Professional Documents
Culture Documents
Kazma SMOKE VENTILATION SYSTEM-1
Kazma SMOKE VENTILATION SYSTEM-1
DORMITORY
Smoke Calculation: GROUND FLOOR, FIRST FLOOR AND SECOND FLOOR
Mf : 0.19 PY3/2
Mf : Mass flow of hot gases entering the smoke layer (Kg/S)
P : Fire Perimeter (M)
y : Height of bottom of smoke layer above floor (M)
Mf : 0.19 x 12 x 2.53/2
=9.01 Kg/Sec.
: Qf
Mf Cp
Q : 9 x 160 = 158.2 oC
9.01 x 1.01
Mechanical Ventilation:
V : Mf Tc / o To
Tc : Temperature of smoke layer (k) = To +
= 303+158.2 = 461.2 oK
Page 1 of 2