You are on page 1of 17

COPYRIGHT:

NO PART OF THIS DOCUMENT


MAY BE REPRODUCED IN ANY
FORM INCUDING PHOTOCOPY,
RECORDING OR ANY INFORMATION
RETRIEVABLE AND STORAGE
SYSTEM, WITHOUT WRITTEN
PERMISSION FROM AQUATIC
TECHNOLOGY POOL & SPA.

DISCLAIMER:
NOT FOR CONSTRUCTION
WITHOUT GEOTECHNICAL
INVESTIGATION AND
STRUCTURAL ENGINEERING,
TO BE PROVIDED BY OTHER
PARTIES.

P.O. Box 130 - Morgan Hill Ca. 95038


Tel. 408-776-8220, Fax 408-776-3112
Ca. Lic. No. 721117, B, C53

APN #:----
PAGE 1 COVER PAGE

TITLE:
PAGE 2 SITE PLAN
PAGE 3 ENLARGED SITE PLAN

Tel. 408-776-8220, Fax 408-776-3112


P.O. Box 130 - Morgan Hill Ca. 95038
PAGE 4 POOL LAYOUT

www.aquatictechnology.com
Ca. Lic. No. 721117, B, C53
PAGE 5 POOL SECTIONS
PAGE 6 SPA SECTION PIPING DETAILS
PAGE 7 POOL PIPING DIAGRAMS (1)
PAGE 8 POOL PIPING DIAGRAMS (2)
PAGE 9 POOL PIPING DIAGRAMS (3
PAGE 10 POOL / SPA LIGHTING
PAGE 11 GENERAL DETAILS (1) NO VALID COPYRIGHT
& NOT FOR CONSTRUCTION
OR PERMITTING WITHOUT

PAGE 12 SYSTEM SCHEMATIC/ EQ LAYOUT


EMBOSSED S.W.D. SEAL,
BY PAOLO BENEDETTI

PAGE 13 AUTOMATION SCHEMATIC / POOL BONDING


PAGE 14 EQUIPMENT ROOM LAYOUT REVISIONS:

PAGE 15 GENERAL NOTES (1)


PAGE 16 GENERAL NOTES (2)
PAGE 17 GENERAL NOTES (3)

DATE:
09/17/2020
SCALE:
AS NOTED
DRN:
M. KRAWCZYK
APPROVED:
PAUL BENEDETTI
DRAWING NO.
09-17-2020 NORRIS

SHEET

COVER PAGE

1 OF 17 SHEETS
COPYRIGHT:
NO PART OF THIS DOCUMENT
MAY BE REPRODUCED IN ANY
FORM INCUDING PHOTOCOPY,
RECORDING OR ANY INFORMATION
RETRIEVABLE AND STORAGE
SYSTEM, WITHOUT WRITTEN
PERMISSION FROM AQUATIC
TECHNOLOGY POOL & SPA.

DISCLAIMER:
NOT FOR CONSTRUCTION
WITHOUT GEOTECHNICAL
INVESTIGATION AND
STRUCTURAL ENGINEERING,
TO BE PROVIDED BY OTHER
PARTIES.

Evan Manor Ln
(24' BC/BC - 50' R/W)
Sewer Line

1180
70.10 CO
S 64°35'03"E

7
.4

APN #:----
31

TITLE:
28.9' 29.1' Water Quality
Easement (21')

20' BSL

29.0' 20.6'

Tel. 408-776-8220, Fax 408-776-3112


P.O. Box 130 - Morgan Hill Ca. 95038
40.5'

17.5'

www.aquatictechnology.com
PENTAIR BIOGUARD UV

Ca. Lic. No. 721117, B, C53


CT120

TREATMENT
0ZONE/UV

PUMP
GENERATOR
OXYGEN

3"
FEATURE

108.78
WATER

PUMP

4"
4"
SPA JET
PUMP

4"
42.5'

4:1 RATIO

CHL
ACID
FILTER
PUMP
Lions Gate Dr

3"

S 25°24'57"W
2.5"

FILTER
JANDY
CV580

2.5"

5' BSL
SOLAR
TO
SOLAR
FROM
N 25°24'57"E

20' BSL
87.21

POLARIS QT

BLOWER
2HP AIR

2.5"

BOOSTER PUMP
HAYWARD
2.5"
2.5"
NAT GAS
HEATER
JANDY
40.5'

( 50' R/W) 28.9' 3.2'


20.6'

8.6'
20.0'
13.4' 13.2'

4.5'
20.1' 10.5'
25' BSL
45.4' 23.0' NO VALID COPYRIGHT
42.8' 37.5' & NOT FOR CONSTRUCTION
OR PERMITTING WITHOUT
20.1' EMBOSSED S.W.D. SEAL,
BY PAOLO BENEDETTI
19.3'

9.50 18.0'

REVISIONS:

En
tra N 69°33'37"W
90.14 1190
nc
e
sig mo
n nu
m
en
t

Fence
Line

Right of Way

Power Pole
50.0

R d
DATE:

Bu f o rd D a m 09/17/2020
SCALE:
AS NOTED
(100'R/W) DRN:
M. KRAWCZYK
APPROVED:
PAUL BENEDETTI
DRAWING NO.
09-17-2020 NORRIS

SHEET

SITE PLAN
SITE PLAN SCALE: N.T.S.

2 OF 17 SHEETS
COPYRIGHT:
NO PART OF THIS DOCUMENT

TREATMENT
0ZONE/UV
MAY BE REPRODUCED IN ANY

PUMP
GENERATOR
FORM INCUDING PHOTOCOPY,

OXYGEN
RECORDING OR ANY INFORMATION
RETRIEVABLE AND STORAGE
SYSTEM, WITHOUT WRITTEN
PERMISSION FROM AQUATIC

3"
TECHNOLOGY POOL & SPA.

FEATURE
WATER

PUMP

4"
DISCLAIMER:
NOT FOR CONSTRUCTION

4"
WITHOUT GEOTECHNICAL

SPA JET
PUMP
INVESTIGATION AND

4"
STRUCTURAL ENGINEERING,

42.5'
TO BE PROVIDED BY OTHER
PARTIES.

4:1 RATIO

CHL
ACID
FILTER
PUMP

3"
2.5"

FILTER
JANDY
CV580

2.5"
SOLAR
TO
SOLAR
FROM
N 25°24'57"E

20' BSL

POLARIS QT

BLOWER
2HP AIR

2.5"

APN #:----
BOOSTER PUMP
HAYWARD
2.5"
2.5"

TITLE:
NAT GAS
HEATER
JANDY

Tel. 408-776-8220, Fax 408-776-3112


P.O. Box 130 - Morgan Hill Ca. 95038
40.5'

www.aquatictechnology.com
Ca. Lic. No. 721117, B, C53
20.6'
28.9' 3.2'
8.6' NO VALID COPYRIGHT

20.0'
& NOT FOR CONSTRUCTION
OR PERMITTING WITHOUT
EMBOSSED S.W.D. SEAL,
BY PAOLO BENEDETTI

13.4' 13.2'
REVISIONS:

4.5'
20.1' 10.5'
25' BSL
45.4' 23.0'
42.8' 37.5'
DATE:
09/17/2020
SCALE:
AS NOTED

20.1' DRN:
M. KRAWCZYK
APPROVED:
PAUL BENEDETTI
DRAWING NO.
09-17-2020 NORRIS

SHEET

ENLARGED
PARTIAL SITE PLAN SCALE: N.T.S. SITE PLAN

3 OF 17 SHEETS
COPYRIGHT:
NO PART OF THIS DOCUMENT
MAY BE REPRODUCED IN ANY
FORM INCUDING PHOTOCOPY,
RECORDING OR ANY INFORMATION
RETRIEVABLE AND STORAGE
SYSTEM, WITHOUT WRITTEN
PERMISSION FROM AQUATIC
TECHNOLOGY POOL & SPA.
POOL SPECIFICATIONS
POOL LENGTH 45-4" DISCLAIMER:
NOT FOR CONSTRUCTION

POOL WIDTH 20'-2" WITHOUT GEOTECHNICAL


INVESTIGATION AND
STRUCTURAL ENGINEERING,
SPA 6'-6" X 9'-9" TO BE PROVIDED BY OTHER
PARTIES.

SPA AREA 63.5 s.f.


POOL AREA 619.5 s.f.
BAJA SHELF 69 S.F. 258 GAL
SPA 18.8 S.F. 994 GAL
POOL (DEEP) 391 S.F. 24,706 GAL
TOTAL VOLUME 25,958 GAL
TOTAL POOL / SPA AREA 683 S.F.
MIN. FILTER RATE @ 6HR 72 GPM

APN #:----
45'-4"
E

TITLE:
C D 5
5
13'-5"
5 11'-9" 6'-11" 13'-3"

Tel. 408-776-8220, Fax 408-776-3112


P.O. Box 130 - Morgan Hill Ca. 95038
1'-6" 1'-0"

www.aquatictechnology.com
Ca. Lic. No. 721117, B, C53
1'-6"

3"
STEP

STEP

4'-6"
6'-6"

3'-0"
3" 3"
1'-0" 1'-6" 6'-3" 1'-6" 1'-0"

1'-6"
B
5

3"
1'-0"
NO VALID COPYRIGHT
& NOT FOR CONSTRUCTION
OR PERMITTING WITHOUT
EMBOSSED S.W.D. SEAL,
BY PAOLO BENEDETTI

9'-9" 1'-0"
1'-0" 1'-0"
6'-6"
20'-2"

10'-6"
REVISIONS:
11'-5"

10'-4"
A
5

NOTE: WING WALL IS TO BE


SEPARATE FROM POOL
WING WALL TO PREVENT DATE:

CRACKING 09/17/2020
SCALE:
AS NOTED
DRN:
NOTE: WING WALL IS TO BE M. KRAWCZYK
SEPARATE FROM POOL APPROVED:
PAUL BENEDETTI
WING WALL TO PREVENT DRAWING NO.

CRACKING 09-17-2020 NORRIS

SHEET

POOL LAYOUT

4 OF 17 SHEETS
COPYRIGHT:
NO PART OF THIS DOCUMENT
MAY BE REPRODUCED IN ANY
FORM INCUDING PHOTOCOPY,
RECORDING OR ANY INFORMATION
RETRIEVABLE AND STORAGE
SYSTEM, WITHOUT WRITTEN
45'-2" PERMISSION FROM AQUATIC
TECHNOLOGY POOL & SPA.

13'-5" 11'-9" 6'-11" 13'-2"


1'-0" 1'-0"
3" 3" DISCLAIMER:
NOT FOR CONSTRUCTION
WITHOUT GEOTECHNICAL
12" 12" 12"
6'-5"

1'-6"
INVESTIGATION AND
1'-6" 1'-6" STRUCTURAL ENGINEERING,
TO BE PROVIDED BY OTHER
PARTIES.
6'-3"

2'-0"
1'-4"

1012"1012"1012"

1'-0"
4"
4'-0"

12"
8'-0"

APN #:----
TITLE:
A POOL LONG SECTION
5

Tel. 408-776-8220, Fax 408-776-3112


P.O. Box 130 - Morgan Hill Ca. 95038

www.aquatictechnology.com
45'-2"

Ca. Lic. No. 721117, B, C53


13'-5" 11'-9" 6'-11" 13'-2"
1'-0" 1'-0"
3" 3"
12" 12" 12"
1'-6" 6'-5"
1'-6" 1'-6"
6'-3"
2'-0"
1'-6"

1012"1012"1012"

1'-0"
6"
4'-0"

12"
8'-0"

NO VALID COPYRIGHT
& NOT FOR CONSTRUCTION
OR PERMITTING WITHOUT
EMBOSSED S.W.D. SEAL,
BY PAOLO BENEDETTI

REVISIONS:

B POOL CROSS SECTION


5

8'-7"
3" 3"
1'-0" 1'-6" 3'-1" 1'-6" 1'-0"

18"
1'-6"

1'-6"

11'-10" 4'-5" 14'-0"


12"
6"

2'-0"

4"

6"
4"
1012"
18"

1012"
1012"
1012"1012"

1012"1012"
1012"1012"

4'-0"
12"

12"
12"

DATE:
09/17/2020
8'-0"

SCALE:
VARIES AS NOTED
VARIES
DRN:
VARIES
M. KRAWCZYK
APPROVED:
PAUL BENEDETTI
DRAWING NO.
09-17-2020 NORRIS

SHEET

POOL SECTIONS (1)


C POOL CROSS SECTION D POOL CROSS SECTION E POOL CROSS SECTION
5 5 5
5 OF 17 SHEETS
COPYRIGHT:
NO PART OF THIS DOCUMENT
MAY BE REPRODUCED IN ANY
FORM INCUDING PHOTOCOPY,
RECORDING OR ANY INFORMATION
RETRIEVABLE AND STORAGE
SYSTEM, WITHOUT WRITTEN
PERMISSION FROM AQUATIC
TECHNOLOGY POOL & SPA.

2" JET AIR RETURN SPA EDGE DISCLAIMER:


NOT FOR CONSTRUCTION
LOOP WITHOUT GEOTECHNICAL

2" SPA JET AIR LOOP


INVESTIGATION AND
STRUCTURAL ENGINEERING,
WATERWAY TO BE PROVIDED BY OTHER

1" 1"
PARTIES.
#210-3310 VENTURI
TEE
1" S X 1" SPIGOT
JET LOCATION AND 1" 1"
ARRANGEMENT TO BE
DETERMINED BY OWNER
MAX 12 JETS PER PUMP SPA SEAT

1" 1" 1" 1"

LED LT.

APN #:----
1 1/2" pipe HYDROCOOL
2.5" SPA JET SUPPLY LOOP

TITLE:
WALL INLET RETURN
SPA FILTER RETURN
1 1/2" pipe
2.5" JET SUPPLY 4 JET LAYOUT
LOOP 1" CONDUIT
SPA FLOOR

Tel. 408-776-8220, Fax 408-776-3112


P.O. Box 130 - Morgan Hill Ca. 95038

www.aquatictechnology.com
Ca. Lic. No. 721117, B, C53
STEEL REINFORCING T.B.D.
AS PER STRUCTURAL ENGINEER

SPA SECTION @ GUTTER SPA EDGE

2" SPA JET AIR LOOP


1" 1"

1" 1" 1" NO VALID COPYRIGHT


SLOPE 2% TO SLOT FOR 3'-0" 1" 1"
& NOT FOR CONSTRUCTION
OR PERMITTING WITHOUT
EMBOSSED S.W.D. SEAL,
BY PAOLO BENEDETTI

SPA SEAT
1" 1" 1" REVISIONS:
4"

2.5" SPA JET SUPPLY LOOP


4"
4" W X 4" D SPA
OVERFLOW PERIMETER 2 JET LAYOUT 1 JET LAYOUT 3 JET LAYOUT
GUTTER RUNS INTO
POOL. SPA FLOOR

ENLARGED SPA GUTTER DETAIL

SPA THERAPY JET LAYOUT OPTIONS

DATE:
09/17/2020
SCALE:
AS NOTED
DRN:
M. KRAWCZYK
APPROVED:
PAUL BENEDETTI
DRAWING NO.
09-17-2020 NORRIS

SHEET

SPA DETAILS

6 OF 17 SHEETS
FIXTURE SCHEDULE: COPYRIGHT:
NO PART OF THIS DOCUMENT
MAY BE REPRODUCED IN ANY
TAG QTY MANUF: PART#: DESCRIPTION: FORM INCUDING PHOTOCOPY,
RECORDING OR ANY INFORMATION
WR 12 . . DIRECTIONAL EYEBALL RETURN RETRIEVABLE AND STORAGE
SYSTEM, WITHOUT WRITTEN
PERMISSION FROM AQUATIC
FR 4 COLORMATCH . PEBBLETOP FLOOR INLET RETURN TECHNOLOGY POOL & SPA.

MD 3 AA MANUF . CHANNEL DRAIN SUMP W/ PEBBLE TOP COVER


DISCLAIMER:
NOT FOR CONSTRUCTION
MD2 3 AQUASTAR . 10" AVRXXXD DEEP SUMP / DRAIN COVER WITHOUT GEOTECHNICAL
INVESTIGATION AND
PTC 3 COLORMATCH 10-PTD-XXXA 10" PEBBLE TOP DRAIN COVER STRUCTURAL ENGINEERING,
TO BE PROVIDED BY OTHER
PARTIES.
SK 2 PENTAIR . .
PSW 1 . . POOL SWEEP RETURN FITTING
MAF 1 PENTAIR T40F XXX MECHANICAL AUTOFILL COLOR T.B.D.
CUSTOM
4SD 3 . 4FT SHEER DESCENT WATERFALL
CASCADES
TJET 24 WATERWAY 210-3330 VENTURI TEE 1" S X 1" SPIGOT
L-LT 9 JANDY HYDROCOOL LED LIGHT REFER TO PLAN FOR WATTS

APN #:----
TITLE:
1.5"
1.5" 2" RESIDENCE

Tel. 408-776-8220, Fax 408-776-3112


P.O. Box 130 - Morgan Hill Ca. 95038
2"
VSK

www.aquatictechnology.com
Ca. Lic. No. 721117, B, C53
2" RETURN LINE FROM OZONE / UV PUMP
VENTURI 1.5" POOL SWEEP RETURN LINE
FLOW
2" SKIMMER VENTURI RETURN LINE

1.5" 3" SKIMMER LINE TO FILTER PUMP

2" 2.5" DRAIN LINE TO OZONE/UV PUMP


VSK

VENTURI
FLOW NO VALID COPYRIGHT
& NOT FOR CONSTRUCTION
OR PERMITTING WITHOUT

1.5" POOL SWEEP RETURN LINE


EMBOSSED S.W.D. SEAL,
BY PAOLO BENEDETTI
MD

REVISIONS:

POOL SWEEP
RETURN LINE WR
WR
PSW
WR 1.5"
LINE
WR
1.5" 2" RETURN
1.5"
1.5"
LINE DATE:

2" RETURN 09/17/2020


SCALE:
AS NOTED
DRN:
M. KRAWCZYK
APPROVED:
PAUL BENEDETTI
DRAWING NO.
09-17-2020 NORRIS

SHEET

POOL PIPING (1)

7 OF 17 SHEETS
FIXTURE SCHEDULE: COPYRIGHT:
NO PART OF THIS DOCUMENT
MAY BE REPRODUCED IN ANY
TAG QTY MANUF: PART#: DESCRIPTION: FORM INCUDING PHOTOCOPY,
RECORDING OR ANY INFORMATION
WR 12 . . DIRECTIONAL EYEBALL RETURN RETRIEVABLE AND STORAGE
SYSTEM, WITHOUT WRITTEN
PERMISSION FROM AQUATIC
FR 4 COLORMATCH . PEBBLETOP FLOOR INLET RETURN TECHNOLOGY POOL & SPA.

MD 3 AA MANUF . CHANNEL DRAIN SUMP W/ PEBBLE TOP COVER


DISCLAIMER:
NOT FOR CONSTRUCTION
MD2 3 AQUASTAR . 10" AVRXXXD DEEP SUMP / DRAIN COVER WITHOUT GEOTECHNICAL
INVESTIGATION AND
PTC 3 COLORMATCH 10-PTD-XXXA 10" PEBBLE TOP DRAIN COVER STRUCTURAL ENGINEERING,
TO BE PROVIDED BY OTHER
PARTIES.
SK 2 PENTAIR . .
PSW 1 . . POOL SWEEP RETURN FITTING
MAF 1 PENTAIR T40F XXX MECHANICAL AUTOFILL COLOR T.B.D.
CUSTOM
4SD 3 . 4FT SHEER DESCENT WATERFALL
CASCADES
TJET 24 WATERWAY 210-3330 VENTURI TEE 1" S X 1" SPIGOT
L-LT 9 JANDY HYDROCOOL LED LIGHT REFER TO PLAN FOR WATTS

APN #:----
TITLE:
4" WATER FEATURE MAIN DRAIN LINE

3" FLOOR INLET RETURN LINE

Tel. 408-776-8220, Fax 408-776-3112


P.O. Box 130 - Morgan Hill Ca. 95038
4" MAIN DRAIN LINE TO WATER FEATURE PUMP

www.aquatictechnology.com
Ca. Lic. No. 721117, B, C53
RESIDENCE

4" SPA MAIN DRAIN LINE (SPA JET PUMP)


3" 3" 3" SPA MAIN DRAIN LINE (FILTER PUMP)
3" 3" 4" WATER FEATURE DRAIN LINE
3" 3"

MD-2 / MD-2 / MD-2 /


PTC PTC PTC MD

MD NO VALID COPYRIGHT
& NOT FOR CONSTRUCTION
OR PERMITTING WITHOUT
EMBOSSED S.W.D. SEAL,
BY PAOLO BENEDETTI

FR
3" FLOOR INLET RETURN LINE

1.5"
REVISIONS:

WR

2"

3" WATER FEATURE SUPPLY LINE


2"

2.5" FR 2.5" FR 2.5" 2.5"

2"
2" WR

1.5"
FR

4SD
DATE:
4SD 09/17/2020
4SD SCALE:
1.5" AS NOTED
1.5" 2"
DRN:
M. KRAWCZYK
2"
1.5" 2" SCENT S UPPLY LINE APPROVED:

2" 2.5" 3" SCHEER DE PAUL BENEDETTI


2.5" DRAWING NO.
09-17-2020 NORRIS
3"
SHEET

POOL PIPING (2)

8 OF 17 SHEETS
FIXTURE SCHEDULE: COPYRIGHT:
NO PART OF THIS DOCUMENT
MAY BE REPRODUCED IN ANY
TAG QTY MANUF: PART#: DESCRIPTION: FORM INCUDING PHOTOCOPY,
RECORDING OR ANY INFORMATION
WR 12 . . DIRECTIONAL EYEBALL RETURN RETRIEVABLE AND STORAGE
SYSTEM, WITHOUT WRITTEN
PERMISSION FROM AQUATIC
FR 4 COLORMATCH . PEBBLETOP FLOOR INLET RETURN TECHNOLOGY POOL & SPA.

MD 3 AA MANUF . CHANNEL DRAIN SUMP W/ PEBBLE TOP COVER


DISCLAIMER:
NOT FOR CONSTRUCTION
MD2 3 AQUASTAR . 10" AVRXXXD DEEP SUMP / DRAIN COVER WITHOUT GEOTECHNICAL
INVESTIGATION AND
PTC 3 COLORMATCH 10-PTD-XXXA 10" PEBBLE TOP DRAIN COVER STRUCTURAL ENGINEERING,
TO BE PROVIDED BY OTHER
PARTIES.
SK 2 PENTAIR . .
PSW 1 . . POOL SWEEP RETURN FITTING
MAF 1 PENTAIR T40F XXX MECHANICAL AUTOFILL COLOR T.B.D.
CUSTOM
4SD 3 . 4FT SHEER DESCENT WATERFALL
CASCADES
TJET 24 WATERWAY 210-3330 VENTURI TEE 1" S X 1" SPIGOT
L-LT 9 JANDY HYDROCOOL LED LIGHT REFER TO PLAN FOR WATTS

APN #:----
TITLE:
EXISTING HOSE BIBB

4" SPA THERAPY JET RETURN LINE


3" SPA BENCH INLET RETURN LINE
1" CONDUIT TO SPA SIDE REMOTE
NEW HOSE BIBB
RISER TEED W/

Tel. 408-776-8220, Fax 408-776-3112


P.O. Box 130 - Morgan Hill Ca. 95038
SHUT OFF
FOR AUTO FILL

www.aquatictechnology.com
HARFORD LOOP WITH IN PLANTER

Ca. Lic. No. 721117, B, C53


BACKFLOW PREVENTION
AND VAC RELEASE.
LOCATE IN PLANTER 1" PIPE
HORIZONTAL LOOP TO AUTOFILL
SPA SIDE
REMOTE RESIDENCE MIN. 1.5" ABOVE SPA PLANTER
WATER LINE
3" SPA BENCH INLET RETURN LINE
1" CONDUIT TO SPA SIDE REMOTE

2" 2" 4" SPA THERAPY JET RETURN LINE

1.5" 1.5" 2" SPA JET AIR LINE FROM BLOWER


1" PIPE NO VALID COPYRIGHT
TO AUTOFILL & NOT FOR CONSTRUCTION

1.5" WR WR OR PERMITTING WITHOUT


PENTAIR EMBOSSED S.W.D. SEAL,
2" T40F
BY PAOLO BENEDETTI

WR WR WR 2"
WR MAF AUTOFILL

1.5" 1.5"
REVISIONS:
2" 1.5" EQUALIZER
JET LAYOUT AND ARRANGEMENT
LINE FROM
IS TO BE DETERMINED AS PER 2" JET AIR AUTOFILL
OWNER LINE LOOP

2.5" JET SUPPLY LOOP

DATE:
09/17/2020
SCALE:
AS NOTED
DRN:
M. KRAWCZYK
APPROVED:
PAUL BENEDETTI
DRAWING NO.
09-17-2020 NORRIS

SHEET

POOL PIPING (2)

9 OF 17 SHEETS
COPYRIGHT:
NO PART OF THIS DOCUMENT
MAY BE REPRODUCED IN ANY
FORM INCUDING PHOTOCOPY,
RECORDING OR ANY INFORMATION
RETRIEVABLE AND STORAGE
SYSTEM, WITHOUT WRITTEN
PERMISSION FROM AQUATIC
TECHNOLOGY POOL & SPA.

DISCLAIMER:
NOT FOR CONSTRUCTION
WITHOUT GEOTECHNICAL
INVESTIGATION AND
STRUCTURAL ENGINEERING,
TO BE PROVIDED BY OTHER
PARTIES.

NEW GFIC
CIRCUIT

NEW 110V 15A


GFIC W/ WP
COVER

APN #:----
J-BOXES
LOCATION

TITLE:
1" CONDUIT TYPICAL
NEW 110V 15A
GFIC W/ WP
COVER RESIDENCE

Tel. 408-776-8220, Fax 408-776-3112


P.O. Box 130 - Morgan Hill Ca. 95038

www.aquatictechnology.com
Ca. Lic. No. 721117, B, C53
1" CONDUIT TYPICAL
PL-7 (24W) PL-6 (24W)

SP-1 (6W)
SP-2 (6W)

PL-3 (24W) PL-2 (24W) PL-1 (6W)

NO VALID COPYRIGHT
& NOT FOR CONSTRUCTION
OR PERMITTING WITHOUT
PL-5 (24W) PL-4 (24W)
PL-7 (24W)
PL-6 (24W)
PL-5 (24W)

EMBOSSED S.W.D. SEAL,


PL-4 (24W)
PL-3 (24W)
PL-2 (24W)

BY PAOLO BENEDETTI
SP-2 (6W)
SP-1 (6W)
PL-1 (6W)

REVISIONS:

1" CONDUITS TYPICAL

INTERMATIC J-BOX
TYP OF 3
LOCATE SIDE OF
1 2 3 HOUSE

J-BOX 1 & 2 MUST BE 8" ABOVE


POOL WATERLINE. 1" CONDUIT FROM INTERMATIC
J-BOX 3 MUST BE 8" ABOVE SPA PX300 TRANSFORMER @
WATERLINE. EQUIPMENT AREA

J-BOX LAYOUT FOR


POOL SPA
LIGHTING

DATE:
09/17/2020
SCALE:
AS NOTED
DRN:
M. KRAWCZYK
APPROVED:
PAUL BENEDETTI

POOL / SPA LIGHTING DIAGRAM


DRAWING NO.

SCALE: N.T.S. 09-17-2020 NORRIS

SHEET

POOL LIGHTING
LAYOUT

10 OF 17 SHEETS
COPYRIGHT:
WATTS N36-MI 3/4" NO PART OF THIS DOCUMENT
MAY BE REPRODUCED IN ANY
VACUUM RELEASE FORM INCUDING PHOTOCOPY,
VALVE RECORDING OR ANY INFORMATION
RETRIEVABLE AND STORAGE
SYSTEM, WITHOUT WRITTEN
PERMISSION FROM AQUATIC
TECHNOLOGY POOL & SPA.

DISCLAIMER:
4" MIN. NOT FOR CONSTRUCTION
WITHOUT GEOTECHNICAL
INVESTIGATION AND
STRUCTURAL ENGINEERING,
TO BE PROVIDED BY OTHER
PARTIES.
1.5"
EQUIVALENT WATER LINE

NOTE:
MINIMUM LOOP HEIGHT TO BE 1 1/2" ABOVE WQUIVALENT
WATER LEVEL

APN #:----
HARTFORD LOOP WITH VACUUM BREAKER POO LED LIGHT DETAIL
(SPA RETURN AND POOL RETURN)

TITLE:
NOT TO SCALE

Tel. 408-776-8220, Fax 408-776-3112


P.O. Box 130 - Morgan Hill Ca. 95038

www.aquatictechnology.com
Ca. Lic. No. 721117, B, C53
MAIN DRAIN SPECIFICATONS
SCALE: N.T.S.

NO VALID COPYRIGHT
& NOT FOR CONSTRUCTION
OR PERMITTING WITHOUT
EMBOSSED S.W.D. SEAL,

DROPPED SKIMMER DETAILS BY PAOLO BENEDETTI

DOUBLE REVISIONS:

GANG BOX

STONE LID 1" SCH 80


PVD ABOVE
SLAB OR
GRADE 1" GALV. PIPE
PROVIDE ADEQUATE LENGTH
W/ CAP ON END

FROM HV
CRISTY BOX
1" ELEC.
COND. DATE:
09/17/2020
SCALE:
AS NOTED
DRN:
M. KRAWCZYK
APPROVED:
PAUL BENEDETTI

HIGH VOLTAGE STUB UP


DRAWING NO.
09-17-2020 NORRIS

N.T.S. SHEET

GENERAL
CHEMISTRY CONTROLLER PH/ORP DETAILS (1)
N.T.S.
11 OF 17 SHEETS
COPYRIGHT:
NO PART OF THIS DOCUMENT
MAY BE REPRODUCED IN ANY
FORM INCUDING PHOTOCOPY,
RECORDING OR ANY INFORMATION
RETRIEVABLE AND STORAGE
SYSTEM, WITHOUT WRITTEN
PERMISSION FROM AQUATIC
TECHNOLOGY POOL & SPA.

DISCLAIMER:
NOT FOR CONSTRUCTION
WITHOUT GEOTECHNICAL
INVESTIGATION AND
STRUCTURAL ENGINEERING,
TO BE PROVIDED BY OTHER
PARTIES.
IPS ORP/PH
CONTROLLER

FLOW CELL TUBING


**OPTIONAL SOLAR**
2" POLY GASLINE

2.5" FROM
BY GC

ARRAY
SOLAR

ARRAY
LV LINE TO AQUALINK

SOLAR
2.5" TO
4"
VENT AUX. CONTACTOR
4" HV LINE TO AQUALINK
VENT JANDY JANDY AUX. CONTACTOR
JX400NN CV580

APN #:----
NAT. GAS CART. JANDY
HEATER FILTER HV LINE TO AQUALINK HV LINE TO AQUALINK HV LINE TO AQUALINK CLEARWATER TECH OZONE

TITLE:
VSFHP270DV2A
AUX. CONTACTOR AUX. CONTACTOR AUX. CONTACTOR SIZED BY MANUFACTURER/FACTORY
PUMP VFD

2.5"
3" FOR SPECIFIED PUMP JANDY #SHPF.50
NAT GAS LINE 2.5" 2.5"
JANDY JANDY JANDY SHPF.50
LV PH FLOW CELL TUBING AIR
SHPF 3.0 VSFHP270DV2A PUMP VFD
CONTROL DRYER
SPA JET PUMP

Tel. 408-776-8220, Fax 408-776-3112


VAC

P.O. Box 130 - Morgan Hill Ca. 95038


TO PUMP
LV LINE TO AQUALINK BRKR
STENNER
2" AIR

www.aquatictechnology.com
Ca. Lic. No. 721117, B, C53
PUMP
GAP
OXYGEN
3" GENERATOR

STENNER STENNER
3" 3" 3" CT 120
45M5 45M5

MAIN DRAIN
CHEMICAL CHEMICAL
4" 4" 4"

RETURN
PUMP PUMP

SUCTION

SUCTION
3" SPA
2" 2"

4" SPA
SUCTION

RETURN

JET
JET
4" SPA

2.5"
4" SPA
PENTAIR

JET

JET
BIO-SHIELD NO VALID COPYRIGHT
& NOT FOR CONSTRUCTION
UV #522638 OR PERMITTING WITHOUT
EMBOSSED S.W.D. SEAL,
BY PAOLO BENEDETTI

2"
2" 3" POOL 3" SPA 3" POOL 3" SPA
SKIMMER FILTER FILTER SKIMMER FILTER REVISIONS:

VENTURI RETURN RETURN SUCTION SUCTION


RETURN LINE LINE LINE LINE

POOL SPA PLUMBING SCHEMATIC

#1 STENNER PUMP (OPT RAIN ROOF)


#2 STENNER PUMP (OPT RAIN ROOF) DIAMON PLATE PANEL
FLOW CELL FO CHEMISTRY CONTROLLER UNISTRUT MOUNTED
i AQUALINK ANTENNAE SOURCE LOCALLY
BOND TO GRID

DATE:
09/17/2020
INTERMATIC PX 300 TRANS.
SCALE:

IPS ORP/PH CONTROLLER AS NOTED


DRN:
JANDY AQUALINK RS W M. KRAWCZYK
RS-PS8 BOARD & SPA APPROVED:
PAUL BENEDETTI
LINK #7227 W/ MUDBOX
DRAWING NO.
#7940 09-17-2020 NORRIS

SHEET

EQUIPMENT CONTROL MOUNTING SYSTEM


SCHEMATICS

12 OF 17 SHEETS
COPYRIGHT:

L.V. = 12V LOW VOLTAGE H.V.= 120V HIGH VOLTAGE


NO PART OF THIS DOCUMENT
INCOMING POWER MAY BE REPRODUCED IN ANY
FORM INCUDING PHOTOCOPY,
SUPPLY
JANDY AQUALINK RS
RECORDING OR ANY INFORMATION
LED LT. PL1 RETRIEVABLE AND STORAGE
MIN. 80A 220V LED LT. PL2
LED LT. PL3
SYSTEM, WITHOUT WRITTEN
PERMISSION FROM AQUATIC
1" CONDUIT TECHNOLOGY POOL & SPA.
TRANS 1" CONDUIT (L.V.) TYP
DATA LINE TO
120V J J DISCLAIMER:
HOUSE KEYPAD LED LT. PL4
LED LT. PL5
NOT FOR CONSTRUCTION

(HARD WIRED) 300W BOX BOX LED LT. PL6


WITHOUT GEOTECHNICAL
INVESTIGATION AND
STRUCTURAL ENGINEERING,
J LED LT. PL7
LED LT. SP1
TO BE PROVIDED BY OTHER
PARTIES.
BOX LED LT. SP2

1" CONDUIT (L.V.)

1" CONDUIT (H.V.)


SPASIDE REMOTE
1" CONDUIT (L.V.)

NOTE: AUX. CIRCUIT PANEL MAY BE 1" CONDUIT TO FILTER PUMP


REQUIRED TO PROVIDE SUFFICIENT 1" CONDUIT TO SPA JET PUMP
BREAKER SLOTS. **ALL POOL NOTE: All pumps shall be provided with a service disconnect

APN #:----
EQUIPMENT AND PUMPS REQUIRE 1" CONDUIT TO WATER FEATURE PUMP (independent from circuit breaker)[NEC 430.19]
GFCI PROTECTION**

TITLE:
1" CONDUIT TO OZONE / UV TREATMENT PUMP
1" CONDUIT TO AIR BLOWER
NOTE: main sub-panel shall be
1" CONDUIT TO J BOX FOR OZONE-UV-ORP/PH CONTROLLER
provided with surge protection
(Square-D Mdl HEPD80 or 1" CONDUIT TO HEATER

Tel. 408-776-8220, Fax 408-776-3112


P.O. Box 130 - Morgan Hill Ca. 95038
QO2175SB) 1" CONDUIT TO POOL CLEANER BOOSTER PUMP
1" CONDUIT FOR DATA LINE TO FILTER PUMP

www.aquatictechnology.com
Ca. Lic. No. 721117, B, C53
1" CONDUIT FOR DATA LINE TO WATERF EATURE PUMP
1" CONDUIT TO RETURN ACTUATOR
1" CONDUIT TO SUCTION ACTUATOR

1" CONDUIT TO HEATER FIREMANS SWITCH


**OPTIONAL**1" CONDUIT TO SOLAR 3 WAY VALVE ACTUATOR
POOL / SPA AUTOMATION SYSTEM
# 8 BARE
COPPER WIRE
NO VALID COPYRIGHT
BONDING GRID EXTENDS 3' TO & NOT FOR CONSTRUCTION
OR PERMITTING WITHOUT
FROM COPING EQUIPMENT EMBOSSED S.W.D. SEAL,
BY PAOLO BENEDETTI

# 8 BARE
COPPER WIRE

REVISIONS:

RESIDENCE

# 6 BARE
COPPER WIRE
# 8 BARE DECK STEEL
COPPER WIRE # 8 BARE
BONDING GRID EXTENDS 3' # 8 BARE
FROM COPING COPPER WIRE COPPER WIRE BONDING GRID EXTENDS 3'
# 8 BARE FROM COPING
COPPER WIRE
SPA STEEL

POOL STEEL

BARE #8 COPPER BOND WIRE


LOOP AROUND POOL PERIMETER
POOL STEEL 6" FROM BEAM.
POOL STEEL
# 8 BARE DATE:
09/17/2020
COPPER WIRE SCALE:
AS NOTED
DRN:
M. KRAWCZYK
APPROVED:
# 8 BARE PAUL BENEDETTI
COPPER WIRE DRAWING NO.
09-17-2020 NORRIS

SHEET

AUTOMATION
SCHEMATIC
TYPICAL BONDING GRID DETAIL /POOL BONDING
13 OF 17 SHEETS
COPYRIGHT:
NO PART OF THIS DOCUMENT
MAY BE REPRODUCED IN ANY
FORM INCUDING PHOTOCOPY,
RECORDING OR ANY INFORMATION
RETRIEVABLE AND STORAGE
SYSTEM, WITHOUT WRITTEN
PERMISSION FROM AQUATIC
TECHNOLOGY POOL & SPA.

DISCLAIMER:
NOT FOR CONSTRUCTION
WITHOUT GEOTECHNICAL
INVESTIGATION AND
STRUCTURAL ENGINEERING,
TO BE PROVIDED BY OTHER
PARTIES.

19'-9"

APN #:----
TITLE:
2.5"

3'-0" POLARIS QT
2HP AIR FROM TO FILTER SPA JET
WATER
FEATURE

Tel. 408-776-8220, Fax 408-776-3112


P.O. Box 130 - Morgan Hill Ca. 95038
BLOWER PUMP PUMP OXYGEN
SOLAR SOLAR PUMP
GENERATOR

CT120

www.aquatictechnology.com
Ca. Lic. No. 721117, B, C53
JANDY
CV580
FILTER
ACID
JANDY 2.5" 4:1 RATIO

6'-0"
NAT GAS
3'-0"

HEATER

2.5"
PENTAIR BIOGUARD UV
2.5" 2.5" 3"

4" 4" 4" 3" 0ZONE/UV


CHL TREATMENT
HAYWARD PUMP NO VALID COPYRIGHT
& NOT FOR CONSTRUCTION
BOOSTER PUMP OR PERMITTING WITHOUT
EMBOSSED S.W.D. SEAL,
BY PAOLO BENEDETTI

4" 3" 4" 3" REVISIONS:

SPA MD SPA JET WATER WATER


3" SUCTION RETURN FEATURE FEATURE
LINE LINE SUCTION RETURN
SPA LINE
3" LINE
SUCTION
SKIMMER LINE
1.5" POOL CLEANER 2.5" RETURN 2.5" RETURN SUCTION
SUPPLY LINE TO LINE TO LINE TO LINE
POOL POOL SPA

DATE:
09/17/2020
SCALE:
AS NOTED
DRN:
M. KRAWCZYK
APPROVED:
PAUL BENEDETTI
DRAWING NO.
09-17-2020 NORRIS

SHEET

EQUIPMENT
ROOM LAYOUT

14 OF 17 SHEETS
COPYRIGHT:
NO PART OF THIS DOCUMENT
MAY BE REPRODUCED IN ANY
FORM INCUDING PHOTOCOPY,
RECORDING OR ANY INFORMATION
RETRIEVABLE AND STORAGE
SYSTEM, WITHOUT WRITTEN
PERMISSION FROM AQUATIC
TECHNOLOGY POOL & SPA.

DISCLAIMER:
NOT FOR CONSTRUCTION
WITHOUT GEOTECHNICAL
INVESTIGATION AND
STRUCTURAL ENGINEERING,
TO BE PROVIDED BY OTHER
PARTIES.

APN #:----
TITLE:

Tel. 408-776-8220, Fax 408-776-3112


P.O. Box 130 - Morgan Hill Ca. 95038

www.aquatictechnology.com
Ca. Lic. No. 721117, B, C53
NO VALID COPYRIGHT
& NOT FOR CONSTRUCTION
OR PERMITTING WITHOUT
EMBOSSED S.W.D. SEAL,
BY PAOLO BENEDETTI

REVISIONS:

DATE:
09/17/2020
SCALE:
AS NOTED
DRN:
M. KRAWCZYK
APPROVED:
PAUL BENEDETTI
DRAWING NO.
09-17-2020 NORRIS

SHEET

GENERAL
NOTES (1)

15 OF 17 SHEETS
TILE CONT'D COPYRIGHT:
NO PART OF THIS DOCUMENT
MAY BE REPRODUCED IN ANY
FORM INCUDING PHOTOCOPY,
RECORDING OR ANY INFORMATION
RETRIEVABLE AND STORAGE
SYSTEM, WITHOUT WRITTEN
PERMISSION FROM AQUATIC
TECHNOLOGY POOL & SPA.

DISCLAIMER:
NOT FOR CONSTRUCTION
WITHOUT GEOTECHNICAL
INVESTIGATION AND
STRUCTURAL ENGINEERING,
TO BE PROVIDED BY OTHER
PARTIES.

APN #:----
TITLE:

Tel. 408-776-8220, Fax 408-776-3112


P.O. Box 130 - Morgan Hill Ca. 95038

www.aquatictechnology.com
Ca. Lic. No. 721117, B, C53
NO VALID COPYRIGHT
& NOT FOR CONSTRUCTION
OR PERMITTING WITHOUT
EMBOSSED S.W.D. SEAL,
BY PAOLO BENEDETTI

REVISIONS:

DATE:
09/17/2020
SCALE:
AS NOTED
DRN:
M. KRAWCZYK
APPROVED:
PAUL BENEDETTI
DRAWING NO.
09-17-2020 NORRIS

SHEET

GENERAL
NOTES (2)

16 OF 17 SHEETS
DROWNING PREVENTION MEASURES CONT''D COPYRIGHT:
NO PART OF THIS DOCUMENT
MAY BE REPRODUCED IN ANY
FORM INCUDING PHOTOCOPY,
RECORDING OR ANY INFORMATION
RETRIEVABLE AND STORAGE
SYSTEM, WITHOUT WRITTEN
PERMISSION FROM AQUATIC
TECHNOLOGY POOL & SPA.

DISCLAIMER:
NOT FOR CONSTRUCTION
WITHOUT GEOTECHNICAL
INVESTIGATION AND
STRUCTURAL ENGINEERING,
TO BE PROVIDED BY OTHER
PARTIES.

APN #:----
TITLE:

Tel. 408-776-8220, Fax 408-776-3112


P.O. Box 130 - Morgan Hill Ca. 95038

www.aquatictechnology.com
Ca. Lic. No. 721117, B, C53
NO VALID COPYRIGHT
& NOT FOR CONSTRUCTION
OR PERMITTING WITHOUT
EMBOSSED S.W.D. SEAL,
BY PAOLO BENEDETTI

REVISIONS:

DATE:
09/17/2020
SCALE:
AS NOTED
DRN:
M. KRAWCZYK
APPROVED:
PAUL BENEDETTI
DRAWING NO.
09-17-2020 NORRIS

SHEET

GENERAL
NOTES (3)

16 OF 17 SHEETS