You are on page 1of 7

MASTECO

MASTECO

VALVE
ALARM VALVE 특허품
Specification 특 허품
Operation
Alarm valve primary and secondary side of the state,
Model No. M-WAV65-N M-WAV80-N M-WAV100-N
filled with water, fire, the clapper is activated, leading
Size 65A 80A 100A to the flow direction of the alarm switch on delay circuit
after the set time has elapsed, the alarm sends an
Test Pressure 2.1MPa(21kgf/㎠)
electrical signal to the cry of the Control Panel draw.
Alarm Valve of The MASTECO Max. Working
1.4MPa(14kgf/㎠)
Pressure
Our alarm valve is used for wet sprinkler system. our alarm valve directly by sensing the movement of the flow when Before Operation After Operation
F l a n g e
the sprinkler is in operation it is possible to detect the exact conventional way of pressurized alarm type alarm valve Specification
KS B 1511 FF 10K
2nd Side 2nd Side

will break away one. And, alarm valve is a built-in delay timer, water hammer occurs during operation of the pump
Direction of
Vertical
in response to the problems on the false. In addition, a built-in drain valve on site glass if applicable that can easily Connection

be installed in a small space is a multi-functional product. 재 질 Ductile Iron, Brass, NBR, EPDM

특 허품
Features 중 량 12kg 13kg 17kg
1nd Side 1nd Side
형 식 번 호 검13-6-1 검13-7 검13-8 Water way Water way

POINT 1 Compact footprint to minimize product!


- Alarm switch is disposed on the front
- Option: Sight-glass built-in drain valve is applicable
특허품
Dimension
- Option: overpressure protection device is applicable

ø B
ø B

ø
ø

H
H
POINT 2 The monitor is accurate and fast!
- Clapper is directly sense the flow of running water
MASTECO
øC F øA øC F øA

POINT 3 To prevent misinformation!

D
25A
- Built-in delay timer

L
E

E
POINT 4 Enhanced safety!

J
I

D
M I
M
K
- Body and cover material is applied to GCD450 øC G
øA K øA
øC G

Standard Type Sight Glass Type


Model No. A B C D E F G H I J K L M Model No. A B C D E F G H I J K L M
● Benefits Overpressure Protection Device
M-WAV65-N 65 140 175 22 190 240 410 19 25A 42 204 254 123 M-WAV65-NS 65 140 175 22 190 240 375 19 25A 20 154 254 123
○ The event of overpressure on the secondary side, the primary side of the
overpressure is automatically discharged M-WAV80-N 80 150 185 22 225 247 445 19 25A 62 210 260 142 M-WAV80-NS 80 150 185 22 225 247 407 19 25A 40 158 260 142
○ No separate adjustment for the primary, secondary, primary pressure is M-WAV100-N 100 175 210 24 245 253 455 19 25A 62 216 278 148 M-WAV100-NS 100 175 210 24 245 218 418 19 25A 40 164 278 148
automatically maintained in the same structure;
○ In accordance with the pressure, a separate set and no need for a separate
operation
No need to have a maintenance and repair
특 허Drawing
Assembly 품

특Option
허품
NO Part Name Q;ty
① Body 1
② Alarm Switch 1
③ Drain Valve 1
④ Nipple 2
MASTECO MASTECO MASTECO ⑤ Niddle Valve 2
⑥ Pressure Gauge 2
⑦ Drain Valve (Sight Glass) 1
[STANDARDS] [SIGHT GLASS TYPE]

[SIGHT GLASS TYPE] [STANDARD+O.C.P VALVE] [SIGHTGLASS+O.C.P]


PRE-ACTIONVALVE(DELUGEVALVE) PRE-ACTION VALVE (DELUGE VALVE)
Pre-Action Valve is used in Dr y-t ype spr inkl er syst em and i t can be wi del y used f or Cl ose and Open
spr i nkl er syst em and Foam syst em . I t does not r equi r e a heat i nsul at i on wor k t o pr event f r eezi ng at 2nd si de pi pe.
FE ATURE
I f t he el ect r oni c bal l val ve equi pped i n t he body i s oper at ed by t he sensor , pr e-act i on val ve whi ch i s bei ng set and
m ai nt ai ned i s opened and an ext i ngui shant wat er i s di schar ged t o a f i r e t hr ough a opened spr i nkl er head and a POINT 1 Reduction Of Wrong Operation
f i r e i s suppr essed.
Reduce the wrong operation by adopting Diaphragm type to absorb water hammering and pressure shock.

POINT 2 User-Friendly
As a multi-functional valve that can be operated by the fire detection of electronic ball valve and by
PRE-ACTION VALVE

OPE RATION manual control in case of an emergency, it is very convenient for the maintenance by integrating an
operation part for the opening of main valve at one place
When a fire breaks out an electronic ball valve that is linked to a sensor is
opened and water is drained to the drain pipe. And then valve is opened and a POINT 3 Prevention of Freezing and Complete Drainage
fire alarm is activated by the operation of 2nd side pressure gauge and an
extinguishant water is rapidl y discharged to a fire at 2nd side(or Test Drained water by the operation of electronic ball valve is drained to the drain pipe. And the automatic
drainage pipe) . drain device equipped to the drain valve can thoroughly discharge the remaining water of 2nd side to
the drain pipe. This advantage makes the floor of valve room kept clean and prevents freezing.

Before Operation After Operation High Product Safety


POINT 4
Improved Product Safety with strict in-house Hydrostatic Test for body (5 times Max.Working
2nd side 2nd side Pressure -70kgf/cm2)

ASSE MBL Y DRAWIN G


Pre-Action Valve 1st side 1st side

(Left)

Specification
Model No. M-PAV80 M-PAV100 M-PAV125 M-PAV150
Size 80A 100A 125A 150A
Pre-Action Valve
DIME N SION
Test Pressure 21 kgf/cm 2
(2.1 MPa)
(Right) Max.Working Pressure 14 kgf/cm 2
(1.4 MPa) No. A B C D E F
Flange Specification KSB 1511 FF 10K M-PAV80 27 20 220 245 160 45
Direction of Connection Vertical M-PAV100 320 210 270 270 160 45
Electric Ball Valve DC24V / Both A utomatic and Manual M-PAV125 350 215 310 310 17 60
Net Weight (Kg) 36 51 67 84 M-PAV150 370 245 345 345 185 60
CHECK VALVE Model : MGCV
DND - 0004 CHECK VALVE
Model : MGCV (2", 2.5", 3", 4", 5")

Description

The Masteco MGCV check valve is compact, light weight, and


hydraulically efficient valve that allows flow in one direction. ULC
MGCV is UL listed and FM approved fire use in fire protection
systems for services up to 300psi (20.7bar). MGCV is available TOP VIEW
from sizes 2 inch (50mm) to 6 inch (150 mm).

MGCV is grooved on both ends to standard ANSI groove


FM
specification and can be installed with standard UL Listed and CHECK
FM approved grooved coupling, such as Victaulics, Grinnel,
F
Tyco, Anvil, etc. Model MGCV can be easily maintained by
removing the grooved coupling. D
VALVE G
This product is manufactured by Masteco Industry Co., LTD. MGCV
The warranty is provided to the original buyer for One years
solely against material defect and workmanship when the NPT 1/2
valve is properly installed and maintained. Check valve not B C
NPT 1/2
properly installed and maintained following NFPA 25 and
local requirement are not subject to warranty. The warranty A
period starts with the manufactured date. Masteco and it’s
distributor are in no way responsible for incidental, indirect, or
consequential damages caused by this product. Damages will
be limited to the sale price of the product.

Specifications SIZE PART NUMBER


2" MGCV – 2G
·Max Working Pressure: 300 psi (20.7 Bars)
·Max. Test Pressure: 500 psi (34.5 Bars) 2.5" MGCV – 2.5G Unit: inch Unit: mm
·Working Temp: 250F (120°C) 3" MGCV – 3G SIZE A B C D E F SIZE A B C D E F
2' 6.69 1.73 2.04 2.37 5.58 3.34 2' 170 44 52 60.3 141 85
4" MGCV – 4G 2 1/2' 7.25 1.73 2.04 2.87 5.78 4.56 2 1/2' 184 44 52 74.5 147 116
Factory Installed UL Approved Tampered Switch for Indoor and Outdoor
Use 6" MGCV – 6G 3' 7.67 1.89 2.16 3.51 6.22 5.19 3' 195 48 55 89.1 158 132
4' 8.07 1.85 2.48 4.5 7.39 6.18 4' 205 47 63 114.3 187.8 157
6' 12.60 2.63 3.38 6.62 10.94 8.66 6' 320 67 86 166.5 278 220
ORDERING INFORMATION
Material See detailed ordering and shipping
informationin the package
·Body: Ductile Iron dimensions section on page 2 of this data
·Color: Red sheet.
·Clapper: 2" - 5" type 304 stainless steel
·Clapper Facing: Grade E EPDM
·Service Temp: -40F to 230F (-40" to 110C) MGCV check valves can be installed either vertically (flow arrow up only) or
horizontally (hinge on top). Install must align arrow on the body of the
·Seat Ring: Type 304 stainless steel check valve with the direction of the flow. The check valve must follow care
INSTALLATION and maintenance requirement specified in latest edition of National Fire
·Spring: ANSI 302 stainless steel Protection Association (NFPA) Standard No. 25 - Standard for the
·Hinge Pin: ANSI 304 stainless steel Inspection, Testing, and Maintenance of Water-Based Fire Protection
Systems and local requirements.
·Hinge Pin Bushings: B148 OR B584 brass bushing
www.masteco.co.kr

Global Leader
Towards
in Fire Fighting Equipment
Masteco Industry Co., Ltd. formerly known as Korea Halon was founded in 1984. Since then, the company has been
providing fire protection solutions to a wide array of customers through its innovative and state-of-the-art water and
gaseous-based fire extinguishing product lines. With extensive experience in the development and manufacturing
of such products, Masteco Industry Co., Ltd. has established itself in the Korean market as the leading and trusted
partner in fire protection. As the company extends its market globally, Masteco Industry Co., Ltd. continues to
endeavor for high-quality products that comply with if not exceed the applicable strictest international standards.

■Head Office ■USA Office ■Main Factory


Room 1009, Byeoksan Valley 5 60-73 4310 Regency Dr. 715-12 Gojan-dong, Namdong_gu
Kasan-dong, Guemcheon-gu Seoul, 153-801, Korea Gleenview, IL 60025 Incheon, 405-821, Korea
Tel.: 82-2-785-1301, Fax: 82-2-785-1313 Tel.: 847-759-8872, Fax: 877-520-5357 Tel.: 82-32-811-1301, Fax: 82-32-811-1305
File EX15244
Project 07CA20223
Project 11CA43950

Issued: June 21, 2007


Revised: September 9, 2011

REPORT

On

CHECK VALVES
(HMER, HMER7)

for

Masteco Industry Co., Ltd.


Incheon, Korea

Copyright  2007 Underwriters Laboratories Inc.

UNDERWRITERS LABORATORIES INC. AUTHORIZES THE ABOVE NAMED COMPANY TO


REPRODUCE THIS REPORT PROVIDED IT IS IN ITS ENTIRETY.
File EX15244 Page 1 Issued: 2007-06-21
Revised: 2011-09-09

DESCRIPTION

PRODUCT COVERED:

* USL, CNL - Models MGCV-2G, MGCV-2.5G, MGCV-3G, MGCV-4G and MGCV-6G


spring loaded swing check valves with grooved ends in sizes 2, 2-1/2, 3, 4,
and 6 in. for pressures not exceeding 300 psig. The check valves are
intended for installation in both the horizontal and vertical positions.

ENGINEERING CONSIDERATIONS (NOT FOR FIELD REPRESENTATIVE'S USE):

CNL refers to an investigation to Canadian requirements.

CONSTRUCTION DETAILS:

The devices have been examined and found to comply with the applicable
requirements of the Standard for Check Valves for Fire Protection Service, UL
312 and the Canadian Requirements for Check Valves, in effect as of the date
of this Report.

USE:

The products covered by this Report are intended for use in accordance with
the National Fire Protection Association Standards for Low Expansion Foam,
NFPA 11, the Installation of Sprinkler Systems, NFPA 13, the Installation of
Standpipe, Private Hydrants, and Hose Systems, NFPA 14, Water Spray Fixed
Systems, NFPA 15, the Installation of Stationary Pumps, NFPA 20, Water Tanks
for Private Fire Protection, NFPA 22 and the Installation of Private Fire
Service Mains and Their Appurtenances, NFPA 24.