRITICAL SETPOINT 3 CONDITIONS
144 COOLING BANK 1 PRESENT RUNNING CURRENT COOLING BANK 1 PRESENT/STEADY STATE CURRENT
145 COOLING BANK 1 MINIMUM RUNNING CURRENT COOLING BANK 1 MINIMUM STEADY STATE CURRENT
146 COOLING BANK 1 MAXIMUM RUNNING CURRENT COOLING BANK 1 MAXIMUM STEADY STATE CURRENT
147 CB1 RUNNING CURRENT UPPER SETPOINT COOLING BANK 1 STEADY STATE CURRENT SETPOINT
148 CB1 RUNNING CURRENT LOWER SETPOINT COOLING BANK 1 STEADY STATE CURRENT SETPOINT
149 CB1 PRESENT PEAK INRUSH CURRENT VALUE COOLING BANK 1 PRESENT PEAK INRUSH CURRENT
150 CB1 MINIMUM PEAK INRUSH CURRENT VALUE COOLING BANK 1 MINIMUM PEAK INRUSH CURRENT
151 CB1 MAXIMUM PEAK INRUSH CURRENT VALUE COOLING BANK 1 MAXIMUM PEAK INRUSH CURRENT
152 CB1 INRUSH CURRENT UPPER SETPOINT VALUE COOLING BANK 1 PEAK INRUSH CURRENT SETPOINT
153 CB1 INRUSH CURRENT LOWER SETPOINT VALUE COOLING BANK 1 PEAK INRUSH CURRENT SETPOINT
154 COOLING BANK 2 PRESENT RUNNING CURRENT COOLING BANK 2 PRESENT/STEADY STATE CURRENT
155 COOLING BANK 2 MINIMUM RUNNING CURRENT COOLING BANK 2 MINIMUM STEADY STATE CURRENT
156 COOLING BANK 2 MAXIMUM RUNNING CURRENT COOLING BANK 2 MAXIMUM STEADY STATE CURRENT
157 CB2 RUNNING CURRENT UPPER SETPOINT COOLING BANK 2 STEADY STATE CURRENT SETPOINT
158 CB2 RUNNING CURRENT LOWER SETPOINT COOLING BANK 2 STEADY STATE CURRENT SETPOINT
159 CB2 PRESENT PEAK INRUSH CURRENT VALUE COOLING BANK 2 PRESENT PEAK INRUSH CURRENT
160 CB2 MINIMUM PEAK INRUSH CURRENT VALUE COOLING BANK 2 MINIMUM PEAK INRUSH CURRENT
161 CB2 MAXIMUM PEAK INRUSH CURRENT VALUE COOLING BANK 2 MAXIMUM PEAK INRUSH CURRENT
162 CB2 INRUSH CURRENT UPPER SETPOINT VALUE COOLING BANK 2 PEAK INRUSH CURRENT SETPOINT
163 CB2 INRUSH CURRENT LOWER SETPOINT VALUE COOLING BANK 2 PEAK INRUSH CURRENT SETPOINT
164 COOLING BANK 3 PRESENT RUNNING CURRENT COOLING BANK 3 PRESENT/STEADY STATE CURRENT
165 COOLING BANK 3 MINIMUM RUNNING CURRENT COOLING BANK 3 MINIMUM STEADY STATE CURRENT
166 COOLING BANK 3 MAXIMUM RUNNING CURRENT COOLING BANK 3 MAXIMUM STEADY STATE CURRENT
167 CB3 RUNNING CURRENT UPPER SETPOINT COOLING BANK 3 STEADY STATE CURRENT SETPOINT
168 CB3 RUNNING CURRENT LOWER SETPOINT COOLING BANK 3 STEADY STATE CURRENT SETPOINT
169 CB3 PRESENT PEAK INRUSH CURRENT VALUE COOLING BANK 3 PRESENT PEAK INRUSH CURRENT

21 www.qualitrolcorp.com
ANALOG INPUT; OBJ 30; VAR 0, 1, 2, 3, 4, 5, 6
POINT POINT VARIABLE DESCRIPTION
170 CB3 MINIMUM PEAK INRUSH CURRENT VALUE COOLING BANK 3 MINIMUM PEAK INRUSH CURRENT
171 CB3 MAXIMUM PEAK INRUSH CURRENT VALUE COOLING BANK 3 MAXIMUM PEAK INRUSH CURRENT
172 CB3 INRUSH CURRENT UPPER SETPOINT VALUE COOLING BANK 3 PEAK INRUSH CURRENT SETPOINT
173 CB3 INRUSH CURRENT LOWER SETPOINT VALUE COOLING BANK 3 PEAK INRUSH CURRENT SETPOINT
174 COOLING BANK 4 PRESENT RUNNING CURRENT COOLING BANK 4 PRESENT/STEADY STATE CURRENT
175 COOLING BANK 4 MINIMUM RUNNING CURRENT COOLING BANK 4 MINIMUM STEADY STATE CURRENT
176 COOLING BANK 4 MAXIMUM RUNNING CURRENT COOLING BANK 4 MAXIMUM STEADY STATE CURRENT
177 CB4 RUNNING CURRENT UPPER SETPOINT COOLING BANK 4 STEADY STATE CURRENT SETPOINT
178 CB4 RUNNING CURRENT LOWER SETPOINT COOLING BANK 4 STEADY STATE CURRENT SETPOINT
179 CB4 PRESENT PEAK INRUSH CURRENT VALUE COOLING BANK 4 PRESENT PEAK INRUSH CURRENT
180 CB4 MINIMUM PEAK INRUSH CURRENT VALUE COOLING BANK 4 MINIMUM PEAK INRUSH CURRENT
181 CB4 MAXIMUM PEAK INRUSH CURRENT VALUE COOLING BANK 4 MAXIMUM PEAK INRUSH CURRENT
182 CB4 INRUSH CURRENT UPPER SETPOINT VALUE COOLING BANK 4 PEAK INRUSH CURRENT SETPOINT
183 CB4 INRUSH CURRENT LOWER SETPOINT VALUE COOLING BANK 4 PEAK INRUSH CURRENT SETPOINT
184 TAP POSITION -16 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-16)
185 TAP POSITION -15 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-15)
186 TAP POSITION -14 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-14)
187 TAP POSITION -13 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-13)
188 TAP POSITION -12 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-12)
189 TAP POSITION -11 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-11)
190 TAP POSITION -10 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-10)
191 TAP POSITION -9 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-9)
192 TAP POSITION -8 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-8)
193 TAP POSITION -7 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-7)
194 TAP POSITION -6 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-6)
195 TAP POSITION -5 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-5)
196 TAP POSITION -4 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-4)
197 TAP POSITION -3 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-3)
198 TAP POSITION -2 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-2)
199 TAP POSITION -1 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-1)
200 TAP POSITION +0 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+0)
201 TAP POSITION +1 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+1)
202 TAP POSITION +2 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+2)
203 TAP POSITION +3 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+3)
204 TAP POSITION +4 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+4)
205 TAP POSITION +5 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+5)
206 TAP POSITION +6 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+6)
207 TAP POSITION +7 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+7)
208 TAP POSITION +8 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+8)
209 TAP POSITION +9 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+9)
210 TAP POSITION +10 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+10)
211 TAP POSITION +11 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+11)
212 TAP POSITION +12 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+12)
213 TAP POSITION +13 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+13)
214 TAP POSITION +14 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+14)
215 TAP POSITION +15 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+15)
216 TAP POSITION +16 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+16)

22 www.qualitrolcorp.com
ANALOG INPUT; OBJ 30; VAR 0, 1, 2, 3, 4, 5, 6
POINT POINT VARIABLE DESCRIPTION
217 TAP POSITION -16 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-16)
218 TAP POSITION -15 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-15)
219 TAP POSITION -14 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-14)
220 TAP POSITION -13 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-13)
221 TAP POSITION -12 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-12)
222 TAP POSITION -11 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-11)
223 TAP POSITION -10 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-10)
224 TAP POSITION -9 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-9)
225 TAP POSITION -8 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-8)
226 TAP POSITION -7 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-7)
227 TAP POSITION -6 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-6)
228 TAP POSITION -5 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-5)
229 TAP POSITION -4 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-4)
230 TAP POSITION -3 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-3)
231 TAP POSITION -2 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-2)
232 TAP POSITION -1 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-1)
233 TAP POSITION +0 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+0)
234 TAP POSITION +1 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+1)
235 TAP POSITION +2 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+2)
236 TAP POSITION +3 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+3)
237 TAP POSITION +4 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+4)
238 TAP POSITION +5 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+5)
239 TAP POSITION +6 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+6)
240 TAP POSITION +7 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+7)
241 TAP POSITION +8 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+8)
242 TAP POSITION +9 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+9)
243 TAP POSITION +10 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+10)
244 TAP POSITION +11 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+11)
245 TAP POSITION +12 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+12)
246 TAP POSITION +13 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+13)
247 TAP POSITION +14 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+14)
248 TAP POSITION +15 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+15)
249 TAP POSITION +16 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+16)
250 LTC HI-ALARM RUN CURRENT UPPER SETPOINT LTC HIGH-PRIORITY STEADY STATE UPPER SETPOINT
251 LTC LO-ALARM RUN CURRENT UPPER SETPOINT LTC LOW-PRIORITY STEADY STATE UPPER SETPOINT
252 LTC HI-ALARM RUN CURRENT LOWER SETPOINT LTC HIGH-PRIORITY STEADY STATE LOWER SETPOINT
253 LTC LO-ALARM RUN CURRENT LOWER SETPOINT LTC LOW-PRIORITY STEADY STATE LOWER SETPOINT
LTC HI-ALARM INRUSH CURRENT UPPER LTC HIGH-PRIORITY INRUSH CURRENT UPPER
254 SETPOINT SETPOINT
LTC LO-ALARM INRUSH CURRENT UPPER LTC LOW-PRIORITY INRUSH CURRENT UPPER
255 SETPOINT SETPOINT
LTC HI-ALARM INRUSH CURRENT LOWER LTC HIGH-PRIORITY INRUSH CURRENT LOWER
256 SETPOINT SETPOINT
LTC LO-ALARM INRUSH CURRENT LOWER LTC LOW-PRIORITY INRUSH CURRENT LOWER
257 SETPOINT SETPOINT
258 MOD 1; FIBER PROBE 1 PRESENT TEMPERATURE HOT SPOT MODULE 1; 1ST PROBE PRESENT TEMP
259 MOD 1; FIBER PROBE 1 MINIMUM TEMPERATURE HOT SPOT MODULE 1; 1ST PROBE MINIMUM TEMP
260 MOD 1; FIBER PROBE 1 MAXIMUM TEMPERATURE HOT SPOT MODULE 1; 1ST PROBE MAXIMUM TEMP
261 MOD 1; FIBER PROBE 2 PRESENT TEMPERATURE HOT SPOT MODULE 1; 2ND PROBE PRESENT TEMP

23 www.qualitrolcorp.com
ANALOG INPUT; OBJ 30; VAR 0, 1, 2, 3, 4, 5, 6
POINT POINT VARIABLE DESCRIPTION
262 MOD 1; FIBER PROBE 2 MINIMUM TEMPERATURE HOT SPOT MODULE 1; 2ND PROBE MINIMUM TEMP
263 MOD 1; FIBER PROBE 2 MAXIMUM TEMPERATURE HOT SPOT MODULE 1; 2ND PROBE MAXIMUM TEMP
264 MOD 1; FIBER PROBE 3 PRESENT TEMPERATURE HOT SPOT MODULE 1; 3RD PROBE PRESENT TEMP
265 MOD 1; FIBER PROBE 3 MINIMUM TEMPERATURE HOT SPOT MODULE 1; 3RD PROBE MINIMUM TEMP
266 MOD 1; FIBER PROBE 3 MAXIMUM TEMPERATURE HOT SPOT MODULE 1; 3RD PROBE MAXIMUM TEMP
267 MOD 1; FIBER PROBE 4 PRESENT TEMPERATURE HOT SPOT MODULE 1; 4TH PROBE PRESENT TEMP
268 MOD 1; FIBER PROBE 4 MINIMUM TEMPERATURE HOT SPOT MODULE 1; 4TH PROBE MINIMUM TEMP
269 MOD 1; FIBER PROBE 4 MAXIMUM TEMPERATURE HOT SPOT MODULE 1; 4TH PROBE MAXIMUM TEMP
270 MOD 1; FIBER PROBE 5 PRESENT TEMPERATURE HOT SPOT MODULE 1; 5TH PROBE PRESENT TEMP
271 MOD 1; FIBER PROBE 5 MINIMUM TEMPERATURE HOT SPOT MODULE 1; 5TH PROBE MINIMUM TEMP
272 MOD 1; FIBER PROBE 5 MAXIMUM TEMPERATURE HOT SPOT MODULE 1; 5TH PROBE MAXIMUM TEMP
273 MOD 1; FIBER PROBE 6 PRESENT TEMPERATURE HOT SPOT MODULE 1; 6TH PROBE PRESENT TEMP
274 MOD 1; FIBER PROBE 6 MINIMUM TEMPERATURE HOT SPOT MODULE 1; 6TH PROBE MINIMUM TEMP
275 MOD 1; FIBER PROBE 6 MAXIMUM TEMPERATURE HOT SPOT MODULE 1; 6TH PROBE MAXIMUM TEMP
276 MOD 1; FIBER PROBE 7 PRESENT TEMPERATURE HOT SPOT MODULE 1; 6TH PROBE PRESENT TEMP
277 MOD 1; FIBER PROBE 7 MINIMUM TEMPERATURE HOT SPOT MODULE 1; 7TH PROBE MINIMUM TEMP
278 MOD 1; FIBER PROBE 7 MAXIMUM TEMPERATURE HOT SPOT MODULE 1; 7TH PROBE MAXIMUM TEMP
279 MOD 1; FIBER PROBE 8 PRESENT TEMPERATURE HOT SPOT MODULE 1; 8TH PROBE PRESENT TEMP
280 MOD 1; FIBER PROBE 8 MINIMUM TEMPERATURE HOT SPOT MODULE 1; 8TH PROBE MINIMUM TEMP
281 MOD 1; FIBER PROBE 8 MAXIMUM TEMPERATURE HOT SPOT MODULE 1; 8TH PROBE MAXIMUM TEMP
282 MOD 2; FIBER PROBE 1 PRESENT TEMPERATURE HOT SPOT MODULE 2; 1ST PROBE PRESENT TEMP
283 MOD 2; FIBER PROBE 1 MINIMUM TEMPERATURE HOT SPOT MODULE 2; 1ST PROBE MINIMUM TEMP
284 MOD 2; FIBER PROBE 1 MAXIMUM TEMPERATURE HOT SPOT MODULE 2; 1ST PROBE MAXIMUM TEMP
285 MOD 2; FIBER PROBE 2 PRESENT TEMPERATURE HOT SPOT MODULE 2; 2ND PROBE PRESENT TEMP
286 MOD 2; FIBER PROBE 2 MINIMUM TEMPERATURE HOT SPOT MODULE 2; 2ND PROBE MINIMUM TEMP
287 MOD 2; FIBER PROBE 2 MAXIMUM TEMPERATURE HOT SPOT MODULE 2; 2ND PROBE MAXIMUM TEMP
288 MOD 2; FIBER PROBE 3 PRESENT TEMPERATURE HOT SPOT MODULE 2; 3RD PROBE PRESENT TEMP
289 MOD 2; FIBER PROBE 3 MINIMUM TEMPERATURE HOT SPOT MODULE 2; 3RD PROBE MINIMUM TEMP
290 MOD 2; FIBER PROBE 3 MAXIMUM TEMPERATURE HOT SPOT MODULE 2; 3RD PROBE MAXIMUM TEMP
291 MOD 2; FIBER PROBE 4 PRESENT TEMPERATURE HOT SPOT MODULE 2; 4TH PROBE PRESENT TEMP
292 MOD 2; FIBER PROBE 4 MINIMUM TEMPERATURE HOT SPOT MODULE 2; 4TH PROBE MINIMUM TEMP
293 MOD 2; FIBER PROBE 4 MAXIMUM TEMPERATURE HOT SPOT MODULE 2; 4TH PROBE MAXIMUM TEMP
294 MOD 2; FIBER PROBE 5 PRESENT TEMPERATURE HOT SPOT MODULE 2; 5TH PROBE PRESENT TEMP
295 MOD 2; FIBER PROBE 5 MINIMUM TEMPERATURE HOT SPOT MODULE 2; 5TH PROBE MINIMUM TEMP
296 MOD 2; FIBER PROBE 5 MAXIMUM TEMPERATURE HOT SPOT MODULE 2; 5TH PROBE MAXIMUM TEMP
297 MOD 2; FIBER PROBE 6 PRESENT TEMPERATURE HOT SPOT MODULE 2; 6TH PROBE PRESENT TEMP
298 MOD 2; FIBER PROBE 6 MINIMUM TEMPERATURE HOT SPOT MODULE 2; 6TH PROBE MINIMUM TEMP
299 MOD 2; FIBER PROBE 6 MAXIMUM TEMPERATURE HOT SPOT MODULE 2; 6TH PROBE MAXIMUM TEMP
300 MOD 2; FIBER PROBE 7 PRESENT TEMPERATURE HOT SPOT MODULE 2; 6TH PROBE PRESENT TEMP
301 MOD 2; FIBER PROBE 7 MINIMUM TEMPERATURE HOT SPOT MODULE 2; 7TH PROBE MINIMUM TEMP
302 MOD 2; FIBER PROBE 7 MAXIMUM TEMPERATURE HOT SPOT MODULE 2; 7TH PROBE MAXIMUM TEMP
303 MOD 2; FIBER PROBE 8 PRESENT TEMPERATURE HOT SPOT MODULE 2; 8TH PROBE PRESENT TEMP
304 MOD 2; FIBER PROBE 8 MINIMUM TEMPERATURE HOT SPOT MODULE 2; 8TH PROBE MINIMUM TEMP
305 MOD 2; FIBER PROBE 8 MAXIMUM TEMPERATURE HOT SPOT MODULE 2; 8TH PROBE MAXIMUM TEMP
TEMP WHERE CONSUMED LIFE EQUALS OPERATING
306 LIFE CONSUMPTION UNITY TEMPERATURE LIFE
LTC HI-ALARM TOTAL TAP COUNT SETPOINT
307 VALUE LTC HIGH-PRIORITY TOTAL TAP COUNT SETPOINT

24 www.qualitrolcorp.com
ANALOG INPUT; OBJ 30; VAR 0, 1, 2, 3, 4, 5, 6
POINT POINT VARIABLE DESCRIPTION
LTC LO-ALARM TOTAL TAP COUNT SETPOINT
308 VALUE LTC LOW-PRIORITY TOTAL TAP COUNT SETPOINT
LTC HI-ALARM MOTOR ACTUATION SETPOINT
309 VALUE LTC HIGH-PRIORITY MOTOR ACTUATION COUNT SPT
LTC LO-ALARM MOTOR ACTUATION SETPOINT
310 VALUE LTC LOW-PRIORITY MOTOR ACTUATION COUNT SPT
311 LTC TAP PERIOD TIME PERIOD TO MEASURE LTC TAP COUNTS
312 LTC PRESENT COUNTS TOTAL COUNTS IN PRESENT TAP PERIOD
313 LTC PREVIOUS COUNTS TOTAL COUNTS IN THE PREVIOUS TAP PERIOD
TRANSLIFE 1; TEMPERATURE PROFILE, 1ST
314 RANGE TOTAL WINDING TEMP TIME IN LOWEST TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 2ND
315 RANGE TOTAL WINDING TEMP TIME IN 2ND TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 3RD
316 RANGE TOTAL WINDING TEMP TIME IN 3RD TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 4TH
317 RANGE TOTAL WINDING TEMP TIME IN 4TH TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 5TH
318 RANGE TOTAL WINDING TEMP TIME IN 5TH TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 6TH
319 RANGE TOTAL WINDING TEMP TIME IN 6TH TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 7TH
320 RANGE TOTAL WINDING TEMP TIME IN 7TH TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 8TH
321 RANGE TOTAL WINDING TEMP TIME IN 8TH TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 9TH
322 RANGE TOTAL WINDING TEMP TIME IN 9TH TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 10TH
323 RANGE TOTAL WINDING TEMP TIME IN 10TH TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 11TH
324 RANGE TOTAL WINDING TEMP TIME IN 11TH TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 12TH
325 RANGE TOTAL WINDING TEMP TIME IN HIGHEST TEMP RANGE
TRANSLIFE 2; TEMPERATURE PROFILE, 1ST
326 RANGE TOTAL WINDING TEMP TIME IN LOWEST TEMP RANGE
TRANSLIFE 2; TEMPERATURE PROFILE, 2ND
327 RANGE TOTAL WINDING TEMP TIME IN 2ND TEMP RANGE
TRANSLIFE 2; TEMPERATURE PROFILE, 3RD
328 RANGE TOTAL WINDING TEMP TIME IN 3RD TEMP RANGE
TRANSLIFE 2; TEMPERATURE PROFILE, 4TH
329 RANGE TOTAL WINDING TEMP TIME IN 4TH TEMP RANGE
TRANSLIFE 2; TEMPERATURE PROFILE, 5TH
330 RANGE TOTAL WINDING TEMP TIME IN 5TH TEMP RANGE
TRANSLIFE 2; TEMPERATURE PROFILE, 6TH
331 RANGE TOTAL WINDING TEMP TIME IN 6TH TEMP RANGE
TRANSLIFE 2; TEMPERATURE PROFILE, 7TH
332 RANGE TOTAL WINDING TEMP TIME IN 7TH TEMP RANGE
TRANSLIFE 2; TEMPERATURE PROFILE, 8TH
333 RANGE TOTAL WINDING TEMP TIME IN 8TH TEMP RANGE
TRANSLIFE 2; TEMPERATURE PROFILE, 9TH
334 RANGE TOTAL WINDING TEMP TIME IN 9TH TEMP RANGE
TRANSLIFE 2; TEMPERATURE PROFILE, 10TH
335 RANGE TOTAL WINDING TEMP TIME IN 10TH TEMP RANGE
TRANSLIFE 2; TEMPERATURE PROFILE, 11TH
336 RANGE TOTAL WINDING TEMP TIME IN 11TH TEMP RANGE
TRANSLIFE 2; TEMPERATURE PROFILE, 12TH
337 RANGE TOTAL WINDING TEMP TIME IN HIGHEST TEMP RANGE
TRANSLIFE 3; TEMPERATURE PROFILE, 1ST
338 RANGE TOTAL WINDING TEMP TIME IN LOWEST TEMP RANGE
TRANSLIFE 3; TEMPERATURE PROFILE, 2ND
339 RANGE TOTAL WINDING TEMP TIME IN 2ND TEMP RANGE
TRANSLIFE 3; TEMPERATURE PROFILE, 3RD
340 RANGE TOTAL WINDING TEMP TIME IN 3RD TEMP RANGE
341 TRANSLIFE 3; TEMPERATURE PROFILE, 4TH TOTAL WINDING TEMP TIME IN 4TH TEMP RANGE

25 www.qualitrolcorp.com
ANALOG INPUT; OBJ 30; VAR 0, 1, 2, 3, 4, 5, 6
POINT POINT VARIABLE DESCRIPTION
RANGE
TRANSLIFE 3; TEMPERATURE PROFILE, 5TH
342 RANGE TOTAL WINDING TEMP TIME IN 5TH TEMP RANGE
TRANSLIFE 3; TEMPERATURE PROFILE, 6TH
343 RANGE TOTAL WINDING TEMP TIME IN 6TH TEMP RANGE
TRANSLIFE 3; TEMPERATURE PROFILE, 7TH
344 RANGE TOTAL WINDING TEMP TIME IN 7TH TEMP RANGE
TRANSLIFE 3; TEMPERATURE PROFILE, 8TH
345 RANGE TOTAL WINDING TEMP TIME IN 8TH TEMP RANGE
TRANSLIFE 3; TEMPERATURE PROFILE, 9TH
346 RANGE TOTAL WINDING TEMP TIME IN 9TH TEMP RANGE
TRANSLIFE 3; TEMPERATURE PROFILE, 10TH
347 RANGE TOTAL WINDING TEMP TIME IN 10TH TEMP RANGE
TRANSLIFE 3; TEMPERATURE PROFILE, 11TH
348 RANGE TOTAL WINDING TEMP TIME IN 11TH TEMP RANGE
TRANSLIFE 3; TEMPERATURE PROFILE, 12TH
349 RANGE TOTAL WINDING TEMP TIME IN HIGHEST TEMP RANGE
TOTAL # OF TIMES THE COOLING FANS HAVE
350 COOLING BANK 1 TOTAL ACTUATION COUNTS ENGAGED
351 COOLING BANK 1 ACTUATION SETPOINT VALUE TOTAL ACTUATION COUNT SETPOINT
352 COOLING BANK 1 TOTAL SYSTEM RUN TIME TOTAL # OF HOURS THAT THE FANS HAVE BEEN ON
353 COOLING BANK 1 RUN TIME SETPOINT VALUE TOTAL RUN TIME SETPOINT
TOTAL # OF TIMES THE COOLING FANS HAVE
354 COOLING BANK 2 TOTAL ACTUATION COUNTS ENGAGED
355 COOLING BANK 2 ACTUATION SETPOINT VALUE TOTAL ACTUATION COUNT SETPOINT
356 COOLING BANK 2 TOTAL SYSTEM RUN TIME TOTAL # OF HOURS THAT THE FANS HAVE BEEN ON
357 COOLING BANK 2 RUN TIME SETPOINT VALUE TOTAL RUN TIME SETPOINT
TOTAL # OF TIMES THE COOLING FANS HAVE
358 COOLING BANK 3 TOTAL ACTUATION COUNTS ENGAGED
359 COOLING BANK 3 ACTUATION SETPOINT VALUE TOTAL ACTUATION COUNT SETPOINT
360 COOLING BANK 3 TOTAL SYSTEM RUN TIME TOTAL # OF HOURS THAT THE FANS HAVE BEEN ON
361 COOLING BANK 3 RUN TIME SETPOINT VALUE TOTAL RUN TIME SETPOINT
TOTAL # OF TIMES THE COOLING FANS HAVE
362 COOLING BANK 4 TOTAL ACTUATION COUNTS ENGAGED
363 COOLING BANK 4 ACTUATION SETPOINT VALUE TOTAL ACTUATION COUNT SETPOINT
364 COOLING BANK 4 TOTAL SYSTEM RUN TIME TOTAL # OF HOURS THAT THE FANS HAVE BEEN ON
365 COOLING BANK 4 RUN TIME SETPOINT VALUE TOTAL RUN TIME SETPOINT
366 LTC, TAP POSITION -16 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-16)
367 LTC, TAP POSITION -15 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-15)
368 LTC, TAP POSITION -14 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-14)
369 LTC, TAP POSITION -13 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-13)
370 LTC, TAP POSITION -12 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-12)
371 LTC, TAP POSITION -11 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-11)
372 LTC, TAP POSITION -10 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-10)
373 LTC, TAP POSITION -9 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-9)
374 LTC, TAP POSITION -8 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-8)
375 LTC, TAP POSITION -7 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-7)
376 LTC, TAP POSITION -6 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-6)
377 LTC, TAP POSITION -5 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-5)
378 LTC, TAP POSITION -4 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-4)
379 LTC, TAP POSITION -3 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-3)
380 LTC, TAP POSITION -2 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-2)
381 LTC, TAP POSITION -1 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-1)

26 www.qualitrolcorp.com
ANALOG INPUT; OBJ 30; VAR 0, 1, 2, 3, 4, 5, 6
POINT POINT VARIABLE DESCRIPTION
382 LTC, TAP POSITION +0 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+0)
383 LTC, TAP POSITION +1 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+1)
384 LTC, TAP POSITION +2 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+2)
385 LTC, TAP POSITION +3 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+3)
386 LTC, TAP POSITION +4 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+4)
387 LTC, TAP POSITION +5 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+5)
388 LTC, TAP POSITION +6 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+6)
389 LTC, TAP POSITION +7 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+7)
390 LTC, TAP POSITION +8 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+8)
391 LTC, TAP POSITION +9 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+9)
392 LTC, TAP POSITION +10 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+10)
393 LTC, TAP POSITION +11 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+11)
394 LTC, TAP POSITION +12 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+12)
395 LTC, TAP POSITION +13 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+13)
396 LTC, TAP POSITION +14 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+14)
397 LTC, TAP POSITION +15 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+15)
398 LTC, TAP POSITION +16 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+16)
399 LTC, TAP POSITION -16 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-16)
400 LTC, TAP POSITION -15 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-15)
401 LTC, TAP POSITION -14 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-14)
402 LTC, TAP POSITION -13 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-13)
403 LTC, TAP POSITION -12 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-12)
404 LTC, TAP POSITION -11 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-11)
405 LTC, TAP POSITION -10 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-10)
406 LTC, TAP POSITION -9 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-9)
407 LTC, TAP POSITION -8 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-8)
408 LTC, TAP POSITION -7 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-7)
409 LTC, TAP POSITION -6 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-6)
410 LTC, TAP POSITION -5 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-5)
411 LTC, TAP POSITION -4 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-4)
412 LTC, TAP POSITION -3 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-3)
413 LTC, TAP POSITION -2 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-2)
414 LTC, TAP POSITION -1 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-1)
415 LTC, TAP POSITION +0 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+0)
416 LTC, TAP POSITION +1 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+1)
417 LTC, TAP POSITION +2 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+2)
418 LTC, TAP POSITION +3 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+3)
419 LTC, TAP POSITION +4 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+4)
420 LTC, TAP POSITION +5 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+5)
421 LTC, TAP POSITION +6 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+6)
422 LTC, TAP POSITION +7 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+7)
423 LTC, TAP POSITION +8 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+8)
424 LTC, TAP POSITION +9 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+9)
425 LTC, TAP POSITION +10 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+10)
426 LTC, TAP POSITION +11 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+11)
427 LTC, TAP POSITION +12 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+12)
428 LTC, TAP POSITION +13 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+13)

27 www.qualitrolcorp.com
ANALOG INPUT; OBJ 30; VAR 0, 1, 2, 3, 4, 5, 6
POINT POINT VARIABLE DESCRIPTION
429 LTC, TAP POSITION +14 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+14)
430 LTC, TAP POSITION +15 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+15)
431 LTC, TAP POSITION +16 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+16)
432 LTC, TOTAL MOTOR ACTUATION COUNTS TOTAL NUMBER OF MOTOR ACTUATION COUNTS
433 FIRMWARE REVISION FOR THIS 509ITM UNIT
434 TRANSFORMER LIFE SPAN EXPECTED TOTAL LIFE SPAN OF TRANSFORMER

ALL MODULES BUT CT, WINDING TEMPERATURE IF THE MODULE IS A CT, WINDING TEMPERATURE
435 INPUT MODULE 9 PRESENT VALUE OR INPUT MODULE 9 PRESENT WINDING TEMP
436 INPUT MODULE 9 MINIMUM VALUE OR INPUT MODULE 9 MINIMUM WINDING TEMP
437 INPUT MODULE 9 MAXIMUM VALUE OR INPUT MODULE 9 MAXIMUM WINDING TEMP
438 0 OR INPUT MODULE 9 PRESENT CURRENT
439 0 OR INPUT MODULE 9 MAXIMUM CURRENT
440 INPUT MODULE 10 PRESENT VALUE OR INPUT MODULE 10 PRESENT WINDING TEMP
441 INPUT MODULE 10 MINIMUM VALUE OR INPUT MODULE 10 MINIMUM WINDING TEMP
442 INPUT MODULE 10 MAXIMUM VALUE OR INPUT MODULE 10 MAXIMUM WINDING TEMP
443 0 OR INPUT MODULE 10 PRESENT CURRENT
444 0 OR INPUT MODULE 10 MAXIMUM CURRENT
445 INPUT MODULE 11 PRESENT VALUE OR INPUT MODULE 11 PRESENT WINDING TEMP
446 INPUT MODULE 11 MINIMUM VALUE OR INPUT MODULE 11 MINIMUM WINDING TEMP
447 INPUT MODULE 11 MAXIMUM VALUE OR INPUT MODULE 11 MAXIMUM WINDING TEMP
448 0 OR INPUT MODULE 11 PRESENT CURRENT
449 0 OR INPUT MODULE 11 MAXIMUM CURRENT
450 INPUT MODULE 12 PRESENT VALUE OR INPUT MODULE 12 PRESENT WINDING TEMP
451 INPUT MODULE 12 MINIMUM VALUE OR INPUT MODULE 12 MINIMUM WINDING TEMP
452 INPUT MODULE 12 MAXIMUM VALUE OR INPUT MODULE 12 MAXIMUM WINDING TEMP
453 0 OR INPUT MODULE 12 PRESENT CURRENT
454 0 OR INPUT MODULE 12 MAXIMUM CURRENT
455 INPUT MODULE 13 PRESENT VALUE OR INPUT MODULE 13 PRESENT WINDING TEMP
456 INPUT MODULE 13 MINIMUM VALUE OR INPUT MODULE 13 MINIMUM WINDING TEMP
457 INPUT MODULE 13 MAXIMUM VALUE OR INPUT MODULE 13 MAXIMUM WINDING TEMP
458 0 OR INPUT MODULE 13 PRESENT CURRENT
459 0 OR INPUT MODULE 13 MAXIMUM CURRENT
460 INPUT MODULE 14 PRESENT VALUE OR INPUT MODULE 14 PRESENT WINDING TEMP
461 INPUT MODULE 14 MINIMUM VALUE OR INPUT MODULE 14 MINIMUM WINDING TEMP
462 INPUT MODULE 14 MAXIMUM VALUE OR INPUT MODULE 14 MAXIMUM WINDING TEMP
463 0 OR INPUT MODULE 14 PRESENT CURRENT
464 0 OR INPUT MODULE 14 MAXIMUM CURRENT
465 INPUT MODULE 15 PRESENT VALUE OR INPUT MODULE 15 PRESENT WINDING TEMP
466 INPUT MODULE 15 MINIMUM VALUE OR INPUT MODULE 15 MINIMUM WINDING TEMP
467 INPUT MODULE 15 MAXIMUM VALUE OR INPUT MODULE 15 MAXIMUM WINDING TEMP
468 0 OR INPUT MODULE 15 PRESENT CURRENT
469 0 OR INPUT MODULE 15 MAXIMUM CURRENT
470 INPUT MODULE 16 PRESENT VALUE OR INPUT MODULE 16 PRESENT WINDING TEMP
471 INPUT MODULE 16 MINIMUM VALUE OR INPUT MODULE 16 MINIMUM WINDING TEMP
472 INPUT MODULE 16 MAXIMUM VALUE OR INPUT MODULE 16 MAXIMUM WINDING TEMP
473 0 OR INPUT MODULE 16 PRESENT CURRENT

28 www.qualitrolcorp.com
ANALOG INPUT; OBJ 30; VAR 0, 1, 2, 3, 4, 5, 6
POINT POINT VARIABLE DESCRIPTION
474 0 OR INPUT MODULE 16 MAXIMUM CURRENT
475 RELAY 1, ACTUATION COUNTS ACTUATION COUNTER FOR RELAY 1
476 RELAY 2, ACTUATION COUNTS ACTUATION COUNTER FOR RELAY 2
477 RELAY 3, ACTUATION COUNTS ACTUATION COUNTER FOR RELAY 3
478 RELAY 4, ACTUATION COUNTS ACTUATION COUNTER FOR RELAY 4
479 RELAY 5, ACTUATION COUNTS ACTUATION COUNTER FOR RELAY 5
480 RELAY 6, ACTUATION COUNTS ACTUATION COUNTER FOR RELAY 6
481 RELAY 7, ACTUATION COUNTS ACTUATION COUNTER FOR RELAY 7
482 RELAY 8, ACTUATION COUNTS ACTUATION COUNTER FOR RELAY 8
483 RELAY 1, RATE OF CHANGE TIME PERIOD RATE OF CHANGE TIME PERIOD FOR RELAY 1
484 RELAY 2, RATE OF CHANGE TIME PERIOD RATE OF CHANGE TIME PERIOD FOR RELAY 2
485 RELAY 3, RATE OF CHANGE TIME PERIOD RATE OF CHANGE TIME PERIOD FOR RELAY 3
486 RELAY 4, RATE OF CHANGE TIME PERIOD RATE OF CHANGE TIME PERIOD FOR RELAY 4
487 RELAY 5, RATE OF CHANGE TIME PERIOD RATE OF CHANGE TIME PERIOD FOR RELAY 5
488 RELAY 6, RATE OF CHANGE TIME PERIOD RATE OF CHANGE TIME PERIOD FOR RELAY 6
489 RELAY 7, RATE OF CHANGE TIME PERIOD RATE OF CHANGE TIME PERIOD FOR RELAY 7
490 RELAY 8, RATE OF CHANGE TIME PERIOD RATE OF CHANGE TIME PERIOD FOR RELAY 8
491 DGA HYDROGEN SENSOR 1, PRESENT VALUE PRESENT VALUE OF DIGITAL HYDROGEN SENSOR # 1
492 DGA HYDROGEN SENSOR 1, MINIMUM VALUE MINIMUM VALUE OF DIGITAL HYDROGEN SENSOR # 1
493 DGA HYDROGEN SENSOR 1, MAXIMUM VALUE MAXIMUM VALUE OF DIGITAL HYDROGEN SENSOR # 1
494 DGA HYDROGEN SENSOR 2, PRESENT VALUE PRESENT VALUE OF DIGITAL HYDROGEN SENSOR # 2
495 DGA HYDROGEN SENSOR 2, MINIMUM VALUE MINIMUM VALUE OF DIGITAL HYDROGEN SENSOR # 2
496 DGA HYDROGEN SENSOR 2, MAXIMUM VALUE MAXIMUM VALUE OF DIGITAL HYDROGEN SENSOR # 2
497 DGA HYDROGEN SENSOR 3, PRESENT VALUE PRESENT VALUE OF DIGITAL HYDROGEN SENSOR # 3
498 DGA HYDROGEN SENSOR 3, MINIMUM VALUE MINIMUM VALUE OF DIGITAL HYDROGEN SENSOR # 3
499 DGA HYDROGEN SENSOR 3, MAXIMUM VALUE MAXIMUM VALUE OF DIGITAL HYDROGEN SENSOR # 3

Analog Output Status Points


The following table lists the Analog Output Status Points (Object 40).
While Analog Output Status Points are included here for completeness, they are not often polled by
DNP 3.0 Masters. It is recommended that Analog Output Status points represent the most recent
DNP “commanded” value for the corresponding Analog Output Control Block point. Analog Output
Status points are not recommended to be included in class 0 polls.
As an alternative, it is recommended that “actual” status values of Analog Output Control Block points
be looped around and mapped as Analog Inputs. (The “actual” status value, as opposed to the
“commanded’ status value, is the value of the actuated control.) For example, a DNP control
command may be blocked through hardware or software mechanisms; in this case, the actual status
value would indicate the control failed because of the blocking. Looping Analog Relay Output Block
actual status values as Analog Inputs has several advantages:
 it allows actual statuses to be included in class 0 polls,
 it allows change event reporting of the actual statuses, which is a more efficient method of
communicating control values,
 and, if analog change events with time variations are supported by the DNP master, it allows
reporting of time-based information associated with controls, including delays before the controls
are actuated.

29 www.qualitrolcorp.com
The default select/control buffer size is large enough to hold 10 of the largest select requests
possible.

ANALOG OUTPUT; OBJ 40; VAR 0, 1, 2, 3, 4


POINT POINT VARIABLE DESCRIPTION
0 RELAY 1, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
1 RELAY 2, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
2 RELAY 3, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
3 RELAY 4, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
4 RELAY 5, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
5 RELAY 6, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
6 RELAY 7, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
7 RELAY 8, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
8 RELAY 1, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
9 RELAY 2, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
10 RELAY 3, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
11 RELAY 4, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
12 RELAY 5, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
13 RELAY 6, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
14 RELAY 7, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
15 RELAY 8, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
16 RELAY 1, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
17 RELAY 2, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
18 RELAY 3, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
19 RELAY 4, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
20 RELAY 5, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
21 RELAY 6, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
22 RELAY 7, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
23 RELAY 8, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
24 RELAY 1, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
25 RELAY 2, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
26 RELAY 3, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
27 RELAY 4, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
28 RELAY 5, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
29 RELAY 6, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
30 RELAY 7, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
31 RELAY 8, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
32 RELAY 1, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
33 RELAY 2, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
34 RELAY 3, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
35 RELAY 4, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
36 RELAY 5, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
37 RELAY 6, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
38 RELAY 7, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
39 RELAY 8, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
40 RELAY 1, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
41 RELAY 2, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
42 RELAY 3, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
43 RELAY 4, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX

30 www.qualitrolcorp.com
ANALOG OUTPUT; OBJ 40; VAR 0, 1, 2, 3, 4
POINT POINT VARIABLE DESCRIPTION
44 RELAY 5, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
45 RELAY 6, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
46 RELAY 7, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
47 RELAY 8, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
48 RELAY 1, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
49 RELAY 2, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
50 RELAY 3, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
51 RELAY 4, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
52 RELAY 5, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
53 RELAY 6, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
54 RELAY 7, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
55 RELAY 8, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
56 RELAY 1, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
57 RELAY 2, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
58 RELAY 3, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
59 RELAY 4, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
60 RELAY 5, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
61 RELAY 6, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
62 RELAY 7, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
63 RELAY 8, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
64 TL1 CRITICAL WINDING TEMP SETPOINT 1 1ST CRITICAL SPT TO CALCULATE TIME TO REACH
65 TL1 CRITICAL WINDING TEMP SETPOINT 2 2ND CRITICAL SPT TO CALCULATE TIME TO REACH
66 TL1 CRITICAL WINDING TEMP SETPOINT 3 3RD CRITICAL SPT TO CALCULATE TIME TO REACH
67 TL2 CRITICAL WINDING TEMP SETPOINT 1 1ST CRITICAL SPT TO CALCULATE TIME TO REACH
68 TL2 CRITICAL WINDING TEMP SETPOINT 2 2ND CRITICAL SPT TO CALCULATE TIME TO REACH
69 TL2 CRITICAL WINDING TEMP SETPOINT 3 3RD CRITICAL SPT TO CALCULATE TIME TO REACH
70 TL3 CRITICAL WINDING TEMP SETPOINT 1 1ST CRITICAL SPT TO CALCULATE TIME TO REACH
71 TL3 CRITICAL WINDING TEMP SETPOINT 2 2ND CRITICAL SPT TO CALCULATE TIME TO REACH
72 TL3 CRITICAL WINDING TEMP SETPOINT 3 3RD CRITICAL SPT TO CALCULATE TIME TO REACH
73 CB1 RUNNING CURRENT UPPER SETPOINT COOLING BANK 1 STEADY STATE CURRENT SETPOINT
74 CB1 RUNNING CURRENT LOWER SETPOINT COOLING BANK 1 STEADY STATE CURRENT SETPOINT
75 CB1 INRUSH CURRENT UPPER SETPOINT VALUE COOLING BANK 1 PEAK INRUSH CURRENT SETPOINT
76 CB1 INRUSH CURRENT LOWER SETPOINT VALUE COOLING BANK 1 PEAK INRUSH CURRENT SETPOINT
77 COOLING BANK 1 ACTUATION SETPOINT VALUE TOTAL ACTUATION COUNT SETPOINT
78 COOLING BANK 1 RUN TIME SETPOINT VALUE COOLING BANK 1 TOTAL RUN TIME SETPOINT
79 CB2 RUNNING CURRENT UPPER SETPOINT COOLING BANK 2 STEADY STATE CURRENT SETPOINT
80 CB2 RUNNING CURRENT LOWER SETPOINT COOLING BANK 2 STEADY STATE CURRENT SETPOINT
81 CB2 INRUSH CURRENT UPPER SETPOINT VALUE COOLING BANK 2 PEAK INRUSH CURRENT SETPOINT
82 CB2 INRUSH CURRENT LOWER SETPOINT VALUE COOLING BANK 2 PEAK INRUSH CURRENT SETPOINT
83 COOLING BANK 2 ACTUATION SETPOINT VALUE TOTAL ACTUATION COUNT SETPOINT
84 COOLING BANK 2 RUN TIME SETPOINT VALUE COOLING BANK 2 TOTAL RUN TIME SETPOINT
85 CB3 RUNNING CURRENT UPPER SETPOINT COOLING BANK 3 STEADY STATE CURRENT SETPOINT
86 CB3 RUNNING CURRENT LOWER SETPOINT COOLING BANK 3 STEADY STATE CURRENT SETPOINT
87 CB3 INRUSH CURRENT UPPER SETPOINT VALUE COOLING BANK 3 PEAK INRUSH CURRENT SETPOINT
88 CB3 INRUSH CURRENT LOWER SETPOINT VALUE COOLING BANK 3 PEAK INRUSH CURRENT SETPOINT
89 COOLING BANK 3 ACTUATION SETPOINT VALUE TOTAL ACTUATION COUNT SETPOINT
90 COOLING BANK 3 RUN TIME SETPOINT VALUE COOLING BANK 3 TOTAL RUN TIME SETPOINT

31 www.qualitrolcorp.com
ANALOG OUTPUT; OBJ 40; VAR 0, 1, 2, 3, 4
POINT POINT VARIABLE DESCRIPTION
91 CB4 RUNNING CURRENT UPPER SETPOINT COOLING BANK 4 STEADY STATE CURRENT SETPOINT
92 CB4 RUNNING CURRENT LOWER SETPOINT COOLING BANK 4 STEADY STATE CURRENT SETPOINT
93 CB4 INRUSH CURRENT UPPER SETPOINT VALUE COOLING BANK 4 PEAK INRUSH CURRENT SETPOINT
94 CB4 INRUSH CURRENT LOWER SETPOINT VALUE COOLING BANK 4 PEAK INRUSH CURRENT SETPOINT
95 COOLING BANK 4 ACTUATION SETPOINT VALUE TOTAL ACTUATION COUNT SETPOINT
96 COOLING BANK 4 RUN TIME SETPOINT VALUE COOLING BANK 4 TOTAL RUN TIME SETPOINT
97 LTC HI-ALARM RUN CURRENT UPPER SETPOINT LTC HIGH-PRIORITY STEADY STATE UPPER SETPOINT
98 LTC LO-ALARM RUN CURRENT UPPER SETPOINT LTC LOW-PRIORITY STEADY STATE UPPER SETPOINT
99 LTC HI-ALARM RUN CURRENT LOWER SETPOINT LTC HIGH-PRIORITY STEADY STATE LOWER SETPOINT
100 LTC LO-ALARM RUN CURRENT LOWER SETPOINT LTC LOW-PRIORITY STEADY STATE LOWER SETPOINT
LTC HI-ALARM INRUSH CURRENT UPPER LTC HIGH-PRIORITY INRUSH CURRENT UPPER
101 SETPOINT SETPOINT
LTC LO-ALARM INRUSH CURRENT UPPER LTC LOW-PRIORITY INRUSH CURRENT UPPER
102 SETPOINT SETPOINT
LTC HI-ALARM INRUSH CURRENT LOWER LTC HIGH-PRIORITY INRUSH CURRENT LOWER
103 SETPOINT SETPOINT
LTC LO-ALARM INRUSH CURRENT LOWER LTC LOW-PRIORITY INRUSH CURRENT LOWER
104 SETPOINT SETPOINT
LTC HI-ALARM TOTAL TAP COUNT SETPOINT
105 VALUE LTC HIGH-PRIORITY TOTAL TAP COUNT SETPOINT
LTC LO-ALARM TOTAL TAP COUNT SETPOINT
106 VALUE LTC LOW-PRIORITY TOTAL TAP COUNT SETPOINT
LTC HI-ALARM MOTOR ACTUATION SETPOINT
107 VALUE LTC HIGH-PRIORITY MOTOR ACTUATION COUNT SPT
LTC LO-ALARM MOTOR ACTUATION SETPOINT
108 VALUE LTC LOW-PRIORITY MOTOR ACTUATION COUNT SPT
109 LTC HI-ALARM TOTAL RUN TIME SETPOINT VALUE LTC HIGH-PRIORITY TOTAL RUN TIME SETPOINT
110 LTC LO-ALARM TOTAL RUN TIME SETPOINT VALUE LTC LOW-PRIORITY TOTAL RUN TIME SETPOINT

Octet Strings
The default string event buffer size is set to allow 10 events.

OCTET STRING; OBJ 110; VAR STRING LENGTH


POINT POINT VARIABLE DESCRIPTION
0 SERIAL NUMBER UP TO 12 CHARACTERS
1 MANUFACTURE DATE OF THE UNIT UP TO 8 CHARACTERS
2 SUBSTATION NAME UP TO 16 CHARACTERS
3 EQUIPMENT NAME UP TO 16 CHARACTERS

Time and Date


TIME AND DATE; OBJ 50; VAR 0, 1
POINT POINT VARIABLE DESCRIPTION
0 TIME AND DATE

32 www.qualitrolcorp.com
Modbus Protocol
General
Qualitrol supports the Modbus RTU transmission mode in which the message is
placed by the transmitting device into a frame that has a known beginning and
ending point. This allows the 509ITM unit to begin at the start of the message, read
the address portion and determine which device is addressed and to know when the
message is completed. Partial messages can be detected and errors can be set as
a result.
When addressing the 509ITM Modbus register map the registers are offset by one
(e.g. to read register 10 request address register 9).
To assist with the development of the Modbus communication for the user, there is a
web site, http://www.win-tech.com/html/demos.htm that offers evaluation software for
most applications.

Function Codes Supported


03 Read Holding Registers
06 Preset Single Register

Modbus Register Map


Binary Parameters
REG # VARIABLE R/W DESCRIPTION
10 RELAY 1 ENABLED READ 1 = ENABLED; 0 = DISABLED
11 RELAY 2 ENABLED READ 1 = ENABLED; 0 = DISABLED
12 RELAY 3 ENABLED READ 1 = ENABLED; 0 = DISABLED
13 RELAY 4 ENABLED READ 1 = ENABLED; 0 = DISABLED
14 RELAY 5 ENABLED READ 1 = ENABLED; 0 = DISABLED
15 RELAY 6 ENABLED READ 1 = ENABLED; 0 = DISABLED
16 RELAY 7 ENABLED READ 1 = ENABLED; 0 = DISABLED
17 RELAY 8 ENABLED READ 1 = ENABLED; 0 = DISABLED
18 RELAY 1 ACTUATED READ 1 = ACTUATED; 0 = NOT ACTUATED
19 RELAY 2 ACTUATED READ 1 = ACTUATED; 0 = NOT ACTUATED
20 RELAY 3 ACTUATED READ 1 = ACTUATED; 0 = NOT ACTUATED

33 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
21 RELAY 4 ACTUATED READ 1 = ACTUATED; 0 = NOT ACTUATED
22 RELAY 5 ACTUATED READ 1 = ACTUATED; 0 = NOT ACTUATED
23 RELAY 6 ACTUATED READ 1 = ACTUATED; 0 = NOT ACTUATED
24 RELAY 7 ACTUATED READ 1 = ACTUATED; 0 = NOT ACTUATED
25 RELAY 8 ACTUATED READ 1 = ACTUATED; 0 = NOT ACTUATED
26 SYSTEM STATUS RELAY READ 1 = ACTUATED; 0 = NOT ACTUATED
27 HEATER STATUS READ 1 = ENABLED; 0 = DISABLED
28 RELAY 1 LATCHING FEATURE READ 1 = ENABLED; 0 = DISABLED
29 RELAY 2 LATCHING FEATURE READ 1 = ENABLED; 0 = DISABLED
30 RELAY 3 LATCHING FEATURE READ 1 = ENABLED; 0 = DISABLED
31 RELAY 4 LATCHING FEATURE READ 1 = ENABLED; 0 = DISABLED
32 RELAY 5 LATCHING FEATURE READ 1 = ENABLED; 0 = DISABLED
33 RELAY 6 LATCHING FEATURE READ 1 = ENABLED; 0 = DISABLED
34 RELAY 7 LATCHING FEATURE READ 1 = ENABLED; 0 = DISABLED
35 RELAY 8 LATCHING FEATURE READ 1 = ENABLED; 0 = DISABLED
36 EVENT RECORDER 1 READ 1 = TRIGGERED; 0 = NOT TRIGGERED
37 EVENT RECORDER 2 READ 1 = TRIGGERED; 0 = NOT TRIGGERED
38 EVENT RECORDER 3 READ 1 = TRIGGERED; 0 = NOT TRIGGERED
39 EVENT RECORDER 4 READ 1 = TRIGGERED; 0 = NOT TRIGGERED
40 EVENT RECORDER 5 READ 1 = TRIGGERED; 0 = NOT TRIGGERED
41 EVENT RECORDER 6 READ 1 = TRIGGERED; 0 = NOT TRIGGERED
42 EVENT RECORDER 7 READ 1 = TRIGGERED; 0 = NOT TRIGGERED
43 EVENT RECORDER 8 READ 1 = TRIGGERED; 0 = NOT TRIGGERED

Binary Parameters
REG # VARIABLE R/W DESCRIPTION
50 RELAY 1 ENABLED RD/WR 1 = ENABLED; 0 = DISABLED
51 RELAY 2 ENABLED RD/WR 1 = ENABLED; 0 = DISABLED
52 RELAY 3 ENABLED RD/WR 1 = ENABLED; 0 = DISABLED
53 RELAY 4 ENABLED RD/WR 1 = ENABLED; 0 = DISABLED
54 RELAY 5 ENABLED RD/WR 1 = ENABLED; 0 = DISABLED
55 RELAY 6 ENABLED RD/WR 1 = ENABLED; 0 = DISABLED
56 RELAY 7 ENABLED RD/WR 1 = ENABLED; 0 = DISABLED
57 RELAY 8 ENABLED RD/WR 1 = ENABLED; 0 = DISABLED
58 INPUT MODULE MAX/MIN RESET RD/WR PULSE/RESET (1)
59 COOLING MONITOR MAX/MIN RESET RD/WR PULSE/RESET (1)
60 LATCHED RELAYS RESET RD/WR PULSE/RESET (1)
61 RELAY 1 AUTO/MANUAL RD/WR 1 = MANUAL OPERATION; 0 = AUTOMATIC
62 RELAY 2 AUTO/MANUAL RD/WR 1 = MANUAL OPERATION; 0 = AUTOMATIC
63 RELAY 3 AUTO/MANUAL RD/WR 1 = MANUAL OPERATION; 0 = AUTOMATIC
64 RELAY 4 AUTO/MANUAL RD/WR 1 = MANUAL OPERATION; 0 = AUTOMATIC
65 RELAY 5 AUTO/MANUAL RD/WR 1 = MANUAL OPERATION; 0 = AUTOMATIC
66 RELAY 6 AUTO/MANUAL RD/WR 1 = MANUAL OPERATION; 0 = AUTOMATIC
67 RELAY 7 AUTO/MANUAL RD/WR 1 = MANUAL OPERATION; 0 = AUTOMATIC
68 RELAY 8 AUTO/MANUAL RD/WR 1 = MANUAL OPERATION; 0 = AUTOMATIC
69 INPUT MODULE 1 ENABLED/DISABLED RD/WR 1 = ENABLED; 0 = DISABLED
70 INPUT MODULE 2 ENABLED/DISABLED RD/WR 1 = ENABLED; 0 = DISABLED

34 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
71 INPUT MODULE 3 ENABLED/DISABLED RD/WR 1 = ENABLED; 0 = DISABLED
72 INPUT MODULE 4 ENABLED/DISABLED RD/WR 1 = ENABLED; 0 = DISABLED
73 INPUT MODULE 5 ENABLED/DISABLED RD/WR 1 = ENABLED; 0 = DISABLED
74 INPUT MODULE 6 ENABLED/DISABLED RD/WR 1 = ENABLED; 0 = DISABLED
75 INPUT MODULE 7 ENABLED/DISABLED RD/WR 1 = ENABLED; 0 = DISABLED
76 INPUT MODULE 8 ENABLED/DISABLED RD/WR 1 = ENABLED; 0 = DISABLED
77 INPUT MODULE 1 READ ERROR READ 1 = READ ERROR; 0 = VALID READ
78 INPUT MODULE 2 READ ERROR READ 1 = READ ERROR; 0 = VALID READ
79 INPUT MODULE 3 READ ERROR READ 1 = READ ERROR; 0 = VALID READ
80 INPUT MODULE 4 READ ERROR READ 1 = READ ERROR; 0 = VALID READ
81 INPUT MODULE 5 READ ERROR READ 1 = READ ERROR; 0 = VALID READ
82 INPUT MODULE 6 READ ERROR READ 1 = READ ERROR; 0 = VALID READ
83 INPUT MODULE 7 READ ERROR READ 1 = READ ERROR; 0 = VALID READ
84 INPUT MODULE 8 READ ERROR READ 1 = READ ERROR; 0 = VALID READ
85 INPUT MODULE 1 SCALING ENABLED READ 1 = SCALING ENABLED; 0 = DISABLED
86 INPUT MODULE 2 SCALING ENABLED READ 1 = SCALING ENABLED; 0 = DISABLED
87 INPUT MODULE 3 SCALING ENABLED READ 1 = SCALING ENABLED; 0 = DISABLED
88 INPUT MODULE 4 SCALING ENABLED READ 1 = SCALING ENABLED; 0 = DISABLED
89 INPUT MODULE 5 SCALING ENABLED READ 1 = SCALING ENABLED; 0 = DISABLED
90 INPUT MODULE 6 SCALING ENABLED READ 1 = SCALING ENABLED; 0 = DISABLED
91 INPUT MODULE 7 SCALING ENABLED READ 1 = SCALING ENABLED; 0 = DISABLED
92 INPUT MODULE 8 SCALING ENABLED READ 1 = SCALING ENABLED; 0 = DISABLED

Analog Parameters
Values in registers 100 thru 693 have been scaled according to their function to offer the greatest
possible resolution. If the description of the value has a (N) then there is no scaling. A (10X) means
the value has been multiplied by 10 and needs to be divided by 10 to read the actual value (e.g. if the
value in the 509ITM is 123.4 then it will be transmitted 1234). A (100X) means the value was
multiplied by 100 and needs to be divided by 100 to read the actual value (e.g. if the value in the
509ITM is 12.34 then it will be transmitted as 1234).
REG # VARIABLE R/W DESCRIPTION
100 RELAY 1, SETPOINT 1 VALUE RD/WR SETPOINT IN THE 1ST COLUMN OF THE MATRIX (10X)
101 RELAY 2, SETPOINT 1 VALUE RD/WR SETPOINT IN THE 1ST COLUMN OF THE MATRIX (10X)
102 RELAY 3, SETPOINT 1 VALUE RD/WR SETPOINT IN THE 1ST COLUMN OF THE MATRIX (10X)
103 RELAY 4, SETPOINT 1 VALUE RD/WR SETPOINT IN THE 1ST COLUMN OF THE MATRIX (10X)
104 RELAY 5, SETPOINT 1 VALUE RD/WR SETPOINT IN THE 1ST COLUMN OF THE MATRIX (10X)
105 RELAY 6, SETPOINT 1 VALUE RD/WR SETPOINT IN THE 1ST COLUMN OF THE MATRIX (10X)
106 RELAY 7, SETPOINT 1 VALUE RD/WR SETPOINT IN THE 1ST COLUMN OF THE MATRIX (10X)
107 RELAY 8, SETPOINT 1 VALUE RD/WR SETPOINT IN THE 1ST COLUMN OF THE MATRIX (10X)
108 RELAY 1, HYSTERESIS 1 VALUE RD/WR HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX (10X)
109 RELAY 2, HYSTERESIS 1 VALUE RD/WR HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX (10X)
110 RELAY 3, HYSTERESIS 1 VALUE RD/WR HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX (10X)
111 RELAY 4, HYSTERESIS 1 VALUE RD/WR HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX (10X)
112 RELAY 5, HYSTERESIS 1 VALUE RD/WR HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX (10X)
113 RELAY 6, HYSTERESIS 1 VALUE RD/WR HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX (10X)
114 RELAY 7, HYSTERESIS 1 VALUE RD/WR HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX (10X)
115 RELAY 8, HYSTERESIS 1 VALUE RD/WR HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX (10X)

35 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION

ALL MODULES BUT CT, WINDING TEMPERATURE IF THE MODULE IS A CT, WINDING TEMPERATURE
116 INPUT MODULE 1 PRESENT VALUE READ OR INPUT MODULE 1 PRESENT WINDING TEMP (10X)
117 INPUT MODULE 1 MINIMUM VALUE READ OR INPUT MODULE 1 MINIMUM WINDING TEMP (10X)
118 INPUT MODULE 1 MAXIMUM VALUE READ OR INPUT MODULE 1 MAXIMUM WINDING TEMP (10X)
119 0 READ OR INPUT MODULE 1 PRESENT CURRENT (10X)
120 0 READ OR INPUT MODULE 1 MAXIMUM CURRENT (10X)
121 INPUT MODULE 2 PRESENT VALUE READ OR INPUT MODULE 2 PRESENT WINDING TEMP (10X)
122 INPUT MODULE 2 MINIMUM VALUE READ OR INPUT MODULE 2 MINIMUM WINDING TEMP (10X)
123 INPUT MODULE 2 MAXIMUM VALUE READ OR INPUT MODULE 2 MAXIMUM WINDING TEMP (10X)
124 0 READ OR INPUT MODULE 2 PRESENT CURRENT (10X)
125 0 READ OR INPUT MODULE 2 MAXIMUM CURRENT (10X)
126 INPUT MODULE 3 PRESENT VALUE READ OR INPUT MODULE 3 PRESENT WINDING TEMP (10X)
127 INPUT MODULE 3 MINIMUM VALUE READ OR INPUT MODULE 3 MINIMUM WINDING TEMP (10X)
128 INPUT MODULE 3 MAXIMUM VALUE READ OR INPUT MODULE 3 MAXIMUM WINDING TEMP (10X)
129 0 READ OR INPUT MODULE 3 PRESENT CURRENT (10X)
130 0 READ OR INPUT MODULE 3 MAXIMUM CURRENT (10X)
131 INPUT MODULE 4 PRESENT VALUE READ OR INPUT MODULE 4 PRESENT WINDING TEMP (10X)
132 INPUT MODULE 4 MINIMUM VALUE READ OR INPUT MODULE 4 MINIMUM WINDING TEMP (10X)
133 INPUT MODULE 4 MAXIMUM VALUE READ OR INPUT MODULE 4 MAXIMUM WINDING TEMP (10X)
134 0 READ OR INPUT MODULE 4 PRESENT CURRENT (10X)
135 0 READ OR INPUT MODULE 4 MAXIMUM CURRENT (10X)
136 INPUT MODULE 5 PRESENT VALUE READ OR INPUT MODULE 5 PRESENT WINDING TEMP (10X)
137 INPUT MODULE 5 MINIMUM VALUE READ OR INPUT MODULE 5 MINIMUM WINDING TEMP (10X)
138 INPUT MODULE 5 MAXIMUM VALUE READ OR INPUT MODULE 5 MAXIMUM WINDING TEMP (10X)
139 0 READ OR INPUT MODULE 5 PRESENT CURRENT (10X)
140 0 READ OR INPUT MODULE 5 MAXIMUM CURRENT (10X)
141 INPUT MODULE 6 PRESENT VALUE READ OR INPUT MODULE 6 PRESENT WINDING TEMP (10X)
142 INPUT MODULE 6 MINIMUM VALUE READ OR INPUT MODULE 6 MINIMUM WINDING TEMP (10X)
143 INPUT MODULE 6 MAXIMUM VALUE READ OR INPUT MODULE 6 MAXIMUM WINDING TEMP (10X)
144 0 READ OR INPUT MODULE 6 PRESENT CURRENT (10X)
145 0 READ OR INPUT MODULE 6 MAXIMUM CURRENT (10X)
146 INPUT MODULE 7 PRESENT VALUE READ OR INPUT MODULE 7 PRESENT WINDING TEMP (10X)
147 INPUT MODULE 7 MINIMUM VALUE READ OR INPUT MODULE 7 MINIMUM WINDING TEMP (10X)
148 INPUT MODULE 7 MAXIMUM VALUE READ OR INPUT MODULE 7 MAXIMUM WINDING TEMP (10X)
149 0 READ OR INPUT MODULE 7 PRESENT CURRENT (10X)
150 0 READ OR INPUT MODULE 7 MAXIMUM CURRENT (10X)
151 INPUT MODULE 8 PRESENT VALUE READ OR INPUT MODULE 8 PRESENT WINDING TEMP (10X)
152 INPUT MODULE 8 MINIMUM VALUE READ OR INPUT MODULE 8 MINIMUM WINDING TEMP (10X)
153 INPUT MODULE 8 MAXIMUM VALUE READ OR INPUT MODULE 8 MAXIMUM WINDING TEMP (10X)
154 0 READ OR INPUT MODULE 8 PRESENT CURRENT (10X)
155 0 READ OR INPUT MODULE 8 MAXIMUM CURRENT (10X)
156 DIFFERENTIAL CALCULATION 1 PRESENT VALUE READ (10X)
157 DIFFERENTIAL CALCULATION 1 MINIMUM VALUE READ (10X)
158 DIFFERENTIAL CALCULATION 1 MAXIMUM VALUE READ (10X)
159 DIFFERENTIAL CALCULATION 2 PRESENT VALUE READ (10X)
160 DIFFERENTIAL CALCULATION 2 MINIMUM VALUE READ (10X)
161 DIFFERENTIAL CALCULATION 2 MAXIMUM VALUE READ (10X)

36 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
162 DIFFERENTIAL CALCULATION 3 PRESENT VALUE READ (10X)
163 DIFFERENTIAL CALCULATION 3 MINIMUM VALUE READ (10X)
164 DIFFERENTIAL CALCULATION 3 MAXIMUM VALUE READ (10X)
165 DIFFERENTIAL CALCULATION 4 PRESENT VALUE READ (10X)
166 DIFFERENTIAL CALCULATION 4 MINIMUM VALUE READ (10X)
167 DIFFERENTIAL CALCULATION 4 MAXIMUM VALUE READ (10X)
168 HOTTEST PRESENT WINDING TEMPERATURE READ OF ALL ACTIVE CT, TEMPERATURE MODULES (10X)
169 TRANSLIFE 1 CONSUMED LIFE FOR LAST HOUR READ CALCULATED CONSUMED LIFE FOR LAST HOUR (100X)
170 TRANSLIFE 1 CONSUMED LIFE FOR LAST DAY READ CALCULATED CONSUMED LIFE FOR LAST DAY (100X)
171 TRANSLIFE 1 REMAINING TRANSFORMER LIFE READ (20 YEARS - CONSUMED LIFE) (100X)
1ST CRITICAL SPT TO CALCULATE TIME TO REACH
172 TL1 CRITICAL WINDING TEMP SETPOINT 1 RD/WR (10X)
2ND CRITICAL SPT TO CALCULATE TIME TO REACH
173 TL1 CRITICAL WINDING TEMP SETPOINT 2 RD/WR (10X)
3RD CRITICAL SPT TO CALCULATE TIME TO REACH
174 TL1 CRITICAL WINDING TEMP SETPOINT 3 RD/WR (10X)
CALCULATED TIME TO 1ST SPT FOR GIVEN
175 TL1 TIME TO CRITICAL SETPOINT 1 READ CONDITIONS (100X)
CALCULATED TIME TO 2ND SPT FOR GIVEN
176 TL1 TIME TO CRITICAL SETPOINT 2 READ CONDITIONS (100X)
CALCULATED TIME TO 3RD SPT FOR GIVEN
177 TL1 TIME TO CRITICAL SETPOINT 3 READ CONDITIONS (100X)
178 TRANSLIFE 2 CONSUMED LIFE FOR LAST HOUR READ CALCULATED CONSUMED LIFE FOR LAST HOUR (100X)
179 TRANSLIFE 2 CONSUMED LIFE FOR LAST DAY READ CALCULATED CONSUMED LIFE FOR LAST DAY (100X)
180 TRANSLIFE 2 REMAINING TRANSFORMER LIFE READ (20 YEARS - CONSUMED LIFE) (100X)
1ST CRITICAL SPT TO CALCULATE TIME TO REACH
181 TL2 CRITICAL WINDING TEMP SETPOINT 1 RD/WR (10X)
2ND CRITICAL SPT TO CALCULATE TIME TO REACH
182 TL2 CRITICAL WINDING TEMP SETPOINT 2 RD/WR (10X)
3RD CRITICAL SPT TO CALCULATE TIME TO REACH
183 TL2 CRITICAL WINDING TEMP SETPOINT 3 RD/WR (10X)
CALCULATED TIME TO 1ST SPT FOR GIVEN
184 TL2 TIME TO CRITICAL SETPOINT 1 READ CONDITIONS (100X)
CALCULATED TIME TO 2ND SPT FOR GIVEN
185 TL2 TIME TO CRITICAL SETPOINT 2 READ CONDITIONS (100X)
CALCULATED TIME TO 3RD SPT FOR GIVEN
186 TL2 TIME TO CRITICAL SETPOINT 3 READ CONDITIONS (100X)
187 TRANSLIFE 3 CONSUMED LIFE FOR LAST HOUR READ CALCULATED CONSUMED LIFE FOR LAST HOUR (100X)
188 TRANSLIFE 3 CONSUMED LIFE FOR LAST DAY READ CALCULATED CONSUMED LIFE FOR LAST DAY (100X)
189 TRANSLIFE 3 REMAINING TRANSFORMER LIFE READ (20 YEARS - CONSUMED LIFE) (100X)
1ST CRITICAL SPT TO CALCULATE TIME TO REACH
190 TL3 CRITICAL WINDING TEMP SETPOINT 1 RD/WR (10X)
2ND CRITICAL SPT TO CALCULATE TIME TO REACH
191 TL3 CRITICAL WINDING TEMP SETPOINT 2 RD/WR (10X)
3RD CRITICAL SPT TO CALCULATE TIME TO REACH
192 TL3 CRITICAL WINDING TEMP SETPOINT 3 RD/WR (10X)
CALCULATED TIME TO 1ST SPT FOR GIVEN
193 TL3 TIME TO CRITICAL SETPOINT 1 READ CONDITIONS (100X)
CALCULATED TIME TO 2ND SPT FOR GIVEN
194 TL3 TIME TO CRITICAL SETPOINT 2 READ CONDITIONS (100X)
CALCULATED TIME TO 3RD SPT FOR GIVEN
195 TL3 TIME TO CRITICAL SETPOINT 3 READ CONDITIONS (100X)
196 FIRMWARE REVISION FOR THIS 509ITM UNIT READ (100X)

COOLING BANK 1 PRESENT/STEADY STATE CURRENT


200 COOLING BANK 1 PRESENT RUNNING CURRENT READ (10X)
COOLING BANK 1 MINIMUM STEADY STATE CURRENT
201 COOLING BANK 1 MINIMUM RUNNING CURRENT READ (10X)
COOLING BANK 1 MAXIMUM STEADY STATE CURRENT
202 COOLING BANK 1 MAXIMUM RUNNING CURRENT READ (10X)

37 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
COOLING BANK 1 STEADY STATE CURRENT SETPOINT
203 CB1 RUNNING CURRENT UPPER SETPOINT RD/WR (10X)
COOLING BANK 1 STEADY STATE CURRENT SETPOINT
204 CB1 RUNNING CURRENT LOWER SETPOINT RD/WR (10X)
COOLING BANK 1 PRESENT PEAK INRUSH CURRENT
205 CB1 PRESENT PEAK INRUSH CURRENT VALUE READ (10X)
COOLING BANK 1 MINIMUM PEAK INRUSH CURRENT
206 CB1 MINIMUM PEAK INRUSH CURRENT VALUE READ (10X)
COOLING BANK 1 MAXIMUM PEAK INRUSH CURRENT
207 CB1 MAXIMUM PEAK INRUSH CURRENT VALUE READ (10X)
COOLING BANK 1 PEAK INRUSH CURRENT SETPOINT
208 CB1 INRUSH CURRENT UPPER SETPOINT VALUE RD/WR (10X)
COOLING BANK 1 PEAK INRUSH CURRENT SETPOINT
209 CB1 INRUSH CURRENT LOWER SETPOINT VALUE RD/WR (10X)
COOLING BANK 2 PRESENT/STEADY STATE CURRENT
210 COOLING BANK 2 PRESENT RUNNING CURRENT READ (10X)
COOLING BANK 2 MINIMUM STEADY STATE CURRENT
211 COOLING BANK 2 MINIMUM RUNNING CURRENT READ (10X)
COOLING BANK 2 MAXIMUM STEADY STATE CURRENT
212 COOLING BANK 2 MAXIMUM RUNNING CURRENT READ (10X)
COOLING BANK 2 STEADY STATE CURRENT SETPOINT
213 CB2 RUNNING CURRENT UPPER SETPOINT RD/WR (10X)
COOLING BANK 2 STEADY STATE CURRENT SETPOINT
214 CB2 RUNNING CURRENT LOWER SETPOINT RD/WR (10X)
COOLING BANK 2 PRESENT PEAK INRUSH CURRENT
215 CB2 PRESENT PEAK INRUSH CURRENT VALUE READ (10X)
COOLING BANK 2 MINIMUM PEAK INRUSH CURRENT
216 CB2 MINIMUM PEAK INRUSH CURRENT VALUE READ (10X)
COOLING BANK 2 MAXIMUM PEAK INRUSH CURRENT
217 CB2 MAXIMUM PEAK INRUSH CURRENT VALUE READ (10X)
COOLING BANK 2 PEAK INRUSH CURRENT SETPOINT
218 CB2 INRUSH CURRENT UPPER SETPOINT VALUE RD/WR (10X)
COOLING BANK 2 PEAK INRUSH CURRENT SETPOINT
219 CB2 INRUSH CURRENT LOWER SETPOINT VALUE RD/WR (10X)
COOLING BANK 3 PRESENT/STEADY STATE CURRENT
220 COOLING BANK 3 PRESENT RUNNING CURRENT READ (10X)
COOLING BANK 3 MINIMUM STEADY STATE CURRENT
221 COOLING BANK 3 MINIMUM RUNNING CURRENT READ (10X)
COOLING BANK 3 MAXIMUM STEADY STATE CURRENT
222 COOLING BANK 3 MAXIMUM RUNNING CURRENT READ (10X)
COOLING BANK 3 STEADY STATE CURRENT SETPOINT
223 CB3 RUNNING CURRENT UPPER SETPOINT RD/WR (10X)
COOLING BANK 3 STEADY STATE CURRENT SETPOINT
224 CB3 RUNNING CURRENT LOWER SETPOINT RD/WR (10X)
COOLING BANK 3 PRESENT PEAK INRUSH CURRENT
225 CB3 PRESENT PEAK INRUSH CURRENT VALUE READ (10X)
COOLING BANK 3 MINIMUM PEAK INRUSH CURRENT
226 CB3 MINIMUM PEAK INRUSH CURRENT VALUE READ (10X)
COOLING BANK 3 MAXIMUM PEAK INRUSH CURRENT
227 CB3 MAXIMUM PEAK INRUSH CURRENT VALUE READ (10X)
COOLING BANK 3 PEAK INRUSH CURRENT SETPOINT
228 CB3 INRUSH CURRENT UPPER SETPOINT VALUE RD/WR (10X)
COOLING BANK 3 PEAK INRUSH CURRENT SETPOINT
229 CB3 INRUSH CURRENT LOWER SETPOINT VALUE RD/WR (10X)
COOLING BANK 4 PRESENT/STEADY STATE CURRENT
230 COOLING BANK 4 PRESENT RUNNING CURRENT READ (10X)
COOLING BANK 4 MINIMUM STEADY STATE CURRENT
231 COOLING BANK 4 MINIMUM RUNNING CURRENT READ (10X)
COOLING BANK 4 MAXIMUM STEADY STATE CURRENT
232 COOLING BANK 4 MAXIMUM RUNNING CURRENT READ (10X)
COOLING BANK 4 STEADY STATE CURRENT SETPOINT
233 CB4 RUNNING CURRENT UPPER SETPOINT RD/WR (10X)
COOLING BANK 4 STEADY STATE CURRENT SETPOINT
234 CB4 RUNNING CURRENT LOWER SETPOINT RD/WR (10X)
COOLING BANK 4 PRESENT PEAK INRUSH CURRENT
235 CB4 PRESENT PEAK INRUSH CURRENT VALUE READ (10X)
236 CB4 MINIMUM PEAK INRUSH CURRENT VALUE READ COOLING BANK 4 MINIMUM PEAK INRUSH CURRENT

38 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
(10X)
COOLING BANK 4 MAXIMUM PEAK INRUSH CURRENT
237 CB4 MAXIMUM PEAK INRUSH CURRENT VALUE READ (10X)
COOLING BANK 4 PEAK INRUSH CURRENT SETPOINT
238 CB4 INRUSH CURRENT UPPER SETPOINT VALUE RD/WR (10X)
COOLING BANK 4 PEAK INRUSH CURRENT SETPOINT
239 CB4 INRUSH CURRENT LOWER SETPOINT VALUE RD/WR (10X)
240 RELAY 1 SETPOINT, 2nd COLUMN OF MATRIX RD/WR SETPOINT IN THE 2ND COLUMN OF THE MATRIX (10X)
241 RELAY 2 SETPOINT, 2nd COLUMN OF MATRIX RD/WR SETPOINT IN THE 2ND COLUMN OF THE MATRIX (10X)
242 RELAY 3 SETPOINT, 2nd COLUMN OF MATRIX RD/WR SETPOINT IN THE 2ND COLUMN OF THE MATRIX (10X)
243 RELAY 4 SETPOINT, 2nd COLUMN OF MATRIX RD/WR SETPOINT IN THE 2ND COLUMN OF THE MATRIX (10X)
244 RELAY 5 SETPOINT, 2nd COLUMN OF MATRIX RD/WR SETPOINT IN THE 2ND COLUMN OF THE MATRIX (10X)
245 RELAY 6 SETPOINT, 2nd COLUMN OF MATRIX RD/WR SETPOINT IN THE 2ND COLUMN OF THE MATRIX (10X)
246 RELAY 7 SETPOINT, 2nd COLUMN OF MATRIX RD/WR SETPOINT IN THE 2ND COLUMN OF THE MATRIX (10X)
247 RELAY 8 SETPOINT, 2nd COLUMN OF MATRIX RD/WR SETPOINT IN THE 2ND COLUMN OF THE MATRIX (10X)
HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
248 RELAY 1 HYSTERESIS, 2nd COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
249 RELAY 2 HYSTERESIS, 2nd COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
250 RELAY 3 HYSTERESIS, 2nd COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
251 RELAY 4 HYSTERESIS, 2nd COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
252 RELAY 5 HYSTERESIS, 2nd COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
253 RELAY 6 HYSTERESIS, 2nd COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
254 RELAY 7 HYSTERESIS, 2nd COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
255 RELAY 8 HYSTERESIS, 2nd COLUMN OF MATRIX RD/WR (10X)
256 RELAY 1 SETPOINT, 3rd COLUMN OF MATRIX RD/WR SETPOINT IN THE 3RD COLUMN OF THE MATRIX (10X)
257 RELAY 2 SETPOINT, 3rd COLUMN OF MATRIX RD/WR SETPOINT IN THE 3RD COLUMN OF THE MATRIX (10X)
258 RELAY 3 SETPOINT, 3rd COLUMN OF MATRIX RD/WR SETPOINT IN THE 3RD COLUMN OF THE MATRIX (10X)
259 RELAY 4 SETPOINT, 3rd COLUMN OF MATRIX RD/WR SETPOINT IN THE 3RD COLUMN OF THE MATRIX (10X)
260 RELAY 5 SETPOINT, 3rd COLUMN OF MATRIX RD/WR SETPOINT IN THE 3RD COLUMN OF THE MATRIX (10X)
261 RELAY 6 SETPOINT, 3rd COLUMN OF MATRIX RD/WR SETPOINT IN THE 3RD COLUMN OF THE MATRIX (10X)
262 RELAY 7 SETPOINT, 3rd COLUMN OF MATRIX RD/WR SETPOINT IN THE 3RD COLUMN OF THE MATRIX (10X)
263 RELAY 8 SETPOINT, 3rd COLUMN OF MATRIX RD/WR SETPOINT IN THE 3RD COLUMN OF THE MATRIX (10X)
HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
264 RELAY 1 HYSTERESIS, 3rd COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
265 RELAY 2 HYSTERESIS, 3rd COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
266 RELAY 3 HYSTERESIS, 3rd COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
267 RELAY 4 HYSTERESIS, 3rd COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
268 RELAY 5 HYSTERESIS, 3rd COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
269 RELAY 6 HYSTERESIS, 3rd COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
270 RELAY 7 HYSTERESIS, 3rd COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
271 RELAY 8 HYSTERESIS, 3rd COLUMN OF MATRIX RD/WR (10X)
272 RELAY 1 SETPOINT, 4th COLUMN OF MATRIX RD/WR SETPOINT IN THE 4TH COLUMN OF THE MATRIX (10X)
273 RELAY 2 SETPOINT, 4th COLUMN OF MATRIX RD/WR SETPOINT IN THE 4TH COLUMN OF THE MATRIX (10X)
274 RELAY 3 SETPOINT, 4th COLUMN OF MATRIX RD/WR SETPOINT IN THE 4TH COLUMN OF THE MATRIX (10X)
275 RELAY 4 SETPOINT, 4th COLUMN OF MATRIX RD/WR SETPOINT IN THE 4TH COLUMN OF THE MATRIX (10X)

39 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
276 RELAY 5 SETPOINT, 4th COLUMN OF MATRIX RD/WR SETPOINT IN THE 4TH COLUMN OF THE MATRIX (10X)
277 RELAY 6 SETPOINT, 4th COLUMN OF MATRIX RD/WR SETPOINT IN THE 4TH COLUMN OF THE MATRIX (10X)
278 RELAY 7 SETPOINT, 4th COLUMN OF MATRIX RD/WR SETPOINT IN THE 4TH COLUMN OF THE MATRIX (10X)
279 RELAY 8 SETPOINT, 4th COLUMN OF MATRIX RD/WR SETPOINT IN THE 4TH COLUMN OF THE MATRIX (10X)
HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
280 RELAY 1 HYSTERESIS, 4th COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
281 RELAY 2 HYSTERESIS, 4th COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
282 RELAY 3 HYSTERESIS, 4th COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
283 RELAY 4 HYSTERESIS, 4th COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
284 RELAY 5 HYSTERESIS, 4th COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
285 RELAY 6 HYSTERESIS, 4th COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
286 RELAY 7 HYSTERESIS, 4th COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
287 RELAY 8 HYSTERESIS, 4th COLUMN OF MATRIX RD/WR (10X)
288 TAP POSITION -16 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (-16) (N)
289 TAP POSITION -15 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (-15) (N)
290 TAP POSITION -14 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (-14) (N)
291 TAP POSITION -13 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (-13) (N)
292 TAP POSITION -12 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (-12) (N)
293 TAP POSITION -11 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (-11) (N)
294 TAP POSITION -10 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (-10) (N)
295 TAP POSITION -9 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (-9) (N)
296 TAP POSITION -8 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (-8) (N)
297 TAP POSITION -7 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (-7) (N)
298 TAP POSITION -6 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (-6) (N)
299 TAP POSITION -5 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (-5) (N)
300 TAP POSITION -4 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (-4) (N)
301 TAP POSITION -3 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (-3) (N)
302 TAP POSITION -2 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (-2) (N)
303 TAP POSITION -1 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (-1) (N)
304 TAP POSITION +0 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (+0) (N)
305 TAP POSITION +1 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (+1) (N)
306 TAP POSITION +2 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (+2) (N)
307 TAP POSITION +3 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (+3) (N)
308 TAP POSITION +4 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (+4) (N)
309 TAP POSITION +5 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (+5) (N)
310 TAP POSITION +6 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (+6) (N)
311 TAP POSITION +7 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (+7) (N)
312 TAP POSITION +8 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (+8) (N)
313 TAP POSITION +9 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (+9) (N)
314 TAP POSITION +10 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (+10) (N)
315 TAP POSITION +11 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (+11) (N)
316 TAP POSITION +12 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (+12) (N)
317 TAP POSITION +13 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (+13) (N)
318 TAP POSITION +14 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (+14) (N)
319 TAP POSITION +15 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (+15) (N)

40 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
320 TAP POSITION +16 AVERAGE MAKE CURRENT READ AVERAGE MAKE CURRENT FOR TAP POSITION (+16) (N)
AVERAGE BREAK CURRENT FOR TAP POSITION (-16)
321 TAP POSITION -16 AVERAGE BREAK CURRENT READ (N)
AVERAGE BREAK CURRENT FOR TAP POSITION (-15)
322 TAP POSITION -15 AVERAGE BREAK CURRENT READ (N)
AVERAGE BREAK CURRENT FOR TAP POSITION (-14)
323 TAP POSITION -14 AVERAGE BREAK CURRENT READ (N)
AVERAGE BREAK CURRENT FOR TAP POSITION (-13)
324 TAP POSITION -13 AVERAGE BREAK CURRENT READ (N)
AVERAGE BREAK CURRENT FOR TAP POSITION (-12)
325 TAP POSITION -12 AVERAGE BREAK CURRENT READ (N)
AVERAGE BREAK CURRENT FOR TAP POSITION (-11)
326 TAP POSITION -11 AVERAGE BREAK CURRENT READ (N)
AVERAGE BREAK CURRENT FOR TAP POSITION (-10)
327 TAP POSITION -10 AVERAGE BREAK CURRENT READ (N)
328 TAP POSITION -9 AVERAGE BREAK CURRENT READ AVERAGE BREAK CURRENT FOR TAP POSITION (-9) (N)
329 TAP POSITION -8 AVERAGE BREAK CURRENT READ AVERAGE BREAK CURRENT FOR TAP POSITION (-8) (N)
330 TAP POSITION -7 AVERAGE BREAK CURRENT READ AVERAGE BREAK CURRENT FOR TAP POSITION (-7) (N)
331 TAP POSITION -6 AVERAGE BREAK CURRENT READ AVERAGE BREAK CURRENT FOR TAP POSITION (-6) (N)
332 TAP POSITION -5 AVERAGE BREAK CURRENT READ AVERAGE BREAK CURRENT FOR TAP POSITION (-5) (N)
333 TAP POSITION -4 AVERAGE BREAK CURRENT READ AVERAGE BREAK CURRENT FOR TAP POSITION (-4) (N)
334 TAP POSITION -3 AVERAGE BREAK CURRENT READ AVERAGE BREAK CURRENT FOR TAP POSITION (-3) (N)
335 TAP POSITION -2 AVERAGE BREAK CURRENT READ AVERAGE BREAK CURRENT FOR TAP POSITION (-2) (N)
336 TAP POSITION -1 AVERAGE BREAK CURRENT READ AVERAGE BREAK CURRENT FOR TAP POSITION (-1) (N)
337 TAP POSITION +0 AVERAGE BREAK CURRENT READ AVERAGE BREAK CURRENT FOR TAP POSITION (+0) (N)
338 TAP POSITION +1 AVERAGE BREAK CURRENT READ AVERAGE BREAK CURRENT FOR TAP POSITION (+1) (N)
339 TAP POSITION +2 AVERAGE BREAK CURRENT READ AVERAGE BREAK CURRENT FOR TAP POSITION (+2) (N)
340 TAP POSITION +3 AVERAGE BREAK CURRENT READ AVERAGE BREAK CURRENT FOR TAP POSITION (+3) (N)
341 TAP POSITION +4 AVERAGE BREAK CURRENT READ AVERAGE BREAK CURRENT FOR TAP POSITION (+4) (N)
342 TAP POSITION +5 AVERAGE BREAK CURRENT READ AVERAGE BREAK CURRENT FOR TAP POSITION (+5) (N)
343 TAP POSITION +6 AVERAGE BREAK CURRENT READ AVERAGE BREAK CURRENT FOR TAP POSITION (+6) (N)
344 TAP POSITION +7 AVERAGE BREAK CURRENT READ AVERAGE BREAK CURRENT FOR TAP POSITION (+7) (N)
345 TAP POSITION +8 AVERAGE BREAK CURRENT READ AVERAGE BREAK CURRENT FOR TAP POSITION (+8) (N)
346 TAP POSITION +9 AVERAGE BREAK CURRENT READ AVERAGE BREAK CURRENT FOR TAP POSITION (+9) (N)
AVERAGE BREAK CURRENT FOR TAP POSITION (+10)
347 TAP POSITION +10 AVERAGE BREAK CURRENT READ (N)
AVERAGE BREAK CURRENT FOR TAP POSITION (+11)
348 TAP POSITION +11 AVERAGE BREAK CURRENT READ (N)
AVERAGE BREAK CURRENT FOR TAP POSITION (+12)
349 TAP POSITION +12 AVERAGE BREAK CURRENT READ (N)
AVERAGE BREAK CURRENT FOR TAP POSITION (+13)
350 TAP POSITION +13 AVERAGE BREAK CURRENT READ (N)
AVERAGE BREAK CURRENT FOR TAP POSITION (+14)
351 TAP POSITION +14 AVERAGE BREAK CURRENT READ (N)
AVERAGE BREAK CURRENT FOR TAP POSITION (+15)
352 TAP POSITION +15 AVERAGE BREAK CURRENT READ (N)
AVERAGE BREAK CURRENT FOR TAP POSITION (+16)
353 TAP POSITION +16 AVERAGE BREAK CURRENT READ (N)
LTC HIGH-PRIORITY STEADY STATE UPPER SETPOINT
354 LTC HI-ALARM RUN CURRENT UPPER SETPOINT RD/WR (10X)
LTC LOW-PRIORITY STEADY STATE UPPER SETPOINT
355 LTC LO-ALARM RUN CURRENT UPPER SETPOINT RD/WR (10X)
LTC HIGH-PRIORITY STEADY STATE LOWER SETPOINT
356 LTC HI-ALARM RUN CURRENT LOWER SETPOINT RD/WR (10X)
LTC LOW-PRIORITY STEADY STATE LOWER SETPOINT
357 LTC LO-ALARM RUN CURRENT LOWER SETPOINT RD/WR (10X)
LTC HI-ALARM INRUSH CURRENT UPPER LTC HIGH-PRIORITY INRUSH CURRENT UPPER
358 SETPOINT RD/WR SETPOINT (10X)
359 LTC LO-ALARM INRUSH CURRENT UPPER RD/WR LTC LOW-PRIORITY INRUSH CURRENT UPPER

41 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
SETPOINT SETPOINT (10X)
LTC HI-ALARM INRUSH CURRENT LOWER LTC HIGH-PRIORITY INRUSH CURRENT LOWER
360 SETPOINT RD/WR SETPOINT (10X)
LTC LO-ALARM INRUSH CURRENT LOWER LTC LOW-PRIORITY INRUSH CURRENT LOWER
361 SETPOINT RD/WR SETPOINT (10X)
HOT SPOT MODULE 1; 1ST PROBE PRESENT TEMP
362 MOD 1; FIBER PROBE 1 PRESENT TEMPERATURE READ (10X)
363 MOD 1; FIBER PROBE 1 MINIMUM TEMPERATURE READ HOT SPOT MODULE 1; 1ST PROBE MINIMUM TEMP (10X)
HOT SPOT MODULE 1; 1ST PROBE MAXIMUM TEMP
364 MOD 1; FIBER PROBE 1 MAXIMUM TEMPERATURE READ (10X)
HOT SPOT MODULE 1; 2ND PROBE PRESENT TEMP
365 MOD 1; FIBER PROBE 2 PRESENT TEMPERATURE READ (10X)
HOT SPOT MODULE 1; 2ND PROBE MINIMUM TEMP
366 MOD 1; FIBER PROBE 2 MINIMUM TEMPERATURE READ (10X)
HOT SPOT MODULE 1; 2ND PROBE MAXIMUM TEMP
367 MOD 1; FIBER PROBE 2 MAXIMUM TEMPERATURE READ (10X)
HOT SPOT MODULE 1; 3RD PROBE PRESENT TEMP
368 MOD 1; FIBER PROBE 3 PRESENT TEMPERATURE READ (10X)
HOT SPOT MODULE 1; 3RD PROBE MINIMUM TEMP
369 MOD 1; FIBER PROBE 3 MINIMUM TEMPERATURE READ (10X)
HOT SPOT MODULE 1; 3RD PROBE MAXIMUM TEMP
370 MOD 1; FIBER PROBE 3 MAXIMUM TEMPERATURE READ (10X)
HOT SPOT MODULE 1; 4TH PROBE PRESENT TEMP
371 MOD 1; FIBER PROBE 4 PRESENT TEMPERATURE READ (10X)
372 MOD 1; FIBER PROBE 4 MINIMUM TEMPERATURE READ HOT SPOT MODULE 1; 4TH PROBE MINIMUM TEMP (10X)
HOT SPOT MODULE 1; 4TH PROBE MAXIMUM TEMP
373 MOD 1; FIBER PROBE 4 MAXIMUM TEMPERATURE READ (10X)
HOT SPOT MODULE 1; 5TH PROBE PRESENT TEMP
374 MOD 1; FIBER PROBE 5 PRESENT TEMPERATURE READ (10X)
375 MOD 1; FIBER PROBE 5 MINIMUM TEMPERATURE READ HOT SPOT MODULE 1; 5TH PROBE MINIMUM TEMP (10X)
HOT SPOT MODULE 1; 5TH PROBE MAXIMUM TEMP
376 MOD 1; FIBER PROBE 5 MAXIMUM TEMPERATURE READ (10X)
HOT SPOT MODULE 1; 6TH PROBE PRESENT TEMP
377 MOD 1; FIBER PROBE 6 PRESENT TEMPERATURE READ (10X)
378 MOD 1; FIBER PROBE 6 MINIMUM TEMPERATURE READ HOT SPOT MODULE 1; 6TH PROBE MINIMUM TEMP (10X)
HOT SPOT MODULE 1; 6TH PROBE MAXIMUM TEMP
379 MOD 1; FIBER PROBE 6 MAXIMUM TEMPERATURE READ (10X)
HOT SPOT MODULE 1; 7TH PROBE PRESENT TEMP
380 MOD 1; FIBER PROBE 7 PRESENT TEMPERATURE READ (10X)
381 MOD 1; FIBER PROBE 7 MINIMUM TEMPERATURE READ HOT SPOT MODULE 1; 7TH PROBE MINIMUM TEMP (10X)
HOT SPOT MODULE 1; 7TH PROBE MAXIMUM TEMP
382 MOD 1; FIBER PROBE 7 MAXIMUM TEMPERATURE READ (10X)
HOT SPOT MODULE 1; 8TH PROBE PRESENT TEMP
383 MOD 1; FIBER PROBE 8 PRESENT TEMPERATURE READ (10X)
384 MOD 1; FIBER PROBE 8 MINIMUM TEMPERATURE READ HOT SPOT MODULE 1; 8TH PROBE MINIMUM TEMP (10X)
HOT SPOT MODULE 1; 8TH PROBE MAXIMUM TEMP
385 MOD 1; FIBER PROBE 8 MAXIMUM TEMPERATURE READ (10X)
HOT SPOT MODULE 2; 1ST PROBE PRESENT TEMP
386 MOD 2; FIBER PROBE 1 PRESENT TEMPERATURE READ (10X)
387 MOD 2; FIBER PROBE 1 MINIMUM TEMPERATURE READ HOT SPOT MODULE 2; 1ST PROBE MINIMUM TEMP (10X)
HOT SPOT MODULE 2; 1ST PROBE MAXIMUM TEMP
388 MOD 2; FIBER PROBE 1 MAXIMUM TEMPERATURE READ (10X)
HOT SPOT MODULE 2; 2ND PROBE PRESENT TEMP
389 MOD 2; FIBER PROBE 2 PRESENT TEMPERATURE READ (10X)
HOT SPOT MODULE 2; 2ND PROBE MINIMUM TEMP
390 MOD 2; FIBER PROBE 2 MINIMUM TEMPERATURE READ (10X)
HOT SPOT MODULE 2; 2ND PROBE MAXIMUM TEMP
391 MOD 2; FIBER PROBE 2 MAXIMUM TEMPERATURE READ (10X)
HOT SPOT MODULE 2; 3RD PROBE PRESENT TEMP
392 MOD 2; FIBER PROBE 3 PRESENT TEMPERATURE READ (10X)
HOT SPOT MODULE 2; 3RD PROBE MINIMUM TEMP
393 MOD 2; FIBER PROBE 3 MINIMUM TEMPERATURE READ (10X)
HOT SPOT MODULE 2; 3RD PROBE MAXIMUM TEMP
394 MOD 2; FIBER PROBE 3 MAXIMUM TEMPERATURE READ (10X)

42 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
HOT SPOT MODULE 2; 4TH PROBE PRESENT TEMP
395 MOD 2; FIBER PROBE 4 PRESENT TEMPERATURE READ (10X)
396 MOD 2; FIBER PROBE 4 MINIMUM TEMPERATURE READ HOT SPOT MODULE 2; 4TH PROBE MINIMUM TEMP (10X)
HOT SPOT MODULE 2; 4TH PROBE MAXIMUM TEMP
397 MOD 2; FIBER PROBE 4 MAXIMUM TEMPERATURE READ (10X)
HOT SPOT MODULE 2; 5TH PROBE PRESENT TEMP
398 MOD 2; FIBER PROBE 5 PRESENT TEMPERATURE READ (10X)
399 MOD 2; FIBER PROBE 5 MINIMUM TEMPERATURE READ HOT SPOT MODULE 2; 5TH PROBE MINIMUM TEMP (10X)
HOT SPOT MODULE 2; 5TH PROBE MAXIMUM TEMP
400 MOD 2; FIBER PROBE 5 MAXIMUM TEMPERATURE READ (10X)
HOT SPOT MODULE 2; 6TH PROBE PRESENT TEMP
401 MOD 2; FIBER PROBE 6 PRESENT TEMPERATURE READ (10X)
402 MOD 2; FIBER PROBE 6 MINIMUM TEMPERATURE READ HOT SPOT MODULE 2; 6TH PROBE MINIMUM TEMP (10X)
HOT SPOT MODULE 2; 6TH PROBE MAXIMUM TEMP
403 MOD 2; FIBER PROBE 6 MAXIMUM TEMPERATURE READ (10X)
HOT SPOT MODULE 2; 7TH PROBE PRESENT TEMP
404 MOD 2; FIBER PROBE 7 PRESENT TEMPERATURE READ (10X)
405 MOD 2; FIBER PROBE 7 MINIMUM TEMPERATURE READ HOT SPOT MODULE 2; 7TH PROBE MINIMUM TEMP (10X)
HOT SPOT MODULE 2; 7TH PROBE MAXIMUM TEMP
406 MOD 2; FIBER PROBE 7 MAXIMUM TEMPERATURE READ (10X)
HOT SPOT MODULE 2; 8TH PROBE PRESENT TEMP
407 MOD 2; FIBER PROBE 8 PRESENT TEMPERATURE READ (10X)
408 MOD 2; FIBER PROBE 8 MINIMUM TEMPERATURE READ HOT SPOT MODULE 2; 8TH PROBE MINIMUM TEMP (10X)
HOT SPOT MODULE 2; 8TH PROBE MAXIMUM TEMP
409 MOD 2; FIBER PROBE 8 MAXIMUM TEMPERATURE READ (10X)
PRESENT VALUE OF DIGITAL HYDROGEN SENSOR # 1
410 DGA HYDROGEN SENSOR 1, PRESENT VALUE READ (N)
MINIMUM VALUE OF DIGITAL HYDROGEN SENSOR # 1
411 DGA HYDROGEN SENSOR 1, MINIMUM VALUE READ (N)
MAXIMUM VALUE OF DIGTIAL HYDROGEN SENSOR # 1
412 DGA HYDROGEN SENSOR 1, MAXIMUM VALUE READ (N)
PRESENT VALUE OF DIGITAL HYDROGEN SENSOR # 2
413 DGA HYDROGEN SENSOR 2, PRESENT VALUE READ (N)
MINIMUM VALUE OF DIGITAL HYDROGEN SENSOR # 2
414 DGA HYDROGEN SENSOR 2, MINIMUM VALUE READ (N)
MAXIMUM VALUE OF DIGTIAL HYDROGEN SENSOR # 2
415 DGA HYDROGEN SENSOR 2, MAXIMUM VALUE READ (N)
PRESENT VALUE OF DIGITAL HYDROGEN SENSOR # 3
416 DGA HYDROGEN SENSOR 3, PRESENT VALUE READ (N)
MINIMUM VALUE OF DIGITAL HYDROGEN SENSOR # 3
417 DGA HYDROGEN SENSOR 3, MINIMUM VALUE READ (N)
MAXIMUM VALUE OF DIGTIAL HYDROGEN SENSOR # 3
418 DGA HYDROGEN SENSOR 3, MAXIMUM VALUE READ (N)

TEMP WHERE CONSUMED LIFE EQUALS OPERATING


450 LIFE CONSUMPTION UNITY TEMPERATURE READ LIFE (N)
451 LTC TAP PERIOD READ TIME PERIOD TO MEASURE LTC TAP COUNTS (N)
452 LTC PRESENT COUNTS READ TOTAL COUNTS IN PRESENT TAP PERIOD (N)
453 LTC PREVIOUS COUNTS READ TOTAL COUNTS IN THE PREVIOUS TAP PERIOD (N)
454 INSTALLED DIGITAL SENSORS READ BIT 16 = FIBER MOD 1 INSTALLED; BIT 15 = MOD 2 (N)
455 PRESENT YEAR READ TODAY'S YEAR IN THE 509ITM UNIT (N)
456 PRESENT MONTH READ TODAY'S MONTH IN THE 509ITM UNIT (N)
457 PRESENT DATE READ TODAY'S DAY IN THE 509ITM UNIT (1 - 31) (N)
458 PRESENT HOUR READ PRESENT HOUR (0 - 23) (N)
459 PRESENT MINUTE READ PRESENT MINUTE (0 - 59) (N)
460 PRESENT SECOND READ PRESENT SECOND (0 - 59) (N)
461 TOTAL NUMBER OF TAPS IN THE LTC READ (E.G. 33, 17, 9) (N)
MODULE NUMBER IF THERE IS AN AMBIENT SENSOR
462 AMBIENT TEMPERATURE MODULE NUMBER READ (N)
463 TRANSFORMER LIFE SPAN READ ENTERED TRANSFORMER LIFE SPAN IN YEARS

43 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION

465 COOLING EXERCISER RUN TIME READ MINUTES FAN EXERCISER WILL RUN WHEN ACTIVE (N)
DAYS BETWEEN EXERCISER RUN TIME BEING ACTIVE
466 COOLING EXERCISER CYCLE TIME READ (N)
467 COOLING EXERCISER START TIME READ HOUR TO BEGIN FAN EXERCISER IN MILITARY TIME (N)
468 STARTING MONTH FOR SEASONAL SETPOINT READ RELAY FEATURE (1 - 12) (N)
469 STARTING DAY FOR SEASONAL SETPOINT READ RELAY FEATURE (1 - 31) (N)
470 ENDING MONTH FOR SEASONAL SETPOINT READ RELAY FEATURE (1 - 12) (N)
471 ENDING DAY FOR SEASONAL SETPOINT READ RELAY FEATURE (1 - 31) (N)
472 AMBIENT TEMPERATURE FORECAST SETPOINT READ RELAY FEATURE (N)
# OF HOURS TO EXCEED SETPOINT FOR ACTIVE
473 AMBIENT TEMPERATURE THRESHOLD HOURS READ FEATURE (N)
ROLLING PERIOD IN HOURS TO MEASURE THRESHOLD
474 AMBIENT TEMPERATURE MEASUREMENT PERIOD READ TEMP (N)
MODULE NUMBER MEASURING AMBIENT MODULE NUMBER IF THERE IS AN AMBIENT SENSOR
475 TEMPERATURE READ (N)

492 RELAY 1, ACTUATION COUNTS READ ACTUATION COUNTER FOR RELAY 1


493 RELAY 2, ACTUATION COUNTS READ ACTUATION COUNTER FOR RELAY 2
494 RELAY 3, ACTUATION COUNTS READ ACTUATION COUNTER FOR RELAY 3
495 RELAY 4, ACTUATION COUNTS READ ACTUATION COUNTER FOR RELAY 4
496 RELAY 5, ACTUATION COUNTS READ ACTUATION COUNTER FOR RELAY 5
497 RELAY 6, ACTUATION COUNTS READ ACTUATION COUNTER FOR RELAY 6
498 RELAY 7, ACTUATION COUNTS READ ACTUATION COUNTER FOR RELAY 7
499 RELAY 8, ACTUATION COUNTS READ ACTUATION COUNTER FOR RELAY 8
500 RELAY 1, RATE OF CHANGE TIME PERIOD READ RATE OF CHANGE TIME PERIOD FOR RELAY 1
501 RELAY 2, RATE OF CHANGE TIME PERIOD READ RATE OF CHANGE TIME PERIOD FOR RELAY 2
502 RELAY 3, RATE OF CHANGE TIME PERIOD READ RATE OF CHANGE TIME PERIOD FOR RELAY 3
503 RELAY 4, RATE OF CHANGE TIME PERIOD READ RATE OF CHANGE TIME PERIOD FOR RELAY 4
504 RELAY 5, RATE OF CHANGE TIME PERIOD READ RATE OF CHANGE TIME PERIOD FOR RELAY 5
505 RELAY 6, RATE OF CHANGE TIME PERIOD READ RATE OF CHANGE TIME PERIOD FOR RELAY 6
506 RELAY 7, RATE OF CHANGE TIME PERIOD READ RATE OF CHANGE TIME PERIOD FOR RELAY 7
507 RELAY 8, RATE OF CHANGE TIME PERIOD READ RATE OF CHANGE TIME PERIOD FOR RELAY 8

COOLING BANK 1 STEADY STATE CURRENT SETPOINT


516 CB1 RUNNING CURRENT UPPER SETPOINT VALUE RD/WR (10X)
COOLING BANK 1 STEADY STATE CURRENT SETPOINT
517 CB1 RUNNING CURRENT LOWER SETPOINT VALUE RD/WR (10X)
COOLING BANK 1 PEAK INRUSH CURRENT SETPOINT
518 CB1 INRUSH CURRENT UPPER SETPOINT VALUE RD/WR (10X)
COOLING BANK 1 PEAK INRUSH CURRENT SETPOINT
519 CB1 INRUSH CURRENT LOWER SETPOINT VALUE RD/WR (10X)
COOLING BANK 2 STEADY STATE CURRENT SETPOINT
520 CB2 RUNNING CURRENT UPPER SETPOINT VALUE RD/WR (10X)
COOLING BANK 2 STEADY STATE CURRENT SETPOINT
521 CB2 RUNNING CURRENT LOWER SETPOINT VALUE RD/WR (10X)
COOLING BANK 2 PEAK INRUSH CURRENT SETPOINT
522 CB2 INRUSH CURRENT UPPER SETPOINT VALUE RD/WR (10X)
COOLING BANK 2 PEAK INRUSH CURRENT SETPOINT
523 CB2 INRUSH CURRENT LOWER SETPOINT VALUE RD/WR (10X)
COOLING BANK 3 STEADY STATE CURRENT SETPOINT
524 CB3 RUNNING CURRENT UPPER SETPOINT VALUE RD/WR (10X)
COOLING BANK 3 STEADY STATE CURRENT SETPOINT
525 CB3 RUNNING CURRENT LOWER SETPOINT VALUE RD/WR (10X)
COOLING BANK 3 PEAK INRUSH CURRENT SETPOINT
526 CB3 INRUSH CURRENT UPPER SETPOINT VALUE RD/WR (10X)

44 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
COOLING BANK 3 PEAK INRUSH CURRENT SETPOINT
527 CB3 INRUSH CURRENT LOWER SETPOINT VALUE RD/WR (10X)
COOLING BANK 4 STEADY STATE CURRENT SETPOINT
528 CB4 RUNNING CURRENT UPPER SETPOINT VALUE RD/WR (10X)
COOLING BANK 4 STEADY STATE CURRENT SETPOINT
529 CB4 RUNNING CURRENT LOWER SETPOINT VALUE RD/WR (10X)
COOLING BANK 4 PEAK INRUSH CURRENT SETPOINT
530 CB4 INRUSH CURRENT UPPER SETPOINT VALUE RD/WR (10X)
COOLING BANK 4 PEAK INRUSH CURRENT SETPOINT
531 CB4 INRUSH CURRENT LOWER SETPOINT VALUE RD/WR (10X)
AVERAGE RUNNING CURRENT FROM LEARN MODE
532 CB1 RUNNING CURRENT AVERAGE READ (10X)
533 CB1 INRUSH CURRENT AVERAGE READ AVERAGE INRUSH CURRENT FROM LEARN MODE (10X)
534 CB1 DIFFERENTIAL TEMPERATURE SETPOINT RD/WR DIFFERENTIAL SETPOINT FOR COOLING BANK 1 (10X)
DIFFERENTIAL HYSTERESIS FOR COOLING BANK 1
535 CB1 DIFFERENTIAL TEMPERATURE HYSTERESIS RD/WR (10X)
AVERAGE RUNNING CURRENT FROM LEARN MODE
536 CB2 RUNNING CURRENT AVERAGE READ (10X)
537 CB2 INRUSH CURRENT AVERAGE READ AVERAGE INRUSH CURRENT FROM LEARN MODE (10X)
538 CB2 DIFFERENTIAL TEMPERATURE SETPOINT RD/WR DIFFERENTIAL SETPOINT FOR COOLING BANK 2 (10X)
DIFFERENTIAL HYSTERESIS FOR COOLING BANK 2
539 CB2 DIFFERENTIAL TEMPERATURE HYSTERESIS RD/WR (10X)
AVERAGE RUNNING CURRENT FROM LEARN MODE
540 CB3 RUNNING CURRENT AVERAGE READ (10X)
541 CB3 INRUSH CURRENT AVERAGE READ AVERAGE INRUSH CURRENT FROM LEARN MODE (10X)
542 CB3 DIFFERENTIAL TEMPERATURE SETPOINT RD/WR DIFFERENTIAL SETPOINT FOR COOLING BANK 3 (10X)
DIFFERENTIAL HYSTERESIS FOR COOLING BANK 3
543 CB3 DIFFERENTIAL TEMPERATURE HYSTERESIS RD/WR (10X)
AVERAGE RUNNING CURRENT FROM LEARN MODE
544 CB4 RUNNING CURRENT AVERAGE READ (10X)
545 CB4 INRUSH CURRENT AVERAGE READ AVERAGE INRUSH CURRENT FROM LEARN MODE (10X)
546 CB4 DIFFERENTIAL TEMPERATURE SETPOINT RD/WR DIFFERENTIAL SETPOINT FOR COOLING BANK 4 (10X)
DIFFERENTIAL HYSTERESIS FOR COOLING BANK 4
547 CB4 DIFFERENTIAL TEMPERATURE HYSTERESIS RD/WR (10X)

560 CURRENT LOOP 1 CONTROL SIGNAL READ VALUE OF SIGNAL CONTROLLING LOOP 1 (10X)
561 CURRENT LOOP 2 CONTROL SIGNAL READ VALUE OF SIGNAL CONTROLLING LOOP 2 (10X)
562 CURRENT LOOP 3 CONTROL SIGNAL READ VALUE OF SIGNAL CONTROLLING LOOP 3 (10X)
563 CURRENT LOOP 4 CONTROL SIGNAL READ VALUE OF SIGNAL CONTROLLING LOOP 4 (10X)
564 CURRENT LOOP 1 MINIMUM SCALING RANGE READ MINIMUM SCALING VALUE FOR CURRENT LOOP 1 (10X)
565 CURRENT LOOP 2 MINIMUM SCALING RANGE READ MINIMUM SCALING VALUE FOR CURRENT LOOP 2 (10X)
566 CURRENT LOOP 3 MINIMUM SCALING RANGE READ MINIMUM SCALING VALUE FOR CURRENT LOOP 3 (10X)
567 CURRENT LOOP 4 MINIMUM SCALING RANGE READ MINIMUM SCALING VALUE FOR CURRENT LOOP 4 (10X)
568 CURRENT LOOP 1 MAXIMUM SCALING RANGE READ MAXIMUM SCALING VALUE FOR CURRENT LOOP 1 (10X)
569 CURRENT LOOP 2 MAXIMUM SCALING RANGE READ MAXIMUM SCALING VALUE FOR CURRENT LOOP 2 (10X)
570 CURRENT LOOP 3 MAXIMUM SCALING RANGE READ MAXIMUM SCALING VALUE FOR CURRENT LOOP 3 (10X)
571 CURRENT LOOP 4 MAXIMUM SCALING RANGE READ MAXIMUM SCALING VALUE FOR CURRENT LOOP 4 (10X)

AMBIENT LOOKBACK FEATURE SETPOINT FOR RELAY 1


600 RELAY 1 AMBIENT SETPOINT VALUE RD/WR (10X)
AMBIENT LOOKBACK FEATURE SETPOINT FOR RELAY 2
601 RELAY 2 AMBIENT SETPOINT VALUE RD/WR (10X)
AMBIENT LOOKBACK FEATURE SETPOINT FOR RELAY 3
602 RELAY 3 AMBIENT SETPOINT VALUE RD/WR (10X)
AMBIENT LOOKBACK FEATURE SETPOINT FOR RELAY 4
603 RELAY 4 AMBIENT SETPOINT VALUE RD/WR (10X)
AMBIENT LOOKBACK FEATURE SETPOINT FOR RELAY 5
604 RELAY 5 AMBIENT SETPOINT VALUE RD/WR (10X)

45 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
AMBIENT LOOKBACK FEATURE SETPOINT FOR RELAY 6
605 RELAY 6 AMBIENT SETPOINT VALUE RD/WR (10X)
AMBIENT LOOKBACK FEATURE SETPOINT FOR RELAY 7
606 RELAY 7 AMBIENT SETPOINT VALUE RD/WR (10X)
AMBIENT LOOKBACK FEATURE SETPOINT FOR RELAY 8
607 RELAY 8 AMBIENT SETPOINT VALUE RD/WR (10X)
608 RELAY 1 SEASONAL SETPOINT VALUE RD/WR SEASONAL SETPOINT VALUE (10X)
609 RELAY 2 SEASONAL SETPOINT VALUE RD/WR SEASONAL SETPOINT VALUE (10X)
610 RELAY 3 SEASONAL SETPOINT VALUE RD/WR SEASONAL SETPOINT VALUE (10X)
611 RELAY 4 SEASONAL SETPOINT VALUE RD/WR SEASONAL SETPOINT VALUE (10X)
612 RELAY 5 SEASONAL SETPOINT VALUE RD/WR SEASONAL SETPOINT VALUE (10X)
613 RELAY 6 SEASONAL SETPOINT VALUE RD/WR SEASONAL SETPOINT VALUE (10X)
614 RELAY 7 SEASONAL SETPOINT VALUE RD/WR SEASONAL SETPOINT VALUE (10X)
615 RELAY 8 SEASONAL SETPOINT VALUE RD/WR SEASONAL SETPOINT VALUE (10X)

632 RELAY 1 ACTUATION DELAY - HOURS VALUE RD/WR ACTUATION DELAY - HOURS (N)
633 RELAY 2 ACTUATION DELAY - HOURS VALUE RD/WR ACTUATION DELAY - HOURS (N)
634 RELAY 3 ACTUATION DELAY - HOURS VALUE RD/WR ACTUATION DELAY - HOURS (N)
635 RELAY 4 ACTUATION DELAY - HOURS VALUE RD/WR ACTUATION DELAY - HOURS (N)
636 RELAY 5 ACTUATION DELAY - HOURS VALUE RD/WR ACTUATION DELAY - HOURS (N)
637 RELAY 6 ACTUATION DELAY - HOURS VALUE RD/WR ACTUATION DELAY - HOURS (N)
638 RELAY 7 ACTUATION DELAY - HOURS VALUE RD/WR ACTUATION DELAY - HOURS (N)
639 RELAY 8 ACTUATION DELAY - HOURS VALUE RD/WR ACTUATION DELAY - HOURS (N)
640 RELAY 1 ACTUATION DELAY - MINUTES VALUE RD/WR ACTUATION DELAY - MINUTES (N)
641 RELAY 2 ACTUATION DELAY - MINUTES VALUE RD/WR ACTUATION DELAY - MINUTES (N)
642 RELAY 3 ACTUATION DELAY - MINUTES VALUE RD/WR ACTUATION DELAY - MINUTES (N)
643 RELAY 4 ACTUATION DELAY - MINUTES VALUE RD/WR ACTUATION DELAY - MINUTES (N)
644 RELAY 5 ACTUATION DELAY - MINUTES VALUE RD/WR ACTUATION DELAY - MINUTES (N)
645 RELAY 6 ACTUATION DELAY - MINUTES VALUE RD/WR ACTUATION DELAY - MINUTES (N)
646 RELAY 7 ACTUATION DELAY - MINUTES VALUE RD/WR ACTUATION DELAY - MINUTES (N)
647 RELAY 8 ACTUATION DELAY - MINUTES VALUE RD/WR ACTUATION DELAY - MINUTES (N)
648 RELAY 1 ACTUATION DELAY - SECONDS VALUE RD/WR ACTUATION DELAY - SECONDS (N)
649 RELAY 2 ACTUATION DELAY - SECONDS VALUE RD/WR ACTUATION DELAY - SECONDS (N)
650 RELAY 3 ACTUATION DELAY - SECONDS VALUE RD/WR ACTUATION DELAY - SECONDS (N)
651 RELAY 4 ACTUATION DELAY - SECONDS VALUE RD/WR ACTUATION DELAY - SECONDS (N)
652 RELAY 5 ACTUATION DELAY - SECONDS VALUE RD/WR ACTUATION DELAY - SECONDS (N)
653 RELAY 6 ACTUATION DELAY - SECONDS VALUE RD/WR ACTUATION DELAY - SECONDS (N)
654 RELAY 7 ACTUATION DELAY - SECONDS VALUE RD/WR ACTUATION DELAY - SECONDS (N)
655 RELAY 8 ACTUATION DELAY - SECONDS VALUE RD/WR ACTUATION DELAY - SECONDS (N)

691 TRANSLIFE 1 PRESENT CONSUMED LIFE RATE READ INSTANTANEOUS LIFE RATE (100X)
692 TRANSLIFE 2 PRESENT CONSUMED LIFE RATE READ INSTANTANEOUS LIFE RATE (100X)
693 TRANSLIFE 3 PRESENT CONSUMED LIFE RATE READ INSTANTANEOUS LIFE RATE (100X)

Analog Parameters
For Registers 702 thru 847 the parameters are 32 bits long with the even registers holding the low
word and the high registers holding the high word (e.g. 702 low word; 703 high word).

46 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
TOTAL LIFE CONSUMPTION CALCULATED; TRANSLIFE 1
702 TRANSLIFE 1; TRANSFORMER LIFE CONSUMPTION READ (N)
TOTAL LIFE CONSUMPTION CALCULATED; TRANSLIFE 2
704 TRANSLIFE 2; TRANSFORMER LIFE CONSUMPTION READ (N)
TOTAL LIFE CONSUMPTION CALCULATED; TRANSLIFE 3
706 TRANSLIFE 3; TRANSFORMER LIFE CONSUMPTION READ (N)
708 TOTAL TRANSFORMER OPERATING HOURS READ CUMULATIVE TRANSFORMER OPERATING HOURS (N)
TOTAL # OF TIMES THE COOLING FANS HAVE
710 COOLING BANK 1 TOTAL ACTUATION COUNTS READ ENGAGED (N)
712 COOLING BANK 1 ACTUATION SETPOINT VALUE READ TOTAL ACTUATION COUNT SETPOINT (N)
714 COOLING BANK 1 TOTAL SYSTEM RUN TIME READ TOTAL # OF HOURS THAT THE FANS HAVE BEEN ON (N)
716 COOLING BANK 1 RUN TIME SETPOINT VALUE READ TOTAL RUN TIME SETPOINT (N)
TOTAL # OF TIMES THE COOLING FANS HAVE
718 COOLING BANK 2 TOTAL ACTUATION COUNTS READ ENGAGED (N)
720 COOLING BANK 2 ACTUATION SETPOINT VALUE READ TOTAL ACTUATION COUNT SETPOINT (N)
722 COOLING BANK 2 TOTAL SYSTEM RUN TIME READ TOTAL # OF HOURS THAT THE FANS HAVE BEEN ON (N)
724 COOLING BANK 2 RUN TIME SETPOINT VALUE READ TOTAL RUN TIME SETPOINT (N)
TOTAL # OF TIMES THE COOLING FANS HAVE
726 COOLING BANK 3 TOTAL ACTUATION COUNTS READ ENGAGED (N)
728 COOLING BANK 3 ACTUATION SETPOINT VALUE READ TOTAL ACTUATION COUNT SETPOINT (N)
730 COOLING BANK 3 TOTAL SYSTEM RUN TIME READ TOTAL # OF HOURS THAT THE FANS HAVE BEEN ON (N)
732 COOLING BANK 3 RUN TIME SETPOINT VALUE READ TOTAL RUN TIME SETPOINT (N)
TOTAL # OF TIMES THE COOLING FANS HAVE
734 COOLING BANK 4 TOTAL ACTUATION COUNTS READ ENGAGED (N)
736 COOLING BANK 4 ACTUATION SETPOINT VALUE READ TOTAL ACTUATION COUNT SETPOINT (N)
738 COOLING BANK 4 TOTAL SYSTEM RUN TIME READ TOTAL # OF HOURS THAT THE FANS HAVE BEEN ON (N)
740 COOLING BANK 4 RUN TIME SETPOINT VALUE READ TOTAL RUN TIME SETPOINT (N)
LIFE 'A' VALUE FOR CALCULATING CONSUMED LIFE
742 TRANSLIFE VARIABLE 'A' VALUE READ (10X)
LIFE 'B' VALUE FOR CALCULATING CONSUMED LIFE
744 TRANSLIFE VARIABLE 'B' VALUE READ (10X)

TRANSLIFE 1; TEMPERATURE PROFILE, 1ST TOTAL WINDING TEMP TIME IN LOWEST TEMP RANGE
748 RANGE READ (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 2ND
750 RANGE READ TOTAL WINDING TEMP TIME IN 2ND TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 3RD
752 RANGE READ TOTAL WINDING TEMP TIME IN 3RD TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 4TH
754 RANGE READ TOTAL WINDING TEMP TIME IN 4TH TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 5TH
756 RANGE READ TOTAL WINDING TEMP TIME IN 5TH TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 6TH
758 RANGE READ TOTAL WINDING TEMP TIME IN 6TH TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 7TH
760 RANGE READ TOTAL WINDING TEMP TIME IN 7TH TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 8TH
762 RANGE READ TOTAL WINDING TEMP TIME IN 8TH TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 9TH
764 RANGE READ TOTAL WINDING TEMP TIME IN 9TH TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 10TH
766 RANGE READ TOTAL WINDING TEMP TIME IN 10TH TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 11TH
768 RANGE READ TOTAL WINDING TEMP TIME IN 11TH TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 12TH TOTAL WINDING TEMP TIME IN HIGHEST TEMP RANGE
770 RANGE READ (N)
TRANSLIFE 2; TEMPERATURE PROFILE, 1ST TOTAL WINDING TEMP TIME IN LOWEST TEMP RANGE
772 RANGE READ (N)
TRANSLIFE 2; TEMPERATURE PROFILE, 2ND
774 RANGE READ TOTAL WINDING TEMP TIME IN 2ND TEMP RANGE (N)

47 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
TRANSLIFE 2; TEMPERATURE PROFILE, 3RD
776 RANGE READ TOTAL WINDING TEMP TIME IN 3RD TEMP RANGE (N)
TRANSLIFE 2; TEMPERATURE PROFILE, 4TH
778 RANGE READ TOTAL WINDING TEMP TIME IN 4TH TEMP RANGE (N)
TRANSLIFE 2; TEMPERATURE PROFILE, 5TH
780 RANGE READ TOTAL WINDING TEMP TIME IN 5TH TEMP RANGE (N)
TRANSLIFE 2; TEMPERATURE PROFILE, 6TH
782 RANGE READ TOTAL WINDING TEMP TIME IN 6TH TEMP RANGE (N)
TRANSLIFE 2; TEMPERATURE PROFILE, 7TH
784 RANGE READ TOTAL WINDING TEMP TIME IN 7TH TEMP RANGE (N)
TRANSLIFE 2; TEMPERATURE PROFILE, 8TH
786 RANGE READ TOTAL WINDING TEMP TIME IN 8TH TEMP RANGE (N)
TRANSLIFE 2; TEMPERATURE PROFILE, 9TH
788 RANGE READ TOTAL WINDING TEMP TIME IN 9TH TEMP RANGE (N)
TRANSLIFE 2; TEMPERATURE PROFILE, 10TH
790 RANGE READ TOTAL WINDING TEMP TIME IN 10TH TEMP RANGE (N)
TRANSLIFE 2; TEMPERATURE PROFILE, 11TH
792 RANGE READ TOTAL WINDING TEMP TIME IN 11TH TEMP RANGE (N)
TRANSLIFE 2; TEMPERATURE PROFILE, 12TH TOTAL WINDING TEMP TIME IN HIGHEST TEMP RANGE
794 RANGE READ (N)
TRANSLIFE 3; TEMPERATURE PROFILE, 1ST TOTAL WINDING TEMP TIME IN LOWEST TEMP RANGE
796 RANGE READ (N)
TRANSLIFE 3; TEMPERATURE PROFILE, 2ND
798 RANGE READ TOTAL WINDING TEMP TIME IN 2ND TEMP RANGE (N)
TRANSLIFE 3; TEMPERATURE PROFILE, 3RD
800 RANGE READ TOTAL WINDING TEMP TIME IN 3RD TEMP RANGE (N)
TRANSLIFE 3; TEMPERATURE PROFILE, 4TH
802 RANGE READ TOTAL WINDING TEMP TIME IN 4TH TEMP RANGE (N)
TRANSLIFE 3; TEMPERATURE PROFILE, 5TH
804 RANGE READ TOTAL WINDING TEMP TIME IN 5TH TEMP RANGE (N)
TRANSLIFE 3; TEMPERATURE PROFILE, 6TH
806 RANGE READ TOTAL WINDING TEMP TIME IN 6TH TEMP RANGE (N)
TRANSLIFE 3; TEMPERATURE PROFILE, 7TH
808 RANGE READ TOTAL WINDING TEMP TIME IN 7TH TEMP RANGE (N)
TRANSLIFE 3; TEMPERATURE PROFILE, 8TH
810 RANGE READ TOTAL WINDING TEMP TIME IN 8TH TEMP RANGE (N)
TRANSLIFE 3; TEMPERATURE PROFILE, 9TH
812 RANGE READ TOTAL WINDING TEMP TIME IN 9TH TEMP RANGE (N)
TRANSLIFE 3; TEMPERATURE PROFILE, 10TH
814 RANGE READ TOTAL WINDING TEMP TIME IN 10TH TEMP RANGE (N)
TRANSLIFE 3; TEMPERATURE PROFILE, 11TH
816 RANGE READ TOTAL WINDING TEMP TIME IN 11TH TEMP RANGE (N)
TRANSLIFE 3; TEMPERATURE PROFILE, 12TH TOTAL WINDING TEMP TIME IN HIGHEST TEMP RANGE
818 RANGE READ (N)
820 COOLING BANK 1 ACTUATION SETPOINT VALUE RD/WR TOTAL ACTUATION COUNT SETPOINT (N)
822 COOLING BANK 1 RUN TIME SETPOINT VALUE RD/WR COOLING BANK 1 TOTAL RUN TIME SETPOINT (N)
824 COOLING BANK 2 ACTUATION SETPOINT VALUE RD/WR TOTAL ACTUATION COUNT SETPOINT (N)
826 COOLING BANK 2 RUN TIME SETPOINT VALUE RD/WR COOLING BANK 2 TOTAL RUN TIME SETPOINT (N)
828 COOLING BANK 3 ACTUATION SETPOINT VALUE RD/WR TOTAL ACTUATION COUNT SETPOINT (N)
830 COOLING BANK 3 RUN TIME SETPOINT VALUE RD/WR COOLING BANK 3 TOTAL RUN TIME SETPOINT (N)
832 COOLING BANK 4 ACTUATION SETPOINT VALUE RD/WR TOTAL ACTUATION COUNT SETPOINT (N)
834 COOLING BANK 4 RUN TIME SETPOINT VALUE RD/WR COOLING BANK 4 TOTAL RUN TIME SETPOINT (N)
LTC HI-ALARM TOTAL TAP COUNT SETPOINT
836 VALUE RD/WR LTC HIGH-PRIORITY TOTAL TAP COUNT SETPOINT (N)
LTC LO-ALARM TOTAL TAP COUNT SETPOINT
838 VALUE RD/WR LTC LOW-PRIORITY TOTAL TAP COUNT SETPOINT (N)
840 LTC HI-ALARM TOTAL RUN TIME SETPOINT VALUE RD/WR LTC HIGH-PRIORITY TOTAL RUN TIME SETPOINT (N)
842 LTC LO-ALARM TOTAL RUN TIME SETPOINT VALUE RD/WR LTC LOW-PRIORITY TOTAL RUN TIME SETPOINT (N)
LTC HI-ALARM MOTOR ACTUATION SETPOINT LTC HIGH-PRIORITY MOTOR ACTUATION COUNT SPT
844 VALUE RD/WR (N)
LTC LO-ALARM MOTOR ACTUATION SETPOINT
846 VALUE RD/WR LTC LOW-PRIORITY MOTOR ACTUATION COUNT SPT (N)

48 www.qualitrolcorp.com
String Parameters
REG # VARIABLE R/W DESCRIPTION
850 SERIAL NUMBER; 12 ASCII CHARACTERS READ SERIAL NUMBER[1] / SERIAL NUMBER[0]
851 SERIAL NUMBER CONTINUED READ SERIAL NUMBER[3] / SERIAL NUMBER [2]
852 SERIAL NUMBER CONTINUED READ SERIAL NUMBER[5] / SERIAL NUMBER [4]
853 SERIAL NUMBER CONTINUED READ SERIAL NUMBER[7] / SERIAL NUMBER [6]
854 SERIAL NUMBER CONTINUED READ SERIAL NUMBER[9] / SERIAL NUMBER [8]
855 SERIAL NUMBER CONTINUED READ SERIAL NUMBER[11] / SERIAL NUMBER [10]
856 MANUFACTURED DATE; 8 ASCII CHARACTERS READ MANUFACTURED DATE[1] / MANUFACTURED DATE [0]
857 MANUFACTURED DATE CONTINUED READ MANUFACTURED DATE[3] / MANUFACTURED DATE [2]
858 MANUFACTURED DATE CONTINUED READ MANUFACTURED DATE[5] / MANUFACTURED DATE [4]
859 MANUFACTURED DATE CONTINUED READ MANUFACTURED DATE[7] / MANUFACTURED DATE [6]
860 SUBSTATION NAME; 16 ASCII CHARACTERS READ SUBSTATION NAME[1] / SUBSTATION NAME[0]
861 SUBSTATION NAME CONTINUED READ SUBSTATION NAME[3] / SUBSTATION NAME[2]
862 SUBSTATION NAME CONTINUED READ SUBSTATION NAME[5] / SUBSTATION NAME[4]
863 SUBSTATION NAME CONTINUED READ SUBSTATION NAME[7] / SUBSTATION NAME[6]
864 SUBSTATION NAME CONTINUED READ SUBSTATION NAME[9] / SUBSTATION NAME[8]
865 SUBSTATION NAME CONTINUED READ SUBSTATION NAME[11] / SUBSTATION NAME[10]
866 SUBSTATION NAME CONTINUED READ SUBSTATION NAME[13] / SUBSTATION NAME[12]
867 SUBSTATION NAME CONTINUED READ SUBSTATION NAME[15] / SUBSTATION NAME[14]
868 EQUIPMENT NAME; 16 ASCII CHARACTERS READ EQUIPMENT NAME[1] / EQUIPMENT NAME[0]
869 EQUIPMENT NAME CONTINUED READ EQUIPMENT NAME[3] / EQUIPMENT NAME[2]
870 EQUIPMENT NAME CONTINUED READ EQUIPMENT NAME[5] / EQUIPMENT NAME[4]
871 EQUIPMENT NAME CONTINUED READ EQUIPMENT NAME[7] / EQUIPMENT NAME[6]
872 EQUIPMENT NAME CONTINUED READ EQUIPMENT NAME[9] / EQUIPMENT NAME[8]
873 EQUIPMENT NAME CONTINUED READ EQUIPMENT NAME[11] / EQUIPMENT NAME[10]
874 EQUIPMENT NAME CONTINUED READ EQUIPMENT NAME[13] / EQUIPMENT NAME[12]
875 EQUIPMENT NAME CONTINUED READ EQUIPMENT NAME[15] / EQUIPMENT NAME[14]
876 MODEL NUMBER; 8 ASCII CHARACTERS READ MODEL NUMBER[1] / MODEL NUMBER[0]
877 MODEL NUMBER CONTINUED READ MODEL NUMBER[3] / MODEL NUMBER[2]
878 MODEL NUMBER CONTINUED READ MODEL NUMBER[5] / MODEL NUMBER[4]
879 MODEL NUMBER CONTINUED READ MODEL NUMBER[7] / MODEL NUMBER[6]

Registers 900 thru 907 have the hex codes of the hardware types for the input modules. The types
are explained in the description side of the registers

REG # VARIABLE R/W DESCRIPTION


900 INPUT MODULE 1 HARDWARE TYPE READ 00 = NONE; 01 = 4-20mA; 02 = 0-1mA; 03 = 0-10VDC;
901 INPUT MODULE 2 HARDWARE TYPE READ 04 = 0-100mVDC; 05 = CT, CURRENT; 06 = CT, TEMP;
902 INPUT MODULE 3 HARDWARE TYPE READ 07 = POTENTIOMETER; 08 = 100 OHM RTD; 09 = 10 OHM
903 INPUT MODULE 4 HARDWARE TYPE READ RTD; 0A = DRY SWITCH DETECTION; 0B = POWERED
904 INPUT MODULE 5 HARDWARE TYPE READ SWITCH DETECTION; 0C = 100 OHM RTD WINDING
905 INPUT MODULE 6 HARDWARE TYPE READ TEMP; 0D = 10 OHM RTD WINDING TEMP; 0E = LTC

49 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
906 INPUT MODULE 7 HARDWARE TYPE READ RESISTOR BRIDGE; 0F = 0-140VAC; 10 = 0-320VAC;
11 = LTC 0-1mA; 12 = LTC 4-20mA; 13 = FIBER OPTIC
907 INPUT MODULE 8 HARDWARE TYPE READ TEMP

Registers 908 thru 997 are packed numbers. For example: reading register 908 gives a decimal
number of 3122. Converting this to hex gives 0C32. Split the bytes in half and it would read 12 hours
and 32 minutes.

REG # VARIABLE R/W DESCRIPTION


908 INPUT MODULE 1 MAXIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
909 INPUT MODULE 1 MAXIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
910 INPUT MODULE 1 MAXIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
911 INPUT MODULE 2 MAXIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
912 INPUT MODULE 2 MAXIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
913 INPUT MODULE 2 MAXIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
914 INPUT MODULE 3 MAXIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
915 INPUT MODULE 3 MAXIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
916 INPUT MODULE 3 MAXIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
917 INPUT MODULE 4 MAXIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
918 INPUT MODULE 4 MAXIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
919 INPUT MODULE 4 MAXIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
920 INPUT MODULE 5 MAXIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
921 INPUT MODULE 5 MAXIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
922 INPUT MODULE 5 MAXIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
923 INPUT MODULE 6 MAXIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
924 INPUT MODULE 6 MAXIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
925 INPUT MODULE 6 MAXIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
926 INPUT MODULE 7 MAXIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
927 INPUT MODULE 7 MAXIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
928 INPUT MODULE 7 MAXIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
929 INPUT MODULE 8 MAXIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
930 INPUT MODULE 8 MAXIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
931 INPUT MODULE 8 MAXIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
932 INPUT MODULE 1 MINIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
933 INPUT MODULE 1 MINIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
934 INPUT MODULE 1 MINIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
935 INPUT MODULE 2 MINIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
936 INPUT MODULE 2 MINIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
937 INPUT MODULE 2 MINIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
938 INPUT MODULE 3 MINIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
939 INPUT MODULE 3 MINIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
940 INPUT MODULE 3 MINIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
941 INPUT MODULE 4 MINIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE

50 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
942 INPUT MODULE 4 MINIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
943 INPUT MODULE 4 MINIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
944 INPUT MODULE 5 MINIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
945 INPUT MODULE 5 MINIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
946 INPUT MODULE 5 MINIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
947 INPUT MODULE 6 MINIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
948 INPUT MODULE 6 MINIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
949 INPUT MODULE 6 MINIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
950 INPUT MODULE 7 MINIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
951 INPUT MODULE 7 MINIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
952 INPUT MODULE 7 MINIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
953 INPUT MODULE 8 MINIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
954 INPUT MODULE 8 MINIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
955 INPUT MODULE 8 MINIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
INPUT MODULE 1 MAXIMUM CURRENT TIME &
956 DATE READ HOURS BYTE / MINUTES BYTE
INPUT MODULE 1 MAXIMUM CURRENT TIME &
957 DATE READ SECONDS BYTE / MONTHS BYTE
INPUT MODULE 1 MAXIMUM CURRENT TIME &
958 DATE READ DAYS BYTE / YEARS BYTE
INPUT MODULE 2 MAXIMUM CURRENT TIME &
959 DATE READ HOURS BYTE / MINUTES BYTE
INPUT MODULE 2 MAXIMUM CURRENT TIME &
960 DATE READ SECONDS BYTE / MONTHS BYTE
INPUT MODULE 2 MAXIMUM CURRENT TIME &
961 DATE READ DAYS BYTE / YEARS BYTE
INPUT MODULE 3 MAXIMUM CURRENT TIME &
962 DATE READ HOURS BYTE / MINUTES BYTE
INPUT MODULE 3 MAXIMUM CURRENT TIME &
963 DATE READ SECONDS BYTE / MONTHS BYTE
INPUT MODULE 3 MAXIMUM CURRENT TIME &
964 DATE READ DAYS BYTE / YEARS BYTE
INPUT MODULE 4 MAXIMUM CURRENT TIME &
965 DATE READ HOURS BYTE / MINUTES BYTE
INPUT MODULE 4 MAXIMUM CURRENT TIME &
966 DATE READ SECONDS BYTE / MONTHS BYTE
INPUT MODULE 4 MAXIMUM CURRENT TIME &
967 DATE READ DAYS BYTE / YEARS BYTE
INPUT MODULE 5 MAXIMUM CURRENT TIME &
968 DATE READ HOURS BYTE / MINUTES BYTE
INPUT MODULE 5 MAXIMUM CURRENT TIME &
969 DATE READ SECONDS BYTE / MONTHS BYTE
INPUT MODULE 5 MAXIMUM CURRENT TIME &
970 DATE READ DAYS BYTE / YEARS BYTE
INPUT MODULE 6 MAXIMUM CURRENT TIME &
971 DATE READ HOURS BYTE / MINUTES BYTE
INPUT MODULE 6 MAXIMUM CURRENT TIME &
972 DATE READ SECONDS BYTE / MONTHS BYTE
INPUT MODULE 6 MAXIMUM CURRENT TIME &
973 DATE READ DAYS BYTE / YEARS BYTE
INPUT MODULE 7 MAXIMUM CURRENT TIME &
974 DATE READ HOURS BYTE / MINUTES BYTE
INPUT MODULE 7 MAXIMUM CURRENT TIME &
975 DATE READ SECONDS BYTE / MONTHS BYTE
INPUT MODULE 7 MAXIMUM CURRENT TIME &
976 DATE READ DAYS BYTE / YEARS BYTE
INPUT MODULE 8 MAXIMUM CURRENT TIME &
977 DATE READ HOURS BYTE / MINUTES BYTE

51 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
INPUT MODULE 8 MAXIMUM CURRENT TIME &
978 DATE READ SECONDS BYTE / MONTHS BYTE
INPUT MODULE 8 MAXIMUM CURRENT TIME &
979 DATE READ DAYS BYTE / YEARS BYTE
980 DGA H2 SENSOR 1 MAXIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
981 DGA H2 SENSOR 1 MAXIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
982 DGA H2 SENSOR 1 MAXIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
983 DGA H2 SENSOR 1 MINIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
984 DGA H2 SENSOR 1 MINIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
985 DGA H2 SENSOR 1 MINIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
986 DGA H2 SENSOR 2 MAXIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
987 DGA H2 SENSOR 2 MAXIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
988 DGA H2 SENSOR 2 MAXIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
989 DGA H2 SENSOR 2 MINIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
990 DGA H2 SENSOR 2 MINIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
991 DGA H2 SENSOR 2 MINIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
992 DGA H2 SENSOR 3 MAXIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
993 DGA H2 SENSOR 3 MAXIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
994 DGA H2 SENSOR 3 MAXIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
995 DGA H2 SENSOR 3 MINIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
996 DGA H2 SENSOR 3 MINIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
997 DGA H2 SENSOR 3 MINIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE

Analog Parameters
For registers 1000 thru 1133 the parameters are 32 bits long with the even registers holding the low
word and the high registers holding the high word (e.g. 1000 low word; 1001 high word).
REG # VARIABLE R/W DESCRIPTION
1000 LTC, TAP POSITION -16 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (-16)
1002 LTC, TAP POSITION -15 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (-15)
1004 LTC, TAP POSITION -14 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (-14)
1006 LTC, TAP POSITION -13 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (-13)
1008 LTC, TAP POSITION -12 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (-12)
1010 LTC, TAP POSITION -11 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (-11)
1012 LTC, TAP POSITION -10 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (-10)
1014 LTC, TAP POSITION -9 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (-9)
1016 LTC, TAP POSITION -8 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (-8)
1018 LTC, TAP POSITION -7 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (-7)
1020 LTC, TAP POSITION -6 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (-6)
1022 LTC, TAP POSITION -5 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (-5)
1024 LTC, TAP POSITION -4 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (-4)
1026 LTC, TAP POSITION -3 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (-3)
1028 LTC, TAP POSITION -2 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (-2)
1030 LTC, TAP POSITION -1 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (-1)
1032 LTC, TAP POSITION +0 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (+0)
1034 LTC, TAP POSITION +1 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (+1)

52 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
1036 LTC, TAP POSITION +2 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (+2)
1038 LTC, TAP POSITION +3 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (+3)
1040 LTC, TAP POSITION +4 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (+4)
1042 LTC, TAP POSITION +5 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (+5)
1044 LTC, TAP POSITION +6 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (+6)
1046 LTC, TAP POSITION +7 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (+7)
1048 LTC, TAP POSITION +8 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (+8)
1050 LTC, TAP POSITION +9 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (+9)
1052 LTC, TAP POSITION +10 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (+10)
1054 LTC, TAP POSITION +11 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (+11)
1056 LTC, TAP POSITION +12 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (+12)
1058 LTC, TAP POSITION +13 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (+13)
1060 LTC, TAP POSITION +14 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (+14)
1062 LTC, TAP POSITION +15 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (+15)
1064 LTC, TAP POSITION +16 TOTAL TAP COUNTS READ TOTAL TAP COUNTS FOR TAP POSITION (+16)
1066 LTC, TAP POSITION -16 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (-16)
1068 LTC, TAP POSITION -15 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (-15)
1070 LTC, TAP POSITION -14 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (-14)
1072 LTC, TAP POSITION -13 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (-13)
1074 LTC, TAP POSITION -12 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (-12)
1076 LTC, TAP POSITION -11 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (-11)
1078 LTC, TAP POSITION -10 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (-10)
1080 LTC, TAP POSITION -9 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (-9)
1082 LTC, TAP POSITION -8 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (-8)
1084 LTC, TAP POSITION -7 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (-7)
1086 LTC, TAP POSITION -6 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (-6)
1088 LTC, TAP POSITION -5 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (-5)
1090 LTC, TAP POSITION -4 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (-4)
1092 LTC, TAP POSITION -3 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (-3)
1094 LTC, TAP POSITION -2 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (-2)
1096 LTC, TAP POSITION -1 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (-1)
1098 LTC, TAP POSITION +0 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (+0)
1100 LTC, TAP POSITION +1 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (+1)
1102 LTC, TAP POSITION +2 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (+2)
1104 LTC, TAP POSITION +3 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (+3)
1106 LTC, TAP POSITION +4 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (+4)
1108 LTC, TAP POSITION +5 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (+5)
1110 LTC, TAP POSITION +6 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (+6)
1112 LTC, TAP POSITION +7 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (+7)
1114 LTC, TAP POSITION +8 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (+8)
1116 LTC, TAP POSITION +9 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (+9)
1118 LTC, TAP POSITION +10 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (+10)
1120 LTC, TAP POSITION +11 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (+11)
1122 LTC, TAP POSITION +12 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (+12)
1124 LTC, TAP POSITION +13 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (+13)
1126 LTC, TAP POSITION +14 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (+14)
1128 LTC, TAP POSITION +15 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (+15)

53 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
1130 LTC, TAP POSITION +16 TOTAL RUN TIME READ TOTAL RUN TIME FOR TAP POSITION (+16)
1132 LTC, TOTAL MOTOR ACTUATION COUNTS READ TOTAL NUMBER OF MOTOR ACTUATION COUNTS

Analog Parameters
Registers 1134 to 1143 are scaled analog values (e.g. N, 10X, 100X, 1000X)

REG # VARIABLE R/W DESCRIPTION


1134 LTC PREVIOUS MOTOR RUN CURRENT READ MOTOR RUN CURRENT FROM LAST ACTUATION (10X)
MOTOR INRUSH CURRENT FROM LAST ACTUATION
1135 LTC PREVIOUS MOTOR INRUSH CURRENT READ (10X)
1136 LTC PREVIOUS MOTOR RUN TIME READ MOTOR ACTUATION TIME FROM LAST ACTUATION (10X)
1137 LTC HI-ALARM DIFFERENTIAL SETPOINT VALUE RD/WR DIFFERENTIAL SETPOINT VALUE FOR HI-ALARM (10X)
1138 LTC HI-ALARM DIFFERENTIAL HYSTERESIS VALUE RD/WR DIFFERENTIAL HYSTERESIS VALUE FOR HI-ALARM (10X)
1139 LTC LO-ALARM DIFFERENTIAL SETPOINT VALUE RD/WR DIFFERENTIAL SETPOINT VALUE FOR LO-ALARM (10X)
DIFFERENTIAL HYSTERESIS VALUE FOR LO-ALARM
1140 LTC LO-ALARM DIFFERENTIAL HYSTERESIS VALUE RD/WR (10X)
1141 LTC HI-ALARM MOTOR RUN TIME SETPOINT RD/WR MOTOR RUN TIME SETPOINT FOR HI-ALARM (N)
1142 LTC LO-ALARM MOTOR RUN TIME SETPOINT RD/WR MOTOR RUN TIME SETPOINT FOR LO-ALARM (N)

String Parameters
REG # VARIABLE R/W DESCRIPTION
1200 INPUT MODULE 1 NAME; 7 ASCII CHARACTERS READ INPUT MODULE 1 NAME[1] / INPUT MODULE 1 NAME[0]
1201 INPUT MODULE 1 NAME; CONTINUED READ INPUT MODULE 1 NAME[3] / INPUT MODULE 1 NAME[2]
1202 INPUT MODULE 1 NAME; CONTINUED READ INPUT MODULE 1 NAME[5] / INPUT MODULE 1 NAME[4]
1203 INPUT MODULE 1 NAME; CONTINUED READ INPUT MODULE 1 ZERO / INPUT MODULE 1 NAME[6]
1204 INPUT MODULE 2 NAME; 7 ASCII CHARACTERS READ INPUT MODULE 2 NAME[1] / INPUT MODULE 2 NAME[0]
1205 INPUT MODULE 2 NAME; CONTINUED READ INPUT MODULE 2 NAME[3] / INPUT MODULE 2 NAME[2]
1206 INPUT MODULE 2 NAME; CONTINUED READ INPUT MODULE 2 NAME[5] / INPUT MODULE 2 NAME[4]
1207 INPUT MODULE 2 NAME; CONTINUED READ INPUT MODULE 2 ZERO / INPUT MODULE 2 NAME[6]
1208 INPUT MODULE 3 NAME; 7 ASCII CHARACTERS READ INPUT MODULE 3 NAME[1] / INPUT MODULE 3 NAME[0]
1209 INPUT MODULE 3 NAME; CONTINUED READ INPUT MODULE 3 NAME[3] / INPUT MODULE 3 NAME[2]
1210 INPUT MODULE 3 NAME; CONTINUED READ INPUT MODULE 3 NAME[5] / INPUT MODULE 3 NAME[4]
1211 INPUT MODULE 3 NAME; CONTINUED READ INPUT MODULE 3 ZERO / INPUT MODULE 3 NAME[6]
1212 INPUT MODULE 4 NAME; 7 ASCII CHARACTERS READ INPUT MODULE 4 NAME[1] / INPUT MODULE 4 NAME[0]
1213 INPUT MODULE 4 NAME; CONTINUED READ INPUT MODULE 4 NAME[3] / INPUT MODULE 4 NAME[2]
1214 INPUT MODULE 4 NAME; CONTINUED READ INPUT MODULE 4 NAME[5] / INPUT MODULE 4 NAME[4]
1215 INPUT MODULE 4 NAME; CONTINUED READ INPUT MODULE 4 ZERO / INPUT MODULE 4 NAME[6]
1216 INPUT MODULE 5 NAME; 7 ASCII CHARACTERS READ INPUT MODULE 5 NAME[1] / INPUT MODULE 5 NAME[0]
1217 INPUT MODULE 5 NAME; CONTINUED READ INPUT MODULE 5 NAME[3] / INPUT MODULE 5 NAME[2]
1218 INPUT MODULE 5 NAME; CONTINUED READ INPUT MODULE 5 NAME[5] / INPUT MODULE 5 NAME[4]
1219 INPUT MODULE 5 NAME; CONTINUED READ INPUT MODULE 5 ZERO / INPUT MODULE 5 NAME[6]
1220 INPUT MODULE 6 NAME; 7 ASCII CHARACTERS READ INPUT MODULE 6 NAME[1] / INPUT MODULE 6 NAME[0]
1221 INPUT MODULE 6 NAME; CONTINUED READ INPUT MODULE 6 NAME[3] / INPUT MODULE 6 NAME[2]
1222 INPUT MODULE 6 NAME; CONTINUED READ INPUT MODULE 6 NAME[5] / INPUT MODULE 6 NAME[4]
1223 INPUT MODULE 6 NAME; CONTINUED READ INPUT MODULE 6 ZERO / INPUT MODULE 6 NAME[6]
1224 INPUT MODULE 7 NAME; 7 ASCII CHARACTERS READ INPUT MODULE 7 NAME[1] / INPUT MODULE 7 NAME[0]
1225 INPUT MODULE 7 NAME; CONTINUED READ INPUT MODULE 7 NAME[3] / INPUT MODULE 7 NAME[2]

54 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
1226 INPUT MODULE 7 NAME; CONTINUED READ INPUT MODULE 7 NAME[5] / INPUT MODULE 7 NAME[4]
1227 INPUT MODULE 7 NAME; CONTINUED READ INPUT MODULE 7 ZERO / INPUT MODULE 7 NAME[6]
1228 INPUT MODULE 8 NAME; 7 ASCII CHARACTERS READ INPUT MODULE 8 NAME[1] / INPUT MODULE 8 NAME[0]
1229 INPUT MODULE 8 NAME; CONTINUED READ INPUT MODULE 8 NAME[3] / INPUT MODULE 8 NAME[2]
1230 INPUT MODULE 8 NAME; CONTINUED READ INPUT MODULE 8 NAME[5] / INPUT MODULE 8 NAME[4]
1231 INPUT MODULE 8 NAME; CONTINUED READ INPUT MODULE 8 ZERO / INPUT MODULE 8 NAME[6]
HOT SPOT MODULE 1; PROBE 1 NAME; 7 ASCII
1232 CHARS READ MODULE 1; PROBE 1 NAME[1] / PROBE 1 NAME[0]
HOT SPOT MODULE 1; PROBE 1 NAME;
1233 CONTINUED READ MODULE 1; PROBE 1 NAME[3] / PROBE 1 NAME[2]
HOT SPOT MODULE 1; PROBE 1 NAME;
1234 CONTINUED READ MODULE 1; PROBE 1 NAME[5] / PROBE 1 NAME[4]
HOT SPOT MODULE 1; PROBE 1 NAME;
1235 CONTINUED READ MODULE 1; PROBE 1 ZERO / PROBE 1 NAME[6]
HOT SPOT MODULE 1; PROBE 2 NAME; 7 ASCII
1236 CHARS READ MODULE 1; PROBE 2 NAME[1] / PROBE 2 NAME[0]
HOT SPOT MODULE 1; PROBE 2 NAME;
1237 CONTINUED READ MODULE 1; PROBE 2 NAME[3] / PROBE 2 NAME[2]
HOT SPOT MODULE 1; PROBE 2 NAME;
1238 CONTINUED READ MODULE 1; PROBE 2 NAME[5] / PROBE 2 NAME[4]
HOT SPOT MODULE 1; PROBE 2 NAME;
1239 CONTINUED READ MODULE 1; PROBE 2 ZERO / PROBE 2 NAME[6]
HOT SPOT MODULE 1; PROBE 3 NAME; 7 ASCII
1240 CHARS READ MODULE 1; PROBE 3 NAME[1] / PROBE 3 NAME[0]
HOT SPOT MODULE 1; PROBE 3 NAME;
1241 CONTINUED READ MODULE 1; PROBE 3 NAME[3] / PROBE 3 NAME[2]
HOT SPOT MODULE 1; PROBE 3 NAME;
1242 CONTINUED READ MODULE 1; PROBE 3 NAME[5] / PROBE 3 NAME[4]
HOT SPOT MODULE 1; PROBE 3 NAME;
1243 CONTINUED READ MODULE 1; PROBE 3 ZERO / PROBE 3 NAME[6]
HOT SPOT MODULE 1; PROBE 4 NAME; 7 ASCII
1244 CHARS READ MODULE 1; PROBE 4 NAME[1] / PROBE 4 NAME[0]
HOT SPOT MODULE 1; PROBE 4 NAME;
1245 CONTINUED READ MODULE 1; PROBE 4 NAME[3] / PROBE 4 NAME[2]
HOT SPOT MODULE 1; PROBE 4 NAME;
1246 CONTINUED READ MODULE 1; PROBE 4 NAME[5] / PROBE 4 NAME[4]
HOT SPOT MODULE 1; PROBE 4 NAME;
1247 CONTINUED READ MODULE 1; PROBE 4 ZERO / PROBE 4 NAME[6]
HOT SPOT MODULE 1; PROBE 5 NAME; 7 ASCII
1248 CHARS READ MODULE 1; PROBE 5 NAME[1] / PROBE 5 NAME[0]
HOT SPOT MODULE 1; PROBE 5 NAME;
1249 CONTINUED READ MODULE 1; PROBE 5 NAME[3] / PROBE 5 NAME[2]
HOT SPOT MODULE 1; PROBE 5 NAME;
1250 CONTINUED READ MODULE 1; PROBE 5 NAME[5] / PROBE 5 NAME[4]
HOT SPOT MODULE 1; PROBE 5 NAME;
1251 CONTINUED READ MODULE 1; PROBE 5 ZERO / PROBE 5 NAME[6]
HOT SPOT MODULE 1; PROBE 6 NAME; 7 ASCII
1252 CHARS READ MODULE 1; PROBE 6 NAME[1] / PROBE 6 NAME[0]
HOT SPOT MODULE 1; PROBE 6 NAME;
1253 CONTINUED READ MODULE 1; PROBE 6 NAME[3] / PROBE 6 NAME[2]
HOT SPOT MODULE 1; PROBE 6 NAME;
1254 CONTINUED READ MODULE 1; PROBE 6 NAME[5] / PROBE 6 NAME[4]
HOT SPOT MODULE 1; PROBE 6 NAME;
1255 CONTINUED READ MODULE 1; PROBE 6 ZERO / PROBE 6 NAME[6]
HOT SPOT MODULE 1; PROBE 7 NAME; 7 ASCII
1256 CHARS READ MODULE 1; PROBE 7 NAME[1] / PROBE 7 NAME[0]
HOT SPOT MODULE 1; PROBE 7 NAME;
1257 CONTINUED READ MODULE 1; PROBE 7 NAME[3] / PROBE 7 NAME[2]
HOT SPOT MODULE 1; PROBE 7 NAME;
1258 CONTINUED READ MODULE 1; PROBE 7 NAME[5] / PROBE 7 NAME[4]
HOT SPOT MODULE 1; PROBE 7 NAME;
1259 CONTINUED READ MODULE 1; PROBE 7 ZERO / PROBE 7 NAME[6]
HOT SPOT MODULE 1; PROBE 8 NAME; 7 ASCII
1260 CHARS READ MODULE 1; PROBE 8 NAME[1] / PROBE 8 NAME[0]

55 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
HOT SPOT MODULE 1; PROBE 8 NAME;
1261 CONTINUED READ MODULE 1; PROBE 8 NAME[3] / PROBE 8 NAME[2]
HOT SPOT MODULE 1; PROBE 8 NAME;
1262 CONTINUED READ MODULE 1; PROBE 8 NAME[5] / PROBE 8 NAME[4]
HOT SPOT MODULE 1; PROBE 8 NAME;
1263 CONTINUED READ MODULE 1; PROBE 8 ZERO / PROBE 8 NAME[6]
HOT SPOT MODULE 2; PROBE 1 NAME; 7 ASCII
1264 CHARS READ MODULE 2; PROBE 1 NAME[1] / PROBE 1 NAME[0]
HOT SPOT MODULE 2; PROBE 1 NAME;
1265 CONTINUED READ MODULE 2; PROBE 1 NAME[3] / PROBE 1 NAME[2]
HOT SPOT MODULE 2; PROBE 1 NAME;
1266 CONTINUED READ MODULE 2; PROBE 1 NAME[5] / PROBE 1 NAME[4]
HOT SPOT MODULE 2; PROBE 1 NAME;
1267 CONTINUED READ MODULE 2; PROBE 1 ZERO / PROBE 1 NAME[6]
HOT SPOT MODULE 2; PROBE 2 NAME; 7 ASCII
1268 CHARS READ MODULE 2; PROBE 2 NAME[1] / PROBE 2 NAME[0]
HOT SPOT MODULE 2; PROBE 2 NAME;
1269 CONTINUED READ MODULE 2; PROBE 2 NAME[3] / PROBE 2 NAME[2]
HOT SPOT MODULE 2; PROBE 2 NAME;
1270 CONTINUED READ MODULE 2; PROBE 2 NAME[5] / PROBE 2 NAME[4]
HOT SPOT MODULE 2; PROBE 2 NAME;
1271 CONTINUED READ MODULE 2; PROBE 2 ZERO / PROBE 2 NAME[6]
HOT SPOT MODULE 2; PROBE 3 NAME; 7 ASCII
1272 CHARS READ MODULE 2; PROBE 3 NAME[1] / PROBE 3 NAME[0]
HOT SPOT MODULE 2; PROBE 3 NAME;
1273 CONTINUED READ MODULE 2; PROBE 3 NAME[3] / PROBE 3 NAME[2]
HOT SPOT MODULE 2; PROBE 3 NAME;
1274 CONTINUED READ MODULE 2; PROBE 3 NAME[5] / PROBE 3 NAME[4]
HOT SPOT MODULE 2; PROBE 3 NAME;
1275 CONTINUED READ MODULE 2; PROBE 3 ZERO / PROBE 3 NAME[6]
HOT SPOT MODULE 2; PROBE 4 NAME; 7 ASCII
1276 CHARS READ MODULE 2; PROBE 4 NAME[1] / PROBE 4 NAME[0]
HOT SPOT MODULE 2; PROBE 4 NAME;
1277 CONTINUED READ MODULE 2; PROBE 4 NAME[3] / PROBE 4 NAME[2]
HOT SPOT MODULE 2; PROBE 4 NAME;
1278 CONTINUED READ MODULE 2; PROBE 4 NAME[5] / PROBE 4 NAME[4]
HOT SPOT MODULE 2; PROBE 4 NAME;
1279 CONTINUED READ MODULE 2; PROBE 4 ZERO / PROBE 4 NAME[6]
HOT SPOT MODULE 2; PROBE 5 NAME; 7 ASCII
1280 CHARS READ MODULE 2; PROBE 5 NAME[1] / PROBE 5 NAME[0]
HOT SPOT MODULE 2; PROBE 5 NAME;
1281 CONTINUED READ MODULE 2; PROBE 5 NAME[3] / PROBE 5 NAME[2]
HOT SPOT MODULE 2; PROBE 5 NAME;
1282 CONTINUED READ MODULE 2; PROBE 5 NAME[5] / PROBE 5 NAME[4]
HOT SPOT MODULE 2; PROBE 5 NAME;
1283 CONTINUED READ MODULE 2; PROBE 5 ZERO / PROBE 5 NAME[6]
HOT SPOT MODULE 2; PROBE 6 NAME; 7 ASCII
1284 CHARS READ MODULE 2; PROBE 6 NAME[1] / PROBE 6 NAME[0]
HOT SPOT MODULE 2; PROBE 6 NAME;
1285 CONTINUED READ MODULE 2; PROBE 6 NAME[3] / PROBE 6 NAME[2]
HOT SPOT MODULE 2; PROBE 6 NAME;
1286 CONTINUED READ MODULE 2; PROBE 6 NAME[5] / PROBE 6 NAME[4]
HOT SPOT MODULE 2; PROBE 6 NAME;
1287 CONTINUED READ MODULE 2; PROBE 6 ZERO / PROBE 6 NAME[6]
HOT SPOT MODULE 2; PROBE 7 NAME; 7 ASCII
1288 CHARS READ MODULE 2; PROBE 7 NAME[1] / PROBE 7 NAME[0]
HOT SPOT MODULE 2; PROBE 7 NAME;
1289 CONTINUED READ MODULE 2; PROBE 7 NAME[3] / PROBE 7 NAME[2]
HOT SPOT MODULE 2; PROBE 7 NAME;
1290 CONTINUED READ MODULE 2; PROBE 7 NAME[5] / PROBE 7 NAME[4]
HOT SPOT MODULE 2; PROBE 7 NAME;
1291 CONTINUED READ MODULE 2; PROBE 7 ZERO / PROBE 7 NAME[6]
HOT SPOT MODULE 2; PROBE 8 NAME; 7 ASCII
1292 CHARS READ MODULE 2; PROBE 8 NAME[1] / PROBE 8 NAME[0]
HOT SPOT MODULE 2; PROBE 8 NAME;
1293 CONTINUED READ MODULE 2; PROBE 8 NAME[3] / PROBE 8 NAME[2]

56 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
HOT SPOT MODULE 2; PROBE 8 NAME;
1294 CONTINUED READ MODULE 2; PROBE 8 NAME[5] / PROBE 8 NAME[4]
HOT SPOT MODULE 2; PROBE 8 NAME;
1295 CONTINUED READ MODULE 2; PROBE 8 ZERO / PROBE 8 NAME[6]
HOT SPOT MODULE 1; PROBE 1 DESCRIPTION; 24
1296 CHAR READ MODULE 1; PROBE 1 DESC[1] / PROBE 1 DESC[0]
HOT SPOT MODULE 1; PROBE 1 DESCRIPTION;
1297 CONT. READ MODULE 1; PROBE 1 DESC[3] / PROBE 1 DESC[2]
HOT SPOT MODULE 1; PROBE 1 DESCRIPTION;
1298 CONT. READ MODULE 1; PROBE 1 DESC[5] / PROBE 1 DESC[4]
HOT SPOT MODULE 1; PROBE 1 DESCRIPTION;
1299 CONT. READ MODULE 1; PROBE 1 DESC[7] / PROBE 1 DESC[6]
HOT SPOT MODULE 1; PROBE 1 DESCRIPTION;
1300 CONT. READ MODULE 1; PROBE 1 DESC[9] / PROBE 1 DESC[8]
HOT SPOT MODULE 1; PROBE 1 DESCRIPTION;
1301 CONT. READ MODULE 1; PROBE 1 DESC[11] / PROBE 1 DESC[10]
HOT SPOT MODULE 1; PROBE 1 DESCRIPTION;
1302 CONT. READ MODULE 1; PROBE 1 DESC[13] / PROBE 1 DESC[12]
HOT SPOT MODULE 1; PROBE 1 DESCRIPTION;
1303 CONT. READ MODULE 1; PROBE 1 DESC[15] / PROBE 1 DESC[14]
HOT SPOT MODULE 1; PROBE 1 DESCRIPTION;
1304 CONT. READ MODULE 1; PROBE 1 DESC[17] / PROBE 1 DESC[16]
HOT SPOT MODULE 1; PROBE 1 DESCRIPTION;
1305 CONT. READ MODULE 1; PROBE 1 DESC[19] / PROBE 1 DESC[18]
HOT SPOT MODULE 1; PROBE 1 DESCRIPTION;
1306 CONT. READ MODULE 1; PROBE 1 DESC[21] / PROBE 1 DESC[20]
HOT SPOT MODULE 1; PROBE 1 DESCRIPTION;
1307 CONT. READ MODULE 1; PROBE 1 DESC[23] / PROBE 1 DESC[22]
HOT SPOT MODULE 1; PROBE 2 DESCRIPTION; 24
1308 CHAR READ MODULE 1; PROBE 2 DESC[1] / PROBE 2 DESC[0]
HOT SPOT MODULE 1; PROBE 2 DESCRIPTION;
1309 CONT. READ MODULE 1; PROBE 2 DESC[3] / PROBE 2 DESC[2]
HOT SPOT MODULE 1; PROBE 2 DESCRIPTION;
1310 CONT. READ MODULE 1; PROBE 2 DESC[5] / PROBE 2 DESC[4]
HOT SPOT MODULE 1; PROBE 2 DESCRIPTION;
1311 CONT. READ MODULE 1; PROBE 2 DESC[7] / PROBE 2 DESC[6]
HOT SPOT MODULE 1; PROBE 2 DESCRIPTION;
1312 CONT. READ MODULE 1; PROBE 2 DESC[9] / PROBE 2 DESC[8]
HOT SPOT MODULE 1; PROBE 2 DESCRIPTION;
1313 CONT. READ MODULE 1; PROBE 2 DESC[11] / PROBE 2 DESC[10]
HOT SPOT MODULE 1; PROBE 2 DESCRIPTION;
1314 CONT. READ MODULE 1; PROBE 2 DESC[13] / PROBE 2 DESC[12]
HOT SPOT MODULE 1; PROBE 2 DESCRIPTION;
1315 CONT. READ MODULE 1; PROBE 2 DESC[15] / PROBE 2 DESC[14]
HOT SPOT MODULE 1; PROBE 2 DESCRIPTION;
1316 CONT. READ MODULE 1; PROBE 2 DESC[17] / PROBE 2 DESC[16]
HOT SPOT MODULE 1; PROBE 2 DESCRIPTION;
1317 CONT. READ MODULE 1; PROBE 2 DESC[19] / PROBE 2 DESC[18]
HOT SPOT MODULE 1; PROBE 2 DESCRIPTION;
1318 CONT. READ MODULE 1; PROBE 2 DESC[21] / PROBE 2 DESC[20]
HOT SPOT MODULE 1; PROBE 2 DESCRIPTION;
1319 CONT. READ MODULE 1; PROBE 2 DESC[23] / PROBE 2 DESC[22]
HOT SPOT MODULE 1; PROBE 3 DESCRIPTION; 24
1320 CHAR READ MODULE 1; PROBE 3 DESC[1] / PROBE 3 DESC[0]
HOT SPOT MODULE 1; PROBE 3 DESCRIPTION;
1321 CONT. READ MODULE 1; PROBE 3 DESC[3] / PROBE 3 DESC[2]
HOT SPOT MODULE 1; PROBE 3 DESCRIPTION;
1322 CONT. READ MODULE 1; PROBE 3 DESC[5] / PROBE 3 DESC[4]
HOT SPOT MODULE 1; PROBE 3 DESCRIPTION;
1323 CONT. READ MODULE 1; PROBE 3 DESC[7] / PROBE 3 DESC[6]
HOT SPOT MODULE 1; PROBE 3 DESCRIPTION;
1324 CONT. READ MODULE 1; PROBE 3 DESC[9] / PROBE 3 DESC[8]
HOT SPOT MODULE 1; PROBE 3 DESCRIPTION;
1325 CONT. READ MODULE 1; PROBE 3 DESC[11] / PROBE 3 DESC[10]
HOT SPOT MODULE 1; PROBE 3 DESCRIPTION;
1326 CONT. READ MODULE 1; PROBE 3 DESC[13] / PROBE 3 DESC[12]

57 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
HOT SPOT MODULE 1; PROBE 3 DESCRIPTION;
1327 CONT. READ MODULE 1; PROBE 3 DESC[15] / PROBE 3 DESC[14]
HOT SPOT MODULE 1; PROBE 3 DESCRIPTION;
1328 CONT. READ MODULE 1; PROBE 3 DESC[17] / PROBE 3 DESC[16]
HOT SPOT MODULE 1; PROBE 3 DESCRIPTION;
1329 CONT. READ MODULE 1; PROBE 3 DESC[19] / PROBE 3 DESC[18]
HOT SPOT MODULE 1; PROBE 3 DESCRIPTION;
1330 CONT. READ MODULE 1; PROBE 3 DESC[21] / PROBE 3 DESC[20]
HOT SPOT MODULE 1; PROBE 3 DESCRIPTION;
1331 CONT. READ MODULE 1; PROBE 3 DESC[23] / PROBE 3 DESC[22]
HOT SPOT MODULE 1; PROBE 4 DESCRIPTION; 24
1332 CHAR READ MODULE 1; PROBE 4 DESC[1] / PROBE 4 DESC[0]
HOT SPOT MODULE 1; PROBE 4 DESCRIPTION;
1333 CONT. READ MODULE 1; PROBE 4 DESC[3] / PROBE 4 DESC[2]
HOT SPOT MODULE 1; PROBE 4 DESCRIPTION;
1334 CONT. READ MODULE 1; PROBE 4 DESC[5] / PROBE 4 DESC[4]
HOT SPOT MODULE 1; PROBE 4 DESCRIPTION;
1335 CONT. READ MODULE 1; PROBE 4 DESC[7] / PROBE 4 DESC[6]
HOT SPOT MODULE 1; PROBE 4 DESCRIPTION;
1336 CONT. READ MODULE 1; PROBE 4 DESC[9] / PROBE 4 DESC[8]
HOT SPOT MODULE 1; PROBE 4 DESCRIPTION;
1337 CONT. READ MODULE 1; PROBE 4 DESC[11] / PROBE 4 DESC[10]
HOT SPOT MODULE 1; PROBE 4 DESCRIPTION;
1338 CONT. READ MODULE 1; PROBE 4 DESC[13] / PROBE 4 DESC[12]
HOT SPOT MODULE 1; PROBE 4 DESCRIPTION;
1339 CONT. READ MODULE 1; PROBE 4 DESC[15] / PROBE 4 DESC[14]
HOT SPOT MODULE 1; PROBE 4 DESCRIPTION;
1340 CONT. READ MODULE 1; PROBE 4 DESC[17] / PROBE 4 DESC[16]
HOT SPOT MODULE 1; PROBE 4 DESCRIPTION;
1341 CONT. READ MODULE 1; PROBE 4 DESC[19] / PROBE 4 DESC[18]
HOT SPOT MODULE 1; PROBE 4 DESCRIPTION;
1342 CONT. READ MODULE 1; PROBE 4 DESC[21] / PROBE 4 DESC[20]
HOT SPOT MODULE 1; PROBE 4 DESCRIPTION;
1343 CONT. READ MODULE 1; PROBE 4 DESC[23] / PROBE 4 DESC[22]
HOT SPOT MODULE 1; PROBE 5 DESCRIPTION; 24
1344 CHAR READ MODULE 1; PROBE 5 DESC[1] / PROBE 5 DESC[0]
HOT SPOT MODULE 1; PROBE 5 DESCRIPTION;
1345 CONT. READ MODULE 1; PROBE 5 DESC[3] / PROBE 5 DESC[2]
HOT SPOT MODULE 1; PROBE 5 DESCRIPTION;
1346 CONT. READ MODULE 1; PROBE 5 DESC[5] / PROBE 5 DESC[4]
HOT SPOT MODULE 1; PROBE 5 DESCRIPTION;
1347 CONT. READ MODULE 1; PROBE 5 DESC[7] / PROBE 5 DESC[6]
HOT SPOT MODULE 1; PROBE 5 DESCRIPTION;
1348 CONT. READ MODULE 1; PROBE 5 DESC[9] / PROBE 5 DESC[8]
HOT SPOT MODULE 1; PROBE 5 DESCRIPTION;
1349 CONT. READ MODULE 1; PROBE 5 DESC[11] / PROBE 5 DESC[10]
HOT SPOT MODULE 1; PROBE 5 DESCRIPTION;
1350 CONT. READ MODULE 1; PROBE 5 DESC[13] / PROBE 5 DESC[12]
HOT SPOT MODULE 1; PROBE 5 DESCRIPTION;
1351 CONT. READ MODULE 1; PROBE 5 DESC[15] / PROBE 5 DESC[14]
HOT SPOT MODULE 1; PROBE 5 DESCRIPTION;
1352 CONT. READ MODULE 1; PROBE 5 DESC[17] / PROBE 5 DESC[16]
HOT SPOT MODULE 1; PROBE 5 DESCRIPTION;
1353 CONT. READ MODULE 1; PROBE 5 DESC[19] / PROBE 5 DESC[18]
HOT SPOT MODULE 1; PROBE 5 DESCRIPTION;
1354 CONT. READ MODULE 1; PROBE 5 DESC[21] / PROBE 5 DESC[20]
HOT SPOT MODULE 1; PROBE 5 DESCRIPTION;
1355 CONT. READ MODULE 1; PROBE 5 DESC[23] / PROBE 5 DESC[22]
HOT SPOT MODULE 1; PROBE 6 DESCRIPTION; 24
1356 CHAR READ MODULE 1; PROBE 6 DESC[1] / PROBE 6 DESC[0]
HOT SPOT MODULE 1; PROBE 6 DESCRIPTION;
1357 CONT. READ MODULE 1; PROBE 6 DESC[3] / PROBE 6 DESC[2]
HOT SPOT MODULE 1; PROBE 6 DESCRIPTION;
1358 CONT. READ MODULE 1; PROBE 6 DESC[5] / PROBE 6 DESC[4]
HOT SPOT MODULE 1; PROBE 6 DESCRIPTION;
1359 CONT. READ MODULE 1; PROBE 6 DESC[7] / PROBE 6 DESC[6]

58 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
HOT SPOT MODULE 1; PROBE 6 DESCRIPTION;
1360 CONT. READ MODULE 1; PROBE 6 DESC[9] / PROBE 6 DESC[8]
HOT SPOT MODULE 1; PROBE 6 DESCRIPTION;
1361 CONT. READ MODULE 1; PROBE 6 DESC[11] / PROBE 6 DESC[10]
HOT SPOT MODULE 1; PROBE 6 DESCRIPTION;
1362 CONT. READ MODULE 1; PROBE 6 DESC[13] / PROBE 6 DESC[12]
HOT SPOT MODULE 1; PROBE 6 DESCRIPTION;
1363 CONT. READ MODULE 1; PROBE 6 DESC[15] / PROBE 6 DESC[14]
HOT SPOT MODULE 1; PROBE 6 DESCRIPTION;
1364 CONT. READ MODULE 1; PROBE 6 DESC[17] / PROBE 6 DESC[16]
HOT SPOT MODULE 1; PROBE 6 DESCRIPTION;
1365 CONT. READ MODULE 1; PROBE 6 DESC[19] / PROBE 6 DESC[18]
HOT SPOT MODULE 1; PROBE 6 DESCRIPTION;
1366 CONT. READ MODULE 1; PROBE 6 DESC[21] / PROBE 6 DESC[20]
HOT SPOT MODULE 1; PROBE 6 DESCRIPTION;
1367 CONT. READ MODULE 1; PROBE 6 DESC[23] / PROBE 6 DESC[22]
HOT SPOT MODULE 1; PROBE 7 DESCRIPTION; 24
1368 CHAR READ MODULE 1; PROBE 7 DESC[1] / PROBE 7 DESC[0]
HOT SPOT MODULE 1; PROBE 7 DESCRIPTION;
1369 CONT. READ MODULE 1; PROBE 7 DESC[3] / PROBE 7 DESC[2]
HOT SPOT MODULE 1; PROBE 7 DESCRIPTION;
1370 CONT. READ MODULE 1; PROBE 7 DESC[5] / PROBE 7 DESC[4]
HOT SPOT MODULE 1; PROBE 7 DESCRIPTION;
1371 CONT. READ MODULE 1; PROBE 7 DESC[7] / PROBE 7 DESC[6]
HOT SPOT MODULE 1; PROBE 7 DESCRIPTION;
1372 CONT. READ MODULE 1; PROBE 7 DESC[9] / PROBE 7 DESC[8]
HOT SPOT MODULE 1; PROBE 7 DESCRIPTION;
1373 CONT. READ MODULE 1; PROBE 7 DESC[11] / PROBE 7 DESC[10]
HOT SPOT MODULE 1; PROBE 7 DESCRIPTION;
1374 CONT. READ MODULE 1; PROBE 7 DESC[13] / PROBE 7 DESC[12]
HOT SPOT MODULE 1; PROBE 7 DESCRIPTION;
1375 CONT. READ MODULE 1; PROBE 7 DESC[15] / PROBE 7 DESC[14]
HOT SPOT MODULE 1; PROBE 7 DESCRIPTION;
1376 CONT. READ MODULE 1; PROBE 7 DESC[17] / PROBE 7 DESC[16]
HOT SPOT MODULE 1; PROBE 7 DESCRIPTION;
1377 CONT. READ MODULE 1; PROBE 7 DESC[19] / PROBE 7 DESC[18]
HOT SPOT MODULE 1; PROBE 7 DESCRIPTION;
1378 CONT. READ MODULE 1; PROBE 7 DESC[21] / PROBE 7 DESC[20]
HOT SPOT MODULE 1; PROBE 7 DESCRIPTION;
1379 CONT. READ MODULE 1; PROBE 7 DESC[23] / PROBE 7 DESC[22]
HOT SPOT MODULE 1; PROBE 8 DESCRIPTION; 24
1380 CHAR READ MODULE 1; PROBE 8 DESC[1] / PROBE 8 DESC[0]
HOT SPOT MODULE 1; PROBE 8 DESCRIPTION;
1381 CONT. READ MODULE 1; PROBE 8 DESC[3] / PROBE 8 DESC[2]
HOT SPOT MODULE 1; PROBE 8 DESCRIPTION;
1382 CONT. READ MODULE 1; PROBE 8 DESC[5] / PROBE 8 DESC[4]
HOT SPOT MODULE 1; PROBE 8 DESCRIPTION;
1383 CONT. READ MODULE 1; PROBE 8 DESC[7] / PROBE 8 DESC[6]
HOT SPOT MODULE 1; PROBE 8 DESCRIPTION;
1384 CONT. READ MODULE 1; PROBE 8 DESC[9] / PROBE 8 DESC[8]
HOT SPOT MODULE 1; PROBE 8 DESCRIPTION;
1385 CONT. READ MODULE 1; PROBE 8 DESC[11] / PROBE 8 DESC[10]
HOT SPOT MODULE 1; PROBE 8 DESCRIPTION;
1386 CONT. READ MODULE 1; PROBE 8 DESC[13] / PROBE 8 DESC[12]
HOT SPOT MODULE 1; PROBE 8 DESCRIPTION;
1387 CONT. READ MODULE 1; PROBE 8 DESC[15] / PROBE 8 DESC[14]
HOT SPOT MODULE 1; PROBE 8 DESCRIPTION;
1388 CONT. READ MODULE 1; PROBE 8 DESC[17] / PROBE 8 DESC[16]
HOT SPOT MODULE 1; PROBE 8 DESCRIPTION;
1389 CONT. READ MODULE 1; PROBE 8 DESC[19] / PROBE 8 DESC[18]
HOT SPOT MODULE 1; PROBE 8 DESCRIPTION;
1390 CONT. READ MODULE 1; PROBE 8 DESC[21] / PROBE 8 DESC[20]
HOT SPOT MODULE 1; PROBE 8 DESCRIPTION;
1391 CONT. READ MODULE 1; PROBE 8 DESC[23] / PROBE 8 DESC[22]
HOT SPOT MODULE 2; PROBE 1 DESCRIPTION; 24
1392 CHAR READ MODULE 2; PROBE 1 DESC[1] / PROBE 1 DESC[0]

59 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
HOT SPOT MODULE 2; PROBE 1 DESCRIPTION;
1393 CONT. READ MODULE 2; PROBE 1 DESC[3] / PROBE 1 DESC[2]
HOT SPOT MODULE 2; PROBE 1 DESCRIPTION;
1394 CONT. READ MODULE 2; PROBE 1 DESC[5] / PROBE 1 DESC[4]
HOT SPOT MODULE 2; PROBE 1 DESCRIPTION;
1395 CONT. READ MODULE 2; PROBE 1 DESC[7] / PROBE 1 DESC[6]
HOT SPOT MODULE 2; PROBE 1 DESCRIPTION;
1396 CONT. READ MODULE 2; PROBE 1 DESC[9] / PROBE 1 DESC[8]
HOT SPOT MODULE 2; PROBE 1 DESCRIPTION;
1397 CONT. READ MODULE 2; PROBE 1 DESC[11] / PROBE 1 DESC[10]
HOT SPOT MODULE 2; PROBE 1 DESCRIPTION;
1398 CONT. READ MODULE 2; PROBE 1 DESC[13] / PROBE 1 DESC[12]
HOT SPOT MODULE 2; PROBE 1 DESCRIPTION;
1399 CONT. READ MODULE 2; PROBE 1 DESC[15] / PROBE 1 DESC[14]
HOT SPOT MODULE 2; PROBE 1 DESCRIPTION;
1400 CONT. READ MODULE 2; PROBE 1 DESC[17] / PROBE 1 DESC[16]
HOT SPOT MODULE 2; PROBE 1 DESCRIPTION;
1401 CONT. READ MODULE 2; PROBE 1 DESC[19] / PROBE 1 DESC[18]
HOT SPOT MODULE 2; PROBE 1 DESCRIPTION;
1402 CONT. READ MODULE 2; PROBE 1 DESC[21] / PROBE 1 DESC[20]
HOT SPOT MODULE 2; PROBE 1 DESCRIPTION;
1403 CONT. READ MODULE 2; PROBE 1 DESC[23] / PROBE 1 DESC[22]
HOT SPOT MODULE 2; PROBE 2 DESCRIPTION; 24
1404 CHAR READ MODULE 2; PROBE 2 DESC[1] / PROBE 2 DESC[0]
HOT SPOT MODULE 2; PROBE 2 DESCRIPTION;
1405 CONT. READ MODULE 2; PROBE 2 DESC[3] / PROBE 2 DESC[2]
HOT SPOT MODULE 2; PROBE 2 DESCRIPTION;
1406 CONT. READ MODULE 2; PROBE 2 DESC[5] / PROBE 2 DESC[4]
HOT SPOT MODULE 2; PROBE 2 DESCRIPTION;
1407 CONT. READ MODULE 2; PROBE 2 DESC[7] / PROBE 2 DESC[6]
HOT SPOT MODULE 2; PROBE 2 DESCRIPTION;
1408 CONT. READ MODULE 2; PROBE 2 DESC[9] / PROBE 2 DESC[8]
HOT SPOT MODULE 2; PROBE 2 DESCRIPTION;
1409 CONT. READ MODULE 2; PROBE 2 DESC[11] / PROBE 2 DESC[10]
HOT SPOT MODULE 2; PROBE 2 DESCRIPTION;
1410 CONT. READ MODULE 2; PROBE 2 DESC[13] / PROBE 2 DESC[12]
HOT SPOT MODULE 2; PROBE 2 DESCRIPTION;
1411 CONT. READ MODULE 2; PROBE 2 DESC[15] / PROBE 2 DESC[14]
HOT SPOT MODULE 2; PROBE 2 DESCRIPTION;
1412 CONT. READ MODULE 2; PROBE 2 DESC[17] / PROBE 2 DESC[16]
HOT SPOT MODULE 2; PROBE 2 DESCRIPTION;
1413 CONT. READ MODULE 2; PROBE 2 DESC[19] / PROBE 2 DESC[18]
HOT SPOT MODULE 2; PROBE 2 DESCRIPTION;
1414 CONT. READ MODULE 2; PROBE 2 DESC[21] / PROBE 2 DESC[20]
HOT SPOT MODULE 2; PROBE 2 DESCRIPTION;
1415 CONT. READ MODULE 2; PROBE 2 DESC[23] / PROBE 2 DESC[22]
HOT SPOT MODULE 2; PROBE 3 DESCRIPTION; 24
1416 CHAR READ MODULE 2; PROBE 3 DESC[1] / PROBE 3 DESC[0]
HOT SPOT MODULE 2; PROBE 3 DESCRIPTION;
1417 CONT. READ MODULE 2; PROBE 3 DESC[3] / PROBE 3 DESC[2]
HOT SPOT MODULE 2; PROBE 3 DESCRIPTION;
1418 CONT. READ MODULE 2; PROBE 3 DESC[5] / PROBE 3 DESC[4]
HOT SPOT MODULE 2; PROBE 3 DESCRIPTION;
1419 CONT. READ MODULE 2; PROBE 3 DESC[7] / PROBE 3 DESC[6]
HOT SPOT MODULE 2; PROBE 3 DESCRIPTION;
1420 CONT. READ MODULE 2; PROBE 3 DESC[9] / PROBE 3 DESC[8]
HOT SPOT MODULE 2; PROBE 3 DESCRIPTION;
1421 CONT. READ MODULE 2; PROBE 3 DESC[11] / PROBE 3 DESC[10]
HOT SPOT MODULE 2; PROBE 3 DESCRIPTION;
1422 CONT. READ MODULE 2; PROBE 3 DESC[13] / PROBE 3 DESC[12]
HOT SPOT MODULE 2; PROBE 3 DESCRIPTION;
1423 CONT. READ MODULE 2; PROBE 3 DESC[15] / PROBE 3 DESC[14]
HOT SPOT MODULE 2; PROBE 3 DESCRIPTION;
1424 CONT. READ MODULE 2; PROBE 3 DESC[17] / PROBE 3 DESC[16]
HOT SPOT MODULE 2; PROBE 3 DESCRIPTION;
1425 CONT. READ MODULE 2; PROBE 3 DESC[19] / PROBE 3 DESC[18]

60 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
HOT SPOT MODULE 2; PROBE 3 DESCRIPTION;
1426 CONT. READ MODULE 2; PROBE 3 DESC[21] / PROBE 3 DESC[20]
HOT SPOT MODULE 2; PROBE 3 DESCRIPTION;
1427 CONT. READ MODULE 2; PROBE 3 DESC[23] / PROBE 3 DESC[22]
HOT SPOT MODULE 2; PROBE 4 DESCRIPTION; 24
1428 CHAR READ MODULE 2; PROBE 4 DESC[1] / PROBE 4 DESC[0]
HOT SPOT MODULE 2; PROBE 4 DESCRIPTION;
1429 CONT. READ MODULE 2; PROBE 4 DESC[3] / PROBE 4 DESC[2]
HOT SPOT MODULE 2; PROBE 4 DESCRIPTION;
1430 CONT. READ MODULE 2; PROBE 4 DESC[5] / PROBE 4 DESC[4]
HOT SPOT MODULE 2; PROBE 4 DESCRIPTION;
1431 CONT. READ MODULE 2; PROBE 4 DESC[7] / PROBE 4 DESC[6]
HOT SPOT MODULE 2; PROBE 4 DESCRIPTION;
1432 CONT. READ MODULE 2; PROBE 4 DESC[9] / PROBE 4 DESC[8]
HOT SPOT MODULE 2; PROBE 4 DESCRIPTION;
1433 CONT. READ MODULE 2; PROBE 4 DESC[11] / PROBE 4 DESC[10]
HOT SPOT MODULE 2; PROBE 4 DESCRIPTION;
1434 CONT. READ MODULE 2; PROBE 4 DESC[13] / PROBE 4 DESC[12]
HOT SPOT MODULE 2; PROBE 4 DESCRIPTION;
1435 CONT. READ MODULE 2; PROBE 4 DESC[15] / PROBE 4 DESC[14]
HOT SPOT MODULE 2; PROBE 4 DESCRIPTION;
1436 CONT. READ MODULE 2; PROBE 4 DESC[17] / PROBE 4 DESC[16]
HOT SPOT MODULE 2; PROBE 4 DESCRIPTION;
1437 CONT. READ MODULE 2; PROBE 4 DESC[19] / PROBE 4 DESC[18]
HOT SPOT MODULE 2; PROBE 4 DESCRIPTION;
1438 CONT. READ MODULE 2; PROBE 4 DESC[21] / PROBE 4 DESC[20]
HOT SPOT MODULE 2; PROBE 4 DESCRIPTION;
1439 CONT. READ MODULE 2; PROBE 4 DESC[23] / PROBE 4 DESC[22]
HOT SPOT MODULE 2; PROBE 5 DESCRIPTION; 24
1440 CHAR READ MODULE 2; PROBE 5 DESC[1] / PROBE 5 DESC[0]
HOT SPOT MODULE 2; PROBE 5 DESCRIPTION;
1441 CONT. READ MODULE 2; PROBE 5 DESC[3] / PROBE 5 DESC[2]
HOT SPOT MODULE 2; PROBE 5 DESCRIPTION;
1442 CONT. READ MODULE 2; PROBE 5 DESC[5] / PROBE 5 DESC[4]
HOT SPOT MODULE 2; PROBE 5 DESCRIPTION;
1443 CONT. READ MODULE 2; PROBE 5 DESC[7] / PROBE 5 DESC[6]
HOT SPOT MODULE 2; PROBE 5 DESCRIPTION;
1444 CONT. READ MODULE 2; PROBE 5 DESC[9] / PROBE 5 DESC[8]
HOT SPOT MODULE 2; PROBE 5 DESCRIPTION;
1445 CONT. READ MODULE 2; PROBE 5 DESC[11] / PROBE 5 DESC[10]
HOT SPOT MODULE 2; PROBE 5 DESCRIPTION;
1446 CONT. READ MODULE 2; PROBE 5 DESC[13] / PROBE 5 DESC[12]
HOT SPOT MODULE 2; PROBE 5 DESCRIPTION;
1447 CONT. READ MODULE 2; PROBE 5 DESC[15] / PROBE 5 DESC[14]
HOT SPOT MODULE 2; PROBE 5 DESCRIPTION;
1448 CONT. READ MODULE 2; PROBE 5 DESC[17] / PROBE 5 DESC[16]
HOT SPOT MODULE 2; PROBE 5 DESCRIPTION;
1449 CONT. READ MODULE 2; PROBE 5 DESC[19] / PROBE 5 DESC[18]
HOT SPOT MODULE 2; PROBE 5 DESCRIPTION;
1450 CONT. READ MODULE 2; PROBE 5 DESC[21] / PROBE 5 DESC[20]
HOT SPOT MODULE 2; PROBE 5 DESCRIPTION;
1451 CONT. READ MODULE 2; PROBE 5 DESC[23] / PROBE 5 DESC[22]
HOT SPOT MODULE 2; PROBE 6 DESCRIPTION; 24
1452 CHAR READ MODULE 2; PROBE 6 DESC[1] / PROBE 6 DESC[0]
HOT SPOT MODULE 2; PROBE 6 DESCRIPTION;
1453 CONT. READ MODULE 2; PROBE 6 DESC[3] / PROBE 6 DESC[2]
HOT SPOT MODULE 2; PROBE 6 DESCRIPTION;
1454 CONT. READ MODULE 2; PROBE 6 DESC[5] / PROBE 6 DESC[4]
HOT SPOT MODULE 2; PROBE 6 DESCRIPTION;
1455 CONT. READ MODULE 2; PROBE 6 DESC[7] / PROBE 6 DESC[6]
HOT SPOT MODULE 2; PROBE 6 DESCRIPTION;
1456 CONT. READ MODULE 2; PROBE 6 DESC[9] / PROBE 6 DESC[8]
HOT SPOT MODULE 2; PROBE 6 DESCRIPTION;
1457 CONT. READ MODULE 2; PROBE 6 DESC[11] / PROBE 6 DESC[10]
HOT SPOT MODULE 2; PROBE 6 DESCRIPTION;
1458 CONT. READ MODULE 2; PROBE 6 DESC[13] / PROBE 6 DESC[12]

61 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
HOT SPOT MODULE 2; PROBE 6 DESCRIPTION;
1459 CONT. READ MODULE 2; PROBE 6 DESC[15] / PROBE 6 DESC[14]
HOT SPOT MODULE 2; PROBE 6 DESCRIPTION;
1460 CONT. READ MODULE 2; PROBE 6 DESC[17] / PROBE 6 DESC[16]
HOT SPOT MODULE 2; PROBE 6 DESCRIPTION;
1461 CONT. READ MODULE 2; PROBE 6 DESC[19] / PROBE 6 DESC[18]
HOT SPOT MODULE 2; PROBE 6 DESCRIPTION;
1462 CONT. READ MODULE 2; PROBE 6 DESC[21] / PROBE 6 DESC[20]
HOT SPOT MODULE 2; PROBE 6 DESCRIPTION;
1463 CONT. READ MODULE 2; PROBE 6 DESC[23] / PROBE 6 DESC[22]
HOT SPOT MODULE 2; PROBE 7 DESCRIPTION; 24
1464 CHAR READ MODULE 2; PROBE 7 DESC[1] / PROBE 7 DESC[0]
HOT SPOT MODULE 2; PROBE 7 DESCRIPTION;
1465 CONT. READ MODULE 2; PROBE 7 DESC[3] / PROBE 7 DESC[2]
HOT SPOT MODULE 2; PROBE 7 DESCRIPTION;
1466 CONT. READ MODULE 2; PROBE 7 DESC[5] / PROBE 7 DESC[4]
HOT SPOT MODULE 2; PROBE 7 DESCRIPTION;
1467 CONT. READ MODULE 2; PROBE 7 DESC[7] / PROBE 7 DESC[6]
HOT SPOT MODULE 2; PROBE 7 DESCRIPTION;
1468 CONT. READ MODULE 2; PROBE 7 DESC[9] / PROBE 7 DESC[8]
HOT SPOT MODULE 2; PROBE 7 DESCRIPTION;
1469 CONT. READ MODULE 2; PROBE 7 DESC[11] / PROBE 7 DESC[10]
HOT SPOT MODULE 2; PROBE 7 DESCRIPTION;
1470 CONT. READ MODULE 2; PROBE 7 DESC[13] / PROBE 7 DESC[12]
HOT SPOT MODULE 2; PROBE 7 DESCRIPTION;
1471 CONT. READ MODULE 2; PROBE 7 DESC[15] / PROBE 7 DESC[14]
HOT SPOT MODULE 2; PROBE 7 DESCRIPTION;
1472 CONT. READ MODULE 2; PROBE 7 DESC[17] / PROBE 7 DESC[16]
HOT SPOT MODULE 2; PROBE 7 DESCRIPTION;
1473 CONT. READ MODULE 2; PROBE 7 DESC[19] / PROBE 7 DESC[18]
HOT SPOT MODULE 2; PROBE 7 DESCRIPTION;
1474 CONT. READ MODULE 2; PROBE 7 DESC[21] / PROBE 7 DESC[20]
HOT SPOT MODULE 2; PROBE 7 DESCRIPTION;
1475 CONT. READ MODULE 2; PROBE 7 DESC[23] / PROBE 7 DESC[22]
HOT SPOT MODULE 2; PROBE 8 DESCRIPTION; 24
1476 CHAR READ MODULE 2; PROBE 8 DESC[1] / PROBE 8 DESC[0]
HOT SPOT MODULE 2; PROBE 8 DESCRIPTION;
1477 CONT. READ MODULE 2; PROBE 8 DESC[3] / PROBE 8 DESC[2]
HOT SPOT MODULE 2; PROBE 8 DESCRIPTION;
1478 CONT. READ MODULE 2; PROBE 8 DESC[5] / PROBE 8 DESC[4]
HOT SPOT MODULE 2; PROBE 8 DESCRIPTION;
1479 CONT. READ MODULE 2; PROBE 8 DESC[7] / PROBE 8 DESC[6]
HOT SPOT MODULE 2; PROBE 8 DESCRIPTION;
1480 CONT. READ MODULE 2; PROBE 8 DESC[9] / PROBE 8 DESC[8]
HOT SPOT MODULE 2; PROBE 8 DESCRIPTION;
1481 CONT. READ MODULE 2; PROBE 8 DESC[11] / PROBE 8 DESC[10]
HOT SPOT MODULE 2; PROBE 8 DESCRIPTION;
1482 CONT. READ MODULE 2; PROBE 8 DESC[13] / PROBE 8 DESC[12]
HOT SPOT MODULE 2; PROBE 8 DESCRIPTION;
1483 CONT. READ MODULE 2; PROBE 8 DESC[15] / PROBE 8 DESC[14]
HOT SPOT MODULE 2; PROBE 8 DESCRIPTION;
1484 CONT. READ MODULE 2; PROBE 8 DESC[17] / PROBE 8 DESC[16]
HOT SPOT MODULE 2; PROBE 8 DESCRIPTION;
1485 CONT. READ MODULE 2; PROBE 8 DESC[19] / PROBE 8 DESC[18]
HOT SPOT MODULE 2; PROBE 8 DESCRIPTION;
1486 CONT. READ MODULE 2; PROBE 8 DESC[21] / PROBE 8 DESC[20]
HOT SPOT MODULE 2; PROBE 8 DESCRIPTION;
1487 CONT. READ MODULE 2; PROBE 8 DESC[23] / PROBE 8 DESC[22]

Analog Parameters
Registers 1500 thru 1507, see appropriate scaling (e.g. N, 10X, 100X, 1000X)

REG # VARIABLE R/W DESCRIPTION


1500 INPUT MODULE 1; CT CLAMP-ON RATING VALUE READ IF INPUT MODULE A CT TYPE; HOLDS SENSOR VALUE (N)

62 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
1501 INPUT MODULE 2; CT CLAMP-ON RATING VALUE READ IF INPUT MODULE A CT TYPE; HOLDS SENSOR VALUE (N)
1502 INPUT MODULE 3; CT CLAMP-ON RATING VALUE READ IF INPUT MODULE A CT TYPE; HOLDS SENSOR VALUE (N)
1503 INPUT MODULE 4; CT CLAMP-ON RATING VALUE READ IF INPUT MODULE A CT TYPE; HOLDS SENSOR VALUE (N)
1504 INPUT MODULE 5; CT CLAMP-ON RATING VALUE READ IF INPUT MODULE A CT TYPE; HOLDS SENSOR VALUE (N)
1505 INPUT MODULE 6; CT CLAMP-ON RATING VALUE READ IF INPUT MODULE A CT TYPE; HOLDS SENSOR VALUE (N)
1506 INPUT MODULE 7; CT CLAMP-ON RATING VALUE READ IF INPUT MODULE A CT TYPE; HOLDS SENSOR VALUE (N)
1507 INPUT MODULE 8; CT CLAMP-ON RATING VALUE READ IF INPUT MODULE A CT TYPE; HOLDS SENSOR VALUE (N)

String Parameters
Registers 1508 thru 1523.

REG # VARIABLE R/W DESCRIPTION


INPUT MODULE 1 MEASUREMENT UNITS; 3 ASCII
1508 CHAR READ INPUT MODULE 1; UNITS[1] / UNITS[0]
INPUT MODULE 1 MEASUREMENT UNITS;
1509 CONTINUED READ INPUT MODULE 1; ZERO / UNITS[2]
INPUT MODULE 2 MEASUREMENT UNITS; 3 ASCII
1510 CHAR READ INPUT MODULE 2; UNITS[1] / UNITS[0]
INPUT MODULE 2 MEASUREMENT UNITS;
1511 CONTINUED READ INPUT MODULE 2; ZERO / UNITS[2]
INPUT MODULE 3 MEASUREMENT UNITS; 3 ASCII
1512 CHAR READ INPUT MODULE 3; UNITS[1] / UNITS[0]
INPUT MODULE 3 MEASUREMENT UNITS;
1513 CONTINUED READ INPUT MODULE 3; ZERO / UNITS[2]
INPUT MODULE 4 MEASUREMENT UNITS; 3 ASCII
1514 CHAR READ INPUT MODULE 4; UNITS[1] / UNITS[0]
INPUT MODULE 4 MEASUREMENT UNITS;
1515 CONTINUED READ INPUT MODULE 4; ZERO / UNITS[2]
INPUT MODULE 5 MEASUREMENT UNITS; 3 ASCII
1516 CHAR READ INPUT MODULE 5; UNITS[1] / UNITS[0]
INPUT MODULE 5 MEASUREMENT UNITS;
1517 CONTINUED READ INPUT MODULE 5; ZERO / UNITS[2]
INPUT MODULE 6 MEASUREMENT UNITS; 3 ASCII
1518 CHAR READ INPUT MODULE 6; UNITS[1] / UNITS[0]
INPUT MODULE 6 MEASUREMENT UNITS;
1519 CONTINUED READ INPUT MODULE 6; ZERO / UNITS[2]
INPUT MODULE 7 MEASUREMENT UNITS; 3 ASCII
1520 CHAR READ INPUT MODULE 7; UNITS[1] / UNITS[0]
INPUT MODULE 7 MEASUREMENT UNITS;
1521 CONTINUED READ INPUT MODULE 7; ZERO / UNITS[2]
INPUT MODULE 8 MEASUREMENT UNITS; 3 ASCII
1522 CHAR READ INPUT MODULE 8; UNITS[1] / UNITS[0]
INPUT MODULE 8 MEASUREMENT UNITS;
1523 CONTINUED READ INPUT MODULE 8; ZERO / UNITS[2]

Analog Parameters
Registers 1524 thru 1823; see appropriate scaling (e.g. N, 10X, 100X, 1000X)
REG # VARIABLE R/W DESCRIPTION
INPUT MODULE 1 OIL TEMPERATURE ADDER IF CT INPUT MODULE; POINTER TO OIL TEMP
1524 POINTER READ MEASUREMENT (N)
INPUT MODULE 2 OIL TEMPERATURE ADDER IF CT INPUT MODULE; POINTER TO OIL TEMP
1525 POINTER READ MEASUREMENT (N)
INPUT MODULE 3 OIL TEMPERATURE ADDER IF CT INPUT MODULE; POINTER TO OIL TEMP
1526 POINTER READ MEASUREMENT (N)
INPUT MODULE 4 OIL TEMPERATURE ADDER IF CT INPUT MODULE; POINTER TO OIL TEMP
1527 POINTER READ MEASUREMENT (N)
INPUT MODULE 5 OIL TEMPERATURE ADDER IF CT INPUT MODULE; POINTER TO OIL TEMP
1528 POINTER READ MEASUREMENT (N)

63 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
INPUT MODULE 6 OIL TEMPERATURE ADDER IF CT INPUT MODULE; POINTER TO OIL TEMP
1529 POINTER READ MEASUREMENT (N)
INPUT MODULE 7 OIL TEMPERATURE ADDER IF CT INPUT MODULE; POINTER TO OIL TEMP
1530 POINTER READ MEASUREMENT (N)
INPUT MODULE 8 OIL TEMPERATURE ADDER IF CT INPUT MODULE; POINTER TO OIL TEMP
1531 POINTER READ MEASUREMENT (N)
1532 INPUT MODULE 1; COOLING STAGE 2 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1533 INPUT MODULE 1; COOLING STAGE 3 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1534 INPUT MODULE 1; COOLING STAGE 4 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1535 INPUT MODULE 2; COOLING STAGE 2 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1536 INPUT MODULE 2; COOLING STAGE 3 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1537 INPUT MODULE 2; COOLING STAGE 4 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1538 INPUT MODULE 3; COOLING STAGE 2 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1539 INPUT MODULE 3; COOLING STAGE 3 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1540 INPUT MODULE 3; COOLING STAGE 4 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1541 INPUT MODULE 4; COOLING STAGE 2 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1542 INPUT MODULE 4; COOLING STAGE 3 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1543 INPUT MODULE 4; COOLING STAGE 4 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1544 INPUT MODULE 5; COOLING STAGE 2 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1545 INPUT MODULE 5; COOLING STAGE 3 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1546 INPUT MODULE 5; COOLING STAGE 4 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1547 INPUT MODULE 6; COOLING STAGE 2 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1548 INPUT MODULE 6; COOLING STAGE 3 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1549 INPUT MODULE 6; COOLING STAGE 4 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1550 INPUT MODULE 7; COOLING STAGE 2 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1551 INPUT MODULE 7; COOLING STAGE 3 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1552 INPUT MODULE 7; COOLING STAGE 4 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1553 INPUT MODULE 8; COOLING STAGE 2 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1554 INPUT MODULE 8; COOLING STAGE 3 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1555 INPUT MODULE 8; COOLING STAGE 4 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)

1600 INPUT MODULE 1; CT RATIO PRIMARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1602 INPUT MODULE 2; CT RATIO PRIMARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1604 INPUT MODULE 3; CT RATIO PRIMARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1606 INPUT MODULE 4; CT RATIO PRIMARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1608 INPUT MODULE 5; CT RATIO PRIMARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1610 INPUT MODULE 6; CT RATIO PRIMARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1612 INPUT MODULE 7; CT RATIO PRIMARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1614 INPUT MODULE 8; CT RATIO PRIMARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1616 INPUT MODULE 1; CT RATIO SECONDARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1618 INPUT MODULE 2; CT RATIO SECONDARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1620 INPUT MODULE 3; CT RATIO SECONDARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1622 INPUT MODULE 4; CT RATIO SECONDARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1624 INPUT MODULE 5; CT RATIO SECONDARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1626 INPUT MODULE 6; CT RATIO SECONDARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1628 INPUT MODULE 7; CT RATIO SECONDARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1630 INPUT MODULE 8; CT RATIO SECONDARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1632 INPUT MODULE 1; SCALING OFFSET VALUE READ SCALING OFFSET CALIBRATION VALUE (1000X)
1634 INPUT MODULE 2; SCALING OFFSET VALUE READ SCALING OFFSET CALIBRATION VALUE (1000X)

64 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
1636 INPUT MODULE 3; SCALING OFFSET VALUE READ SCALING OFFSET CALIBRATION VALUE (1000X)
1638 INPUT MODULE 4; SCALING OFFSET VALUE READ SCALING OFFSET CALIBRATION VALUE (1000X)
1640 INPUT MODULE 5; SCALING OFFSET VALUE READ SCALING OFFSET CALIBRATION VALUE (1000X)
1642 INPUT MODULE 6; SCALING OFFSET VALUE READ SCALING OFFSET CALIBRATION VALUE (1000X)
1644 INPUT MODULE 7; SCALING OFFSET VALUE READ SCALING OFFSET CALIBRATION VALUE (1000X)
1646 INPUT MODULE 8; SCALING OFFSET VALUE READ SCALING OFFSET CALIBRATION VALUE (1000X)
1648 INPUT MODULE 1; SCALING GAIN VALUE READ SCALING GAIN CALIBRATION VALUE (1000X)
1650 INPUT MODULE 2; SCALING GAIN VALUE READ SCALING GAIN CALIBRATION VALUE (1000X)
1652 INPUT MODULE 3; SCALING GAIN VALUE READ SCALING GAIN CALIBRATION VALUE (1000X)
1654 INPUT MODULE 4; SCALING GAIN VALUE READ SCALING GAIN CALIBRATION VALUE (1000X)
1656 INPUT MODULE 5; SCALING GAIN VALUE READ SCALING GAIN CALIBRATION VALUE (1000X)
1658 INPUT MODULE 6; SCALING GAIN VALUE READ SCALING GAIN CALIBRATION VALUE (1000X)
1660 INPUT MODULE 7; SCALING GAIN VALUE READ SCALING GAIN CALIBRATION VALUE (1000X)
1662 INPUT MODULE 8; SCALING GAIN VALUE READ SCALING GAIN CALIBRATION VALUE (1000X)

FOR REGISTERS 1664 THRU 1823 THE PARAMETERS ARE 32 BITS LONG WITH THE EVEN REGISTERS HOLDING THE LOW WORD
AND THE HIGH REGISTERS HOLDING THE HIGH WORD (E.G. 1664 LOW WORD; 1665 HIGH WORD). THESE REGISTERS ARE FOR
THOSE APPLICATIONS WHERE THE INPUT MODULE VALUE COULD BE GREATER THAN 3200.
ALL MODULES BUT CT, WINDING TEMPERATURE IF THE MODULE IS A CT, WINDING TEMPERATURE
1664 INPUT MODULE 1 PRESENT VALUE READ OR INPUT MODULE 1 PRESENT WINDING TEMP (10X)
1666 INPUT MODULE 1 MINIMUM VALUE READ OR INPUT MODULE 1 MINIMUM WINDING TEMP (10X)
1668 INPUT MODULE 1 MAXIMUM VALUE READ OR INPUT MODULE 1 MAXIMUM WINDING TEMP (10X)
1670 0 READ OR INPUT MODULE 1 PRESENT CURRENT (10X)
1672 0 READ OR INPUT MODULE 1 MAXIMUM CURRENT (10X)
1674 INPUT MODULE 2 PRESENT VALUE READ OR INPUT MODULE 2 PRESENT WINDING TEMP (10X)
1676 INPUT MODULE 2 MINIMUM VALUE READ OR INPUT MODULE 2 MINIMUM WINDING TEMP (10X)
1678 INPUT MODULE 2 MAXIMUM VALUE READ OR INPUT MODULE 2 MAXIMUM WINDING TEMP (10X)
1680 0 READ OR INPUT MODULE 2 PRESENT CURRENT (10X)
1682 0 READ OR INPUT MODULE 2 MAXIMUM CURRENT (10X)
1684 INPUT MODULE 3 PRESENT VALUE READ OR INPUT MODULE 3 PRESENT WINDING TEMP (10X)
1686 INPUT MODULE 3 MINIMUM VALUE READ OR INPUT MODULE 3 MINIMUM WINDING TEMP (10X)
1688 INPUT MODULE 3 MAXIMUM VALUE READ OR INPUT MODULE 3 MAXIMUM WINDING TEMP (10X)
1690 0 READ OR INPUT MODULE 3 PRESENT CURRENT (10X)
1692 0 READ OR INPUT MODULE 3 MAXIMUM CURRENT (10X)
1694 INPUT MODULE 4 PRESENT VALUE READ OR INPUT MODULE 4 PRESENT WINDING TEMP (10X)
1696 INPUT MODULE 4 MINIMUM VALUE READ OR INPUT MODULE 4 MINIMUM WINDING TEMP (10X)
1698 INPUT MODULE 4 MAXIMUM VALUE READ OR INPUT MODULE 4 MAXIMUM WINDING TEMP (10X)
1700 0 READ OR INPUT MODULE 4 PRESENT CURRENT (10X)
1702 0 READ OR INPUT MODULE 4 MAXIMUM CURRENT (10X)
1704 INPUT MODULE 5 PRESENT VALUE READ OR INPUT MODULE 5 PRESENT WINDING TEMP (10X)
1706 INPUT MODULE 5 MINIMUM VALUE READ OR INPUT MODULE 5 MINIMUM WINDING TEMP (10X)
1708 INPUT MODULE 5 MAXIMUM VALUE READ OR INPUT MODULE 5 MAXIMUM WINDING TEMP (10X)
1710 0 READ OR INPUT MODULE 5 PRESENT CURRENT (10X)
1712 0 READ OR INPUT MODULE 5 MAXIMUM CURRENT (10X)
1714 INPUT MODULE 6 PRESENT VALUE READ OR INPUT MODULE 6 PRESENT WINDING TEMP (10X)
1716 INPUT MODULE 6 MINIMUM VALUE READ OR INPUT MODULE 6 MINIMUM WINDING TEMP (10X)
1718 INPUT MODULE 6 MAXIMUM VALUE READ OR INPUT MODULE 6 MAXIMUM WINDING TEMP (10X)
1720 0 READ OR INPUT MODULE 6 PRESENT CURRENT (10X)
1722 0 READ OR INPUT MODULE 6 MAXIMUM CURRENT (10X)

65 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
1724 INPUT MODULE 7 PRESENT VALUE READ OR INPUT MODULE 7 PRESENT WINDING TEMP (10X)
1726 INPUT MODULE 7 MINIMUM VALUE READ OR INPUT MODULE 7 MINIMUM WINDING TEMP (10X)
1728 INPUT MODULE 7 MAXIMUM VALUE READ OR INPUT MODULE 7 MAXIMUM WINDING TEMP (10X)
1730 0 READ OR INPUT MODULE 7 PRESENT CURRENT (10X)
1732 0 READ OR INPUT MODULE 7 MAXIMUM CURRENT (10X)
1734 INPUT MODULE 8 PRESENT VALUE READ OR INPUT MODULE 8 PRESENT WINDING TEMP (10X)
1736 INPUT MODULE 8 MINIMUM VALUE READ OR INPUT MODULE 8 MINIMUM WINDING TEMP (10X)
1738 INPUT MODULE 8 MAXIMUM VALUE READ OR INPUT MODULE 8 MAXIMUM WINDING TEMP (10X)
1740 0 READ OR INPUT MODULE 8 PRESENT CURRENT (10X)
1742 0 READ OR INPUT MODULE 8 MAXIMUM CURRENT (10X)
1744 INPUT MODULE 9 PRESENT VALUE READ OR INPUT MODULE 9 PRESENT WINDING TEMP (10X)
1746 INPUT MODULE 9 MINIMUM VALUE READ OR INPUT MODULE 9 MINIMUM WINDING TEMP (10X)
1748 INPUT MODULE 9 MAXIMUM VALUE READ OR INPUT MODULE 9 MAXIMUM WINDING TEMP (10X)
1750 0 READ OR INPUT MODULE 9 PRESENT CURRENT (10X)
1752 0 READ OR INPUT MODULE 9 MAXIMUM CURRENT (10X)
1754 INPUT MODULE 10 PRESENT VALUE READ OR INPUT MODULE 10 PRESENT WINDING TEMP (10X)
1756 INPUT MODULE 10 MINIMUM VALUE READ OR INPUT MODULE 10 MINIMUM WINDING TEMP (10X)
1758 INPUT MODULE 10 MAXIMUM VALUE READ OR INPUT MODULE 10 MAXIMUM WINDING TEMP (10X)
1760 0 READ OR INPUT MODULE 10 PRESENT CURRENT (10X)
1762 0 READ OR INPUT MODULE 10 MAXIMUM CURRENT (10X)
1764 INPUT MODULE 11 PRESENT VALUE READ OR INPUT MODULE 11 PRESENT WINDING TEMP (10X)
1766 INPUT MODULE 11 MINIMUM VALUE READ OR INPUT MODULE 11 MINIMUM WINDING TEMP (10X)
1768 INPUT MODULE 11 MAXIMUM VALUE READ OR INPUT MODULE 11 MAXIMUM WINDING TEMP (10X)
1770 0 READ OR INPUT MODULE 11 PRESENT CURRENT (10X)
1772 0 READ OR INPUT MODULE 11 MAXIMUM CURRENT (10X)
1774 INPUT MODULE 12 PRESENT VALUE READ OR INPUT MODULE 12 PRESENT WINDING TEMP (10X)
1776 INPUT MODULE 12 MINIMUM VALUE READ OR INPUT MODULE 12 MINIMUM WINDING TEMP (10X)
1778 INPUT MODULE 12 MAXIMUM VALUE READ OR INPUT MODULE 12 MAXIMUM WINDING TEMP (10X)
1780 0 READ OR INPUT MODULE 12 PRESENT CURRENT (10X)
1782 0 READ OR INPUT MODULE 12 MAXIMUM CURRENT (10X)
1784 INPUT MODULE 13 PRESENT VALUE READ OR INPUT MODULE 13 PRESENT WINDING TEMP (10X)
1786 INPUT MODULE 13 MINIMUM VALUE READ OR INPUT MODULE 13 MINIMUM WINDING TEMP (10X)
1788 INPUT MODULE 13 MAXIMUM VALUE READ OR INPUT MODULE 13 MAXIMUM WINDING TEMP (10X)
1790 0 READ OR INPUT MODULE 13 PRESENT CURRENT (10X)
1792 0 READ OR INPUT MODULE 13 MAXIMUM CURRENT (10X)
1794 INPUT MODULE 14 PRESENT VALUE READ OR INPUT MODULE 14 PRESENT WINDING TEMP (10X)
1796 INPUT MODULE 14 MINIMUM VALUE READ OR INPUT MODULE 14 MINIMUM WINDING TEMP (10X)
1798 INPUT MODULE 14 MAXIMUM VALUE READ OR INPUT MODULE 14 MAXIMUM WINDING TEMP (10X)
1800 0 READ OR INPUT MODULE 14 PRESENT CURRENT (10X)
1802 0 READ OR INPUT MODULE 14 MAXIMUM CURRENT (10X)
1804 INPUT MODULE 15 PRESENT VALUE READ OR INPUT MODULE 15 PRESENT WINDING TEMP (10X)
1806 INPUT MODULE 15 MINIMUM VALUE READ OR INPUT MODULE 15 MINIMUM WINDING TEMP (10X)
1808 INPUT MODULE 15 MAXIMUM VALUE READ OR INPUT MODULE 15 MAXIMUM WINDING TEMP (10X)
1810 0 READ OR INPUT MODULE 15 PRESENT CURRENT (10X)
1812 0 READ OR INPUT MODULE 15 MAXIMUM CURRENT (10X)
1814 INPUT MODULE 16 PRESENT VALUE READ OR INPUT MODULE 16 PRESENT WINDING TEMP (10X)
1816 INPUT MODULE 16 MINIMUM VALUE READ OR INPUT MODULE 16 MINIMUM WINDING TEMP (10X)
1818 INPUT MODULE 16 MAXIMUM VALUE READ OR INPUT MODULE 16 MAXIMUM WINDING TEMP (10X)

66 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
1820 0 READ OR INPUT MODULE 16 PRESENT CURRENT (10X)
1822 0 READ OR INPUT MODULE 16 MAXIMUM CURRENT (10X)

String Parameters
Registers 1824 thru 1871.
REG # VARIABLE R/W DESCRIPTION
DGA HYDROGEN SENSOR 1 NAME; 7 ASCII
1824 CHARS READ HYDROGEN SENSOR 1 NAME[1] / PROBE 1 NAME[0]
1825 DGA HYDROGEN SENSOR 1 NAME; CONTINUED READ HYDROGEN SENSOR 1 NAME[3] / PROBE 1 NAME[2]
1826 DGA HYDROGEN SENSOR 1 NAME; CONTINUED READ HYDROGEN SENSOR 1 NAME[5] / PROBE 1 NAME[4]
1827 DGA HYDROGEN SENSOR 1 NAME; CONTINUED READ HYDROGEN SENSOR 1 ZERO / PROBE 1 NAME[6]
DGA HYDROGEN SENSOR 2 NAME; 7 ASCII
1828 CHARS READ HYDROGEN SENSOR 2 NAME[1] / PROBE 1 NAME[0]
1829 DGA HYDROGEN SENSOR 2 NAME; CONTINUED READ HYDROGEN SENSOR 2 NAME[3] / PROBE 1 NAME[2]
1830 DGA HYDROGEN SENSOR 2 NAME; CONTINUED READ HYDROGEN SENSOR 2 NAME[5] / PROBE 1 NAME[4]
1831 DGA HYDROGEN SENSOR 2 NAME; CONTINUED READ HYDROGEN SENSOR 2 ZERO / PROBE 1 NAME[6]
DGA HYDROGEN SENSOR 3 NAME; 7 ASCII
1832 CHARS READ HYDROGEN SENSOR 3 NAME[1] / PROBE 1 NAME[0]
1833 DGA HYDROGEN SENSOR 3 NAME; CONTINUED READ HYDROGEN SENSOR 3 NAME[3] / PROBE 1 NAME[2]
1834 DGA HYDROGEN SENSOR 3 NAME; CONTINUED READ HYDROGEN SENSOR 3 NAME[5] / PROBE 1 NAME[4]
1835 DGA HYDROGEN SENSOR 3 NAME; CONTINUED READ HYDROGEN SENSOR 3 ZERO / PROBE 1 NAME[6]
H2 SENSOR 1 LAST CALIBRATION DATE; 8
1836 CHARS READ DGA 1 DATE[1] / DATE[0]; MONTH ONES / MONTHS TENS
H2 SENSOR 1 LAST CALIBRATION DATE;
1837 CONTINUED READ DGA 1 DATE[3] / DATE[2]; DAY TENS / BACKSLASH
H2 SENSOR 1 LAST CALIBRATION DATE;
1838 CONTINUED READ DGA 1 DATE[5] / DATE[4]; BACKSLASH / DAY ONES
H2 SENSOR 1 LAST CALIBRATION DATE;
1839 CONTINUED READ DGA 1 DATE[7] / DATE[6]; YEAR ONES / YEAR TENS
H2 SENSOR 1 NEXT CALIBRATION DATE; 8
1840 CHARS READ DGA 1 DATE[1] / DATE[0]; MONTH ONES / MONTHS TENS
H2 SENSOR 1 NEXT CALIBRATION DATE;
1841 CONTINUED READ DGA 1 DATE[3] / DATE[2]; DAY TENS / BACKSLASH
H2 SENSOR 1 NEXT CALIBRATION DATE;
1842 CONTINUED READ DGA 1 DATE[5] / DATE[4]; BACKSLASH / DAY ONES
H2 SENSOR 1 NEXT CALIBRATION DATE;
1843 CONTINUED READ DGA 1 DATE[7] / DATE[6]; YEAR ONES / YEAR TENS
1844 H2 SENSOR 1 LAB OIL SAMPLE DATE; 8 CHARS READ DGA 1 DATE[1] / DATE[0]; MONTH ONES / MONTHS TENS
H2 SENSOR 1 LAB OIL SAMPLE DATE;
1845 CONTINUED READ DGA 1 DATE[3] / DATE[2]; DAY TENS / BACKSLASH
H2 SENSOR 1 LAB OIL SAMPLE DATE;
1846 CONTINUED READ DGA 1 DATE[5] / DATE[4]; BACKSLASH / DAY ONES
H2 SENSOR 1 LAB OIL SAMPLE DATE;
1847 CONTINUED READ DGA 1 DATE[7] / DATE[6]; YEAR ONES / YEAR TENS
H2 SENSOR 2 LAST CALIBRATION DATE; 8
1848 CHARS READ DGA 2 DATE[1] / DATE[0]; MONTH ONES / MONTHS TENS
H2 SENSOR 2 LAST CALIBRATION DATE;
1849 CONTINUED READ DGA 2 DATE[3] / DATE[2]; DAY TENS / BACKSLASH
H2 SENSOR 2 LAST CALIBRATION DATE;
1850 CONTINUED READ DGA 2 DATE[5] / DATE[4]; BACKSLASH / DAY ONES
H2 SENSOR 2 LAST CALIBRATION DATE;
1851 CONTINUED READ DGA 2 DATE[7] / DATE[6]; YEAR ONES / YEAR TENS
H2 SENSOR 2 NEXT CALIBRATION DATE; 8
1852 CHARS READ DGA 2 DATE[1] / DATE[0]; MONTH ONES / MONTHS TENS
H2 SENSOR 2 NEXT CALIBRATION DATE;
1853 CONTINUED READ DGA 2 DATE[3] / DATE[2]; DAY TENS / BACKSLASH
H2 SENSOR 2 NEXT CALIBRATION DATE;
1854 CONTINUED READ DGA 2 DATE[5] / DATE[4]; BACKSLASH / DAY ONES
1855 H2 SENSOR 2 NEXT CALIBRATION DATE; READ DGA 2 DATE[7] / DATE[6]; YEAR ONES / YEAR TENS

67 www.qualitrolcorp.com
CONTINUED

1856 H2 SENSOR 2 LAB OIL SAMPLE DATE; 8 CHARS READ DGA 2 DATE[1] / DATE[0]; MONTH ONES / MONTHS TENS
H2 SENSOR 2 LAB OIL SAMPLE DATE;
1857 CONTINUED READ DGA 2 DATE[3] / DATE[2]; DAY TENS / BACKSLASH
H2 SENSOR 2 LAB OIL SAMPLE DATE;
1858 CONTINUED READ DGA 2 DATE[5] / DATE[4]; BACKSLASH / DAY ONES
H2 SENSOR 2 LAB OIL SAMPLE DATE;
1859 CONTINUED READ DGA 2 DATE[7] / DATE[6]; YEAR ONES / YEAR TENS
H2 SENSOR 3 LAST CALIBRATION DATE; 8
1860 CHARS READ DGA 3 DATE[1] / DATE[0]; MONTH ONES / MONTHS TENS
H2 SENSOR 3 LAST CALIBRATION DATE;
1861 CONTINUED READ DGA 3 DATE[3] / DATE[2]; DAY TENS / BACKSLASH
H2 SENSOR 3 LAST CALIBRATION DATE;
1862 CONTINUED READ DGA 3 DATE[5] / DATE[4]; BACKSLASH / DAY ONES
H2 SENSOR 3 LAST CALIBRATION DATE;
1863 CONTINUED READ DGA 3 DATE[7] / DATE[6]; YEAR ONES / YEAR TENS
H2 SENSOR 3 NEXT CALIBRATION DATE; 8
1864 CHARS READ DGA 3 DATE[1] / DATE[0]; MONTH ONES / MONTHS TENS
H2 SENSOR 3 NEXT CALIBRATION DATE;
1865 CONTINUED READ DGA 3 DATE[3] / DATE[2]; DAY TENS / BACKSLASH
H2 SENSOR 3 NEXT CALIBRATION DATE;
1866 CONTINUED READ DGA 3 DATE[5] / DATE[4]; BACKSLASH / DAY ONES
H2 SENSOR 3 NEXT CALIBRATION DATE;
1867 CONTINUED READ DGA 3 DATE[7] / DATE[6]; YEAR ONES / YEAR TENS
1868 H2 SENSOR 3 LAB OIL SAMPLE DATE; 8 CHARS READ DGA 3 DATE[1] / DATE[0]; MONTH ONES / MONTHS TENS
H2 SENSOR 3 LAB OIL SAMPLE DATE;
1869 CONTINUED READ DGA 3 DATE[3] / DATE[2]; DAY TENS / BACKSLASH
H2 SENSOR 3 LAB OIL SAMPLE DATE;
1870 CONTINUED READ DGA 3 DATE[5] / DATE[4]; BACKSLASH / DAY ONES
H2 SENSOR 3 LAB OIL SAMPLE DATE;
1871 CONTINUED READ DGA 3 DATE[7] / DATE[6]; YEAR ONES / YEAR TENS
1872 DGA H2 SENSOR 1 CONFIGURATION READ DGA 1 SENSOR CONFIGURATION
1873 DGA H2 SENSOR 2 CONFIGURATION READ DGA 2 SENSOR CONFIGURATION
1874 DGA H2 SENSOR 3 CONFIGURATION READ DGA 3 SENSOR CONFIGURATION

Analog Parameters
Registers 2100 thru 2315; see appropriate scaling (e.g. N, 10X, 100X, 1000X)
REG # VARIABLE R/W DESCRIPTION
SIMPLE CALCULATION WINDING RISE TEMPERATURE
2100 INPUT MODULE 1; WINDING RISE TEMPERATURE READ (100X)
SIMPLE CALCULATION WINDING RISE TEMPERATURE
2101 INPUT MODULE 2; WINDING RISE TEMPERATURE READ (100X)
SIMPLE CALCULATION WINDING RISE TEMPERATURE
2102 INPUT MODULE 3; WINDING RISE TEMPERATURE READ (100X)
SIMPLE CALCULATION WINDING RISE TEMPERATURE
2103 INPUT MODULE 4; WINDING RISE TEMPERATURE READ (100X)
SIMPLE CALCULATION WINDING RISE TEMPERATURE
2104 INPUT MODULE 5; WINDING RISE TEMPERATURE READ (100X)
SIMPLE CALCULATION WINDING RISE TEMPERATURE
2105 INPUT MODULE 6; WINDING RISE TEMPERATURE READ (100X)
SIMPLE CALCULATION WINDING RISE TEMPERATURE
2106 INPUT MODULE 7; WINDING RISE TEMPERATURE READ (100X)
SIMPLE CALCULATION WINDING RISE TEMPERATURE
2107 INPUT MODULE 8; WINDING RISE TEMPERATURE READ (100X)
2108 INPUT MODULE 1; CURRENT FACTOR READ SIMPLE CALCULATION CURRENT FACTOR (100X)
2109 INPUT MODULE 2; CURRENT FACTOR READ SIMPLE CALCULATION CURRENT FACTOR (100X)
2110 INPUT MODULE 3; CURRENT FACTOR READ SIMPLE CALCULATION CURRENT FACTOR (100X)
2111 INPUT MODULE 4; CURRENT FACTOR READ SIMPLE CALCULATION CURRENT FACTOR (100X)
2112 INPUT MODULE 5; CURRENT FACTOR READ SIMPLE CALCULATION CURRENT FACTOR (100X)
2113 INPUT MODULE 6; CURRENT FACTOR READ SIMPLE CALCULATION CURRENT FACTOR (100X)

68 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
2114 INPUT MODULE 7; CURRENT FACTOR READ SIMPLE CALCULATION CURRENT FACTOR (100X)
2115 INPUT MODULE 8; CURRENT FACTOR READ SIMPLE CALCULATION CURRENT FACTOR (100X)
2116 INPUT MODULE 1; WINDING TIME CONSTANT READ SIMPLE CALCULATION WINDING TIME CONSTANT (N)
2117 INPUT MODULE 2; WINDING TIME CONSTANT READ SIMPLE CALCULATION WINDING TIME CONSTANT (N)
2118 INPUT MODULE 3; WINDING TIME CONSTANT READ SIMPLE CALCULATION WINDING TIME CONSTANT (N)
2119 INPUT MODULE 4; WINDING TIME CONSTANT READ SIMPLE CALCULATION WINDING TIME CONSTANT (N)
2120 INPUT MODULE 5; WINDING TIME CONSTANT READ SIMPLE CALCULATION WINDING TIME CONSTANT (N)
2121 INPUT MODULE 6; WINDING TIME CONSTANT READ SIMPLE CALCULATION WINDING TIME CONSTANT (N)
2122 INPUT MODULE 7; WINDING TIME CONSTANT READ SIMPLE CALCULATION WINDING TIME CONSTANT (N)
2123 INPUT MODULE 8; WINDING TIME CONSTANT READ SIMPLE CALCULATION WINDING TIME CONSTANT (N)
INPUT MODULE 1; OIL RISE TEMPERATURE;
2124 STAGE 1 READ COOLING STAGE 1 OIL RISE TEMPERATURE (100X)
INPUT MODULE 1; OIL RISE TEMPERATURE;
2125 STAGE 2 READ COOLING STAGE 2 OIL RISE TEMPERATURE (100X)
INPUT MODULE 1; OIL RISE TEMPERATURE;
2126 STAGE 3 READ COOLING STAGE 3 OIL RISE TEMPERATURE (100X)
INPUT MODULE 1; OIL RISE TEMPERATURE;
2127 STAGE 4 READ COOLING STAGE 4 OIL RISE TEMPERATURE (100X)
INPUT MODULE 2; OIL RISE TEMPERATURE;
2128 STAGE 1 READ COOLING STAGE 1 OIL RISE TEMPERATURE (100X)
INPUT MODULE 2; OIL RISE TEMPERATURE;
2129 STAGE 2 READ COOLING STAGE 2 OIL RISE TEMPERATURE (100X)
INPUT MODULE 2; OIL RISE TEMPERATURE;
2130 STAGE 3 READ COOLING STAGE 3 OIL RISE TEMPERATURE (100X)
INPUT MODULE 2; OIL RISE TEMPERATURE;
2131 STAGE 4 READ COOLING STAGE 4 OIL RISE TEMPERATURE (100X)
INPUT MODULE 3; OIL RISE TEMPERATURE;
2132 STAGE 1 READ COOLING STAGE 1 OIL RISE TEMPERATURE (100X)
INPUT MODULE 3; OIL RISE TEMPERATURE;
2133 STAGE 2 READ COOLING STAGE 2 OIL RISE TEMPERATURE (100X)
INPUT MODULE 3; OIL RISE TEMPERATURE;
2134 STAGE 3 READ COOLING STAGE 3 OIL RISE TEMPERATURE (100X)
INPUT MODULE 3; OIL RISE TEMPERATURE;
2135 STAGE 4 READ COOLING STAGE 4 OIL RISE TEMPERATURE (100X)
INPUT MODULE 4; OIL RISE TEMPERATURE;
2136 STAGE 1 READ COOLING STAGE 1 OIL RISE TEMPERATURE (100X)
INPUT MODULE 4; OIL RISE TEMPERATURE;
2137 STAGE 2 READ COOLING STAGE 2 OIL RISE TEMPERATURE (100X)
INPUT MODULE 4; OIL RISE TEMPERATURE;
2138 STAGE 3 READ COOLING STAGE 3 OIL RISE TEMPERATURE (100X)
INPUT MODULE 4; OIL RISE TEMPERATURE;
2139 STAGE 4 READ COOLING STAGE 4 OIL RISE TEMPERATURE (100X)
INPUT MODULE 5; OIL RISE TEMPERATURE;
2140 STAGE 1 READ COOLING STAGE 1 OIL RISE TEMPERATURE (100X)
INPUT MODULE 5; OIL RISE TEMPERATURE;
2141 STAGE 2 READ COOLING STAGE 2 OIL RISE TEMPERATURE (100X)
INPUT MODULE 5; OIL RISE TEMPERATURE;
2142 STAGE 3 READ COOLING STAGE 3 OIL RISE TEMPERATURE (100X)
INPUT MODULE 5; OIL RISE TEMPERATURE;
2143 STAGE 4 READ COOLING STAGE 4 OIL RISE TEMPERATURE (100X)
INPUT MODULE 6; OIL RISE TEMPERATURE;
2144 STAGE 1 READ COOLING STAGE 1 OIL RISE TEMPERATURE (100X)
INPUT MODULE 6; OIL RISE TEMPERATURE;
2145 STAGE 2 READ COOLING STAGE 2 OIL RISE TEMPERATURE (100X)
INPUT MODULE 6; OIL RISE TEMPERATURE;
2146 STAGE 3 READ COOLING STAGE 3 OIL RISE TEMPERATURE (100X)
INPUT MODULE 6; OIL RISE TEMPERATURE;
2147 STAGE 4 READ COOLING STAGE 4 OIL RISE TEMPERATURE (100X)
INPUT MODULE 7; OIL RISE TEMPERATURE;
2148 STAGE 1 READ COOLING STAGE 1 OIL RISE TEMPERATURE (100X)
INPUT MODULE 7; OIL RISE TEMPERATURE;
2149 STAGE 2 READ COOLING STAGE 2 OIL RISE TEMPERATURE (100X)
2150 INPUT MODULE 7; OIL RISE TEMPERATURE; READ COOLING STAGE 3 OIL RISE TEMPERATURE (100X)

69 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
STAGE 3
INPUT MODULE 7; OIL RISE TEMPERATURE;
2151 STAGE 4 READ COOLING STAGE 4 OIL RISE TEMPERATURE (100X)
INPUT MODULE 8; OIL RISE TEMPERATURE;
2152 STAGE 1 READ COOLING STAGE 1 OIL RISE TEMPERATURE (100X)
INPUT MODULE 8; OIL RISE TEMPERATURE;
2153 STAGE 2 READ COOLING STAGE 2 OIL RISE TEMPERATURE (100X)
INPUT MODULE 8; OIL RISE TEMPERATURE;
2154 STAGE 3 READ COOLING STAGE 3 OIL RISE TEMPERATURE (100X)
INPUT MODULE 8; OIL RISE TEMPERATURE;
2155 STAGE 4 READ COOLING STAGE 4 OIL RISE TEMPERATURE (100X)
INPUT MODULE 1; OIL RISE TIME CONSTANT;
2156 STAGE 1 READ COOLING STAGE 1 OIL RISE TIME CONSTANT (N)
INPUT MODULE 1; OIL RISE TIME CONSTANT;
2157 STAGE 2 READ COOLING STAGE 2 OIL RISE TIME CONSTANT (N)
INPUT MODULE 1; OIL RISE TIME CONSTANT;
2158 STAGE 3 READ COOLING STAGE 3 OIL RISE TIME CONSTANT (N)
INPUT MODULE 1; OIL RISE TIME CONSTANT;
2159 STAGE 4 READ COOLING STAGE 4 OIL RISE TIME CONSTANT (N)
INPUT MODULE 2; OIL RISE TIME CONSTANT;
2160 STAGE 1 READ COOLING STAGE 1 OIL RISE TIME CONSTANT (N)
INPUT MODULE 2; OIL RISE TIME CONSTANT;
2161 STAGE 2 READ COOLING STAGE 2 OIL RISE TIME CONSTANT (N)
INPUT MODULE 2; OIL RISE TIME CONSTANT;
2162 STAGE 3 READ COOLING STAGE 3 OIL RISE TIME CONSTANT (N)
INPUT MODULE 2; OIL RISE TIME CONSTANT;
2163 STAGE 4 READ COOLING STAGE 4 OIL RISE TIME CONSTANT (N)
INPUT MODULE 3; OIL RISE TIME CONSTANT;
2164 STAGE 1 READ COOLING STAGE 1 OIL RISE TIME CONSTANT (N)
INPUT MODULE 3; OIL RISE TIME CONSTANT;
2165 STAGE 2 READ COOLING STAGE 2 OIL RISE TIME CONSTANT (N)
INPUT MODULE 3; OIL RISE TIME CONSTANT;
2166 STAGE 3 READ COOLING STAGE 3 OIL RISE TIME CONSTANT (N)
INPUT MODULE 3; OIL RISE TIME CONSTANT;
2167 STAGE 4 READ COOLING STAGE 4 OIL RISE TIME CONSTANT (N)
INPUT MODULE 4; OIL RISE TIME CONSTANT;
2168 STAGE 1 READ COOLING STAGE 1 OIL RISE TIME CONSTANT (N)
INPUT MODULE 4; OIL RISE TIME CONSTANT;
2169 STAGE 2 READ COOLING STAGE 2 OIL RISE TIME CONSTANT (N)
INPUT MODULE 4; OIL RISE TIME CONSTANT;
2170 STAGE 3 READ COOLING STAGE 3 OIL RISE TIME CONSTANT (N)
INPUT MODULE 4; OIL RISE TIME CONSTANT;
2171 STAGE 4 READ COOLING STAGE 4 OIL RISE TIME CONSTANT (N)
INPUT MODULE 5; OIL RISE TIME CONSTANT;
2172 STAGE 1 READ COOLING STAGE 1 OIL RISE TIME CONSTANT (N)
INPUT MODULE 5; OIL RISE TIME CONSTANT;
2173 STAGE 2 READ COOLING STAGE 2 OIL RISE TIME CONSTANT (N)
INPUT MODULE 5; OIL RISE TIME CONSTANT;
2174 STAGE 3 READ COOLING STAGE 3 OIL RISE TIME CONSTANT (N)
INPUT MODULE 5; OIL RISE TIME CONSTANT;
2175 STAGE 4 READ COOLING STAGE 4 OIL RISE TIME CONSTANT (N)
INPUT MODULE 6; OIL RISE TIME CONSTANT;
2176 STAGE 1 READ COOLING STAGE 1 OIL RISE TIME CONSTANT (N)
INPUT MODULE 6; OIL RISE TIME CONSTANT;
2177 STAGE 2 READ COOLING STAGE 2 OIL RISE TIME CONSTANT (N)
INPUT MODULE 6; OIL RISE TIME CONSTANT;
2178 STAGE 3 READ COOLING STAGE 3 OIL RISE TIME CONSTANT (N)
INPUT MODULE 6; OIL RISE TIME CONSTANT;
2179 STAGE 4 READ COOLING STAGE 4 OIL RISE TIME CONSTANT (N)
INPUT MODULE 7; OIL RISE TIME CONSTANT;
2180 STAGE 1 READ COOLING STAGE 1 OIL RISE TIME CONSTANT (N)
INPUT MODULE 7; OIL RISE TIME CONSTANT;
2181 STAGE 2 READ COOLING STAGE 2 OIL RISE TIME CONSTANT (N)
INPUT MODULE 7; OIL RISE TIME CONSTANT;
2182 STAGE 3 READ COOLING STAGE 3 OIL RISE TIME CONSTANT (N)
INPUT MODULE 7; OIL RISE TIME CONSTANT;
2183 STAGE 4 READ COOLING STAGE 4 OIL RISE TIME CONSTANT (N)

70 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
INPUT MODULE 8; OIL RISE TIME CONSTANT;
2184 STAGE 1 READ COOLING STAGE 1 OIL RISE TIME CONSTANT (N)
INPUT MODULE 8; OIL RISE TIME CONSTANT;
2185 STAGE 2 READ COOLING STAGE 2 OIL RISE TIME CONSTANT (N)
INPUT MODULE 8; OIL RISE TIME CONSTANT;
2186 STAGE 3 READ COOLING STAGE 3 OIL RISE TIME CONSTANT (N)
INPUT MODULE 8; OIL RISE TIME CONSTANT;
2187 STAGE 4 READ COOLING STAGE 4 OIL RISE TIME CONSTANT (N)
COOLING STAGE 1 ADVANCED CURRENT FACTOR
2188 INPUT MODULE 1; CURRENT FACTOR; STAGE 1 READ (100X)
COOLING STAGE 2 ADVANCED CURRENT FACTOR
2189 INPUT MODULE 1; CURRENT FACTOR; STAGE 2 READ (100X)
COOLING STAGE 3 ADVANCED CURRENT FACTOR
2190 INPUT MODULE 1; CURRENT FACTOR; STAGE 3 READ (100X)
COOLING STAGE 4 ADVANCED CURRENT FACTOR
2191 INPUT MODULE 1; CURRENT FACTOR; STAGE 4 READ (100X)
COOLING STAGE 1 ADVANCED CURRENT FACTOR
2192 INPUT MODULE 2; CURRENT FACTOR; STAGE 1 READ (100X)
COOLING STAGE 2 ADVANCED CURRENT FACTOR
2193 INPUT MODULE 2; CURRENT FACTOR; STAGE 2 READ (100X)
COOLING STAGE 3 ADVANCED CURRENT FACTOR
2194 INPUT MODULE 2; CURRENT FACTOR; STAGE 3 READ (100X)
COOLING STAGE 4 ADVANCED CURRENT FACTOR
2195 INPUT MODULE 2; CURRENT FACTOR; STAGE 4 READ (100X)
COOLING STAGE 1 ADVANCED CURRENT FACTOR
2196 INPUT MODULE 3; CURRENT FACTOR; STAGE 1 READ (100X)
COOLING STAGE 2 ADVANCED CURRENT FACTOR
2197 INPUT MODULE 3; CURRENT FACTOR; STAGE 2 READ (100X)
COOLING STAGE 3 ADVANCED CURRENT FACTOR
2198 INPUT MODULE 3; CURRENT FACTOR; STAGE 3 READ (100X)
COOLING STAGE 4 ADVANCED CURRENT FACTOR
2199 INPUT MODULE 3; CURRENT FACTOR; STAGE 4 READ (100X)
COOLING STAGE 1 ADVANCED CURRENT FACTOR
2200 INPUT MODULE 4; CURRENT FACTOR; STAGE 1 READ (100X)
COOLING STAGE 2 ADVANCED CURRENT FACTOR
2201 INPUT MODULE 4; CURRENT FACTOR; STAGE 2 READ (100X)
COOLING STAGE 3 ADVANCED CURRENT FACTOR
2202 INPUT MODULE 4; CURRENT FACTOR; STAGE 3 READ (100X)
COOLING STAGE 4 ADVANCED CURRENT FACTOR
2203 INPUT MODULE 4; CURRENT FACTOR; STAGE 4 READ (100X)
COOLING STAGE 1 ADVANCED CURRENT FACTOR
2204 INPUT MODULE 5; CURRENT FACTOR; STAGE 1 READ (100X)
COOLING STAGE 2 ADVANCED CURRENT FACTOR
2205 INPUT MODULE 5; CURRENT FACTOR; STAGE 2 READ (100X)
COOLING STAGE 3 ADVANCED CURRENT FACTOR
2206 INPUT MODULE 5; CURRENT FACTOR; STAGE 3 READ (100X)
COOLING STAGE 4 ADVANCED CURRENT FACTOR
2207 INPUT MODULE 5; CURRENT FACTOR; STAGE 4 READ (100X)
COOLING STAGE 1 ADVANCED CURRENT FACTOR
2208 INPUT MODULE 6; CURRENT FACTOR; STAGE 1 READ (100X)
COOLING STAGE 2 ADVANCED CURRENT FACTOR
2209 INPUT MODULE 6; CURRENT FACTOR; STAGE 2 READ (100X)
COOLING STAGE 3 ADVANCED CURRENT FACTOR
2210 INPUT MODULE 6; CURRENT FACTOR; STAGE 3 READ (100X)
COOLING STAGE 4 ADVANCED CURRENT FACTOR
2211 INPUT MODULE 6; CURRENT FACTOR; STAGE 4 READ (100X)
COOLING STAGE 1 ADVANCED CURRENT FACTOR
2212 INPUT MODULE 7; CURRENT FACTOR; STAGE 1 READ (100X)
COOLING STAGE 2 ADVANCED CURRENT FACTOR
2213 INPUT MODULE 7; CURRENT FACTOR; STAGE 2 READ (100X)
COOLING STAGE 3 ADVANCED CURRENT FACTOR
2214 INPUT MODULE 7; CURRENT FACTOR; STAGE 3 READ (100X)
COOLING STAGE 4 ADVANCED CURRENT FACTOR
2215 INPUT MODULE 7; CURRENT FACTOR; STAGE 4 READ (100X)
COOLING STAGE 1 ADVANCED CURRENT FACTOR
2216 INPUT MODULE 8; CURRENT FACTOR; STAGE 1 READ (100X)
2217 INPUT MODULE 8; CURRENT FACTOR; STAGE 2 READ COOLING STAGE 2 ADVANCED CURRENT FACTOR

71 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
(100X)
COOLING STAGE 3 ADVANCED CURRENT FACTOR
2218 INPUT MODULE 8; CURRENT FACTOR; STAGE 3 READ (100X)
COOLING STAGE 4 ADVANCED CURRENT FACTOR
2219 INPUT MODULE 8; CURRENT FACTOR; STAGE 4 READ (100X)
COOLING STAGE 1; ADVANCED WINDING RISE TEMP
2220 INPUT MODULE 1; WINDING RISE TEMP; STAGE 1 READ (100X)
COOLING STAGE 2; ADVANCED WINDING RISE TEMP
2221 INPUT MODULE 1; WINDING RISE TEMP; STAGE 2 READ (100X)
COOLING STAGE 3; ADVANCED WINDING RISE TEMP
2222 INPUT MODULE 1; WINDING RISE TEMP; STAGE 3 READ (100X)
COOLING STAGE 4; ADVANCED WINDING RISE TEMP
2223 INPUT MODULE 1; WINDING RISE TEMP; STAGE 4 READ (100X)
COOLING STAGE 1; ADVANCED WINDING RISE TEMP
2224 INPUT MODULE 2; WINDING RISE TEMP; STAGE 1 READ (100X)
COOLING STAGE 2; ADVANCED WINDING RISE TEMP
2225 INPUT MODULE 2; WINDING RISE TEMP; STAGE 2 READ (100X)
COOLING STAGE 3; ADVANCED WINDING RISE TEMP
2226 INPUT MODULE 2; WINDING RISE TEMP; STAGE 3 READ (100X)
COOLING STAGE 4; ADVANCED WINDING RISE TEMP
2227 INPUT MODULE 2; WINDING RISE TEMP; STAGE 4 READ (100X)
COOLING STAGE 1; ADVANCED WINDING RISE TEMP
2228 INPUT MODULE 3; WINDING RISE TEMP; STAGE 1 READ (100X)
COOLING STAGE 2; ADVANCED WINDING RISE TEMP
2229 INPUT MODULE 3; WINDING RISE TEMP; STAGE 2 READ (100X)
COOLING STAGE 3; ADVANCED WINDING RISE TEMP
2230 INPUT MODULE 3; WINDING RISE TEMP; STAGE 3 READ (100X)
COOLING STAGE 4; ADVANCED WINDING RISE TEMP
2231 INPUT MODULE 3; WINDING RISE TEMP; STAGE 4 READ (100X)
COOLING STAGE 1; ADVANCED WINDING RISE TEMP
2232 INPUT MODULE 4; WINDING RISE TEMP; STAGE 1 READ (100X)
COOLING STAGE 2; ADVANCED WINDING RISE TEMP
2233 INPUT MODULE 4; WINDING RISE TEMP; STAGE 2 READ (100X)
COOLING STAGE 3; ADVANCED WINDING RISE TEMP
2234 INPUT MODULE 4; WINDING RISE TEMP; STAGE 3 READ (100X)
COOLING STAGE 4; ADVANCED WINDING RISE TEMP
2235 INPUT MODULE 4; WINDING RISE TEMP; STAGE 4 READ (100X)
COOLING STAGE 1; ADVANCED WINDING RISE TEMP
2236 INPUT MODULE 5; WINDING RISE TEMP; STAGE 1 READ (100X)
COOLING STAGE 2; ADVANCED WINDING RISE TEMP
2237 INPUT MODULE 5; WINDING RISE TEMP; STAGE 2 READ (100X)
COOLING STAGE 3; ADVANCED WINDING RISE TEMP
2238 INPUT MODULE 5; WINDING RISE TEMP; STAGE 3 READ (100X)
COOLING STAGE 4; ADVANCED WINDING RISE TEMP
2239 INPUT MODULE 5; WINDING RISE TEMP; STAGE 4 READ (100X)
COOLING STAGE 1; ADVANCED WINDING RISE TEMP
2240 INPUT MODULE 6; WINDING RISE TEMP; STAGE 1 READ (100X)
COOLING STAGE 2; ADVANCED WINDING RISE TEMP
2241 INPUT MODULE 6; WINDING RISE TEMP; STAGE 2 READ (100X)
COOLING STAGE 3; ADVANCED WINDING RISE TEMP
2242 INPUT MODULE 6; WINDING RISE TEMP; STAGE 3 READ (100X)
COOLING STAGE 4; ADVANCED WINDING RISE TEMP
2243 INPUT MODULE 6; WINDING RISE TEMP; STAGE 4 READ (100X)
COOLING STAGE 1; ADVANCED WINDING RISE TEMP
2244 INPUT MODULE 7; WINDING RISE TEMP; STAGE 1 READ (100X)
COOLING STAGE 2; ADVANCED WINDING RISE TEMP
2245 INPUT MODULE 7; WINDING RISE TEMP; STAGE 2 READ (100X)
COOLING STAGE 3; ADVANCED WINDING RISE TEMP
2246 INPUT MODULE 7; WINDING RISE TEMP; STAGE 3 READ (100X)
COOLING STAGE 4; ADVANCED WINDING RISE TEMP
2247 INPUT MODULE 7; WINDING RISE TEMP; STAGE 4 READ (100X)
COOLING STAGE 1; ADVANCED WINDING RISE TEMP
2248 INPUT MODULE 8; WINDING RISE TEMP; STAGE 1 READ (100X)
COOLING STAGE 2; ADVANCED WINDING RISE TEMP
2249 INPUT MODULE 8; WINDING RISE TEMP; STAGE 2 READ (100X)
COOLING STAGE 3; ADVANCED WINDING RISE TEMP
2250 INPUT MODULE 8; WINDING RISE TEMP; STAGE 3 READ (100X)

72 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
COOLING STAGE 4; ADVANCED WINDING RISE TEMP
2251 INPUT MODULE 8; WINDING RISE TEMP; STAGE 4 READ (100X)
INPUT MODULE 1; WINDING CALC EXPONENT;
2252 STAGE 1 READ COOLING STAGE 1; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 1; WINDING CALC EXPONENT;
2253 STAGE 2 READ COOLING STAGE 2; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 1; WINDING CALC EXPONENT;
2254 STAGE 3 READ COOLING STAGE 3; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 1; WINDING CALC EXPONENT;
2255 STAGE 4 READ COOLING STAGE 4; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 2; WINDING CALC EXPONENT;
2256 STAGE 1 READ COOLING STAGE 1; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 2; WINDING CALC EXPONENT;
2257 STAGE 2 READ COOLING STAGE 2; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 2; WINDING CALC EXPONENT;
2258 STAGE 3 READ COOLING STAGE 3; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 2; WINDING CALC EXPONENT;
2259 STAGE 4 READ COOLING STAGE 4; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 3; WINDING CALC EXPONENT;
2260 STAGE 1 READ COOLING STAGE 1; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 3; WINDING CALC EXPONENT;
2261 STAGE 2 READ COOLING STAGE 2; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 3; WINDING CALC EXPONENT;
2262 STAGE 3 READ COOLING STAGE 3; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 3; WINDING CALC EXPONENT;
2263 STAGE 4 READ COOLING STAGE 4; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 4; WINDING CALC EXPONENT;
2264 STAGE 1 READ COOLING STAGE 1; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 4; WINDING CALC EXPONENT;
2265 STAGE 2 READ COOLING STAGE 2; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 4; WINDING CALC EXPONENT;
2266 STAGE 3 READ COOLING STAGE 3; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 4; WINDING CALC EXPONENT;
2267 STAGE 4 READ COOLING STAGE 4; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 5; WINDING CALC EXPONENT;
2268 STAGE 1 READ COOLING STAGE 1; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 5; WINDING CALC EXPONENT;
2269 STAGE 2 READ COOLING STAGE 2; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 5; WINDING CALC EXPONENT;
2270 STAGE 3 READ COOLING STAGE 3; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 5; WINDING CALC EXPONENT;
2271 STAGE 4 READ COOLING STAGE 4; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 6; WINDING CALC EXPONENT;
2272 STAGE 1 READ COOLING STAGE 1; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 6; WINDING CALC EXPONENT;
2273 STAGE 2 READ COOLING STAGE 2; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 6; WINDING CALC EXPONENT;
2274 STAGE 3 READ COOLING STAGE 3; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 6; WINDING CALC EXPONENT;
2275 STAGE 4 READ COOLING STAGE 4; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 7; WINDING CALC EXPONENT;
2276 STAGE 1 READ COOLING STAGE 1; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 7; WINDING CALC EXPONENT;
2277 STAGE 2 READ COOLING STAGE 2; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 7; WINDING CALC EXPONENT;
2278 STAGE 3 READ COOLING STAGE 3; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 7; WINDING CALC EXPONENT;
2279 STAGE 4 READ COOLING STAGE 4; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 8; WINDING CALC EXPONENT;
2280 STAGE 1 READ COOLING STAGE 1; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 8; WINDING CALC EXPONENT;
2281 STAGE 2 READ COOLING STAGE 2; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 8; WINDING CALC EXPONENT;
2282 STAGE 3 READ COOLING STAGE 3; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 8; WINDING CALC EXPONENT;
2283 STAGE 4 READ COOLING STAGE 4; ADVANCED CALC EXPONENT (10X)
2284 INPUT MODULE 1; WINDING TIME CONSTANT; READ COOLING STAGE 1; WINDING TIME CONSTANT (N)

73 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
STAGE 1
INPUT MODULE 1; WINDING TIME CONSTANT;
2285 STAGE 2 READ COOLING STAGE 2; WINDING TIME CONSTANT (N)
INPUT MODULE 1; WINDING TIME CONSTANT;
2286 STAGE 3 READ COOLING STAGE 3; WINDING TIME CONSTANT (N)
INPUT MODULE 1; WINDING TIME CONSTANT;
2287 STAGE 4 READ COOLING STAGE 4; WINDING TIME CONSTANT (N)
INPUT MODULE 2; WINDING TIME CONSTANT;
2288 STAGE 1 READ COOLING STAGE 1; WINDING TIME CONSTANT (N)
INPUT MODULE 2; WINDING TIME CONSTANT;
2289 STAGE 2 READ COOLING STAGE 2; WINDING TIME CONSTANT (N)
INPUT MODULE 2; WINDING TIME CONSTANT;
2290 STAGE 3 READ COOLING STAGE 3; WINDING TIME CONSTANT (N)
INPUT MODULE 2; WINDING TIME CONSTANT;
2291 STAGE 4 READ COOLING STAGE 4; WINDING TIME CONSTANT (N)
INPUT MODULE 3; WINDING TIME CONSTANT;
2292 STAGE 1 READ COOLING STAGE 1; WINDING TIME CONSTANT (N)
INPUT MODULE 3; WINDING TIME CONSTANT;
2293 STAGE 2 READ COOLING STAGE 2; WINDING TIME CONSTANT (N)
INPUT MODULE 3; WINDING TIME CONSTANT;
2294 STAGE 3 READ COOLING STAGE 3; WINDING TIME CONSTANT (N)
INPUT MODULE 3; WINDING TIME CONSTANT;
2295 STAGE 4 READ COOLING STAGE 4; WINDING TIME CONSTANT (N)
INPUT MODULE 4; WINDING TIME CONSTANT;
2296 STAGE 1 READ COOLING STAGE 1; WINDING TIME CONSTANT (N)
INPUT MODULE 4; WINDING TIME CONSTANT;
2297 STAGE 2 READ COOLING STAGE 2; WINDING TIME CONSTANT (N)
INPUT MODULE 4; WINDING TIME CONSTANT;
2298 STAGE 3 READ COOLING STAGE 3; WINDING TIME CONSTANT (N)
INPUT MODULE 4; WINDING TIME CONSTANT;
2299 STAGE 4 READ COOLING STAGE 4; WINDING TIME CONSTANT (N)
INPUT MODULE 5; WINDING TIME CONSTANT;
2300 STAGE 1 READ COOLING STAGE 1; WINDING TIME CONSTANT (N)
INPUT MODULE 5; WINDING TIME CONSTANT;
2301 STAGE 2 READ COOLING STAGE 2; WINDING TIME CONSTANT (N)
INPUT MODULE 5; WINDING TIME CONSTANT;
2302 STAGE 3 READ COOLING STAGE 3; WINDING TIME CONSTANT (N)
INPUT MODULE 5; WINDING TIME CONSTANT;
2303 STAGE 4 READ COOLING STAGE 4; WINDING TIME CONSTANT (N)
INPUT MODULE 6; WINDING TIME CONSTANT;
2304 STAGE 1 READ COOLING STAGE 1; WINDING TIME CONSTANT (N)
INPUT MODULE 6; WINDING TIME CONSTANT;
2305 STAGE 2 READ COOLING STAGE 2; WINDING TIME CONSTANT (N)
INPUT MODULE 6; WINDING TIME CONSTANT;
2306 STAGE 3 READ COOLING STAGE 3; WINDING TIME CONSTANT (N)
INPUT MODULE 6; WINDING TIME CONSTANT;
2307 STAGE 4 READ COOLING STAGE 4; WINDING TIME CONSTANT (N)
INPUT MODULE 7; WINDING TIME CONSTANT;
2308 STAGE 1 READ COOLING STAGE 1; WINDING TIME CONSTANT (N)
INPUT MODULE 7; WINDING TIME CONSTANT;
2309 STAGE 2 READ COOLING STAGE 2; WINDING TIME CONSTANT (N)
INPUT MODULE 7; WINDING TIME CONSTANT;
2310 STAGE 3 READ COOLING STAGE 3; WINDING TIME CONSTANT (N)
INPUT MODULE 7; WINDING TIME CONSTANT;
2311 STAGE 4 READ COOLING STAGE 4; WINDING TIME CONSTANT (N)
INPUT MODULE 8; WINDING TIME CONSTANT;
2312 STAGE 1 READ COOLING STAGE 1; WINDING TIME CONSTANT (N)
INPUT MODULE 8; WINDING TIME CONSTANT;
2313 STAGE 2 READ COOLING STAGE 2; WINDING TIME CONSTANT (N)
INPUT MODULE 8; WINDING TIME CONSTANT;
2314 STAGE 3 READ COOLING STAGE 3; WINDING TIME CONSTANT (N)
INPUT MODULE 8; WINDING TIME CONSTANT;
2315 STAGE 4 READ COOLING STAGE 4; WINDING TIME CONSTANT (N)

74 www.qualitrolcorp.com
Registers 2316 thru 2411 are packed numbers. For example: reading register 908 gives a decimal
number of 3122. Converting this to hex gives 0C32. Split the bytes in half and it would read 12
hours and 32 minutes.

REG # VARIABLE R/W DESCRIPTION


HOT SPOT MODULE 1; PROBE 1; MIN TIME &
2316 DATE READ MINIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 1; PROBE 1; MIN TIME &
2317 DATE READ MINIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 1; PROBE 1; MIN TIME &
2318 DATE READ MINIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 1; PROBE 1; MAX TIME &
2319 DATE READ MAXIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 1; PROBE 1; MAX TIME &
2320 DATE READ MAXIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 1; PROBE 1; MAX TIME &
2321 DATE READ MAXIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 1; PROBE 2; MIN TIME &
2322 DATE READ MINIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 1; PROBE 2; MIN TIME &
2323 DATE READ MINIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 1; PROBE 2; MIN TIME &
2324 DATE READ MINIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 1; PROBE 2; MAX TIME &
2325 DATE READ MAXIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 1; PROBE 2; MAX TIME &
2326 DATE READ MAXIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 1; PROBE 2; MAX TIME &
2327 DATE READ MAXIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 1; PROBE 3; MIN TIME &
2328 DATE READ MINIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 1; PROBE 3; MIN TIME &
2329 DATE READ MINIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 1; PROBE 3; MIN TIME &
2330 DATE READ MINIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 1; PROBE 3; MAX TIME &
2331 DATE READ MAXIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 1; PROBE 3; MAX TIME &
2332 DATE READ MAXIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 1; PROBE 3; MAX TIME &
2333 DATE READ MAXIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 1; PROBE 4; MIN TIME &
2334 DATE READ MINIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 1; PROBE 4; MIN TIME &
2335 DATE READ MINIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 1; PROBE 4; MIN TIME &
2336 DATE READ MINIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 1; PROBE 4; MAX TIME &
2337 DATE READ MAXIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 1; PROBE 4; MAX TIME &
2338 DATE READ MAXIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 1; PROBE 4; MAX TIME &
2339 DATE READ MAXIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 1; PROBE 5; MIN TIME &
2340 DATE READ MINIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 1; PROBE 5; MIN TIME &
2341 DATE READ MINIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 1; PROBE 5; MIN TIME &
2342 DATE READ MINIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 1; PROBE 5; MAX TIME &
2343 DATE READ MAXIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 1; PROBE 5; MAX TIME &
2344 DATE READ MAXIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 1; PROBE 5; MAX TIME &
2345 DATE READ MAXIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 1; PROBE 6; MIN TIME &
2346 DATE READ MINIMUM VALUE; HOURS BYTE / MINUTES BYTE

75 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
HOT SPOT MODULE 1; PROBE 6; MIN TIME &
2347 DATE READ MINIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 1; PROBE 6; MIN TIME &
2348 DATE READ MINIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 1; PROBE 6; MAX TIME &
2349 DATE READ MAXIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 1; PROBE 6; MAX TIME &
2350 DATE READ MAXIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 1; PROBE 6; MAX TIME &
2351 DATE READ MAXIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 1; PROBE 7; MIN TIME &
2352 DATE READ MINIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 1; PROBE 7; MIN TIME &
2353 DATE READ MINIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 1; PROBE 7; MIN TIME &
2354 DATE READ MINIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 1; PROBE 7; MAX TIME &
2355 DATE READ MAXIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 1; PROBE 7; MAX TIME &
2356 DATE READ MAXIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 1; PROBE 7; MAX TIME &
2357 DATE READ MAXIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 1; PROBE 8; MIN TIME &
2358 DATE READ MINIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 1; PROBE 8; MIN TIME &
2359 DATE READ MINIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 1; PROBE 8; MIN TIME &
2360 DATE READ MINIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 1; PROBE 8; MAX TIME &
2361 DATE READ MAXIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 1; PROBE 8; MAX TIME &
2362 DATE READ MAXIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 1; PROBE 8; MAX TIME &
2363 DATE READ MAXIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 2; PROBE 1; MIN TIME &
2364 DATE READ MINIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 2; PROBE 1; MIN TIME &
2365 DATE READ MINIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 2; PROBE 1; MIN TIME &
2366 DATE READ MINIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 2; PROBE 1; MAX TIME &
2367 DATE READ MAXIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 2; PROBE 1; MAX TIME &
2368 DATE READ MAXIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 2; PROBE 1; MAX TIME &
2369 DATE READ MAXIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 2; PROBE 2; MIN TIME &
2370 DATE READ MINIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 2; PROBE 2; MIN TIME &
2371 DATE READ MINIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 2; PROBE 2; MIN TIME &
2372 DATE READ MINIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 2; PROBE 2; MAX TIME &
2373 DATE READ MAXIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 2; PROBE 2; MAX TIME &
2374 DATE READ MAXIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 2; PROBE 2; MAX TIME &
2375 DATE READ MAXIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 2; PROBE 3; MIN TIME &
2376 DATE READ MINIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 2; PROBE 3; MIN TIME &
2377 DATE READ MINIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 2; PROBE 3; MIN TIME &
2378 DATE READ MINIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 2; PROBE 3; MAX TIME &
2379 DATE READ MAXIMUM VALUE; HOURS BYTE / MINUTES BYTE

76 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
HOT SPOT MODULE 2; PROBE 3; MAX TIME &
2380 DATE READ MAXIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 2; PROBE 3; MAX TIME &
2381 DATE READ MAXIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 2; PROBE 4; MIN TIME &
2382 DATE READ MINIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 2; PROBE 4; MIN TIME &
2383 DATE READ MINIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 2; PROBE 4; MIN TIME &
2384 DATE READ MINIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 2; PROBE 4; MAX TIME &
2385 DATE READ MAXIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 2; PROBE 4; MAX TIME &
2386 DATE READ MAXIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 2; PROBE 4; MAX TIME &
2387 DATE READ MAXIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 2; PROBE 5; MIN TIME &
2388 DATE READ MINIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 2; PROBE 5; MIN TIME &
2389 DATE READ MINIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 2; PROBE 5; MIN TIME &
2390 DATE READ MINIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 2; PROBE 5; MAX TIME &
2391 DATE READ MAXIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 2; PROBE 5; MAX TIME &
2392 DATE READ MAXIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 2; PROBE 5; MAX TIME &
2393 DATE READ MAXIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 2; PROBE 6; MIN TIME &
2394 DATE READ MINIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 2; PROBE 6; MIN TIME &
2395 DATE READ MINIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 2; PROBE 6; MIN TIME &
2396 DATE READ MINIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 2; PROBE 6; MAX TIME &
2397 DATE READ MAXIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 2; PROBE 6; MAX TIME &
2398 DATE READ MAXIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 2; PROBE 6; MAX TIME &
2399 DATE READ MAXIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 2; PROBE 7; MIN TIME &
2400 DATE READ MINIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 2; PROBE 7; MIN TIME &
2401 DATE READ MINIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 2; PROBE 7; MIN TIME &
2402 DATE READ MINIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 2; PROBE 7; MAX TIME &
2403 DATE READ MAXIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 2; PROBE 7; MAX TIME &
2404 DATE READ MAXIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 2; PROBE 7; MAX TIME &
2405 DATE READ MAXIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 2; PROBE 8; MIN TIME &
2406 DATE READ MINIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 2; PROBE 8; MIN TIME &
2407 DATE READ MINIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 2; PROBE 8; MIN TIME &
2408 DATE READ MINIMUM VALUE; DAYS BYTE / YEARS BYTE
HOT SPOT MODULE 2; PROBE 8; MAX TIME &
2409 DATE READ MAXIMUM VALUE; HOURS BYTE / MINUTES BYTE
HOT SPOT MODULE 2; PROBE 8; MAX TIME &
2410 DATE READ MAXIMUM VALUE; SECONDS BYTE / MONTHS BYTE
HOT SPOT MODULE 2; PROBE 8; MAX TIME &
2411 DATE READ MAXIMUM VALUE; DAYS BYTE / YEARS BYTE

77 www.qualitrolcorp.com
Binary Parameters
REG # VARIABLE R/W DESCRIPTION
2500 INPUT MODULE 9 ENABLED/DISABLED RD/WR 1 = ENABLED; 0 = DISABLED
2501 INPUT MODULE 10 ENABLED/DISABLED RD/WR 1 = ENABLED; 0 = DISABLED
2502 INPUT MODULE 11 ENABLED/DISABLED RD/WR 1 = ENABLED; 0 = DISABLED
2503 INPUT MODULE 12 ENABLED/DISABLED RD/WR 1 = ENABLED; 0 = DISABLED
2504 INPUT MODULE 13 ENABLED/DISABLED RD/WR 1 = ENABLED; 0 = DISABLED
2505 INPUT MODULE 14 ENABLED/DISABLED RD/WR 1 = ENABLED; 0 = DISABLED
2506 INPUT MODULE 15 ENABLED/DISABLED RD/WR 1 = ENABLED; 0 = DISABLED
2507 INPUT MODULE 16 ENABLED/DISABLED RD/WR 1 = ENABLED; 0 = DISABLED
2508 INPUT MODULE 9 READ ERROR READ 1 = READ ERROR; 0 = VALID READ
2509 INPUT MODULE 10 READ ERROR READ 1 = READ ERROR; 0 = VALID READ
2510 INPUT MODULE 11 READ ERROR READ 1 = READ ERROR; 0 = VALID READ
2511 INPUT MODULE 12 READ ERROR READ 1 = READ ERROR; 0 = VALID READ
2512 INPUT MODULE 13 READ ERROR READ 1 = READ ERROR; 0 = VALID READ
2513 INPUT MODULE 14 READ ERROR READ 1 = READ ERROR; 0 = VALID READ
2514 INPUT MODULE 15 READ ERROR READ 1 = READ ERROR; 0 = VALID READ
2515 INPUT MODULE 16 READ ERROR READ 1 = READ ERROR; 0 = VALID READ
2516 INPUT MODULE 9 SCALING ENABLED READ 1 = SCALING ENABLED; 0 = DISABLED
2517 INPUT MODULE 10 SCALING ENABLED READ 1 = SCALING ENABLED; 0 = DISABLED
2518 INPUT MODULE 11 SCALING ENABLED READ 1 = SCALING ENABLED; 0 = DISABLED
2519 INPUT MODULE 12 SCALING ENABLED READ 1 = SCALING ENABLED; 0 = DISABLED
2520 INPUT MODULE 13 SCALING ENABLED READ 1 = SCALING ENABLED; 0 = DISABLED
2521 INPUT MODULE 14 SCALING ENABLED READ 1 = SCALING ENABLED; 0 = DISABLED
2522 INPUT MODULE 15 SCALING ENABLED READ 1 = SCALING ENABLED; 0 = DISABLED
2523 INPUT MODULE 16 SCALING ENABLED READ 1 = SCALING ENABLED; 0 = DISABLED

Registers 2600 thru 2607 have the hex codes of the hardware types for the input modules. The types
are explained in the description side of the registers

REG # VARIABLE R/W DESCRIPTION


2600 INPUT MODULE 1 HARDWARE TYPE READ 00 = NONE; 01 = 4-20mA; 02 = 0-1mA; 03 = 0-10VDC;
2601 INPUT MODULE 2 HARDWARE TYPE READ 04 = 0-100mVDC; 05 = CT, CURRENT; 06 = CT, TEMP;
2602 INPUT MODULE 3 HARDWARE TYPE READ 07 = POTENTIOMETER; 08 = 100 OHM RTD; 09 = 10 OHM
2603 INPUT MODULE 4 HARDWARE TYPE READ RTD; 0A = DRY SWITCH DETECTION; 0B = POWERED
2604 INPUT MODULE 5 HARDWARE TYPE READ SWITCH DETECTION; 0C = 100 OHM RTD WINDING
2605 INPUT MODULE 6 HARDWARE TYPE READ TEMP; 0D = 10 OHM RTD WINDING TEMP; 0E = LTC
2606 INPUT MODULE 7 HARDWARE TYPE READ RESISTOR BRIDGE; 0F = 0-140VAC; 10 = 0-320VAC;
2607 INPUT MODULE 8 HARDWARE TYPE READ 11 = LTC 0-1mA; 12 = LTC 4-20mA; 13 = FIBER OPTIC TEMP

Analog Parameters
Values in registers 2608 thru 2967 have been scaled according to their function to offer the greatest
possible resolution. If the description of the value has a (N) then there is no scaling. A (10X) means
the value has been multiplied by 10 and needs to be divided by 10 to read the actual value (e.g. if the
value in the 509ITM is 123.4 then it will be transmitted 1234). A (100X) means the value was
multiplied by 100 and needs to be divided by 100 to read the actual value (e.g. if the value in the
509ITM is 12.34 then it will be transmitted as 1234).

78 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
ALL MODULES BUT CT, WINDING
TEMPERATURE IF THE MODULE IS A CT, WINDING TEMPERATURE
2608 INPUT MODULE 9 PRESENT VALUE READ OR INPUT MODULE 9 PRESENT WINDING TEMP (10X)
2609 INPUT MODULE 9 MINIMUM VALUE READ OR INPUT MODULE 9 MINIMUM WINDING TEMP (10X)
2610 INPUT MODULE 9 MAXIMUM VALUE READ OR INPUT MODULE 9 MAXIMUM WINDING TEMP (10X)
2611 0 READ OR INPUT MODULE 9 PRESENT CURRENT (10X)
2612 0 READ OR INPUT MODULE 9 MAXIMUM CURRENT (10X)
2613 INPUT MODULE 10 PRESENT VALUE READ OR INPUT MODULE 10 PRESENT WINDING TEMP (10X)
2614 INPUT MODULE 10 MINIMUM VALUE READ OR INPUT MODULE 10 MINIMUM WINDING TEMP (10X)
2615 INPUT MODULE 10 MAXIMUM VALUE READ OR INPUT MODULE 10 MAXIMUM WINDING TEMP (10X)
2616 0 READ OR INPUT MODULE 10 PRESENT CURRENT (10X)
2617 0 READ OR INPUT MODULE 10 MAXIMUM CURRENT (10X)
2618 INPUT MODULE 11 PRESENT VALUE READ OR INPUT MODULE 11 PRESENT WINDING TEMP (10X)
2619 INPUT MODULE 11 MINIMUM VALUE READ OR INPUT MODULE 11 MINIMUM WINDING TEMP (10X)
2620 INPUT MODULE 11 MAXIMUM VALUE READ OR INPUT MODULE 11 MAXIMUM WINDING TEMP (10X)
2621 0 READ OR INPUT MODULE 11 PRESENT CURRENT (10X)
2622 0 READ OR INPUT MODULE 11 MAXIMUM CURRENT (10X)
2623 INPUT MODULE 12 PRESENT VALUE READ OR INPUT MODULE 12 PRESENT WINDING TEMP (10X)
2624 INPUT MODULE 12 MINIMUM VALUE READ OR INPUT MODULE 12 MINIMUM WINDING TEMP (10X)
2625 INPUT MODULE 12 MAXIMUM VALUE READ OR INPUT MODULE 12 MAXIMUM WINDING TEMP (10X)
2626 0 READ OR INPUT MODULE 12 PRESENT CURRENT (10X)
2627 0 READ OR INPUT MODULE 12 MAXIMUM CURRENT (10X)
2628 INPUT MODULE 13 PRESENT VALUE READ OR INPUT MODULE 13 PRESENT WINDING TEMP (10X)
2629 INPUT MODULE 13 MINIMUM VALUE READ OR INPUT MODULE 13 MINIMUM WINDING TEMP (10X)
2630 INPUT MODULE 13 MAXIMUM VALUE READ OR INPUT MODULE 13 MAXIMUM WINDING TEMP (10X)
2631 0 READ OR INPUT MODULE 13 PRESENT CURRENT (10X)
2632 0 READ OR INPUT MODULE 13 MAXIMUM CURRENT (10X)
2633 INPUT MODULE 14 PRESENT VALUE READ OR INPUT MODULE 14 PRESENT WINDING TEMP (10X)
2634 INPUT MODULE 14 MINIMUM VALUE READ OR INPUT MODULE 14 MINIMUM WINDING TEMP (10X)
2635 INPUT MODULE 14 MAXIMUM VALUE READ OR INPUT MODULE 14 MAXIMUM WINDING TEMP (10X)
2636 0 READ OR INPUT MODULE 14 PRESENT CURRENT (10X)
2637 0 READ OR INPUT MODULE 14 MAXIMUM CURRENT (10X)
2638 INPUT MODULE 15 PRESENT VALUE READ OR INPUT MODULE 15 PRESENT WINDING TEMP (10X)
2639 INPUT MODULE 15 MINIMUM VALUE READ OR INPUT MODULE 15 MINIMUM WINDING TEMP (10X)
2640 INPUT MODULE 15 MAXIMUM VALUE READ OR INPUT MODULE 15 MAXIMUM WINDING TEMP (10X)
2641 0 READ OR INPUT MODULE 15 PRESENT CURRENT (10X)
2642 0 READ OR INPUT MODULE 15 MAXIMUM CURRENT (10X)
2643 INPUT MODULE 16 PRESENT VALUE READ OR INPUT MODULE 16 PRESENT WINDING TEMP (10X)
2644 INPUT MODULE 16 MINIMUM VALUE READ OR INPUT MODULE 16 MINIMUM WINDING TEMP (10X)
2645 INPUT MODULE 16 MAXIMUM VALUE READ OR INPUT MODULE 16 MAXIMUM WINDING TEMP (10X)
2646 0 READ OR INPUT MODULE 16 PRESENT CURRENT (10X)
2647 0 READ OR INPUT MODULE 16 MAXIMUM CURRENT (10X)

INPUT MODULE 9; CT CLAMP-ON RATING


2648 VALUE READ IF INPUT MODULE A CT TYPE; HOLDS SENSOR VALUE (N)
INPUT MODULE 10; CT CLAMP-ON RATING
2649 VALUE READ IF INPUT MODULE A CT TYPE; HOLDS SENSOR VALUE (N)
INPUT MODULE 11; CT CLAMP-ON RATING
2650 VALUE READ IF INPUT MODULE A CT TYPE; HOLDS SENSOR VALUE (N)
INPUT MODULE 12; CT CLAMP-ON RATING
2651 VALUE READ IF INPUT MODULE A CT TYPE; HOLDS SENSOR VALUE (N)

79 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
INPUT MODULE 13; CT CLAMP-ON RATING
2652 VALUE READ IF INPUT MODULE A CT TYPE; HOLDS SENSOR VALUE (N)
INPUT MODULE 14; CT CLAMP-ON RATING
2653 VALUE READ IF INPUT MODULE A CT TYPE; HOLDS SENSOR VALUE (N)
INPUT MODULE 15; CT CLAMP-ON RATING
2654 VALUE READ IF INPUT MODULE A CT TYPE; HOLDS SENSOR VALUE (N)
INPUT MODULE 16; CT CLAMP-ON RATING
2655 VALUE READ IF INPUT MODULE A CT TYPE; HOLDS SENSOR VALUE (N)
INPUT MODULE 9 OIL TEMPERATURE IF CT INPUT MODULE; POINTER TO OIL TEMP
2656 ADDER POINTER READ MEASUREMENT (N)
INPUT MODULE 10 OIL TEMPERATURE IF CT INPUT MODULE; POINTER TO OIL TEMP
2657 ADDER POINTER READ MEASUREMENT (N)
INPUT MODULE 11 OIL TEMPERATURE IF CT INPUT MODULE; POINTER TO OIL TEMP
2658 ADDER POINTER READ MEASUREMENT (N)
INPUT MODULE 12 OIL TEMPERATURE IF CT INPUT MODULE; POINTER TO OIL TEMP
2659 ADDER POINTER READ MEASUREMENT (N)
INPUT MODULE 13 OIL TEMPERATURE IF CT INPUT MODULE; POINTER TO OIL TEMP
2660 ADDER POINTER READ MEASUREMENT (N)
INPUT MODULE 14 OIL TEMPERATURE IF CT INPUT MODULE; POINTER TO OIL TEMP
2661 ADDER POINTER READ MEASUREMENT (N)
INPUT MODULE 15 OIL TEMPERATURE IF CT INPUT MODULE; POINTER TO OIL TEMP
2662 ADDER POINTER READ MEASUREMENT (N)
INPUT MODULE 16 OIL TEMPERATURE IF CT INPUT MODULE; POINTER TO OIL TEMP
2663 ADDER POINTER READ MEASUREMENT (N)
INPUT MODULE 9; COOLING STAGE 2
2664 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
INPUT MODULE 9; COOLING STAGE 3
2665 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
INPUT MODULE 9; COOLING STAGE 4
2666 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
INPUT MODULE 10; COOLING STAGE 2
2667 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
INPUT MODULE 10; COOLING STAGE 3
2668 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
INPUT MODULE 10; COOLING STAGE 4
2669 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
INPUT MODULE 11; COOLING STAGE 2
2670 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
INPUT MODULE 11; COOLING STAGE 3
2671 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
INPUT MODULE 11; COOLING STAGE 4
2672 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
INPUT MODULE 12; COOLING STAGE 2
2673 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
INPUT MODULE 12; COOLING STAGE 3
2674 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
INPUT MODULE 12; COOLING STAGE 4
2675 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
INPUT MODULE 13; COOLING STAGE 2
2676 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
INPUT MODULE 13; COOLING STAGE 3
2677 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
INPUT MODULE 13; COOLING STAGE 4
2678 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
INPUT MODULE 14; COOLING STAGE 2
2679 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
INPUT MODULE 14; COOLING STAGE 3
2680 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
INPUT MODULE 14; COOLING STAGE 4
2681 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
INPUT MODULE 15; COOLING STAGE 2
2682 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
INPUT MODULE 15; COOLING STAGE 3
2683 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
INPUT MODULE 15; COOLING STAGE 4
2684 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
2685 INPUT MODULE 16; COOLING STAGE 2 READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)

80 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
RELAY #
INPUT MODULE 16; COOLING STAGE 3
2686 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
INPUT MODULE 16; COOLING STAGE 4
2687 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)

2688 INPUT MODULE 9; CT RATIO PRIMARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
2690 INPUT MODULE 10; CT RATIO PRIMARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
2692 INPUT MODULE 11; CT RATIO PRIMARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
2694 INPUT MODULE 12; CT RATIO PRIMARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
2696 INPUT MODULE 13; CT RATIO PRIMARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
2698 INPUT MODULE 14; CT RATIO PRIMARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
2700 INPUT MODULE 15; CT RATIO PRIMARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
2702 INPUT MODULE 16; CT RATIO PRIMARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
INPUT MODULE 9; CT RATIO SECONDARY
2704 # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
INPUT MODULE 10; CT RATIO
2706 SECONDARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
INPUT MODULE 11; CT RATIO
2708 SECONDARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
INPUT MODULE 12; CT RATIO
2710 SECONDARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
INPUT MODULE 13; CT RATIO
2712 SECONDARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
INPUT MODULE 14; CT RATIO
2714 SECONDARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
INPUT MODULE 15; CT RATIO
2716 SECONDARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
INPUT MODULE 16; CT RATIO
2718 SECONDARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
INPUT MODULE 9; SCALING OFFSET
2720 VALUE READ SCALING OFFSET CALIBRATION VALUE (1000X)
INPUT MODULE 10; SCALING OFFSET
2722 VALUE READ SCALING OFFSET CALIBRATION VALUE (1000X)
INPUT MODULE 11; SCALING OFFSET
2724 VALUE READ SCALING OFFSET CALIBRATION VALUE (1000X)
INPUT MODULE 12; SCALING OFFSET
2726 VALUE READ SCALING OFFSET CALIBRATION VALUE (1000X)
INPUT MODULE 13; SCALING OFFSET
2728 VALUE READ SCALING OFFSET CALIBRATION VALUE (1000X)
INPUT MODULE 14; SCALING OFFSET
2730 VALUE READ SCALING OFFSET CALIBRATION VALUE (1000X)
INPUT MODULE 15; SCALING OFFSET
2732 VALUE READ SCALING OFFSET CALIBRATION VALUE (1000X)
INPUT MODULE 16; SCALING OFFSET
2734 VALUE READ SCALING OFFSET CALIBRATION VALUE (1000X)
2736 INPUT MODULE 9; SCALING GAIN VALUE READ SCALING GAIN CALIBRATION VALUE (1000X)
2738 INPUT MODULE 10; SCALING GAIN VALUE READ SCALING GAIN CALIBRATION VALUE (1000X)
2740 INPUT MODULE 11; SCALING GAIN VALUE READ SCALING GAIN CALIBRATION VALUE (1000X)
2742 INPUT MODULE 12; SCALING GAIN VALUE READ SCALING GAIN CALIBRATION VALUE (1000X)
2744 INPUT MODULE 13; SCALING GAIN VALUE READ SCALING GAIN CALIBRATION VALUE (1000X)
2746 INPUT MODULE 14; SCALING GAIN VALUE READ SCALING GAIN CALIBRATION VALUE (1000X)
2748 INPUT MODULE 15; SCALING GAIN VALUE READ SCALING GAIN CALIBRATION VALUE (1000X)
2750 INPUT MODULE 16; SCALING GAIN VALUE READ SCALING GAIN CALIBRATION VALUE (1000X)

INPUT MODULE 9; WINDING RISE SIMPLE CALCULATION WINDING RISE TEMPERATURE


2752 TEMPERATURE READ (100X)
INPUT MODULE 10; WINDING RISE SIMPLE CALCULATION WINDING RISE TEMPERATURE
2753 TEMPERATURE READ (100X)

81 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
INPUT MODULE 11; WINDING RISE SIMPLE CALCULATION WINDING RISE TEMPERATURE
2754 TEMPERATURE READ (100X)
INPUT MODULE 12; WINDING RISE SIMPLE CALCULATION WINDING RISE TEMPERATURE
2755 TEMPERATURE READ (100X)
INPUT MODULE 13; WINDING RISE SIMPLE CALCULATION WINDING RISE TEMPERATURE
2756 TEMPERATURE READ (100X)
INPUT MODULE 14; WINDING RISE SIMPLE CALCULATION WINDING RISE TEMPERATURE
2757 TEMPERATURE READ (100X)
INPUT MODULE 15; WINDING RISE SIMPLE CALCULATION WINDING RISE TEMPERATURE
2758 TEMPERATURE READ (100X)
INPUT MODULE 16; WINDING RISE SIMPLE CALCULATION WINDING RISE TEMPERATURE
2759 TEMPERATURE READ (100X)
2760 INPUT MODULE 9; CURRENT FACTOR READ SIMPLE CALCULATION CURRENT FACTOR (100X)
2761 INPUT MODULE 10; CURRENT FACTOR READ SIMPLE CALCULATION CURRENT FACTOR (100X)
2762 INPUT MODULE 11; CURRENT FACTOR READ SIMPLE CALCULATION CURRENT FACTOR (100X)
2763 INPUT MODULE 12; CURRENT FACTOR READ SIMPLE CALCULATION CURRENT FACTOR (100X)
2764 INPUT MODULE 13; CURRENT FACTOR READ SIMPLE CALCULATION CURRENT FACTOR (100X)
2765 INPUT MODULE 14; CURRENT FACTOR READ SIMPLE CALCULATION CURRENT FACTOR (100X)
2766 INPUT MODULE 15; CURRENT FACTOR READ SIMPLE CALCULATION CURRENT FACTOR (100X)
2767 INPUT MODULE 16; CURRENT FACTOR READ SIMPLE CALCULATION CURRENT FACTOR (100X)
INPUT MODULE 9; WINDING TIME
2768 CONSTANT READ SIMPLE CALCULATION WINDING TIME CONSTANT (N)
INPUT MODULE 10; WINDING TIME
2769 CONSTANT READ SIMPLE CALCULATION WINDING TIME CONSTANT (N)
INPUT MODULE 11; WINDING TIME
2770 CONSTANT READ SIMPLE CALCULATION WINDING TIME CONSTANT (N)
INPUT MODULE 12; WINDING TIME
2771 CONSTANT READ SIMPLE CALCULATION WINDING TIME CONSTANT (N)
INPUT MODULE 13; WINDING TIME
2772 CONSTANT READ SIMPLE CALCULATION WINDING TIME CONSTANT (N)
INPUT MODULE 14; WINDING TIME
2773 CONSTANT READ SIMPLE CALCULATION WINDING TIME CONSTANT (N)
INPUT MODULE 15; WINDING TIME
2774 CONSTANT READ SIMPLE CALCULATION WINDING TIME CONSTANT (N)
INPUT MODULE 16; WINDING TIME
2775 CONSTANT READ SIMPLE CALCULATION WINDING TIME CONSTANT (N)
INPUT MODULE 9; OIL RISE
2776 TEMPERATURE; STAGE 1 READ COOLING STAGE 1 OIL RISE TEMPERATURE (100X)
INPUT MODULE 9; OIL RISE
2777 TEMPERATURE; STAGE 2 READ COOLING STAGE 2 OIL RISE TEMPERATURE (100X)
INPUT MODULE 9; OIL RISE
2778 TEMPERATURE; STAGE 3 READ COOLING STAGE 3 OIL RISE TEMPERATURE (100X)
INPUT MODULE 9; OIL RISE
2779 TEMPERATURE; STAGE 4 READ COOLING STAGE 4 OIL RISE TEMPERATURE (100X)
INPUT MODULE 10; OIL RISE
2780 TEMPERATURE; STAGE 1 READ COOLING STAGE 1 OIL RISE TEMPERATURE (100X)
INPUT MODULE 10; OIL RISE
2781 TEMPERATURE; STAGE 2 READ COOLING STAGE 2 OIL RISE TEMPERATURE (100X)
INPUT MODULE 10; OIL RISE
2782 TEMPERATURE; STAGE 3 READ COOLING STAGE 3 OIL RISE TEMPERATURE (100X)
INPUT MODULE 10; OIL RISE
2783 TEMPERATURE; STAGE 4 READ COOLING STAGE 4 OIL RISE TEMPERATURE (100X)
INPUT MODULE 11; OIL RISE
2784 TEMPERATURE; STAGE 1 READ COOLING STAGE 1 OIL RISE TEMPERATURE (100X)
INPUT MODULE 11; OIL RISE
2785 TEMPERATURE; STAGE 2 READ COOLING STAGE 2 OIL RISE TEMPERATURE (100X)
INPUT MODULE 11; OIL RISE
2786 TEMPERATURE; STAGE 3 READ COOLING STAGE 3 OIL RISE TEMPERATURE (100X)
INPUT MODULE 11; OIL RISE
2787 TEMPERATURE; STAGE 4 READ COOLING STAGE 4 OIL RISE TEMPERATURE (100X)
INPUT MODULE 12; OIL RISE
2788 TEMPERATURE; STAGE 1 READ COOLING STAGE 1 OIL RISE TEMPERATURE (100X)
INPUT MODULE 12; OIL RISE
2789 TEMPERATURE; STAGE 2 READ COOLING STAGE 2 OIL RISE TEMPERATURE (100X)

82 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
INPUT MODULE 12; OIL RISE
2790 TEMPERATURE; STAGE 3 READ COOLING STAGE 3 OIL RISE TEMPERATURE (100X)
INPUT MODULE 12; OIL RISE
2791 TEMPERATURE; STAGE 4 READ COOLING STAGE 4 OIL RISE TEMPERATURE (100X)
INPUT MODULE 13; OIL RISE
2792 TEMPERATURE; STAGE 1 READ COOLING STAGE 1 OIL RISE TEMPERATURE (100X)
INPUT MODULE 13; OIL RISE
2793 TEMPERATURE; STAGE 2 READ COOLING STAGE 2 OIL RISE TEMPERATURE (100X)
INPUT MODULE 13; OIL RISE
2794 TEMPERATURE; STAGE 3 READ COOLING STAGE 3 OIL RISE TEMPERATURE (100X)
INPUT MODULE 13; OIL RISE
2795 TEMPERATURE; STAGE 4 READ COOLING STAGE 4 OIL RISE TEMPERATURE (100X)
INPUT MODULE 14; OIL RISE
2796 TEMPERATURE; STAGE 1 READ COOLING STAGE 1 OIL RISE TEMPERATURE (100X)
INPUT MODULE 14; OIL RISE
2797 TEMPERATURE; STAGE 2 READ COOLING STAGE 2 OIL RISE TEMPERATURE (100X)
INPUT MODULE 14; OIL RISE
2798 TEMPERATURE; STAGE 3 READ COOLING STAGE 3 OIL RISE TEMPERATURE (100X)
INPUT MODULE 14; OIL RISE
2799 TEMPERATURE; STAGE 4 READ COOLING STAGE 4 OIL RISE TEMPERATURE (100X)
INPUT MODULE 15; OIL RISE
2800 TEMPERATURE; STAGE 1 READ COOLING STAGE 1 OIL RISE TEMPERATURE (100X)
INPUT MODULE 15; OIL RISE
2801 TEMPERATURE; STAGE 2 READ COOLING STAGE 2 OIL RISE TEMPERATURE (100X)
INPUT MODULE 15; OIL RISE
2802 TEMPERATURE; STAGE 3 READ COOLING STAGE 3 OIL RISE TEMPERATURE (100X)
INPUT MODULE 15; OIL RISE
2803 TEMPERATURE; STAGE 4 READ COOLING STAGE 4 OIL RISE TEMPERATURE (100X)
INPUT MODULE 16; OIL RISE
2804 TEMPERATURE; STAGE 1 READ COOLING STAGE 1 OIL RISE TEMPERATURE (100X)
INPUT MODULE 16; OIL RISE
2805 TEMPERATURE; STAGE 2 READ COOLING STAGE 2 OIL RISE TEMPERATURE (100X)
INPUT MODULE 16; OIL RISE
2806 TEMPERATURE; STAGE 3 READ COOLING STAGE 3 OIL RISE TEMPERATURE (100X)
INPUT MODULE 16; OIL RISE
2807 TEMPERATURE; STAGE 4 READ COOLING STAGE 4 OIL RISE TEMPERATURE (100X)
INPUT MODULE 9; OIL RISE TIME
2808 CONSTANT; STAGE 1 READ COOLING STAGE 1 OIL RISE TIME CONSTANT (N)
INPUT MODULE 9; OIL RISE TIME
2809 CONSTANT; STAGE 2 READ COOLING STAGE 2 OIL RISE TIME CONSTANT (N)
INPUT MODULE 9; OIL RISE TIME
2810 CONSTANT; STAGE 3 READ COOLING STAGE 3 OIL RISE TIME CONSTANT (N)
INPUT MODULE 9; OIL RISE TIME
2811 CONSTANT; STAGE 4 READ COOLING STAGE 4 OIL RISE TIME CONSTANT (N)
INPUT MODULE 10; OIL RISE TIME
2812 CONSTANT; STAGE 1 READ COOLING STAGE 1 OIL RISE TIME CONSTANT (N)
INPUT MODULE 10; OIL RISE TIME
2813 CONSTANT; STAGE 2 READ COOLING STAGE 2 OIL RISE TIME CONSTANT (N)
INPUT MODULE 10; OIL RISE TIME
2814 CONSTANT; STAGE 3 READ COOLING STAGE 3 OIL RISE TIME CONSTANT (N)
INPUT MODULE 10; OIL RISE TIME
2815 CONSTANT; STAGE 4 READ COOLING STAGE 4 OIL RISE TIME CONSTANT (N)
INPUT MODULE 11; OIL RISE TIME
2816 CONSTANT; STAGE 1 READ COOLING STAGE 1 OIL RISE TIME CONSTANT (N)
INPUT MODULE 11; OIL RISE TIME
2817 CONSTANT; STAGE 2 READ COOLING STAGE 2 OIL RISE TIME CONSTANT (N)
INPUT MODULE 11; OIL RISE TIME
2818 CONSTANT; STAGE 3 READ COOLING STAGE 3 OIL RISE TIME CONSTANT (N)
INPUT MODULE 11; OIL RISE TIME
2819 CONSTANT; STAGE 4 READ COOLING STAGE 4 OIL RISE TIME CONSTANT (N)
INPUT MODULE 12; OIL RISE TIME
2820 CONSTANT; STAGE 1 READ COOLING STAGE 1 OIL RISE TIME CONSTANT (N)
INPUT MODULE 12; OIL RISE TIME
2821 CONSTANT; STAGE 2 READ COOLING STAGE 2 OIL RISE TIME CONSTANT (N)
INPUT MODULE 12; OIL RISE TIME
2822 CONSTANT; STAGE 3 READ COOLING STAGE 3 OIL RISE TIME CONSTANT (N)
2823 INPUT MODULE 12; OIL RISE TIME READ COOLING STAGE 4 OIL RISE TIME CONSTANT (N)

83 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
CONSTANT; STAGE 4
INPUT MODULE 13; OIL RISE TIME
2824 CONSTANT; STAGE 1 READ COOLING STAGE 1 OIL RISE TIME CONSTANT (N)
INPUT MODULE 13; OIL RISE TIME
2825 CONSTANT; STAGE 2 READ COOLING STAGE 2 OIL RISE TIME CONSTANT (N)
INPUT MODULE 13; OIL RISE TIME
2826 CONSTANT; STAGE 3 READ COOLING STAGE 3 OIL RISE TIME CONSTANT (N)
INPUT MODULE 13; OIL RISE TIME
2827 CONSTANT; STAGE 4 READ COOLING STAGE 4 OIL RISE TIME CONSTANT (N)
INPUT MODULE 14; OIL RISE TIME
2828 CONSTANT; STAGE 1 READ COOLING STAGE 1 OIL RISE TIME CONSTANT (N)
INPUT MODULE 14; OIL RISE TIME
2829 CONSTANT; STAGE 2 READ COOLING STAGE 2 OIL RISE TIME CONSTANT (N)
INPUT MODULE 14; OIL RISE TIME
2830 CONSTANT; STAGE 3 READ COOLING STAGE 3 OIL RISE TIME CONSTANT (N)
INPUT MODULE 14; OIL RISE TIME
2831 CONSTANT; STAGE 4 READ COOLING STAGE 4 OIL RISE TIME CONSTANT (N)
INPUT MODULE 15; OIL RISE TIME
2832 CONSTANT; STAGE 1 READ COOLING STAGE 1 OIL RISE TIME CONSTANT (N)
INPUT MODULE 15; OIL RISE TIME
2833 CONSTANT; STAGE 2 READ COOLING STAGE 2 OIL RISE TIME CONSTANT (N)
INPUT MODULE 15; OIL RISE TIME
2834 CONSTANT; STAGE 3 READ COOLING STAGE 3 OIL RISE TIME CONSTANT (N)
INPUT MODULE 15; OIL RISE TIME
2835 CONSTANT; STAGE 4 READ COOLING STAGE 4 OIL RISE TIME CONSTANT (N)
INPUT MODULE 16; OIL RISE TIME
2836 CONSTANT; STAGE 1 READ COOLING STAGE 1 OIL RISE TIME CONSTANT (N)
INPUT MODULE 16; OIL RISE TIME
2837 CONSTANT; STAGE 2 READ COOLING STAGE 2 OIL RISE TIME CONSTANT (N)
INPUT MODULE 16; OIL RISE TIME
2838 CONSTANT; STAGE 3 READ COOLING STAGE 3 OIL RISE TIME CONSTANT (N)
INPUT MODULE 16; OIL RISE TIME
2839 CONSTANT; STAGE 4 READ COOLING STAGE 4 OIL RISE TIME CONSTANT (N)
INPUT MODULE 9; CURRENT FACTOR;
2840 STAGE 1 READ COOLING STAGE 1 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 9; CURRENT FACTOR;
2841 STAGE 2 READ COOLING STAGE 2 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 9; CURRENT FACTOR;
2842 STAGE 3 READ COOLING STAGE 3 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 9; CURRENT FACTOR;
2843 STAGE 4 READ COOLING STAGE 4 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 10; CURRENT FACTOR;
2844 STAGE 1 READ COOLING STAGE 1 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 10; CURRENT FACTOR;
2845 STAGE 2 READ COOLING STAGE 2 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 10; CURRENT FACTOR;
2846 STAGE 3 READ COOLING STAGE 3 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 10; CURRENT FACTOR;
2847 STAGE 4 READ COOLING STAGE 4 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 11; CURRENT FACTOR;
2848 STAGE 1 READ COOLING STAGE 1 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 11; CURRENT FACTOR;
2849 STAGE 2 READ COOLING STAGE 2 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 11; CURRENT FACTOR;
2850 STAGE 3 READ COOLING STAGE 3 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 11; CURRENT FACTOR;
2851 STAGE 4 READ COOLING STAGE 4 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 12; CURRENT FACTOR;
2852 STAGE 1 READ COOLING STAGE 1 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 12; CURRENT FACTOR;
2853 STAGE 2 READ COOLING STAGE 2 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 12; CURRENT FACTOR;
2854 STAGE 3 READ COOLING STAGE 3 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 12; CURRENT FACTOR;
2855 STAGE 4 READ COOLING STAGE 4 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 13; CURRENT FACTOR;
2856 STAGE 1 READ COOLING STAGE 1 ADVANCED CURRENT FACTOR (100X)

84 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
INPUT MODULE 13; CURRENT FACTOR;
2857 STAGE 2 READ COOLING STAGE 2 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 13; CURRENT FACTOR;
2858 STAGE 3 READ COOLING STAGE 3 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 13; CURRENT FACTOR;
2859 STAGE 4 READ COOLING STAGE 4 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 14; CURRENT FACTOR;
2860 STAGE 1 READ COOLING STAGE 1 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 14; CURRENT FACTOR;
2861 STAGE 2 READ COOLING STAGE 2 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 14; CURRENT FACTOR;
2862 STAGE 3 READ COOLING STAGE 3 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 14; CURRENT FACTOR;
2863 STAGE 4 READ COOLING STAGE 4 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 15; CURRENT FACTOR;
2864 STAGE 1 READ COOLING STAGE 1 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 15; CURRENT FACTOR;
2865 STAGE 2 READ COOLING STAGE 2 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 15; CURRENT FACTOR;
2866 STAGE 3 READ COOLING STAGE 3 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 15; CURRENT FACTOR;
2867 STAGE 4 READ COOLING STAGE 4 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 16; CURRENT FACTOR;
2868 STAGE 1 READ COOLING STAGE 1 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 16; CURRENT FACTOR;
2869 STAGE 2 READ COOLING STAGE 2 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 16; CURRENT FACTOR;
2870 STAGE 3 READ COOLING STAGE 3 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 16; CURRENT FACTOR;
2871 STAGE 4 READ COOLING STAGE 4 ADVANCED CURRENT FACTOR (100X)
INPUT MODULE 9; WINDING RISE TEMP; COOLING STAGE 1; ADVANCED WINDING RISE TEMP
2872 STAGE 1 READ (100X)
INPUT MODULE 9; WINDING RISE TEMP; COOLING STAGE 2; ADVANCED WINDING RISE TEMP
2873 STAGE 2 READ (100X)
INPUT MODULE 9; WINDING RISE TEMP; COOLING STAGE 3; ADVANCED WINDING RISE TEMP
2874 STAGE 3 READ (100X)
INPUT MODULE 9; WINDING RISE TEMP; COOLING STAGE 4; ADVANCED WINDING RISE TEMP
2875 STAGE 4 READ (100X)
INPUT MODULE 10; WINDING RISE TEMP; COOLING STAGE 1; ADVANCED WINDING RISE TEMP
2876 STAGE 1 READ (100X)
INPUT MODULE 10; WINDING RISE TEMP; COOLING STAGE 2; ADVANCED WINDING RISE TEMP
2877 STAGE 2 READ (100X)
INPUT MODULE 10; WINDING RISE TEMP; COOLING STAGE 3; ADVANCED WINDING RISE TEMP
2878 STAGE 3 READ (100X)
INPUT MODULE 10; WINDING RISE TEMP; COOLING STAGE 4; ADVANCED WINDING RISE TEMP
2879 STAGE 4 READ (100X)
INPUT MODULE 11; WINDING RISE TEMP; COOLING STAGE 1; ADVANCED WINDING RISE TEMP
2880 STAGE 1 READ (100X)
INPUT MODULE 11; WINDING RISE TEMP; COOLING STAGE 2; ADVANCED WINDING RISE TEMP
2881 STAGE 2 READ (100X)
INPUT MODULE 11; WINDING RISE TEMP; COOLING STAGE 3; ADVANCED WINDING RISE TEMP
2882 STAGE 3 READ (100X)
INPUT MODULE 11; WINDING RISE TEMP; COOLING STAGE 4; ADVANCED WINDING RISE TEMP
2883 STAGE 4 READ (100X)
INPUT MODULE 12; WINDING RISE TEMP; COOLING STAGE 1; ADVANCED WINDING RISE TEMP
2884 STAGE 1 READ (100X)
INPUT MODULE 12; WINDING RISE TEMP; COOLING STAGE 2; ADVANCED WINDING RISE TEMP
2885 STAGE 2 READ (100X)
INPUT MODULE 12; WINDING RISE TEMP; COOLING STAGE 3; ADVANCED WINDING RISE TEMP
2886 STAGE 3 READ (100X)
INPUT MODULE 12; WINDING RISE TEMP; COOLING STAGE 4; ADVANCED WINDING RISE TEMP
2887 STAGE 4 READ (100X)
INPUT MODULE 13; WINDING RISE TEMP; COOLING STAGE 1; ADVANCED WINDING RISE TEMP
2888 STAGE 1 READ (100X)
INPUT MODULE 13; WINDING RISE TEMP; COOLING STAGE 2; ADVANCED WINDING RISE TEMP
2889 STAGE 2 READ (100X)
2890 INPUT MODULE 13; WINDING RISE TEMP; READ COOLING STAGE 3; ADVANCED WINDING RISE TEMP

85 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
STAGE 3 (100X)
INPUT MODULE 13; WINDING RISE TEMP; COOLING STAGE 4; ADVANCED WINDING RISE TEMP
2891 STAGE 4 READ (100X)
INPUT MODULE 14; WINDING RISE TEMP; COOLING STAGE 1; ADVANCED WINDING RISE TEMP
2892 STAGE 1 READ (100X)
INPUT MODULE 14; WINDING RISE TEMP; COOLING STAGE 2; ADVANCED WINDING RISE TEMP
2893 STAGE 2 READ (100X)
INPUT MODULE 14; WINDING RISE TEMP; COOLING STAGE 3; ADVANCED WINDING RISE TEMP
2894 STAGE 3 READ (100X)
INPUT MODULE 14; WINDING RISE TEMP; COOLING STAGE 4; ADVANCED WINDING RISE TEMP
2895 STAGE 4 READ (100X)
INPUT MODULE 15; WINDING RISE TEMP; COOLING STAGE 1; ADVANCED WINDING RISE TEMP
2896 STAGE 1 READ (100X)
INPUT MODULE 15; WINDING RISE TEMP; COOLING STAGE 2; ADVANCED WINDING RISE TEMP
2897 STAGE 2 READ (100X)
INPUT MODULE 15; WINDING RISE TEMP; COOLING STAGE 3; ADVANCED WINDING RISE TEMP
2898 STAGE 3 READ (100X)
INPUT MODULE 15; WINDING RISE TEMP; COOLING STAGE 4; ADVANCED WINDING RISE TEMP
2899 STAGE 4 READ (100X)
INPUT MODULE 16; WINDING RISE TEMP; COOLING STAGE 1; ADVANCED WINDING RISE TEMP
2900 STAGE 1 READ (100X)
INPUT MODULE 16; WINDING RISE TEMP; COOLING STAGE 2; ADVANCED WINDING RISE TEMP
2901 STAGE 2 READ (100X)
INPUT MODULE 16; WINDING RISE TEMP; COOLING STAGE 3; ADVANCED WINDING RISE TEMP
2902 STAGE 3 READ (100X)
INPUT MODULE 16; WINDING RISE TEMP; COOLING STAGE 4; ADVANCED WINDING RISE TEMP
2903 STAGE 4 READ (100X)
INPUT MODULE 9; WINDING CALC
2904 EXPONENT; STAGE 1 READ COOLING STAGE 1; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 9; WINDING CALC
2905 EXPONENT; STAGE 2 READ COOLING STAGE 2; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 9; WINDING CALC
2906 EXPONENT; STAGE 3 READ COOLING STAGE 3; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 9; WINDING CALC
2907 EXPONENT; STAGE 4 READ COOLING STAGE 4; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 10; WINDING CALC
2908 EXPONENT; STAGE 1 READ COOLING STAGE 1; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 10; WINDING CALC
2909 EXPONENT; STAGE 2 READ COOLING STAGE 2; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 10; WINDING CALC
2910 EXPONENT; STAGE 3 READ COOLING STAGE 3; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 10; WINDING CALC
2911 EXPONENT; STAGE 4 READ COOLING STAGE 4; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 11; WINDING CALC
2912 EXPONENT; STAGE 1 READ COOLING STAGE 1; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 11; WINDING CALC
2913 EXPONENT; STAGE 2 READ COOLING STAGE 2; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 11; WINDING CALC
2914 EXPONENT; STAGE 3 READ COOLING STAGE 3; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 11; WINDING CALC
2915 EXPONENT; STAGE 4 READ COOLING STAGE 4; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 12; WINDING CALC
2916 EXPONENT; STAGE 1 READ COOLING STAGE 1; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 12; WINDING CALC
2917 EXPONENT; STAGE 2 READ COOLING STAGE 2; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 12; WINDING CALC
2918 EXPONENT; STAGE 3 READ COOLING STAGE 3; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 12; WINDING CALC
2919 EXPONENT; STAGE 4 READ COOLING STAGE 4; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 13; WINDING CALC
2920 EXPONENT; STAGE 1 READ COOLING STAGE 1; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 13; WINDING CALC
2921 EXPONENT; STAGE 2 READ COOLING STAGE 2; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 13; WINDING CALC
2922 EXPONENT; STAGE 3 READ COOLING STAGE 3; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 13; WINDING CALC
2923 EXPONENT; STAGE 4 READ COOLING STAGE 4; ADVANCED CALC EXPONENT (10X)

86 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
INPUT MODULE 14; WINDING CALC
2924 EXPONENT; STAGE 1 READ COOLING STAGE 1; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 14; WINDING CALC
2925 EXPONENT; STAGE 2 READ COOLING STAGE 2; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 14; WINDING CALC
2926 EXPONENT; STAGE 3 READ COOLING STAGE 3; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 14; WINDING CALC
2927 EXPONENT; STAGE 4 READ COOLING STAGE 4; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 15; WINDING CALC
2928 EXPONENT; STAGE 1 READ COOLING STAGE 1; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 15; WINDING CALC
2929 EXPONENT; STAGE 2 READ COOLING STAGE 2; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 15; WINDING CALC
2930 EXPONENT; STAGE 3 READ COOLING STAGE 3; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 15; WINDING CALC
2931 EXPONENT; STAGE 4 READ COOLING STAGE 4; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 16; WINDING CALC
2932 EXPONENT; STAGE 1 READ COOLING STAGE 1; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 16; WINDING CALC
2933 EXPONENT; STAGE 2 READ COOLING STAGE 2; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 16; WINDING CALC
2934 EXPONENT; STAGE 3 READ COOLING STAGE 3; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 16; WINDING CALC
2935 EXPONENT; STAGE 4 READ COOLING STAGE 4; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 9; WINDING TIME
2936 CONSTANT; STAGE 1 READ COOLING STAGE 1; WINDING TIME CONSTANT (N)
INPUT MODULE 9; WINDING TIME
2937 CONSTANT; STAGE 2 READ COOLING STAGE 2; WINDING TIME CONSTANT (N)
INPUT MODULE 9; WINDING TIME
2938 CONSTANT; STAGE 3 READ COOLING STAGE 3; WINDING TIME CONSTANT (N)
INPUT MODULE 9; WINDING TIME
2939 CONSTANT; STAGE 4 READ COOLING STAGE 4; WINDING TIME CONSTANT (N)
INPUT MODULE 10; WINDING TIME
2940 CONSTANT; STAGE 1 READ COOLING STAGE 1; WINDING TIME CONSTANT (N)
INPUT MODULE 10; WINDING TIME
2941 CONSTANT; STAGE 2 READ COOLING STAGE 2; WINDING TIME CONSTANT (N)
INPUT MODULE 10; WINDING TIME
2942 CONSTANT; STAGE 3 READ COOLING STAGE 3; WINDING TIME CONSTANT (N)
INPUT MODULE 10; WINDING TIME
2943 CONSTANT; STAGE 4 READ COOLING STAGE 4; WINDING TIME CONSTANT (N)
INPUT MODULE 11; WINDING TIME
2944 CONSTANT; STAGE 1 READ COOLING STAGE 1; WINDING TIME CONSTANT (N)
INPUT MODULE 11; WINDING TIME
2945 CONSTANT; STAGE 2 READ COOLING STAGE 2; WINDING TIME CONSTANT (N)
INPUT MODULE 11; WINDING TIME
2946 CONSTANT; STAGE 3 READ COOLING STAGE 3; WINDING TIME CONSTANT (N)
INPUT MODULE 11; WINDING TIME
2947 CONSTANT; STAGE 4 READ COOLING STAGE 4; WINDING TIME CONSTANT (N)
INPUT MODULE 12; WINDING TIME
2948 CONSTANT; STAGE 1 READ COOLING STAGE 1; WINDING TIME CONSTANT (N)
INPUT MODULE 12; WINDING TIME
2949 CONSTANT; STAGE 2 READ COOLING STAGE 2; WINDING TIME CONSTANT (N)
INPUT MODULE 12; WINDING TIME
2950 CONSTANT; STAGE 3 READ COOLING STAGE 3; WINDING TIME CONSTANT (N)
INPUT MODULE 12; WINDING TIME
2951 CONSTANT; STAGE 4 READ COOLING STAGE 4; WINDING TIME CONSTANT (N)
INPUT MODULE 13; WINDING TIME
2952 CONSTANT; STAGE 1 READ COOLING STAGE 1; WINDING TIME CONSTANT (N)
INPUT MODULE 13; WINDING TIME
2953 CONSTANT; STAGE 2 READ COOLING STAGE 2; WINDING TIME CONSTANT (N)
INPUT MODULE 13; WINDING TIME
2954 CONSTANT; STAGE 3 READ COOLING STAGE 3; WINDING TIME CONSTANT (N)
INPUT MODULE 13; WINDING TIME
2955 CONSTANT; STAGE 4 READ COOLING STAGE 4; WINDING TIME CONSTANT (N)
INPUT MODULE 14; WINDING TIME
2956 CONSTANT; STAGE 1 READ COOLING STAGE 1; WINDING TIME CONSTANT (N)
2957 INPUT MODULE 14; WINDING TIME READ COOLING STAGE 2; WINDING TIME CONSTANT (N)

87 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
CONSTANT; STAGE 2
INPUT MODULE 14; WINDING TIME
2958 CONSTANT; STAGE 3 READ COOLING STAGE 3; WINDING TIME CONSTANT (N)
INPUT MODULE 14; WINDING TIME
2959 CONSTANT; STAGE 4 READ COOLING STAGE 4; WINDING TIME CONSTANT (N)
INPUT MODULE 15; WINDING TIME
2960 CONSTANT; STAGE 1 READ COOLING STAGE 1; WINDING TIME CONSTANT (N)
INPUT MODULE 15; WINDING TIME
2961 CONSTANT; STAGE 2 READ COOLING STAGE 2; WINDING TIME CONSTANT (N)
INPUT MODULE 15; WINDING TIME
2962 CONSTANT; STAGE 3 READ COOLING STAGE 3; WINDING TIME CONSTANT (N)
INPUT MODULE 15; WINDING TIME
2963 CONSTANT; STAGE 4 READ COOLING STAGE 4; WINDING TIME CONSTANT (N)
INPUT MODULE 16; WINDING TIME
2964 CONSTANT; STAGE 1 READ COOLING STAGE 1; WINDING TIME CONSTANT (N)
INPUT MODULE 16; WINDING TIME
2965 CONSTANT; STAGE 2 READ COOLING STAGE 2; WINDING TIME CONSTANT (N)
INPUT MODULE 16; WINDING TIME
2966 CONSTANT; STAGE 3 READ COOLING STAGE 3; WINDING TIME CONSTANT (N)
INPUT MODULE 16; WINDING TIME
2967 CONSTANT; STAGE 4 READ COOLING STAGE 4; WINDING TIME CONSTANT (N)

Registers 3000 thru 3071 are packed numbers. For example: reading register 908 gives a decimal
number of 3122. Converting this to hex gives 0C32. Split the bytes in half and it would read 12
hours and 32 minutes.
REG # VARIABLE R/W DESCRIPTION
ALL MODULES BUT CT, WINDING TEMPERATURE IF THE MODULE IS A CT, WINDING TEMPERATURE
3000 INPUT MODULE 9 MAXIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
3001 INPUT MODULE 9 MAXIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
3002 INPUT MODULE 9 MAXIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
3003 INPUT MODULE 10 MAXIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
3004 INPUT MODULE 10 MAXIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
3005 INPUT MODULE 10 MAXIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
3006 INPUT MODULE 11 MAXIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
3007 INPUT MODULE 11 MAXIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
3008 INPUT MODULE 11 MAXIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
3009 INPUT MODULE 12 MAXIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
3010 INPUT MODULE 12 MAXIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
3011 INPUT MODULE 12 MAXIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
3012 INPUT MODULE 13 MAXIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
3013 INPUT MODULE 13 MAXIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
3014 INPUT MODULE 13 MAXIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
3015 INPUT MODULE 14 MAXIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
3016 INPUT MODULE 14 MAXIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
3017 INPUT MODULE 14 MAXIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
3018 INPUT MODULE 15 MAXIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
3019 INPUT MODULE 15 MAXIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
3020 INPUT MODULE 15 MAXIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
3021 INPUT MODULE 16 MAXIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
3022 INPUT MODULE 16 MAXIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
3023 INPUT MODULE 16 MAXIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
3024 INPUT MODULE 9 MINIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
3025 INPUT MODULE 9 MINIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
3026 INPUT MODULE 9 MINIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE

88 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
3027 INPUT MODULE 10 MINIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
3028 INPUT MODULE 10 MINIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
3029 INPUT MODULE 10 MINIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
3030 INPUT MODULE 11 MINIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
3031 INPUT MODULE 11 MINIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
3032 INPUT MODULE 11 MINIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
3033 INPUT MODULE 12 MINIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
3034 INPUT MODULE 12 MINIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
3035 INPUT MODULE 12 MINIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
3036 INPUT MODULE 13 MINIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
3037 INPUT MODULE 13 MINIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
3038 INPUT MODULE 13 MINIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
3039 INPUT MODULE 14 MINIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
3040 INPUT MODULE 14 MINIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
3041 INPUT MODULE 14 MINIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
3042 INPUT MODULE 15 MINIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
3043 INPUT MODULE 15 MINIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
3044 INPUT MODULE 15 MINIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
3045 INPUT MODULE 16 MINIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
3046 INPUT MODULE 16 MINIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
3047 INPUT MODULE 16 MINIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
INPUT MODULE 9 MAXIMUM CURRENT TIME &
3048 DATE READ HOURS BYTE / MINUTES BYTE
INPUT MODULE 9 MAXIMUM CURRENT TIME &
3049 DATE READ SECONDS BYTE / MONTHS BYTE
INPUT MODULE 9 MAXIMUM CURRENT TIME &
3050 DATE READ DAYS BYTE / YEARS BYTE
INPUT MODULE 10 MAXIMUM CURRENT TIME &
3051 DATE READ HOURS BYTE / MINUTES BYTE
INPUT MODULE 10 MAXIMUM CURRENT TIME &
3052 DATE READ SECONDS BYTE / MONTHS BYTE
INPUT MODULE 10 MAXIMUM CURRENT TIME &
3053 DATE READ DAYS BYTE / YEARS BYTE
INPUT MODULE 11 MAXIMUM CURRENT TIME &
3054 DATE READ HOURS BYTE / MINUTES BYTE
INPUT MODULE 11 MAXIMUM CURRENT TIME &
3055 DATE READ SECONDS BYTE / MONTHS BYTE
INPUT MODULE 11 MAXIMUM CURRENT TIME &
3056 DATE READ DAYS BYTE / YEARS BYTE
INPUT MODULE 12 MAXIMUM CURRENT TIME &
3057 DATE READ HOURS BYTE / MINUTES BYTE
INPUT MODULE 12 MAXIMUM CURRENT TIME &
3058 DATE READ SECONDS BYTE / MONTHS BYTE
INPUT MODULE 12 MAXIMUM CURRENT TIME &
3059 DATE READ DAYS BYTE / YEARS BYTE
INPUT MODULE 13 MAXIMUM CURRENT TIME &
3060 DATE READ HOURS BYTE / MINUTES BYTE
INPUT MODULE 13 MAXIMUM CURRENT TIME &
3061 DATE READ SECONDS BYTE / MONTHS BYTE
INPUT MODULE 13 MAXIMUM CURRENT TIME &
3062 DATE READ DAYS BYTE / YEARS BYTE
INPUT MODULE 14 MAXIMUM CURRENT TIME &
3063 DATE READ HOURS BYTE / MINUTES BYTE
INPUT MODULE 14 MAXIMUM CURRENT TIME &
3064 DATE READ SECONDS BYTE / MONTHS BYTE
INPUT MODULE 14 MAXIMUM CURRENT TIME &
3065 DATE READ DAYS BYTE / YEARS BYTE
INPUT MODULE 15 MAXIMUM CURRENT TIME &
3066 DATE READ HOURS BYTE / MINUTES BYTE

89 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
INPUT MODULE 15 MAXIMUM CURRENT TIME &
3067 DATE READ SECONDS BYTE / MONTHS BYTE
INPUT MODULE 15 MAXIMUM CURRENT TIME &
3068 DATE READ DAYS BYTE / YEARS BYTE
INPUT MODULE 16 MAXIMUM CURRENT TIME &
3069 DATE READ HOURS BYTE / MINUTES BYTE
INPUT MODULE 16 MAXIMUM CURRENT TIME &
3070 DATE READ SECONDS BYTE / MONTHS BYTE
INPUT MODULE 16 MAXIMUM CURRENT TIME &
3071 DATE READ DAYS BYTE / YEARS BYTE

String Parameters
Registers 3072 thru 3119.
REG # VARIABLE R/W DESCRIPTION
ALL MODULES BUT CT, WINDING
TEMPERATURE IF THE MODULE IS A CT, WINDING TEMPERATURE
3072 INPUT MODULE 9 NAME; 7 ASCII CHARACTERS READ INPUT MODULE 1 NAME[1] / INPUT MODULE 1 NAME[0]
3073 INPUT MODULE 9 NAME; CONTINUED READ INPUT MODULE 1 NAME[3] / INPUT MODULE 1 NAME[2]
3074 INPUT MODULE 9 NAME; CONTINUED READ INPUT MODULE 1 NAME[5] / INPUT MODULE 1 NAME[4]
3075 INPUT MODULE 9 NAME; CONTINUED READ INPUT MODULE 1 ZERO / INPUT MODULE 1 NAME[6]
3076 INPUT MODULE 10 NAME; 7 ASCII CHARACTERS READ INPUT MODULE 2 NAME[1] / INPUT MODULE 2 NAME[0]
3077 INPUT MODULE 10 NAME; CONTINUED READ INPUT MODULE 2 NAME[3] / INPUT MODULE 2 NAME[2]
3078 INPUT MODULE 10 NAME; CONTINUED READ INPUT MODULE 2 NAME[5] / INPUT MODULE 2 NAME[4]
3079 INPUT MODULE 10 NAME; CONTINUED READ INPUT MODULE 2 ZERO / INPUT MODULE 2 NAME[6]
3080 INPUT MODULE 11 NAME; 7 ASCII CHARACTERS READ INPUT MODULE 3 NAME[1] / INPUT MODULE 3 NAME[0]
3081 INPUT MODULE 11 NAME; CONTINUED READ INPUT MODULE 3 NAME[3] / INPUT MODULE 3 NAME[2]
3082 INPUT MODULE 11 NAME; CONTINUED READ INPUT MODULE 3 NAME[5] / INPUT MODULE 3 NAME[4]
3083 INPUT MODULE 11 NAME; CONTINUED READ INPUT MODULE 3 ZERO / INPUT MODULE 3 NAME[6]
3084 INPUT MODULE 12 NAME; 7 ASCII CHARACTERS READ INPUT MODULE 4 NAME[1] / INPUT MODULE 4 NAME[0]
3085 INPUT MODULE 12 NAME; CONTINUED READ INPUT MODULE 4 NAME[3] / INPUT MODULE 4 NAME[2]
3086 INPUT MODULE 12 NAME; CONTINUED READ INPUT MODULE 4 NAME[5] / INPUT MODULE 4 NAME[4]
3087 INPUT MODULE 12 NAME; CONTINUED READ INPUT MODULE 4 ZERO / INPUT MODULE 4 NAME[6]
3088 INPUT MODULE 13 NAME; 7 ASCII CHARACTERS READ INPUT MODULE 5 NAME[1] / INPUT MODULE 5 NAME[0]
3089 INPUT MODULE 13 NAME; CONTINUED READ INPUT MODULE 5 NAME[3] / INPUT MODULE 5 NAME[2]
3090 INPUT MODULE 13 NAME; CONTINUED READ INPUT MODULE 5 NAME[5] / INPUT MODULE 5 NAME[4]
3091 INPUT MODULE 13 NAME; CONTINUED READ INPUT MODULE 5 ZERO / INPUT MODULE 5 NAME[6]
3092 INPUT MODULE 14 NAME; 7 ASCII CHARACTERS READ INPUT MODULE 6 NAME[1] / INPUT MODULE 6 NAME[0]
3093 INPUT MODULE 14 NAME; CONTINUED READ INPUT MODULE 6 NAME[3] / INPUT MODULE 6 NAME[2]
3094 INPUT MODULE 14 NAME; CONTINUED READ INPUT MODULE 6 NAME[5] / INPUT MODULE 6 NAME[4]
3095 INPUT MODULE 14 NAME; CONTINUED READ INPUT MODULE 6 ZERO / INPUT MODULE 6 NAME[6]
3096 INPUT MODULE 15 NAME; 7 ASCII CHARACTERS READ INPUT MODULE 7 NAME[1] / INPUT MODULE 7 NAME[0]
3097 INPUT MODULE 15 NAME; CONTINUED READ INPUT MODULE 7 NAME[3] / INPUT MODULE 7 NAME[2]
3098 INPUT MODULE 15 NAME; CONTINUED READ INPUT MODULE 7 NAME[5] / INPUT MODULE 7 NAME[4]
3099 INPUT MODULE 15 NAME; CONTINUED READ INPUT MODULE 7 ZERO / INPUT MODULE 7 NAME[6]
3100 INPUT MODULE 16 NAME; 7 ASCII CHARACTERS READ INPUT MODULE 8 NAME[1] / INPUT MODULE 8 NAME[0]
3101 INPUT MODULE 16 NAME; CONTINUED READ INPUT MODULE 8 NAME[3] / INPUT MODULE 8 NAME[2]
3102 INPUT MODULE 16 NAME; CONTINUED READ INPUT MODULE 8 NAME[5] / INPUT MODULE 8 NAME[4]
3103 INPUT MODULE 16 NAME; CONTINUED READ INPUT MODULE 8 ZERO / INPUT MODULE 8 NAME[6]

90 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION

INPUT MODULE 9 MEASUREMENT UNITS; 3


3104 ASCII CHAR READ INPUT MODULE 1; UNITS[1] / UNITS[0]
INPUT MODULE 9 MEASUREMENT UNITS;
3105 CONTINUED READ INPUT MODULE 1; ZERO / UNITS[2]
INPUT MODULE 10 MEASUREMENT UNITS; 3
3106 ASCII CHAR READ INPUT MODULE 2; UNITS[1] / UNITS[0]
INPUT MODULE 10 MEASUREMENT UNITS;
3107 CONTINUED READ INPUT MODULE 2; ZERO / UNITS[2]
INPUT MODULE 11 MEASUREMENT UNITS; 3
3108 ASCII CHAR READ INPUT MODULE 3; UNITS[1] / UNITS[0]
INPUT MODULE 11 MEASUREMENT UNITS;
3109 CONTINUED READ INPUT MODULE 3; ZERO / UNITS[2]
INPUT MODULE 12 MEASUREMENT UNITS; 3
3110 ASCII CHAR READ INPUT MODULE 4; UNITS[1] / UNITS[0]
INPUT MODULE 12 MEASUREMENT UNITS;
3111 CONTINUED READ INPUT MODULE 4; ZERO / UNITS[2]
INPUT MODULE 13 MEASUREMENT UNITS; 3
3112 ASCII CHAR READ INPUT MODULE 5; UNITS[1] / UNITS[0]
INPUT MODULE 13 MEASUREMENT UNITS;
3113 CONTINUED READ INPUT MODULE 5; ZERO / UNITS[2]
INPUT MODULE 14 MEASUREMENT UNITS; 3
3114 ASCII CHAR READ INPUT MODULE 6; UNITS[1] / UNITS[0]
INPUT MODULE 14 MEASUREMENT UNITS;
3115 CONTINUED READ INPUT MODULE 6; ZERO / UNITS[2]
INPUT MODULE 15 MEASUREMENT UNITS; 3
3116 ASCII CHAR READ INPUT MODULE 7; UNITS[1] / UNITS[0]
INPUT MODULE 15 MEASUREMENT UNITS;
3117 CONTINUED READ INPUT MODULE 7; ZERO / UNITS[2]
INPUT MODULE 16 MEASUREMENT UNITS; 3
3118 ASCII CHAR READ INPUT MODULE 8; UNITS[1] / UNITS[0]
INPUT MODULE 16 MEASUREMENT UNITS;
3119 CONTINUED READ INPUT MODULE 8; ZERO / UNITS[2]

91 www.qualitrolcorp.com
IEC 60870-5-101/-104 Configuration/
Interoperability Guide
Introduction
The purpose of this document is to describe the specific implementation of the IEC 60870-5-101/104
for the 509ITM (an IEC 60870-5-101/104 Slave device).
This document and the documents listed below provide complete information on how to communicate
with the 509ITM via the IEC 60870-5-101/104 protocol.
 IEC 60870-5-101 = Companion standard for basic telecontrol tasks
 IEC 60870-5-5 = Basic Application Functions
 IEC 60870-5-2 = Link Transmission Procedures
 IEC 60870-5-4 = Definition and Coding of Application Information Elements
 IEC 60870-5-3 = General Structure of Application Data
 IEC 60870-5-1 = Transmission Frame Formats

Interoperability
The pages in this section have been extracted from the 60870-5-101/104 © IEC:2003, Section 8. The
section numbers below have been purposely retained from that document for reference.
This companion standard presents sets of parameters and alternatives from which subsets have to
be selected to implement particular telecontrol systems. Certain parameter values, such as the
number of octets in the COMMON ADDRESS of ASDUs represent mutually exclusive alternatives.
This means that only one value of the defined parameters is admitted per system. Other parameters,
such as the listed set of different process information in command and in monitor direction allow the
specification of the complete set or subsets, as appropriate for given applications. This Clause
summarizes the parameters of the previous Clauses to facilitate a suitable selection for a specific
application. If a system is composed of equipment stemming from different manufacturers it is
necessary that all partners agree on the selected parameters.
The selected parameters should be marked in the white boxes as follows:

 Function or ASDU is not used


 Function or ASDU is used as standardized (default)
R Function or ASDU is used in reverse mode
B Function or ASDU is used in standard and reverse mode
The possible selection (blank, X, R, or B) is specified for each specific Clause or parameter.

92 www.qualitrolcorp.com
System or device
System definition
Controlling station definition (master)
Controlled station definition (slave)
Network Configuration
 Point-to-point  Multipoint-party line
 Multiple point-to-point  Multipoint-star

Physical Layer
Transmission Speed (control direction)
Unbalanced interchange Unbalanced interchange Balanced interchange
Circuit V.24/V.28 Circuit V.24/V.28 Circuit X.24/X.27
Standard Recommended if >1 200 bit/s
 100 bit/s  2400 bit/s  2400 bit/s 
56000 bit/s
 200 bit/s 4800 bit/s  4800 bit/s 
64000 bit/s
 300 bit/s 9600 bit/s  9600 bit/s
 600 bit/s  19200 bit/s
1200 bit/s  38400 bit/s
Transmission speed (monitor direction)
Unbalanced interchange Unbalanced interchange Balanced interchange
Circuit V.24/V.28 Circuit V.24/V.28 Circuit X.24/X.27
Standard Recommended if >1 200 bit/s
 100 bit/s  2400 bit/s  2400 bit/s 
56000 bit/s
 200 bit/s 4800 bit/s  4800 bit/s 
64000 bit/s
 300 bit/s 9600 bit/s  9600 bit/s
 600 bit/s  19200 bit/s
1200 bit/s  38400 bit/s
Link Layer
Frame format FT 1.2, single character 1 and the fixed time out interval are used exclusively in this
companion standard.

Link transmission procedure Address field of link


 Balanced transmission  Not present (balanced transmission only)
 Unbalanced transmission  One octet
 Two octets
 Structured
  Unstructured

93 www.qualitrolcorp.com
Frame length
255 Maximum length L (control direction)
255 Maximum length L (monitor direction)
Configurable Time during which repetitions are permitted (Trp) or number of repetitions

 The standard assignment of ASDUs to class 2 messages is used as follows:


Type identification Cause of transmission
9, 11, 13, 21 <1>

 A special assignment of ASDUs to class 2 messages is used as follows:


Type identification Cause of transmission
1,3,5,7,9,11,13,20,21,110,111 <2>
,112

Note: In response to a class 2 poll, a controlled station may respond with class 1 data when there is
no class 2 data available.

Application Layer
Transmission mode for application data
Mode 1 (Least significant octet first), as defined in clause 4.10 of IEC 60870-5-4, is used exclusively
in this companion standard.

Common address of ASDU


 One octet  Two octets
Information object address
 One octet  structured
 Two octets  unstructured
 Three octets
Cause of transmission
 One octet  Two octets (with originator address)
Set to zero in case of no originator address

94 www.qualitrolcorp.com
Selection of standard ASDUs
Process information in monitor direction

<1>:= Single-point information M_SP_NA_1


<2>:= Single-point information with time tag M_SP_TA_1
<3>:= Double-point information M_DP_NA_1
<4>:= Double-point information with time tag M_DP_TA_1
<5>:= Step position information M_ST_NA_1
<6>:= Step position information with time tag M_ST_TA_1
<7>:= Bit string of 32 bit M_BO_NA_1
<8>:= Bit string of 32 bit with time tag M_BO_TA_1
<9>:= Measured value, normalized value M_ME_NA_1
<10>:= Measured value, normalized value with time tag M_ME_TA_1
<11>:= Measured value, scaled value M_ME_NB_1
<12>:= Measured value, scaled value with time tag M_ME_TB_1
<13>:= Measured value, short floating point value M_ME_NC_I
<14>:= Measured value, short floating point value with time tag M_ME_TC_1
<15>:= Integrated totals M_IT_NA_1
<16>:= Integrated totals with time tag M_IT_TA_1
<17>:= Event of protection equipment with time tag M_EP_TA_1
<18>:= Packed start events of protection equipment with time tag M_EP_TB_1
<19>:= Packed output circuit information of protection equipment with time tag M_EP_TC_1
<20>:= Packed single-point information with status change detection M_PS_NA_1
<21>:= Measured value, normalized value without quality descriptor M_ME_ND_1
<30>:= Single-point information with time tag CP56Time2a M_SP_TB_1
<31>:= Double-point information with time tag CP56Time2A M_DP_TB_1
<32>:= Step position information with time tag CP56Time2A M_ST_TB_1
<33>:= Bit string of 32 bit with time tag CP56Time2A M_BO_TB_1
<34>:= Measured value, normalized value with time tag CP56Time2A M_ME_TD_1
<35>:= Measured value, scaled value with time tag CP56Time2A M_ME_TE_1
<36>:= Measured value, short floating point value with time tag CP56Time2A M_ME_TF_1
<37>:= Integrated totals with time tag CP56Time2A M_IT_TB_1
<38>:= Event of protection equipment with time tag CP56Time2A M_EP_TD_1
<39>:= Packed start events of protection equipment with time tag CP56time2A M_EP_TE_1
<40>:= Packed output circuit information of protection equipment with time M_EP_TF_1
tag

Process information in control direction

95 www.qualitrolcorp.com
<45>:= Single command C_SC_NA_1
<46>:= Double command C_DC_NA_1
<47>:= Regulating step command C_RC_NA_1
<48>:= Set point command, normalized value C_SE_NA_1
<49>:= Set point command, scaled value C_SE_NB_1
<50>:= Set point command, short floating point value C_SE_NC_1
<51>:= Bitstring of 32 bit C_BO_NA_1

System information in monitor direction


<70>:= End of initialization M_EI_NA_1

System information in control direction


<100>:= Interrogation command C_IC_NA_1
<101>:= Counter interrogation command C_CI_NA_1
<102>:= Read command C_RD_NA_1
<103>:= Clock synchronization command C_CS_NA_1
<104>:= Test command C_TS_NB_1
<105>:= Reset process command C_RP_NC_1
<106>:= Delay acquisition command C_CD_NA_1

Parameter in control direction

<110>:= Parameter of measured value, normalized value P_ME_NA_1


<111>:= Parameter of measured value, scaled value P_ME_NB_1
<112>:= Parameter of measured value, short floating point value P_ME_NC_1
<113>:= Parameter activation P_AC_NA_1\

File transfer

<120>:= File ready F_FR_NA_1


<121>:= Section ready F_SR_NA_1
<122>:= Call directory, select file, call file, call section F_SC_NA_1
<123>:= Last section, last segment F_LS_NA_1
<124>:= Ack file, ack section F_AF_NA_1
<125>:= Segment F_SG_NA_1
<126>:= Directory F_DR_TA_1

96 www.qualitrolcorp.com
Type identification and cause of transmission assignments
(station-specific parameters)

Type identification Cause of transmission

request by group <n> counter request

unknown information object address


unknown common address of ASDU
return info caused by a remote cmd

return info caused by a local cmd

interrogated by group <number>

unknown cause of transmission


unknown type identification
deactivation confirmation
activation confirmation

activation termination
request or requested
background scan
periodic, cyclic

spontaneous

deactivation

file transfer
activation
initialized

20 37
1 2 3 4 5 6 7 8 9 10 11 12 13 to to 44 45 46 47
36 41

<1> M_SP_NA_1 X X X X X X
<2> M_SP_TA_1 X X X X
<3> M_DP_NA_1 X X X X X X
<4> M_DP_TA_1 X X X X
<5> M_ST_NA_1 X X X X X X
<6> M_ST_TA_1 X X X X
<7> M_BO_NA_1 X X X X
<8> M_BO_TA_1 X X
<9> M_ME_NA_1 X X X X X
<10> M_ME_TA_1 X X
<11> M_ME_NB_1 X X X X X
<12> M_ME_TB_1 X X
<13> M_ME_NC_1 X X X X X
<14> M_ME_TC_1 X X
<15> M_IT_NA_1 X X
<16> M_IT_TA_1 X X
<17> M_EP_TA_1 X
<18> M_EP_TB_1 X
<19> M_EP_TC_1 X
<20> M_PS_NA_1 X X X X X X
<21> M_ME_ND_1 X X X X X
<30> M_SP_TB_1 X X X X
<31> M_DP_TB_1 X X X X
<32> M_ST_TB_1 X X X X

97 www.qualitrolcorp.com
Type identification Cause of transmission

request by group <n> counter request

unknown information object address


unknown common address of ASDU
return info caused by a remote cmd

return info caused by a local cmd

interrogated by group <number>

unknown cause of transmission


unknown type identification
deactivation confirmation
activation confirmation

activation termination
request or requested
background scan
periodic, cyclic

spontaneous

deactivation

file transfer
activation
initialized
20 37
1 2 3 4 5 6 7 8 9 10 11 12 13 to to 44 45 46 47
36 41

<33> M_BO_TB_1 X X
<34> M_ME_TD_1 X X
<35> M_ME_TE_1 X X
<36> M_ME_TF_1 X X
<37> M_IT_TB_1 X X
<38> M_EP_TD_1 X
<39> M_EP_TE_1 X
<40> M_EP_TF_1 X
<45> C_SC_NA_1 X X X X X X X X X
<46> C_DC_NA_1 X X X X X X X X X
<47> C_RC_NA_1 X X X X X X X X X
<48> C_SE_NA_1 X X X X X X X X X
<49> C_SE_NB_1 X X X X X X X X X
<50> C_SE_NC_1 X X X X X X X X X
<51> C_BO_NA_1 X X X X X X X X X
<70> M_EI_NA_1* X
<100> C_IC_NA_1 X X X X X X X X X
<101> C_CI_NA_1 X X X X X X X
<102> C_RD_NA_1 X X X X X
<103> C_CS_NA_1 X X X X X X X
<104> C_TS_NA_1 X X X X X X
<105> C_RP_NA_1 X X X X X X
<106> C_CD_NA_1 X X X X X X X
<110> P_ME_NA_1

<111> P_ME_NB_1

<112> P_ME_NC_1

<113> P_AC_NA_1

98 www.qualitrolcorp.com
Type identification Cause of transmission

request by group <n> counter request

unknown information object address


unknown common address of ASDU
return info caused by a remote cmd

return info caused by a local cmd

interrogated by group <number>

unknown cause of transmission


unknown type identification
deactivation confirmation
activation confirmation

activation termination
request or requested
background scan
periodic, cyclic

spontaneous

deactivation

file transfer
activation
initialized
20 37
1 2 3 4 5 6 7 8 9 10 11 12 13 to to 44 45 46 47
36 41

<120> F_FR_NA_1

<121> F_SR_NA_1

<122> F_SC_NA_1

<123> F_LS_NA_1

<124> F_AF_NA_1

<125> F_SG_NA_1

<126> F_DR_TA_1*

* Blank or X only

Basic Application Functions


Station initialization
 Remote initialization
Cyclic data transmission
 Cyclic data transmission
Read procedure
 Read procedure
Spontaneous transmission
 Spontaneous
Double transmission of information objects with cause of transmission spontaneous
The following type identifications may be transmitted in succession caused by a single status
change of an information object. The particular information object addresses for which double
transmission is enabled are defined in a project-specific list.

99 www.qualitrolcorp.com
 Double-point information M_DP_NA_1, M_DP_TA_1 and M_DP_TB_1
 Step position information M_ST_NA_1, M_ST_TA_1 and M_ST_TB_1
 Bit string of 32 bit M_BO_NA_1, M_BO_TA_1 and M_BO_TB_1
 Measured value, normalized value M_ME_NA_1, M_ME_TA_1, M_ME_ND_1 &
M_ME_TD_1
 Measured value, scaled value M_ME_NB_1, M_ME_TB_1 and M_ME_TE_1
 Measured value, short floating point number M_ME_NC_1, M_ME_TC_1, and
M_ME_TF_1

Station interrogation
 global
 group 1  group 7  group 13
 group 2  group 8  group l4
 group 3  group 9  group 15
 group 4  group 10  group 16
 group 5  group 11
 group 6  group 12 Information object addresses assigned to each
group must be show in a separate table

Clock synchronization
 Clock synchronization
 Day of week used
 RES1, GEN (time tag substituted/ not substituted) used
 SU-bit (summertime) used
Command transmission
 Direct command transmission  Select and execute command
 Direct set point command transmission  Select and execute set point command
 C_SE_ACTTERM used
 No additional definition
 Short pulse duration (duration determined by a system parameter in the outstation)
 Long pulse duration (duration determined by a system parameter in the outstation)
 Persistent output
Transmission of Integrated totals
 Mode A: Local freeze with spontaneous
 Mode B: Local freeze with counter
 Mode C Freeze and transmit by counter interrogation
 Mode C Freeze by counter-interrogation command, frozen values reported
 Counter read

100 www.qualitrolcorp.com
 Counter freeze without reset
 Counter freeze without reset
 Counter reset
 General request counter
 Request counter group 1
 Request counter group 2
 Request counter group 3
 Request counter group 4
Parameter loading
 Threshold value
 Smoothing factor
 Low limit for transmission of measured value
 High limit for transmission of measured value
Parameter activation
 Act/deact of persistent cyclic or periodic transmission of the addressed object
Test procedure

Test procedure

File transfer
File transfer in monitor direction
 Transparent file
 Transmission of disturbance data of protection
 Transmission of sequences of events
 Transmission of sequences of recorded analog values
File transfer in control direction
 Transparent file

Background scan
 Background scan

Acquisition of transmission delay


 Acquisition of transmission delay

101 www.qualitrolcorp.com
IEC 60870-5-101 / -104 I/O DATA MAP
BINARY INPUT
I/O ADD DATA VARIABLE DESCRIPTION
0 RELAY 1 ENABLED 1 = ENABLED; 0 = DISABLED
1 RELAY 2 ENABLED 1 = ENABLED; 0 = DISABLED
2 RELAY 3 ENABLED 1 = ENABLED; 0 = DISABLED
3 RELAY 4 ENABLED 1 = ENABLED; 0 = DISABLED
4 RELAY 5 ENABLED 1 = ENABLED; 0 = DISABLED
5 RELAY 6 ENABLED 1 = ENABLED; 0 = DISABLED
6 RELAY 7 ENABLED 1 = ENABLED; 0 = DISABLED
7 RELAY 8 ENABLED 1 = ENABLED; 0 = DISABLED
8 RELAY 1 ACTUATED 1 = ACTUATED; 0 = NOT ACTUATED
9 RELAY 2 ACTUATED 1 = ACTUATED; 0 = NOT ACTUATED
10 RELAY 3 ACTUATED 1 = ACTUATED; 0 = NOT ACTUATED
11 RELAY 4 ACTUATED 1 = ACTUATED; 0 = NOT ACTUATED
12 RELAY 5 ACTUATED 1 = ACTUATED; 0 = NOT ACTUATED
13 RELAY 6 ACTUATED 1 = ACTUATED; 0 = NOT ACTUATED
14 RELAY 7 ACTUATED 1 = ACTUATED; 0 = NOT ACTUATED
15 RELAY 8 ACTUATED 1 = ACTUATED; 0 = NOT ACTUATED
16 SYSTEM STATUS RELAY 1 = ACTUATED; 0 = NOT ACTUATED
17 HEATER STATUS 1 = ENABLED; 0 = DISABLED
18 RELAY 1 LATCHING FEATURE 1 = ENABLED; 0 = DISABLED
19 RELAY 2 LATCHING FEATURE 1 = ENABLED; 0 = DISABLED
20 RELAY 3 LATCHING FEATURE 1 = ENABLED; 0 = DISABLED
21 RELAY 4 LATCHING FEATURE 1 = ENABLED; 0 = DISABLED
22 RELAY 5 LATCHING FEATURE 1 = ENABLED; 0 = DISABLED
23 RELAY 6 LATCHING FEATURE 1 = ENABLED; 0 = DISABLED
24 RELAY 7 LATCHING FEATURE 1 = ENABLED; 0 = DISABLED
25 RELAY 8 LATCHING FEATURE 1 = ENABLED; 0 = DISABLED
26 RELAY 1 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
27 RELAY 2 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
28 RELAY 3 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
29 RELAY 4 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
30 RELAY 5 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
31 RELAY 6 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
32 RELAY 7 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
33 RELAY 8 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
34 EVENT RECORD 1 1 = TRIGGERED; 0 = NOT TRIGGERED
35 EVENT RECORD 2 1 = TRIGGERED; 0 = NOT TRIGGERED
36 EVENT RECORD 3 1 = TRIGGERED; 0 = NOT TRIGGERED
37 EVENT RECORD 4 1 = TRIGGERED; 0 = NOT TRIGGERED
38 EVENT RECORD 5 1 = TRIGGERED; 0 = NOT TRIGGERED
39 EVENT RECORD 6 1 = TRIGGERED; 0 = NOT TRIGGERED
40 EVENT RECORD 7 1 = TRIGGERED; 0 = NOT TRIGGERED
41 EVENT RECORD 8 1 = TRIGGERED; 0 = NOT TRIGGERED
42 INPUT MODULE 1 ENABLED/DISABLED 1 = ENABLED; 0 = DISABLED
43 INPUT MODULE 2 ENABLED/DISABLED 1 = ENABLED; 0 = DISABLED

102 www.qualitrolcorp.com
BINARY INPUT
I/O ADD DATA VARIABLE DESCRIPTION
44 INPUT MODULE 3 ENABLED/DISABLED 1 = ENABLED; 0 = DISABLED
45 INPUT MODULE 4 ENABLED/DISABLED 1 = ENABLED; 0 = DISABLED
46 INPUT MODULE 5 ENABLED/DISABLED 1 = ENABLED; 0 = DISABLED
47 INPUT MODULE 6 ENABLED/DISABLED 1 = ENABLED; 0 = DISABLED
48 INPUT MODULE 7 ENABLED/DISABLED 1 = ENABLED; 0 = DISABLED
49 INPUT MODULE 8 ENABLED/DISABLED 1 = ENABLED; 0 = DISABLED

BINARY OUTPUT
I/O ADD DATA VARIABLE DESCRIPTION
50 RELAY 1 ENABLED 1 = ENABLED; 0 = DISABLED
51 RELAY 2 ENABLED 1 = ENABLED; 0 = DISABLED
52 RELAY 3 ENABLED 1 = ENABLED; 0 = DISABLED
53 RELAY 4 ENABLED 1 = ENABLED; 0 = DISABLED
54 RELAY 5 ENABLED 1 = ENABLED; 0 = DISABLED
55 RELAY 6 ENABLED 1 = ENABLED; 0 = DISABLED
56 RELAY 7 ENABLED 1 = ENABLED; 0 = DISABLED
57 RELAY 8 ENABLED 1 = ENABLED; 0 = DISABLED
58 INPUT MODULE MAX/MIN RESET PULSE/RESET (1)
59 COOLING MONITOR MAX/MIN RESET PULSE/RESET (1)
60 LATCHED RELAYS RESET PULSE/RESET (1)
61 RELAY 1 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
62 RELAY 2 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
63 RELAY 3 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
64 RELAY 4 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
65 RELAY 5 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
66 RELAY 6 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
67 RELAY 7 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
68 RELAY 8 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
69 INPUT MODULE 1 ENABLED/DISABLED 1 = ENABLED; 0 = DISABLED
70 INPUT MODULE 2 ENABLED/DISABLED 1 = ENABLED; 0 = DISABLED
71 INPUT MODULE 3 ENABLED/DISABLED 1 = ENABLED; 0 = DISABLED
72 INPUT MODULE 4 ENABLED/DISABLED 1 = ENABLED; 0 = DISABLED
73 INPUT MODULE 5 ENABLED/DISABLED 1 = ENABLED; 0 = DISABLED
74 INPUT MODULE 6 ENABLED/DISABLED 1 = ENABLED; 0 = DISABLED
75 INPUT MODULE 7 ENABLED/DISABLED 1 = ENABLED; 0 = DISABLED
76 INPUT MODULE 8 ENABLED/DISABLED 1 = ENABLED; 0 = DISABLED

BINARY INPUT
I/O ADD DATA VARIABLE DESCRIPTION
77 INPUT MODULE 1 READ ERROR 1 = READ ERROR; 0 = VALID READ
78 INPUT MODULE 2 READ ERROR 1 = READ ERROR; 0 = VALID READ
79 INPUT MODULE 3 READ ERROR 1 = READ ERROR; 0 = VALID READ
80 INPUT MODULE 4 READ ERROR 1 = READ ERROR; 0 = VALID READ
81 INPUT MODULE 5 READ ERROR 1 = READ ERROR; 0 = VALID READ
82 INPUT MODULE 6 READ ERROR 1 = READ ERROR; 0 = VALID READ

103 www.qualitrolcorp.com
BINARY INPUT
I/O ADD DATA VARIABLE DESCRIPTION
83 INPUT MODULE 7 READ ERROR 1 = READ ERROR; 0 = VALID READ
84 INPUT MODULE 8 READ ERROR 1 = READ ERROR; 0 = VALID READ
85 INPUT MODULE 1 CUSTOM SCALING 1 = ENABLED; 0 = DISABLED
86 INPUT MODULE 2 CUSTOM SCALING 1 = ENABLED; 0 = DISABLED
87 INPUT MODULE 3 CUSTOM SCALING 1 = ENABLED; 0 = DISABLED
88 INPUT MODULE 4 CUSTOM SCALING 1 = ENABLED; 0 = DISABLED
89 INPUT MODULE 5 CUSTOM SCALING 1 = ENABLED; 0 = DISABLED
90 INPUT MODULE 6 CUSTOM SCALING 1 = ENABLED; 0 = DISABLED
91 INPUT MODULE 7 CUSTOM SCALING 1 = ENABLED; 0 = DISABLED
92 INPUT MODULE 8 CUSTOM SCALING 1 = ENABLED; 0 = DISABLED

ANALOG INPUT
I/O
ADD DATA VARIABLE DESCRIPTION
100 RELAY 1, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
101 RELAY 2, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
102 RELAY 3, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
103 RELAY 4, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
104 RELAY 5, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
105 RELAY 6, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
106 RELAY 7, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
107 RELAY 8, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
108 RELAY 1, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
109 RELAY 2, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
110 RELAY 3, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
111 RELAY 4, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
112 RELAY 5, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
113 RELAY 6, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
114 RELAY 7, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
115 RELAY 8, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX

ALL MODULES BUT CT, WINDING TEMPERATURE IF THE MODULE IS A CT, WINDING TEMPERATURE
116 INPUT MODULE 1 PRESENT VALUE OR INPUT MODULE 1 PRESENT WINDING TEMP
117 INPUT MODULE 1 MINIMUM VALUE OR INPUT MODULE 1 MINIMUM WINDING TEMP
118 INPUT MODULE 1 MAXIMUM VALUE OR INPUT MODULE 1 MAXIMUM WINDING TEMP
119 0 OR INPUT MODULE 1 PRESENT CURRENT
120 0 OR INPUT MODULE 1 MAXIMUM CURRENT
121 INPUT MODULE 2 PRESENT VALUE OR INPUT MODULE 2 PRESENT WINDING TEMP
122 INPUT MODULE 2 MINIMUM VALUE OR INPUT MODULE 2 MINIMUM WINDING TEMP
123 INPUT MODULE 2 MAXIMUM VALUE OR INPUT MODULE 2 MAXIMUM WINDING TEMP
124 0 OR INPUT MODULE 2 PRESENT CURRENT
125 0 OR INPUT MODULE 2 MAXIMUM CURRENT
126 INPUT MODULE 3 PRESENT VALUE OR INPUT MODULE 3 PRESENT WINDING TEMP
127 INPUT MODULE 3 MINIMUM VALUE OR INPUT MODULE 3 MINIMUM WINDING TEMP
128 INPUT MODULE 3 MAXIMUM VALUE OR INPUT MODULE 3 MAXIMUM WINDING TEMP
129 0 OR INPUT MODULE 3 PRESENT CURRENT
130 0 OR INPUT MODULE 3 MAXIMUM CURRENT

104 www.qualitrolcorp.com
ANALOG INPUT
I/O
ADD DATA VARIABLE DESCRIPTION
131 INPUT MODULE 4 PRESENT VALUE OR INPUT MODULE 4 PRESENT WINDING TEMP
132 INPUT MODULE 4 MINIMUM VALUE OR INPUT MODULE 4 MINIMUM WINDING TEMP
133 INPUT MODULE 4 MAXIMUM VALUE OR INPUT MODULE 4 MAXIMUM WINDING TEMP
134 0 OR INPUT MODULE 4 PRESENT CURRENT
135 0 OR INPUT MODULE 4 MAXIMUM CURRENT
136 INPUT MODULE 5 PRESENT VALUE OR INPUT MODULE 5 PRESENT WINDING TEMP
137 INPUT MODULE 5 MINIMUM VALUE OR INPUT MODULE 5 MINIMUM WINDING TEMP
138 INPUT MODULE 5 MAXIMUM VALUE OR INPUT MODULE 5 MAXIMUM WINDING TEMP
139 0 OR INPUT MODULE 5 PRESENT CURRENT
140 0 OR INPUT MODULE 5 MAXIMUM CURRENT
141 INPUT MODULE 6 PRESENT VALUE OR INPUT MODULE 6 PRESENT WINDING TEMP
142 INPUT MODULE 6 MINIMUM VALUE OR INPUT MODULE 6 MINIMUM WINDING TEMP
143 INPUT MODULE 6 MAXIMUM VALUE OR INPUT MODULE 6 MAXIMUM WINDING TEMP
144 0 OR INPUT MODULE 6 PRESENT CURRENT
145 0 OR INPUT MODULE 6 MAXIMUM CURRENT
146 INPUT MODULE 7 PRESENT VALUE OR INPUT MODULE 7 PRESENT WINDING TEMP
147 INPUT MODULE 7 MINIMUM VALUE OR INPUT MODULE 7 MINIMUM WINDING TEMP
148 INPUT MODULE 7 MAXIMUM VALUE OR INPUT MODULE 7 MAXIMUM WINDING TEMP
149 0 OR INPUT MODULE 7 PRESENT CURRENT
150 0 OR INPUT MODULE 7 MAXIMUM CURRENT
151 INPUT MODULE 8 PRESENT VALUE OR INPUT MODULE 8 PRESENT WINDING TEMP
152 INPUT MODULE 8 MINIMUM VALUE OR INPUT MODULE 8 MINIMUM WINDING TEMP
153 INPUT MODULE 8 MAXIMUM VALUE OR INPUT MODULE 8 MAXIMUM WINDING TEMP
154 0 OR INPUT MODULE 8 PRESENT CURRENT
155 0 OR INPUT MODULE 8 MAXIMUM CURRENT
156 DIFFERENTIAL CALCULATION 1 PRESENT VALUE
157 DIFFERENTIAL CALCULATION 1 MINIMUM VALUE
158 DIFFERENTIAL CALCULATION 1 MAXIMUM VALUE
159 DIFFERENTIAL CALCULATION 2 PRESENT VALUE
160 DIFFERENTIAL CALCULATION 2 MINIMUM VALUE
161 DIFFERENTIAL CALCULATION 2 MAXIMUM VALUE
162 DIFFERENTIAL CALCULATION 3 PRESENT VALUE
163 DIFFERENTIAL CALCULATION 3 MINIMUM VALUE
164 DIFFERENTIAL CALCULATION 3 MAXIMUM VALUE
165 DIFFERENTIAL CALCULATION 4 PRESENT VALUE
166 DIFFERENTIAL CALCULATION 4 MINIMUM VALUE
167 DIFFERENTIAL CALCULATION 4 MAXIMUM VALUE
168 HOTTEST PRESENT WINDING TEMPERATURE OF ALL ACTIVE CT, TEMPERATURE MODULES
169 RELAY 1, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
170 RELAY 2, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
171 RELAY 3, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
172 RELAY 4, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
173 RELAY 5, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
174 RELAY 6, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
175 RELAY 7, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
176 RELAY 8, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX

105 www.qualitrolcorp.com
ANALOG INPUT
I/O
ADD DATA VARIABLE DESCRIPTION
177 RELAY 1, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
178 RELAY 2, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
179 RELAY 3, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
180 RELAY 4, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
181 RELAY 5, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
182 RELAY 6, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
183 RELAY 7, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
184 RELAY 8, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
185 RELAY 1, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
186 RELAY 2, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
187 RELAY 3, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
188 RELAY 4, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
189 RELAY 5, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
190 RELAY 6, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
191 RELAY 7, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
192 RELAY 8, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
193 RELAY 1, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
194 RELAY 2, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
195 RELAY 3, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
196 RELAY 4, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
197 RELAY 5, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
198 RELAY 6, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
199 RELAY 7, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
200 RELAY 8, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
201 RELAY 1, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
202 RELAY 2, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
203 RELAY 3, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
204 RELAY 4, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
205 RELAY 5, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
206 RELAY 6, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
207 RELAY 7, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
208 RELAY 8, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
209 RELAY 1, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
210 RELAY 2, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
211 RELAY 3, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
212 RELAY 4, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
213 RELAY 5, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
214 RELAY 6, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
215 RELAY 7, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
216 RELAY 8, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
217 TRANSLIFE 1 CONSUMED LIFE FOR LAST HOUR CALCULATED CONSUMED LIFE FOR LAST HOUR
218 TRANSLIFE 1 CONSUMED LIFE FOR LAST DAY CALCULATED CONSUMED LIFE FOR LAST DAY
219 TRANSLIFE 1 REMAINING TRANSFORMER LIFE (20 YEARS - CONSUMED LIFE)
220 TL1 CRITICAL WINDING TEMP SETPOINT 1 1ST CRITICAL SPT TO CALCULATE TIME TO REACH
221 TL1 CRITICAL WINDING TEMP SETPOINT 2 2ND CRITICAL SPT TO CALCULATE TIME TO REACH
222 TL1 CRITICAL WINDING TEMP SETPOINT 3 3RD CRITICAL SPT TO CALCULATE TIME TO REACH

106 www.qualitrolcorp.com
ANALOG INPUT
I/O
ADD DATA VARIABLE DESCRIPTION
223 TL1 TIME TO CRITICAL SETPOINT 1 CALCULATED TIME TO 1ST SPT FOR GIVEN CONDITIONS
224 TL1 TIME TO CRITICAL SETPOINT 2 CALCULATED TIME TO 2ND SPT FOR GIVEN CONDITIONS
225 TL1 TIME TO CRITICAL SETPOINT 3 CALCULATED TIME TO 3RD SPT FOR GIVEN CONDITIONS
226 TRANSLIFE 2 CONSUMED LIFE FOR LAST HOUR CALCULATED CONSUMED LIFE FOR LAST HOUR
227 TRANSLIFE 2 CONSUMED LIFE FOR LAST DAY CALCULATED CONSUMED LIFE FOR LAST DAY
228 TRANSLIFE 2 REMAINING TRANSFORMER LIFE (20 YEARS - CONSUMED LIFE)
229 TL2 CRITICAL WINDING TEMP SETPOINT 1 1ST CRITICAL SPT TO CALCULATE TIME TO REACH
230 TL2 CRITICAL WINDING TEMP SETPOINT 2 2ND CRITICAL SPT TO CALCULATE TIME TO REACH
231 TL2 CRITICAL WINDING TEMP SETPOINT 3 3RD CRITICAL SPT TO CALCULATE TIME TO REACH
232 TL2 TIME TO CRITICAL SETPOINT 1 CALCULATED TIME TO 1ST SPT FOR GIVEN CONDITIONS
233 TL2 TIME TO CRITICAL SETPOINT 2 CALCULATED TIME TO 2ND SPT FOR GIVEN CONDITIONS
234 TL2 TIME TO CRITICAL SETPOINT 3 CALCULATED TIME TO 3RD SPT FOR GIVEN CONDITIONS
235 TRANSLIFE 3 CONSUMED LIFE FOR LAST HOUR CALCULATED CONSUMED LIFE FOR LAST HOUR
236 TRANSLIFE 3 CONSUMED LIFE FOR LAST DAY CALCULATED CONSUMED LIFE FOR LAST DAY
237 TRANSLIFE 3 REMAINING TRANSFORMER LIFE (20 YEARS - CONSUMED LIFE)
238 TL3 CRITICAL WINDING TEMP SETPOINT 1 1ST CRITICAL SPT TO CALCULATE TIME TO REACH
239 TL3 CRITICAL WINDING TEMP SETPOINT 2 2ND CRITICAL SPT TO CALCULATE TIME TO REACH
240 TL3 CRITICAL WINDING TEMP SETPOINT 3 3RD CRITICAL SPT TO CALCULATE TIME TO REACH
241 TL3 TIME TO CRITICAL SETPOINT 1 CALCULATED TIME TO 1ST SPT FOR GIVEN CONDITIONS
242 TL3 TIME TO CRITICAL SETPOINT 2 CALCULATED TIME TO 2ND SPT FOR GIVEN CONDITIONS
243 TL3 TIME TO CRITICAL SETPOINT 3 CALCULATED TIME TO 3RD SPT FOR GIVEN CONDITIONS
244 COOLING BANK 1 PRESENT RUNNING CURRENT COOLING BANK 1 PRESENT/STEADY STATE CURRENT
245 COOLING BANK 1 MINIMUM RUNNING CURRENT COOLING BANK 1 MINIMUM STEADY STATE CURRENT
246 COOLING BANK 1 MAXIMUM RUNNING CURRENT COOLING BANK 1 MAXIMUM STEADY STATE CURRENT
247 CB1 RUNNING CURRENT UPPER SETPOINT COOLING BANK 1 STEADY STATE CURRENT SETPOINT
248 CB1 RUNNING CURRENT LOWER SETPOINT COOLING BANK 1 STEADY STATE CURRENT SETPOINT
249 CB1 PRESENT PEAK INRUSH CURRENT VALUE COOLING BANK 1 PRESENT PEAK INRUSH CURRENT
250 CB1 MINIMUM PEAK INRUSH CURRENT VALUE COOLING BANK 1 MINIMUM PEAK INRUSH CURRENT
251 CB1 MAXIMUM PEAK INRUSH CURRENT VALUE COOLING BANK 1 MAXIMUM PEAK INRUSH CURRENT
252 CB1 INRUSH CURRENT UPPER SETPOINT VALUE COOLING BANK 1 PEAK INRUSH CURRENT SETPOINT
253 CB1 INRUSH CURRENT LOWER SETPOINT VALUE COOLING BANK 1 PEAK INRUSH CURRENT SETPOINT
254 COOLING BANK 2 PRESENT RUNNING CURRENT COOLING BANK 2 PRESENT/STEADY STATE CURRENT
255 COOLING BANK 2 MINIMUM RUNNING CURRENT COOLING BANK 2 MINIMUM STEADY STATE CURRENT
256 COOLING BANK 2 MAXIMUM RUNNING CURRENT COOLING BANK 2 MAXIMUM STEADY STATE CURRENT
257 CB2 RUNNING CURRENT UPPER SETPOINT COOLING BANK 2 STEADY STATE CURRENT SETPOINT
258 CB2 RUNNING CURRENT LOWER SETPOINT COOLING BANK 2 STEADY STATE CURRENT SETPOINT
259 CB2 PRESENT PEAK INRUSH CURRENT VALUE COOLING BANK 2 PRESENT PEAK INRUSH CURRENT
260 CB2 MINIMUM PEAK INRUSH CURRENT VALUE COOLING BANK 2 MINIMUM PEAK INRUSH CURRENT
261 CB2 MAXIMUM PEAK INRUSH CURRENT VALUE COOLING BANK 2 MAXIMUM PEAK INRUSH CURRENT
262 CB2 INRUSH CURRENT UPPER SETPOINT VALUE COOLING BANK 2 PEAK INRUSH CURRENT SETPOINT
263 CB2 INRUSH CURRENT LOWER SETPOINT VALUE COOLING BANK 2 PEAK INRUSH CURRENT SETPOINT
264 COOLING BANK 3 PRESENT RUNNING CURRENT COOLING BANK 3 PRESENT/STEADY STATE CURRENT
265 COOLING BANK 3 MINIMUM RUNNING CURRENT COOLING BANK 3 MINIMUM STEADY STATE CURRENT
266 COOLING BANK 3 MAXIMUM RUNNING CURRENT COOLING BANK 3 MAXIMUM STEADY STATE CURRENT
267 CB3 RUNNING CURRENT UPPER SETPOINT COOLING BANK 3 STEADY STATE CURRENT SETPOINT
268 CB3 RUNNING CURRENT LOWER SETPOINT COOLING BANK 3 STEADY STATE CURRENT SETPOINT

107 www.qualitrolcorp.com
ANALOG INPUT
I/O
ADD DATA VARIABLE DESCRIPTION
269 CB3 PRESENT PEAK INRUSH CURRENT VALUE COOLING BANK 3 PRESENT PEAK INRUSH CURRENT
270 CB3 MINIMUM PEAK INRUSH CURRENT VALUE COOLING BANK 3 MINIMUM PEAK INRUSH CURRENT
271 CB3 MAXIMUM PEAK INRUSH CURRENT VALUE COOLING BANK 3 MAXIMUM PEAK INRUSH CURRENT
272 CB3 INRUSH CURRENT UPPER SETPOINT VALUE COOLING BANK 3 PEAK INRUSH CURRENT SETPOINT
273 CB3 INRUSH CURRENT LOWER SETPOINT VALUE COOLING BANK 3 PEAK INRUSH CURRENT SETPOINT
274 COOLING BANK 4 PRESENT RUNNING CURRENT COOLING BANK 4 PRESENT/STEADY STATE CURRENT
275 COOLING BANK 4 MINIMUM RUNNING CURRENT COOLING BANK 4 MINIMUM STEADY STATE CURRENT
276 COOLING BANK 4 MAXIMUM RUNNING CURRENT COOLING BANK 4 MAXIMUM STEADY STATE CURRENT
277 CB4 RUNNING CURRENT UPPER SETPOINT COOLING BANK 4 STEADY STATE CURRENT SETPOINT
278 CB4 RUNNING CURRENT LOWER SETPOINT COOLING BANK 4 STEADY STATE CURRENT SETPOINT
279 CB4 PRESENT PEAK INRUSH CURRENT VALUE COOLING BANK 4 PRESENT PEAK INRUSH CURRENT
280 CB4 MINIMUM PEAK INRUSH CURRENT VALUE COOLING BANK 4 MINIMUM PEAK INRUSH CURRENT
281 CB4 MAXIMUM PEAK INRUSH CURRENT VALUE COOLING BANK 4 MAXIMUM PEAK INRUSH CURRENT
282 CB4 INRUSH CURRENT UPPER SETPOINT VALUE COOLING BANK 4 PEAK INRUSH CURRENT SETPOINT
283 CB4 INRUSH CURRENT LOWER SETPOINT VALUE COOLING BANK 4 PEAK INRUSH CURRENT SETPOINT
284 TAP POSITION -16 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-16)
285 TAP POSITION -15 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-15)
286 TAP POSITION -14 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-14)
287 TAP POSITION -13 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-13)
288 TAP POSITION -12 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-12)
289 TAP POSITION -11 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-11)
290 TAP POSITION -10 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-10)
291 TAP POSITION -9 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-9)
292 TAP POSITION -8 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-8)
293 TAP POSITION -7 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-7)
294 TAP POSITION -6 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-6)
295 TAP POSITION -5 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-5)
296 TAP POSITION -4 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-4)
297 TAP POSITION -3 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-3)
298 TAP POSITION -2 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-2)
299 TAP POSITION -1 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (-1)
300 TAP POSITION +0 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+0)
301 TAP POSITION +1 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+1)
302 TAP POSITION +2 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+2)
303 TAP POSITION +3 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+3)
304 TAP POSITION +4 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+4)
305 TAP POSITION +5 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+5)
306 TAP POSITION +6 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+6)
307 TAP POSITION +7 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+7)
308 TAP POSITION +8 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+8)
309 TAP POSITION +9 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+9)
310 TAP POSITION +10 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+10)
311 TAP POSITION +11 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+11)
312 TAP POSITION +12 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+12)
313 TAP POSITION +13 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+13)
314 TAP POSITION +14 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+14)

108 www.qualitrolcorp.com
ANALOG INPUT
I/O
ADD DATA VARIABLE DESCRIPTION
315 TAP POSITION +15 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+15)
316 TAP POSITION +16 AVERAGE MAKE CURRENT AVERAGE MAKE CURRENT FOR TAP POSITION (+16)
317 TAP POSITION -16 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-16)
318 TAP POSITION -15 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-15)
319 TAP POSITION -14 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-14)
320 TAP POSITION -13 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-13)
321 TAP POSITION -12 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-12)
322 TAP POSITION -11 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-11)
323 TAP POSITION -10 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-10)
324 TAP POSITION -9 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-9)
325 TAP POSITION -8 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-8)
326 TAP POSITION -7 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-7)
327 TAP POSITION -6 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-6)
328 TAP POSITION -5 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-5)
329 TAP POSITION -4 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-4)
330 TAP POSITION -3 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-3)
331 TAP POSITION -2 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-2)
332 TAP POSITION -1 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (-1)
333 TAP POSITION +0 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+0)
334 TAP POSITION +1 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+1)
335 TAP POSITION +2 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+2)
336 TAP POSITION +3 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+3)
337 TAP POSITION +4 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+4)
338 TAP POSITION +5 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+5)
339 TAP POSITION +6 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+6)
340 TAP POSITION +7 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+7)
341 TAP POSITION +8 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+8)
342 TAP POSITION +9 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+9)
343 TAP POSITION +10 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+10)
344 TAP POSITION +11 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+11)
345 TAP POSITION +12 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+12)
346 TAP POSITION +13 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+13)
347 TAP POSITION +14 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+14)
348 TAP POSITION +15 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+15)
349 TAP POSITION +16 AVERAGE BREAK CURRENT AVERAGE BREAK CURRENT FOR TAP POSITION (+16)
350 LTC HI-ALARM RUN CURRENT UPPER SETPOINT LTC HIGH-PRIORITY STEADY STATE UPPER SETPOINT
351 LTC LO-ALARM RUN CURRENT UPPER SETPOINT LTC LOW-PRIORITY STEADY STATE UPPER SETPOINT
352 LTC HI-ALARM RUN CURRENT LOWER SETPOINT LTC HIGH-PRIORITY STEADY STATE LOWER SETPOINT
353 LTC LO-ALARM RUN CURRENT LOWER SETPOINT LTC LOW-PRIORITY STEADY STATE LOWER SETPOINT
LTC HI-ALARM INRUSH CURRENT UPPER
354 SETPOINT LTC HIGH-PRIORITY INRUSH CURRENT UPPER SETPOINT
LTC LO-ALARM INRUSH CURRENT UPPER
355 SETPOINT LTC LOW-PRIORITY INRUSH CURRENT UPPER SETPOINT
LTC HI-ALARM INRUSH CURRENT LOWER
356 SETPOINT LTC HIGH-PRIORITY INRUSH CURRENT LOWER SETPOINT
LTC LO-ALARM INRUSH CURRENT LOWER
357 SETPOINT LTC LOW-PRIORITY INRUSH CURRENT LOWER SETPOINT
358 MOD 1; FIBER PROBE 1 PRESENT TEMPERATURE HOT SPOT MODULE 1; 1ST PROBE PRESENT TEMP

109 www.qualitrolcorp.com
ANALOG INPUT
I/O
ADD DATA VARIABLE DESCRIPTION
359 MOD 1; FIBER PROBE 1 MINIMUM TEMPERATURE HOT SPOT MODULE 1; 1ST PROBE MINIMUM TEMP
360 MOD 1; FIBER PROBE 1 MAXIMUM TEMPERATURE HOT SPOT MODULE 1; 1ST PROBE MAXIMUM TEMP
361 MOD 1; FIBER PROBE 2 PRESENT TEMPERATURE HOT SPOT MODULE 1; 2ND PROBE PRESENT TEMP
362 MOD 1; FIBER PROBE 2 MINIMUM TEMPERATURE HOT SPOT MODULE 1; 2ND PROBE MINIMUM TEMP
363 MOD 1; FIBER PROBE 2 MAXIMUM TEMPERATURE HOT SPOT MODULE 1; 2ND PROBE MAXIMUM TEMP
364 MOD 1; FIBER PROBE 3 PRESENT TEMPERATURE HOT SPOT MODULE 1; 3RD PROBE PRESENT TEMP
365 MOD 1; FIBER PROBE 3 MINIMUM TEMPERATURE HOT SPOT MODULE 1; 3RD PROBE MINIMUM TEMP
366 MOD 1; FIBER PROBE 3 MAXIMUM TEMPERATURE HOT SPOT MODULE 1; 3RD PROBE MAXIMUM TEMP
367 MOD 1; FIBER PROBE 4 PRESENT TEMPERATURE HOT SPOT MODULE 1; 4TH PROBE PRESENT TEMP
368 MOD 1; FIBER PROBE 4 MINIMUM TEMPERATURE HOT SPOT MODULE 1; 4TH PROBE MINIMUM TEMP
369 MOD 1; FIBER PROBE 4 MAXIMUM TEMPERATURE HOT SPOT MODULE 1; 4TH PROBE MAXIMUM TEMP
370 MOD 1; FIBER PROBE 5 PRESENT TEMPERATURE HOT SPOT MODULE 1; 5TH PROBE PRESENT TEMP
371 MOD 1; FIBER PROBE 5 MINIMUM TEMPERATURE HOT SPOT MODULE 1; 5TH PROBE MINIMUM TEMP
372 MOD 1; FIBER PROBE 5 MAXIMUM TEMPERATURE HOT SPOT MODULE 1; 5TH PROBE MAXIMUM TEMP
373 MOD 1; FIBER PROBE 6 PRESENT TEMPERATURE HOT SPOT MODULE 1; 6TH PROBE PRESENT TEMP
374 MOD 1; FIBER PROBE 6 MINIMUM TEMPERATURE HOT SPOT MODULE 1; 6TH PROBE MINIMUM TEMP
375 MOD 1; FIBER PROBE 6 MAXIMUM TEMPERATURE HOT SPOT MODULE 1; 6TH PROBE MAXIMUM TEMP
376 MOD 1; FIBER PROBE 7 PRESENT TEMPERATURE HOT SPOT MODULE 1; 6TH PROBE PRESENT TEMP
377 MOD 1; FIBER PROBE 7 MINIMUM TEMPERATURE HOT SPOT MODULE 1; 7TH PROBE MINIMUM TEMP
378 MOD 1; FIBER PROBE 7 MAXIMUM TEMPERATURE HOT SPOT MODULE 1; 7TH PROBE MAXIMUM TEMP
379 MOD 1; FIBER PROBE 8 PRESENT TEMPERATURE HOT SPOT MODULE 1; 8TH PROBE PRESENT TEMP
380 MOD 1; FIBER PROBE 8 MINIMUM TEMPERATURE HOT SPOT MODULE 1; 8TH PROBE MINIMUM TEMP
381 MOD 1; FIBER PROBE 8 MAXIMUM TEMPERATURE HOT SPOT MODULE 1; 8TH PROBE MAXIMUM TEMP
382 MOD 2; FIBER PROBE 1 PRESENT TEMPERATURE HOT SPOT MODULE 2; 1ST PROBE PRESENT TEMP
383 MOD 2; FIBER PROBE 1 MINIMUM TEMPERATURE HOT SPOT MODULE 2; 1ST PROBE MINIMUM TEMP
384 MOD 2; FIBER PROBE 1 MAXIMUM TEMPERATURE HOT SPOT MODULE 2; 1ST PROBE MAXIMUM TEMP
385 MOD 2; FIBER PROBE 2 PRESENT TEMPERATURE HOT SPOT MODULE 2; 2ND PROBE PRESENT TEMP
386 MOD 2; FIBER PROBE 2 MINIMUM TEMPERATURE HOT SPOT MODULE 2; 2ND PROBE MINIMUM TEMP
387 MOD 2; FIBER PROBE 2 MAXIMUM TEMPERATURE HOT SPOT MODULE 2; 2ND PROBE MAXIMUM TEMP
388 MOD 2; FIBER PROBE 3 PRESENT TEMPERATURE HOT SPOT MODULE 2; 3RD PROBE PRESENT TEMP
389 MOD 2; FIBER PROBE 3 MINIMUM TEMPERATURE HOT SPOT MODULE 2; 3RD PROBE MINIMUM TEMP
390 MOD 2; FIBER PROBE 3 MAXIMUM TEMPERATURE HOT SPOT MODULE 2; 3RD PROBE MAXIMUM TEMP
391 MOD 2; FIBER PROBE 4 PRESENT TEMPERATURE HOT SPOT MODULE 2; 4TH PROBE PRESENT TEMP
392 MOD 2; FIBER PROBE 4 MINIMUM TEMPERATURE HOT SPOT MODULE 2; 4TH PROBE MINIMUM TEMP
393 MOD 2; FIBER PROBE 4 MAXIMUM TEMPERATURE HOT SPOT MODULE 2; 4TH PROBE MAXIMUM TEMP
394 MOD 2; FIBER PROBE 5 PRESENT TEMPERATURE HOT SPOT MODULE 2; 5TH PROBE PRESENT TEMP
395 MOD 2; FIBER PROBE 5 MINIMUM TEMPERATURE HOT SPOT MODULE 2; 5TH PROBE MINIMUM TEMP
396 MOD 2; FIBER PROBE 5 MAXIMUM TEMPERATURE HOT SPOT MODULE 2; 5TH PROBE MAXIMUM TEMP
397 MOD 2; FIBER PROBE 6 PRESENT TEMPERATURE HOT SPOT MODULE 2; 6TH PROBE PRESENT TEMP
398 MOD 2; FIBER PROBE 6 MINIMUM TEMPERATURE HOT SPOT MODULE 2; 6TH PROBE MINIMUM TEMP
399 MOD 2; FIBER PROBE 6 MAXIMUM TEMPERATURE HOT SPOT MODULE 2; 6TH PROBE MAXIMUM TEMP
400 MOD 2; FIBER PROBE 7 PRESENT TEMPERATURE HOT SPOT MODULE 2; 6TH PROBE PRESENT TEMP
401 MOD 2; FIBER PROBE 7 MINIMUM TEMPERATURE HOT SPOT MODULE 2; 7TH PROBE MINIMUM TEMP
402 MOD 2; FIBER PROBE 7 MAXIMUM TEMPERATURE HOT SPOT MODULE 2; 7TH PROBE MAXIMUM TEMP
403 MOD 2; FIBER PROBE 8 PRESENT TEMPERATURE HOT SPOT MODULE 2; 8TH PROBE PRESENT TEMP
404 MOD 2; FIBER PROBE 8 MINIMUM TEMPERATURE HOT SPOT MODULE 2; 8TH PROBE MINIMUM TEMP

110 www.qualitrolcorp.com
ANALOG INPUT
I/O
ADD DATA VARIABLE DESCRIPTION
405 MOD 2; FIBER PROBE 8 MAXIMUM TEMPERATURE HOT SPOT MODULE 2; 8TH PROBE MAXIMUM TEMP
406 LIFE CONSUMPTION UNITY TEMPERATURE TEMP WHERE CONSUMED LIFE EQUALS OPERATING LIFE
LTC HI-ALARM TOTAL TAP COUNT SETPOINT
407 VALUE LTC HIGH-PRIORITY TOTAL TAP COUNT SETPOINT
LTC LO-ALARM TOTAL TAP COUNT SETPOINT
408 VALUE LTC LOW-PRIORITY TOTAL TAP COUNT SETPOINT
LTC HI-ALARM MOTOR ACTUATION SETPOINT
409 VALUE LTC HIGH-PRIORITY MOTOR ACTUATION COUNT SPT
LTC LO-ALARM MOTOR ACTUATION SETPOINT
410 VALUE LTC LOW-PRIORITY MOTOR ACTUATION COUNT SPT
411 LTC TAP PERIOD TIME PERIOD TO MEASURE LTC TAP COUNTS
412 LTC PRESENT COUNTS TOTAL COUNTS IN PRESENT TAP PERIOD
413 LTC PREVIOUS COUNTS TOTAL COUNTS IN THE PREVIOUS TAP PERIOD
TRANSLIFE 1; TEMPERATURE PROFILE, 1ST
414 RANGE TOTAL WINDING TEMP TIME IN LOWEST TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 2ND
415 RANGE TOTAL WINDING TEMP TIME IN 2ND TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 3RD
416 RANGE TOTAL WINDING TEMP TIME IN 3RD TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 4TH
417 RANGE TOTAL WINDING TEMP TIME IN 4TH TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 5TH
418 RANGE TOTAL WINDING TEMP TIME IN 5TH TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 6TH
419 RANGE TOTAL WINDING TEMP TIME IN 6TH TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 7TH
420 RANGE TOTAL WINDING TEMP TIME IN 7TH TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 8TH
421 RANGE TOTAL WINDING TEMP TIME IN 8TH TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 9TH
422 RANGE TOTAL WINDING TEMP TIME IN 9TH TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 10TH
423 RANGE TOTAL WINDING TEMP TIME IN 10TH TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 11TH
424 RANGE TOTAL WINDING TEMP TIME IN 11TH TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 12TH
425 RANGE TOTAL WINDING TEMP TIME IN HIGHEST TEMP RANGE
TRANSLIFE 2; TEMPERATURE PROFILE, 1ST
426 RANGE TOTAL WINDING TEMP TIME IN LOWEST TEMP RANGE
TRANSLIFE 2; TEMPERATURE PROFILE, 2ND
427 RANGE TOTAL WINDING TEMP TIME IN 2ND TEMP RANGE
TRANSLIFE 2; TEMPERATURE PROFILE, 3RD
428 RANGE TOTAL WINDING TEMP TIME IN 3RD TEMP RANGE
TRANSLIFE 2; TEMPERATURE PROFILE, 4TH
429 RANGE TOTAL WINDING TEMP TIME IN 4TH TEMP RANGE
TRANSLIFE 2; TEMPERATURE PROFILE, 5TH
430 RANGE TOTAL WINDING TEMP TIME IN 5TH TEMP RANGE
TRANSLIFE 2; TEMPERATURE PROFILE, 6TH
431 RANGE TOTAL WINDING TEMP TIME IN 6TH TEMP RANGE
TRANSLIFE 2; TEMPERATURE PROFILE, 7TH
432 RANGE TOTAL WINDING TEMP TIME IN 7TH TEMP RANGE
TRANSLIFE 2; TEMPERATURE PROFILE, 8TH
433 RANGE TOTAL WINDING TEMP TIME IN 8TH TEMP RANGE
TRANSLIFE 2; TEMPERATURE PROFILE, 9TH
434 RANGE TOTAL WINDING TEMP TIME IN 9TH TEMP RANGE
TRANSLIFE 2; TEMPERATURE PROFILE, 10TH
435 RANGE TOTAL WINDING TEMP TIME IN 10TH TEMP RANGE
TRANSLIFE 2; TEMPERATURE PROFILE, 11TH
436 RANGE TOTAL WINDING TEMP TIME IN 11TH TEMP RANGE
TRANSLIFE 2; TEMPERATURE PROFILE, 12TH
437 RANGE TOTAL WINDING TEMP TIME IN HIGHEST TEMP RANGE
TRANSLIFE 3; TEMPERATURE PROFILE, 1ST
438 RANGE TOTAL WINDING TEMP TIME IN LOWEST TEMP RANGE

111 www.qualitrolcorp.com
ANALOG INPUT
I/O
ADD DATA VARIABLE DESCRIPTION
TRANSLIFE 3; TEMPERATURE PROFILE, 2ND
439 RANGE TOTAL WINDING TEMP TIME IN 2ND TEMP RANGE
TRANSLIFE 3; TEMPERATURE PROFILE, 3RD
440 RANGE TOTAL WINDING TEMP TIME IN 3RD TEMP RANGE
TRANSLIFE 3; TEMPERATURE PROFILE, 4TH
441 RANGE TOTAL WINDING TEMP TIME IN 4TH TEMP RANGE
TRANSLIFE 3; TEMPERATURE PROFILE, 5TH
442 RANGE TOTAL WINDING TEMP TIME IN 5TH TEMP RANGE
TRANSLIFE 3; TEMPERATURE PROFILE, 6TH
443 RANGE TOTAL WINDING TEMP TIME IN 6TH TEMP RANGE
TRANSLIFE 3; TEMPERATURE PROFILE, 7TH
444 RANGE TOTAL WINDING TEMP TIME IN 7TH TEMP RANGE
TRANSLIFE 3; TEMPERATURE PROFILE, 8TH
445 RANGE TOTAL WINDING TEMP TIME IN 8TH TEMP RANGE
TRANSLIFE 3; TEMPERATURE PROFILE, 9TH
446 RANGE TOTAL WINDING TEMP TIME IN 9TH TEMP RANGE
TRANSLIFE 3; TEMPERATURE PROFILE, 10TH
447 RANGE TOTAL WINDING TEMP TIME IN 10TH TEMP RANGE
TRANSLIFE 3; TEMPERATURE PROFILE, 11TH
448 RANGE TOTAL WINDING TEMP TIME IN 11TH TEMP RANGE
TRANSLIFE 3; TEMPERATURE PROFILE, 12TH
449 RANGE TOTAL WINDING TEMP TIME IN HIGHEST TEMP RANGE
450 COOLING BANK 1 TOTAL ACTUATION COUNTS TOTAL # OF TIMES THE COOLING FANS HAVE ENGAGED
451 COOLING BANK 1 ACTUATION SETPOINT VALUE TOTAL ACTUATION COUNT SETPOINT
452 COOLING BANK 1 TOTAL SYSTEM RUN TIME TOTAL # OF HOURS THAT THE FANS HAVE BEEN ON
453 COOLING BANK 1 RUN TIME SETPOINT VALUE TOTAL RUN TIME SETPOINT
454 COOLING BANK 2 TOTAL ACTUATION COUNTS TOTAL # OF TIMES THE COOLING FANS HAVE ENGAGED
455 COOLING BANK 2 ACTUATION SETPOINT VALUE TOTAL ACTUATION COUNT SETPOINT
456 COOLING BANK 2 TOTAL SYSTEM RUN TIME TOTAL # OF HOURS THAT THE FANS HAVE BEEN ON
457 COOLING BANK 2 RUN TIME SETPOINT VALUE TOTAL RUN TIME SETPOINT
458 COOLING BANK 3 TOTAL ACTUATION COUNTS TOTAL # OF TIMES THE COOLING FANS HAVE ENGAGED
459 COOLING BANK 3 ACTUATION SETPOINT VALUE TOTAL ACTUATION COUNT SETPOINT
460 COOLING BANK 3 TOTAL SYSTEM RUN TIME TOTAL # OF HOURS THAT THE FANS HAVE BEEN ON
461 COOLING BANK 3 RUN TIME SETPOINT VALUE TOTAL RUN TIME SETPOINT
462 COOLING BANK 4 TOTAL ACTUATION COUNTS TOTAL # OF TIMES THE COOLING FANS HAVE ENGAGED
463 COOLING BANK 4 ACTUATION SETPOINT VALUE TOTAL ACTUATION COUNT SETPOINT
464 COOLING BANK 4 TOTAL SYSTEM RUN TIME TOTAL # OF HOURS THAT THE FANS HAVE BEEN ON
465 COOLING BANK 4 RUN TIME SETPOINT VALUE TOTAL RUN TIME SETPOINT
466 LTC, TAP POSITION -16 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-16)
467 LTC, TAP POSITION -15 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-15)
468 LTC, TAP POSITION -14 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-14)
469 LTC, TAP POSITION -13 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-13)
470 LTC, TAP POSITION -12 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-12)
471 LTC, TAP POSITION -11 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-11)
472 LTC, TAP POSITION -10 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-10)
473 LTC, TAP POSITION -9 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-9)
474 LTC, TAP POSITION -8 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-8)
475 LTC, TAP POSITION -7 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-7)
476 LTC, TAP POSITION -6 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-6)
477 LTC, TAP POSITION -5 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-5)
478 LTC, TAP POSITION -4 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-4)
479 LTC, TAP POSITION -3 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-3)

112 www.qualitrolcorp.com
ANALOG INPUT
I/O
ADD DATA VARIABLE DESCRIPTION
480 LTC, TAP POSITION -2 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-2)
481 LTC, TAP POSITION -1 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (-1)
482 LTC, TAP POSITION +0 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+0)
483 LTC, TAP POSITION +1 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+1)
484 LTC, TAP POSITION +2 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+2)
485 LTC, TAP POSITION +3 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+3)
486 LTC, TAP POSITION +4 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+4)
487 LTC, TAP POSITION +5 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+5)
488 LTC, TAP POSITION +6 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+6)
489 LTC, TAP POSITION +7 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+7)
490 LTC, TAP POSITION +8 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+8)
491 LTC, TAP POSITION +9 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+9)
492 LTC, TAP POSITION +10 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+10)
493 LTC, TAP POSITION +11 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+11)
494 LTC, TAP POSITION +12 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+12)
495 LTC, TAP POSITION +13 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+13)
496 LTC, TAP POSITION +14 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+14)
497 LTC, TAP POSITION +15 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+15)
498 LTC, TAP POSITION +16 TOTAL TAP COUNTS TOTAL TAP COUNTS FOR TAP POSITION (+16)
499 LTC, TAP POSITION -16 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-16)
500 LTC, TAP POSITION -15 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-15)
501 LTC, TAP POSITION -14 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-14)
502 LTC, TAP POSITION -13 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-13)
503 LTC, TAP POSITION -12 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-12)
504 LTC, TAP POSITION -11 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-11)
505 LTC, TAP POSITION -10 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-10)
506 LTC, TAP POSITION -9 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-9)
507 LTC, TAP POSITION -8 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-8)
508 LTC, TAP POSITION -7 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-7)
509 LTC, TAP POSITION -6 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-6)
510 LTC, TAP POSITION -5 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-5)
511 LTC, TAP POSITION -4 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-4)
512 LTC, TAP POSITION -3 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-3)
513 LTC, TAP POSITION -2 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-2)
514 LTC, TAP POSITION -1 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (-1)
515 LTC, TAP POSITION +0 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+0)
516 LTC, TAP POSITION +1 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+1)
517 LTC, TAP POSITION +2 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+2)
518 LTC, TAP POSITION +3 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+3)
519 LTC, TAP POSITION +4 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+4)
520 LTC, TAP POSITION +5 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+5)
521 LTC, TAP POSITION +6 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+6)
522 LTC, TAP POSITION +7 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+7)
523 LTC, TAP POSITION +8 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+8)
524 LTC, TAP POSITION +9 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+9)
525 LTC, TAP POSITION +10 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+10)

113 www.qualitrolcorp.com
ANALOG INPUT
I/O
ADD DATA VARIABLE DESCRIPTION
526 LTC, TAP POSITION +11 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+11)
527 LTC, TAP POSITION +12 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+12)
528 LTC, TAP POSITION +13 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+13)
529 LTC, TAP POSITION +14 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+14)
530 LTC, TAP POSITION +15 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+15)
531 LTC, TAP POSITION +16 TOTAL RUN TIME TOTAL RUN TIME FOR TAP POSITION (+16)
532 LTC, TOTAL MOTOR ACTUATION COUNTS TOTAL NUMBER OF MOTOR ACTUATION COUNTS
533 FIRMWARE REVISION FOR THIS 509ITM UNIT
534 INSTALLED DIGITAL SENSORS
535 SYSTEM DATE YEAR VALUE
536 SYSTEM DATE MONTH VALUE
537 SYSTEM DATE DAY VALUE
538 SYSTEM TIME HOUR VALUE
539 SYSTEM TIME MINUTE VALUE
540 SYSTEM TIME SECOND VALUE
541 TOTAL PHYSICAL NUMBER OF TAPS # OF TAPS IN LTC; E.G. 33, 17, 9
542 AMBIENT TEMPERATURE MODULE NUMBER
543 TRANSLIFE LIFE CONSUMPTION 'A' VARIABLE
544 TRANSLIFE LIFE CONSUMPTION 'B' VARIABLE
545 COOLING EXERCISER RUN TIME MINUTES FAN EXERCISER WILL RUN WHEN ACTIVE
546 COOLING EXERCISER CYCLE TIME DAYS BETWEEN EXERCISER RUN TIME BEING ACTIVE
547 COOLING EXERCISER START TIME HOUR TO BEGIN FAN EXERCISER IN MILITARY TIME
548 STARTING MONTH FOR SEASONAL SETPOINT RELAY FEATURE (1 - 12)
549 STARTING DAY FOR SEASONAL SETPOINT RELAY FEATURE (1 - 31)
550 ENDING MONTH FOR SEASONAL SETPOINT RELAY FEATURE (1 - 12)
551 ENDING DAY FOR SEASONAL SETPOINT RELAY FEATURE (1 - 31)
552 AMBIENT TEMPERATURE FORECAST SETPOINT RELAY FEATURE
553 AMBIENT TEMPERATURE THRESHOLD HOURS # OF HOURS TO EXCEED SETPOINT TO BECOME ACTIVE
ROLLING PERIOD IN HOURS TO MEASURE THRESHOLD
554 AMBIENT TEMPERATURE MEASUREMENT PERIOD TEMP
555 MODULE # MEASURING AMBIENT TEMPERATURE MODULE # IF THERE IS AN AMBIENT SENSOR
556 COOLING BANK 1 AVERAGE RUNNING CURRENT CB1 AVERAGE STEADY STATE CURRENT VALUE
557 COOLING BANK 1 AVERAGE INRUSH CURRENT CB1 AVERAGE INRUSH CURRENT VALUE
558 COOLING BANK 1 DIFFERENTIAL SETPOINT CB1 DIFFERENTIAL SETPOINT VALUE
559 COOLING BANK 1 DIFFERENTIAL HYSTERESIS CB1 DIFFERENTIAL HYSTERESIS VALUE
560 COOLING BANK 2 AVERAGE RUNNING CURRENT CB2 AVERAGE STEADY STATE CURRENT VALUE
561 COOLING BANK 2 AVERAGE INRUSH CURRENT CB2 AVERAGE INRUSH CURRENT VALUE
562 COOLING BANK 2 DIFFERENTIAL SETPOINT CB2 DIFFERENTIAL SETPOINT VALUE
563 COOLING BANK 2 DIFFERENTIAL HYSTERESIS CB2 DIFFERENTIAL HYSTERESIS VALUE
564 COOLING BANK 3 AVERAGE RUNNING CURRENT CB3 AVERAGE STEADY STATE CURRENT VALUE
565 COOLING BANK 3 AVERAGE INRUSH CURRENT CB3 AVERAGE INRUSH CURRENT VALUE
566 COOLING BANK 3 DIFFERENTIAL SETPOINT CB3 DIFFERENTIAL SETPOINT VALUE
567 COOLING BANK 3 DIFFERENTIAL HYSTERESIS CB3 DIFFERENTIAL HYSTERESIS VALUE
568 COOLING BANK 4 AVERAGE RUNNING CURRENT CB4 AVERAGE STEADY STATE CURRENT VALUE
569 COOLING BANK 4 AVERAGE INRUSH CURRENT CB4 AVERAGE INRUSH CURRENT VALUE
570 COOLING BANK 4 DIFFERENTIAL SETPOINT CB4 DIFFERENTIAL SETPOINT VALUE
571 COOLING BANK 4 DIFFERENTIAL HYSTERESIS CB4 DIFFERENTIAL HYSTERESIS VALUE

114 www.qualitrolcorp.com
ANALOG INPUT
I/O
ADD DATA VARIABLE DESCRIPTION
572 CURRENT LOOP 1 CONTROL SIGNAL VALUE OF SIGNAL CONTROLLING LOOP 1
573 CURRENT LOOP 2 CONTROL SIGNAL VALUE OF SIGNAL CONTROLLING LOOP 2
574 CURRENT LOOP 3 CONTROL SIGNAL VALUE OF SIGNAL CONTROLLING LOOP 3
575 CURRENT LOOP 4 CONTROL SIGNAL VALUE OF SIGNAL CONTROLLING LOOP 4
576 CURRENT LOOP 1 MINIMUM SCALING RANGE MINIMUM SCALING VALUE FOR CURRENT LOOP 1
577 CURRENT LOOP 2 MINIMUM SCALING RANGE MINIMUM SCALING VALUE FOR CURRENT LOOP 2
578 CURRENT LOOP 3 MINIMUM SCALING RANGE MINIMUM SCALING VALUE FOR CURRENT LOOP 3
579 CURRENT LOOP 4 MINIMUM SCALING RANGE MINIMUM SCALING VALUE FOR CURRENT LOOP 4
580 CURRENT LOOP 1 MAXIMUM SCALING RANGE MAXIMUM SCALING VALUE FOR CURRENT LOOP 1
581 CURRENT LOOP 2 MAXIMUM SCALING RANGE MAXIMUM SCALING VALUE FOR CURRENT LOOP 2
582 CURRENT LOOP 3 MAXIMUM SCALING RANGE MAXIMUM SCALING VALUE FOR CURRENT LOOP 3
583 CURRENT LOOP 4 MAXIMUM SCALING RANGE MAXIMUM SCALING VALUE FOR CURRENT LOOP 4
584 RELAY 1 AMBIENT SETPOINT VALUE AMBIENT LOOKBACK FEATURE SETPOINT
585 RELAY 2 AMBIENT SETPOINT VALUE AMBIENT LOOKBACK FEATURE SETPOINT
586 RELAY 3 AMBIENT SETPOINT VALUE AMBIENT LOOKBACK FEATURE SETPOINT
587 RELAY 4 AMBIENT SETPOINT VALUE AMBIENT LOOKBACK FEATURE SETPOINT
588 RELAY51 AMBIENT SETPOINT VALUE AMBIENT LOOKBACK FEATURE SETPOINT
589 RELAY 6 AMBIENT SETPOINT VALUE AMBIENT LOOKBACK FEATURE SETPOINT
590 RELAY 7 AMBIENT SETPOINT VALUE AMBIENT LOOKBACK FEATURE SETPOINT
591 RELAY 8 AMBIENT SETPOINT VALUE AMBIENT LOOKBACK FEATURE SETPOINT
592 RELAY 1 SEASONAL SETPOINT VALUE SEASONAL SETPOINT VALUE
593 RELAY 2 SEASONAL SETPOINT VALUE SEASONAL SETPOINT VALUE
594 RELAY 3 SEASONAL SETPOINT VALUE SEASONAL SETPOINT VALUE
595 RELAY 4 SEASONAL SETPOINT VALUE SEASONAL SETPOINT VALUE
596 RELAY 5 SEASONAL SETPOINT VALUE SEASONAL SETPOINT VALUE
597 RELAY 6 SEASONAL SETPOINT VALUE SEASONAL SETPOINT VALUE
598 RELAY 7 SEASONAL SETPOINT VALUE SEASONAL SETPOINT VALUE
599 RELAY 8 SEASONAL SETPOINT VALUE SEASONAL SETPOINT VALUE
600 RELAY 1 ACTUATION DELAY - HOURS VALUE ACTUATION DELAY - HOURS
601 RELAY 2 ACTUATION DELAY - HOURS VALUE ACTUATION DELAY - HOURS
602 RELAY 3 ACTUATION DELAY - HOURS VALUE ACTUATION DELAY - HOURS
603 RELAY 4 ACTUATION DELAY - HOURS VALUE ACTUATION DELAY - HOURS
604 RELAY 5 ACTUATION DELAY - HOURS VALUE ACTUATION DELAY - HOURS
605 RELAY 6 ACTUATION DELAY - HOURS VALUE ACTUATION DELAY - HOURS
606 RELAY 7 ACTUATION DELAY - HOURS VALUE ACTUATION DELAY - HOURS
607 RELAY 8 ACTUATION DELAY - HOURS VALUE ACTUATION DELAY - HOURS
608 RELAY 1 ACTUATION DELAY - MINUTES VALUE ACTUATION DELAY - MINUTES
609 RELAY 2 ACTUATION DELAY - MINUTES VALUE ACTUATION DELAY - MINUTES
610 RELAY 3 ACTUATION DELAY - MINUTES VALUE ACTUATION DELAY - MINUTES
611 RELAY 4 ACTUATION DELAY - MINUTES VALUE ACTUATION DELAY - MINUTES
612 RELAY 5 ACTUATION DELAY - MINUTES VALUE ACTUATION DELAY - MINUTES
613 RELAY 6 ACTUATION DELAY - MINUTES VALUE ACTUATION DELAY - MINUTES
614 RELAY 7 ACTUATION DELAY - MINUTES VALUE ACTUATION DELAY - MINUTES
615 RELAY 8 ACTUATION DELAY - MINUTES VALUE ACTUATION DELAY - MINUTES
616 RELAY 1 ACTUATION DELAY - SECONDS VALUE ACTUATION DELAY - SECONDS
617 RELAY 2 ACTUATION DELAY - SECONDS VALUE ACTUATION DELAY - SECONDS

115 www.qualitrolcorp.com
ANALOG INPUT
I/O
ADD DATA VARIABLE DESCRIPTION
618 RELAY 3 ACTUATION DELAY - SECONDS VALUE ACTUATION DELAY - SECONDS
619 RELAY 4 ACTUATION DELAY - SECONDS VALUE ACTUATION DELAY - SECONDS
620 RELAY 5 ACTUATION DELAY - SECONDS VALUE ACTUATION DELAY - SECONDS
621 RELAY 6 ACTUATION DELAY - SECONDS VALUE ACTUATION DELAY - SECONDS
622 RELAY 7 ACTUATION DELAY - SECONDS VALUE ACTUATION DELAY - SECONDS
623 RELAY 8 ACTUATION DELAY - SECONDS VALUE ACTUATION DELAY - SECONDS
624 LTC PREVIOUS MOTOR RUN CURRENT MOTOR RUN CURRENT FROM LAST ACTUATION
625 LTC PREVIOUS MOTOR INRUSH CURRENT MOTOR INRUSH CURRENT FROM LAST ACTUATION
626 LTC PREVIOUS MOTOR RUN TIME MOTOR ACTUATION TIME FROM LAST ACTUATION
627 LTC HI-ALARM DIFFERENTIAL SETPOINT VALUE DIFFERENTIAL SETPOINT VALUE FOR HI-ALARM
628 LTC HI-ALARM DIFFERENTIAL HYSTERSIS VALUE DIFFERENTIAL HYSTERESIS VALUE FOR HI-ALARM
629 LTC LO-ALARM DIFFERENTIAL SETPOINT VALUE DIFFERENTIAL SETPOINT VALUE FOR LO-ALARM
630 LTC LO-ALARM DIFFERENTIAL HYSTERSIS VALUE DIFFERENTIAL HYSTERESIS VALUE FOR LO-ALARM
631 LTC HI-ALARM MOTOR RUN TIME SETPOINT MOTOR RUN TIME SETPOINT FOR HI-ALARM
632 LTC LO-ALARM MOTOR RUN TIME SETPOINT MOTOR RUN TIME SETPOINT FOR LO-ALARM
633 LTC MODULE CONFIGURATION
634 LTC HI-ALARM CONFIGURATION
635 LTC LO-ALARM CONFIGURATION
ALL MODULES BUT CT, WINDING TEMPERATURE IF THE MODULE IS A CT, WINDING TEMPERATURE
636 INPUT MODULE 9 PRESENT VALUE OR INPUT MODULE 9 PRESENT WINDING TEMP
637 INPUT MODULE 9 MINIMUM VALUE OR INPUT MODULE 9 MINIMUM WINDING TEMP
638 INPUT MODULE 9 MAXIMUM VALUE OR INPUT MODULE 9 MAXIMUM WINDING TEMP
639 0 OR INPUT MODULE 9 PRESENT CURRENT
640 0 OR INPUT MODULE 9 MAXIMUM CURRENT
641 INPUT MODULE 10 PRESENT VALUE OR INPUT MODULE 10 PRESENT WINDING TEMP
642 INPUT MODULE 10 MINIMUM VALUE OR INPUT MODULE 10 MINIMUM WINDING TEMP
643 INPUT MODULE 10 MAXIMUM VALUE OR INPUT MODULE 10 MAXIMUM WINDING TEMP
644 0 OR INPUT MODULE 10 PRESENT CURRENT
645 0 OR INPUT MODULE 10 MAXIMUM CURRENT
646 INPUT MODULE 11 PRESENT VALUE OR INPUT MODULE 11 PRESENT WINDING TEMP
647 INPUT MODULE 11 MINIMUM VALUE OR INPUT MODULE 11 MINIMUM WINDING TEMP
648 INPUT MODULE 11 MAXIMUM VALUE OR INPUT MODULE 11 MAXIMUM WINDING TEMP
649 0 OR INPUT MODULE 11 PRESENT CURRENT
650 0 OR INPUT MODULE 11 MAXIMUM CURRENT
651 INPUT MODULE 12 PRESENT VALUE OR INPUT MODULE 12 PRESENT WINDING TEMP
652 INPUT MODULE 12 MINIMUM VALUE OR INPUT MODULE 12 MINIMUM WINDING TEMP
653 INPUT MODULE 12 MAXIMUM VALUE OR INPUT MODULE 12 MAXIMUM WINDING TEMP
654 0 OR INPUT MODULE 12 PRESENT CURRENT
655 0 OR INPUT MODULE 12 MAXIMUM CURRENT
656 INPUT MODULE 13 PRESENT VALUE OR INPUT MODULE 13 PRESENT WINDING TEMP
657 INPUT MODULE 13 MINIMUM VALUE OR INPUT MODULE 13 MINIMUM WINDING TEMP
658 INPUT MODULE 13 MAXIMUM VALUE OR INPUT MODULE 13 MAXIMUM WINDING TEMP
659 0 OR INPUT MODULE 13 PRESENT CURRENT
660 0 OR INPUT MODULE 13 MAXIMUM CURRENT
661 INPUT MODULE 14 PRESENT VALUE OR INPUT MODULE 14 PRESENT WINDING TEMP
662 INPUT MODULE 14 MINIMUM VALUE OR INPUT MODULE 14 MINIMUM WINDING TEMP

116 www.qualitrolcorp.com
ANALOG INPUT
I/O
ADD DATA VARIABLE DESCRIPTION
663 INPUT MODULE 14 MAXIMUM VALUE OR INPUT MODULE 14 MAXIMUM WINDING TEMP
664 0 OR INPUT MODULE 14 PRESENT CURRENT
665 0 OR INPUT MODULE 14 MAXIMUM CURRENT
666 INPUT MODULE 15 PRESENT VALUE OR INPUT MODULE 15 PRESENT WINDING TEMP
667 INPUT MODULE 15 MINIMUM VALUE OR INPUT MODULE 15 MINIMUM WINDING TEMP
668 INPUT MODULE 15 MAXIMUM VALUE OR INPUT MODULE 15 MAXIMUM WINDING TEMP
669 0 OR INPUT MODULE 15 PRESENT CURRENT
670 0 OR INPUT MODULE 15 MAXIMUM CURRENT
671 INPUT MODULE 16 PRESENT VALUE OR INPUT MODULE 16 PRESENT WINDING TEMP
672 INPUT MODULE 16 MINIMUM VALUE OR INPUT MODULE 16 MINIMUM WINDING TEMP
673 INPUT MODULE 16 MAXIMUM VALUE OR INPUT MODULE 16 MAXIMUM WINDING TEMP
674 0 OR INPUT MODULE 16 PRESENT CURRENT
675 0 OR INPUT MODULE 16 MAXIMUM CURRENT
676 RELAY 1 ACTUATION COUNTS ACTUATION COUNTER FOR RELAY 1
677 RELAY 2 ACTUATION COUNTS ACTUATION COUNTER FOR RELAY 2
678 RELAY 3 ACTUATION COUNTS ACTUATION COUNTER FOR RELAY 3
679 RELAY 4 ACTUATION COUNTS ACTUATION COUNTER FOR RELAY 4
680 RELAY 5 ACTUATION COUNTS ACTUATION COUNTER FOR RELAY 5
681 RELAY 6 ACTUATION COUNTS ACTUATION COUNTER FOR RELAY 6
682 RELAY 7 ACTUATION COUNTS ACTUATION COUNTER FOR RELAY 7
683 RELAY 8 ACTUATION COUNTS ACTUATION COUNTER FOR RELAY 8
684 DGA HYDROGEN SENSOR 1 PRESENT VALUE PRESENT VALUE OF DGA H2 SENSOR # 1
685 DGA HYDROGEN SENSOR 1 MINIMUM VALUE MINIMUM VALUE OF DGA H2 SENSOR # 1
686 DGA HYDROGEN SENSOR 1 MAXIMUM VALUE MAXIMUM VALUE OF DGA H2 SENSOR # 1
687 DGA HYDROGEN SENSOR 2 PRESENT VALUE PRESENT VALUE OF DGA H2 SENSOR # 2
688 DGA HYDROGEN SENSOR 2 MINIMUM VALUE MINIMUM VALUE OF DGA H2 SENSOR # 2
689 DGA HYDROGEN SENSOR 2 MAXIMUM VALUE MAXIMUM VALUE OF DGA H2 SENSOR # 2
690 DGA HYDROGEN SENSOR 3 PRESENT VALUE PRESENT VALUE OF DGA H2 SENSOR # 3
691 DGA HYDROGEN SENSOR 3 MINIMUM VALUE MINIMUM VALUE OF DGA H2 SENSOR # 3
692 DGA HYDROGEN SENSOR 3 MAXIMUM VALUE MAXIMUM VALUE OF DGA H2 SENSOR # 3
693 TRANSFORMER LIFE SPAN YEARS ENTERED BY CUSTOMER FOR TRANSFORMER LIFE

ANALOG OUTPUTS
I/O
ADD DATA VARIABLE DESCRIPTION
700 RELAY 1, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
701 RELAY 2, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
702 RELAY 3, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
703 RELAY 4, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
704 RELAY 5, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
705 RELAY 6, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
706 RELAY 7, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
707 RELAY 8, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
708 RELAY 1, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
709 RELAY 2, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
710 RELAY 3, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX

117 www.qualitrolcorp.com
ANALOG OUTPUTS
I/O
ADD DATA VARIABLE DESCRIPTION
711 RELAY 4, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
712 RELAY 5, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
713 RELAY 6, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
714 RELAY 7, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
715 RELAY 8, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
716 RELAY 1, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
717 RELAY 2, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
718 RELAY 3, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
719 RELAY 4, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
720 RELAY 5, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
721 RELAY 6, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
722 RELAY 7, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
723 RELAY 8, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
724 RELAY 1, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
725 RELAY 2, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
726 RELAY 3, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
727 RELAY 4, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
728 RELAY 5, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
729 RELAY 6, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
730 RELAY 7, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
731 RELAY 8, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
732 RELAY 1, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
733 RELAY 2, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
734 RELAY 3, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
735 RELAY 4, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
736 RELAY 5, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
737 RELAY 6, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
738 RELAY 7, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
739 RELAY 8, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
740 RELAY 1, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
741 RELAY 2, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
742 RELAY 3, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
743 RELAY 4, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
744 RELAY 5, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
745 RELAY 6, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
746 RELAY 7, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
747 RELAY 8, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
748 RELAY 1, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
749 RELAY 2, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
750 RELAY 3, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
751 RELAY 4, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
752 RELAY 5, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
753 RELAY 6, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
754 RELAY 7, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
755 RELAY 8, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
756 RELAY 1, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX

118 www.qualitrolcorp.com
ANALOG OUTPUTS
I/O
ADD DATA VARIABLE DESCRIPTION
757 RELAY 2, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
758 RELAY 3, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
759 RELAY 4, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
760 RELAY 5, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
761 RELAY 6, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
762 RELAY 7, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
763 RELAY 8, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
764 TL1 CRITICAL WINDING TEMP SETPOINT 1 1ST CRITICAL SPT TO CALCULATE TIME TO REACH
765 TL1 CRITICAL WINDING TEMP SETPOINT 2 2ND CRITICAL SPT TO CALCULATE TIME TO REACH
766 TL1 CRITICAL WINDING TEMP SETPOINT 3 3RD CRITICAL SPT TO CALCULATE TIME TO REACH
767 TL2 CRITICAL WINDING TEMP SETPOINT 1 1ST CRITICAL SPT TO CALCULATE TIME TO REACH
768 TL2 CRITICAL WINDING TEMP SETPOINT 2 2ND CRITICAL SPT TO CALCULATE TIME TO REACH
769 TL2 CRITICAL WINDING TEMP SETPOINT 3 3RD CRITICAL SPT TO CALCULATE TIME TO REACH
770 TL3 CRITICAL WINDING TEMP SETPOINT 1 1ST CRITICAL SPT TO CALCULATE TIME TO REACH
771 TL3 CRITICAL WINDING TEMP SETPOINT 2 2ND CRITICAL SPT TO CALCULATE TIME TO REACH
772 TL3 CRITICAL WINDING TEMP SETPOINT 3 3RD CRITICAL SPT TO CALCULATE TIME TO REACH
773 CB1 RUNNING CURRENT UPPER SETPOINT COOLING BANK 1 STEADY STATE CURRENT SETPOINT
774 CB1 RUNNING CURRENT LOWER SETPOINT COOLING BANK 1 STEADY STATE CURRENT SETPOINT
775 CB1 INRUSH CURRENT UPPER SETPOINT VALUE COOLING BANK 1 PEAK INRUSH CURRENT SETPOINT
776 CB1 INRUSH CURRENT LOWER SETPOINT VALUE COOLING BANK 1 PEAK INRUSH CURRENT SETPOINT
777 COOLING BANK 1 ACTUATION SETPOINT VALUE TOTAL ACTUATION COUNT SETPOINT
778 COOLING BANK 1 RUN TIME SETPOINT VALUE COOLING BANK 1 TOTAL RUN TIME SETPOINT
779 CB2 RUNNING CURRENT UPPER SETPOINT COOLING BANK 2 STEADY STATE CURRENT SETPOINT
780 CB2 RUNNING CURRENT LOWER SETPOINT COOLING BANK 2 STEADY STATE CURRENT SETPOINT
781 CB2 INRUSH CURRENT UPPER SETPOINT VALUE COOLING BANK 2 PEAK INRUSH CURRENT SETPOINT
782 CB2 INRUSH CURRENT LOWER SETPOINT VALUE COOLING BANK 2 PEAK INRUSH CURRENT SETPOINT
783 COOLING BANK 2 ACTUATION SETPOINT VALUE TOTAL ACTUATION COUNT SETPOINT
784 COOLING BANK 2 RUN TIME SETPOINT VALUE COOLING BANK 2 TOTAL RUN TIME SETPOINT
785 CB3 RUNNING CURRENT UPPER SETPOINT COOLING BANK 3 STEADY STATE CURRENT SETPOINT
786 CB3 RUNNING CURRENT LOWER SETPOINT COOLING BANK 3 STEADY STATE CURRENT SETPOINT
787 CB3 INRUSH CURRENT UPPER SETPOINT VALUE COOLING BANK 3 PEAK INRUSH CURRENT SETPOINT
788 CB3 INRUSH CURRENT LOWER SETPOINT VALUE COOLING BANK 3 PEAK INRUSH CURRENT SETPOINT
789 COOLING BANK 3 ACTUATION SETPOINT VALUE TOTAL ACTUATION COUNT SETPOINT
790 COOLING BANK 3 RUN TIME SETPOINT VALUE COOLING BANK 3 TOTAL RUN TIME SETPOINT
791 CB4 RUNNING CURRENT UPPER SETPOINT COOLING BANK 4 STEADY STATE CURRENT SETPOINT
792 CB4 RUNNING CURRENT LOWER SETPOINT COOLING BANK 4 STEADY STATE CURRENT SETPOINT
793 CB4 INRUSH CURRENT UPPER SETPOINT VALUE COOLING BANK 4 PEAK INRUSH CURRENT SETPOINT
794 CB4 INRUSH CURRENT LOWER SETPOINT VALUE COOLING BANK 4 PEAK INRUSH CURRENT SETPOINT
795 COOLING BANK 4 ACTUATION SETPOINT VALUE TOTAL ACTUATION COUNT SETPOINT
796 COOLING BANK 4 RUN TIME SETPOINT VALUE COOLING BANK 4 TOTAL RUN TIME SETPOINT
797 LTC HI-ALARM RUN CURRENT UPPER SETPOINT LTC HIGH-PRIORITY STEADY STATE UPPER SETPOINT
798 LTC LO-ALARM RUN CURRENT UPPER SETPOINT LTC LOW-PRIORITY STEADY STATE UPPER SETPOINT
799 LTC HI-ALARM RUN CURRENT LOWER SETPOINT LTC HIGH-PRIORITY STEADY STATE LOWER SETPOINT
800 LTC LO-ALARM RUN CURRENT LOWER SETPOINT LTC LOW-PRIORITY STEADY STATE LOWER SETPOINT
LTC HIGH-PRIORITY INRUSH CURRENT UPPER
801 LTC HI-ALARM INRUSH CURRENT UPPER SETPOINT SETPOINT
802 LTC LO-ALARM INRUSH CURRENT UPPER SETPOINT LTC LOW-PRIORITY INRUSH CURRENT UPPER SETPOINT

119 www.qualitrolcorp.com
ANALOG OUTPUTS
I/O
ADD DATA VARIABLE DESCRIPTION
LTC HIGH-PRIORITY INRUSH CURRENT LOWER
803 LTC HI-ALARM INRUSH CURRENT LOWER SETPOINT SETPOINT
LTC LOW-PRIORITY INRUSH CURRENT LOWER
804 LTC LO-ALARM INRUSH CURRENT LOWER SETPOINT SETPOINT
805 LTC HI-ALARM TOTAL TAP COUNT SETPOINT VALUE LTC HIGH-PRIORITY TOTAL TAP COUNT SETPOINT
806 LTC LO-ALARM TOTAL TAP COUNT SETPOINT VALUE LTC LOW-PRIORITY TOTAL TAP COUNT SETPOINT
LTC HI-ALARM MOTOR ACTUATION SETPOINT
807 VALUE LTC HIGH-PRIORITY MOTOR ACTUATION COUNT SPT
LTC LO-ALARM MOTOR ACTUATION SETPOINT
808 VALUE LTC LOW-PRIORITY MOTOR ACTUATION COUNT SPT
809 LTC HI-ALARM TOTAL RUN TIME SETPOINT VALUE LTC HIGH-PRIORITY TOTAL RUN TIME SETPOINT
810 LTC LO-ALARM TOTAL RUN TIME SETPOINT VALUE LTC LOW-PRIORITY TOTAL RUN TIME SETPOINT
811 COOLING BANK 1 DIFFERENTIAL SETPOINT CB1 DIFFERENTIAL SETPOINT VALUE
812 COOLING BANK 1 DIFFERENTIAL HYSTERESIS CB1 DIFFERENTIAL HYSTERESIS VALUE
813 COOLING BANK 2 DIFFERENTIAL SETPOINT CB2 DIFFERENTIAL SETPOINT VALUE
814 COOLING BANK 2 DIFFERENTIAL HYSTERESIS CB2 DIFFERENTIAL HYSTERESIS VALUE
815 COOLING BANK 3 DIFFERENTIAL SETPOINT CB3 DIFFERENTIAL SETPOINT VALUE
816 COOLING BANK 3 DIFFERENTIAL HYSTERESIS CB3 DIFFERENTIAL HYSTERESIS VALUE
817 COOLING BANK 4 DIFFERENTIAL SETPOINT CB4 DIFFERENTIAL SETPOINT VALUE
818 COOLING BANK 4 DIFFERENTIAL HYSTERESIS CB4 DIFFERENTIAL HYSTERESIS VALUE
819 RELAY 1 AMBIENT SETPOINT VALUE AMBIENT LOOKBACK FEATURE SETPOINT
820 RELAY 2 AMBIENT SETPOINT VALUE AMBIENT LOOKBACK FEATURE SETPOINT
821 RELAY 3 AMBIENT SETPOINT VALUE AMBIENT LOOKBACK FEATURE SETPOINT
822 RELAY 4 AMBIENT SETPOINT VALUE AMBIENT LOOKBACK FEATURE SETPOINT
823 RELAY51 AMBIENT SETPOINT VALUE AMBIENT LOOKBACK FEATURE SETPOINT
824 RELAY 6 AMBIENT SETPOINT VALUE AMBIENT LOOKBACK FEATURE SETPOINT
825 RELAY 7 AMBIENT SETPOINT VALUE AMBIENT LOOKBACK FEATURE SETPOINT
826 RELAY 8 AMBIENT SETPOINT VALUE AMBIENT LOOKBACK FEATURE SETPOINT
827 RELAY 1 SEASONAL SETPOINT VALUE SEASONAL SETPOINT VALUE
828 RELAY 2 SEASONAL SETPOINT VALUE SEASONAL SETPOINT VALUE
829 RELAY 3 SEASONAL SETPOINT VALUE SEASONAL SETPOINT VALUE
830 RELAY 4 SEASONAL SETPOINT VALUE SEASONAL SETPOINT VALUE
831 RELAY 5 SEASONAL SETPOINT VALUE SEASONAL SETPOINT VALUE
832 RELAY 6 SEASONAL SETPOINT VALUE SEASONAL SETPOINT VALUE
833 RELAY 7 SEASONAL SETPOINT VALUE SEASONAL SETPOINT VALUE
834 RELAY 8 SEASONAL SETPOINT VALUE SEASONAL SETPOINT VALUE
835 LTC HI-ALARM DIFFERENTIAL SETPOINT VALUE DIFFERENTIAL SETPOINT VALUE FOR HI-ALARM
836 LTC HI-ALARM DIFFERENTIAL HYSTERSIS VALUE DIFFERENTIAL HYSTERESIS VALUE FOR HI-ALARM
837 LTC LO-ALARM DIFFERENTIAL SETPOINT VALUE DIFFERENTIAL SETPOINT VALUE FOR LO-ALARM
838 LTC LO-ALARM DIFFERENTIAL HYSTERSIS VALUE DIFFERENTIAL HYSTERESIS VALUE FOR LO-ALARM
839 LTC HI-ALARM MOTOR RUN TIME SETPOINT MOTOR RUN TIME SETPOINT FOR HI-ALARM
840 LTC LO-ALARM MOTOR RUN TIME SETPOINT MOTOR RUN TIME SETPOINT FOR LO-ALARM

INTEGRATED TOTALS
I/O
ADD DATA VARIABLE DESCRIPTION
TRANSLIFE 1; TRANSFORMER LIFE
1000 CONSUMPTION TOTAL LIFE CONSUMPTION CALCULATED; TRANSLIFE 1
TRANSLIFE 2; TRANSFORMER LIFE
1001 CONSUMPTION TOTAL LIFE CONSUMPTION CALCULATED; TRANSLIFE 2

120 www.qualitrolcorp.com
INTEGRATED TOTALS
I/O
ADD DATA VARIABLE DESCRIPTION
TRANSLIFE 3; TRANSFORMER LIFE
1002 CONSUMPTION TOTAL LIFE CONSUMPTION CALCULATED; TRANSLIFE 3
1003 TOTAL TRANSFORMER OPERATING HOURS CUMULATIVE TRANSFORMER OPERATING HOURS
1004 COOLING BANK 1 ACTUATION SETPOINT VALUE TOTAL ACTUATION COUNT SETPOINT
1005 COOLING BANK 1 RUN TIME SETPOINT VALUE COOLING BANK 1 TOTAL RUN TIME SETPOINT
1006 COOLING BANK 2 ACTUATION SETPOINT VALUE TOTAL ACTUATION COUNT SETPOINT
1007 COOLING BANK 2 RUN TIME SETPOINT VALUE COOLING BANK 2 TOTAL RUN TIME SETPOINT
1008 COOLING BANK 3 ACTUATION SETPOINT VALUE TOTAL ACTUATION COUNT SETPOINT
1009 COOLING BANK 3 RUN TIME SETPOINT VALUE COOLING BANK 3 TOTAL RUN TIME SETPOINT
1010 COOLING BANK 4 ACTUATION SETPOINT VALUE TOTAL ACTUATION COUNT SETPOINT
1011 COOLING BANK 4 RUN TIME SETPOINT VALUE COOLING BANK 4 TOTAL RUN TIME SETPOINT
1012 LTC HI-ALARM TOTAL TAP COUNT SETPOINT LTC HIGH-PRIORITY TOTAL TAP COUNT SETPOINT
1013 LTC LO-ALARM TOTAL TAP COUNT SETPOINT LTC LOW-PRIORITY TOTAL TAP COUNT SETPOINT
1014 LTC HI-ALARM TOTAL RUN TIME SETPOINT LTC HIGH-PRIORITY TOTAL RUN TIME SETPOINT
1015 LTC LO-ALARM TOTAL RUN TIME SETPOINT LTC LOW-PRIORITY TOTAL RUN TIME SETPOINT
1016 LTC HI-ALARM MOTOR ACTUATION SETPOINT LTC HIGH-PRIORITY MOTOR ACTUATION COUNT SETPOINT
1017 LTC LO-ALARM MOTOR ACTUATION SETPOINT LTC LOW-PRIORITY MOTOR ACTUATION COUNT SETPOINT

BINARY INPUT
I/O
ADD DATA VARIABLE DESCRIPTION
1100 RELAY 9 ENABLED 1 = ENABLED; 0 = DISABLED
1101 RELAY 10 ENABLED 1 = ENABLED; 0 = DISABLED
1102 RELAY 11 ENABLED 1 = ENABLED; 0 = DISABLED
1103 RELAY 12 ENABLED 1 = ENABLED; 0 = DISABLED
1104 RELAY 13 ENABLED 1 = ENABLED; 0 = DISABLED
1105 RELAY 14 ENABLED 1 = ENABLED; 0 = DISABLED
1106 RELAY 15 ENABLED 1 = ENABLED; 0 = DISABLED
1107 RELAY 16 ENABLED 1 = ENABLED; 0 = DISABLED
1108 INPUT MODULE 9 READ ERROR 1 = READ ERROR; 0 = VALID READ
1109 INPUT MODULE 10 READ ERROR 1 = READ ERROR; 0 = VALID READ
1110 INPUT MODULE 11 READ ERROR 1 = READ ERROR; 0 = VALID READ
1111 INPUT MODULE 12 READ ERROR 1 = READ ERROR; 0 = VALID READ
1112 INPUT MODULE 13 READ ERROR 1 = READ ERROR; 0 = VALID READ
1113 INPUT MODULE 14 READ ERROR 1 = READ ERROR; 0 = VALID READ
1114 INPUT MODULE 15 READ ERROR 1 = READ ERROR; 0 = VALID READ
1115 INPUT MODULE 16 READ ERROR 1 = READ ERROR; 0 = VALID READ
1116 INPUT MODULE 9 CUSTOM SCALING 1 = ENABLED; 0 = DISABLED
1117 INPUT MODULE 10 CUSTOM SCALING 1 = ENABLED; 0 = DISABLED
1118 INPUT MODULE 11 CUSTOM SCALING 1 = ENABLED; 0 = DISABLED
1119 INPUT MODULE 12 CUSTOM SCALING 1 = ENABLED; 0 = DISABLED
1120 INPUT MODULE 13 CUSTOM SCALING 1 = ENABLED; 0 = DISABLED
1121 INPUT MODULE 14 CUSTOM SCALING 1 = ENABLED; 0 = DISABLED
1122 INPUT MODULE 15 CUSTOM SCALING 1 = ENABLED; 0 = DISABLED
1123 INPUT MODULE 16 CUSTOM SCALING 1 = ENABLED; 0 = DISABLED

BINARY OUTPUT

121 www.qualitrolcorp.com
I/O
ADD DATA VARIABLE DESCRIPTION
1150 RELAY 9 ENABLED 1 = ENABLED; 0 = DISABLED
1151 RELAY 10 ENABLED 1 = ENABLED; 0 = DISABLED
1152 RELAY 11 ENABLED 1 = ENABLED; 0 = DISABLED
1153 RELAY 12 ENABLED 1 = ENABLED; 0 = DISABLED
1154 RELAY 13 ENABLED 1 = ENABLED; 0 = DISABLED
1155 RELAY 14 ENABLED 1 = ENABLED; 0 = DISABLED
1156 RELAY 15 ENABLED 1 = ENABLED; 0 = DISABLED
1157 RELAY 16 ENABLED 1 = ENABLED; 0 = DISABLED

ANALOG OUTPUTS
I/O
ADD DATA VARIABLE DESCRIPTION
1200 RELAY 1 RATE OF CHANGE DYNAMIC RATE OF CHANGE VALUE FOR COLUMN 1
1201 RELAY 2 RATE OF CHANGE DYNAMIC RATE OF CHANGE VALUE FOR COLUMN 1
1202 RELAY 3 RATE OF CHANGE DYNAMIC RATE OF CHANGE VALUE FOR COLUMN 1
1203 RELAY 4 RATE OF CHANGE DYNAMIC RATE OF CHANGE VALUE FOR COLUMN 1
1204 RELAY 5 RATE OF CHANGE DYNAMIC RATE OF CHANGE VALUE FOR COLUMN 1
1205 RELAY 6 RATE OF CHANGE DYNAMIC RATE OF CHANGE VALUE FOR COLUMN 1
1206 RELAY 7 RATE OF CHANGE DYNAMIC RATE OF CHANGE VALUE FOR COLUMN 1
1207 RELAY 8 RATE OF CHANGE DYNAMIC RATE OF CHANGE VALUE FOR COLUMN 1

122 www.qualitrolcorp.com
IEC 61850 COMMUNICATIONS
Introduction
IEC 61850 is an Ethernet protocol therefore to function properly the 509ITM must have the Ethernet
option installed on the device. Once verifying that the Ethernet is installed then the communication
port must be configured through the ITM Manager Software Suite. Start the software and enter the
Customer-Setup section. In the Customer-Setup click on the Communications button and see the
following window.

123 www.qualitrolcorp.com
Select the Ethernet tab and enter the IP Address, Subnet Mask and the Gateway addresses.

124 www.qualitrolcorp.com
Click on the IEC 61850 tab to see the following window.

125 www.qualitrolcorp.com
Enter the passwords if required. To configure the client for IEC 61850 reference the following
documents:
IST-100-2 509ITM Model Implementation Conformance Statement
IST-100-6 509ITM Devices Organization

126 www.qualitrolcorp.com
QUALITROL® Field Services
QUALITROL® provides on-site commissioning/ start-up and comprehensive maintenance contracts to all customers
worldwide. To further improve reliability, an extended warranty is available on selected products commissioned by
QUALITROL®.
QUALITROL® Educational Services
®
QUALITROL professional training (designed to achieve hands-on performance based objectives) prepares operations,
maintenance, and engineering personnel to install, test, configure, operate and maintain QUALITROL® products.
QUALITROL® Accelerated Delivery
®
QUALITROL provides accelerated delivery on many products and services including replacements, spare parts and
repairs.

About Qualitrol:
Qualitrol manufactures substation and transformer monitoring and protection devices used by electric utilities and
manufacturing companies. It is the global leader in sales and installations of transformer asset protection equipment, fault
recorders and fault locators. Established in 1945, Qualitrol produces thousands of different types of products on demand,
each customized to customers' unique requirements.
©2008 QUALITROL Company LLC, an ISO 9001 system certified company. All rights reserved. Information subject to change without notice.
®

All trademarks are properties of their respective companies, as noted herein. IST-099-1.

127 www.qualitrolcorp.com