No: SSIEC-SRM-V008335
SHINSUNG
HAZARDOUS VOLTAGE
CAN SHOCK, BURN,
OR CAUSE DEATH
Do not attempt to handle, install, use or
service this product before reading
instruction book
The SIREC auto circuit recloser should be installed within the design limitations as described
on its nameplate and in these instructions. Also follow your company’s safety procedures.
This recloser should not be used by itself as the sole means of isolating a high voltage circuit.
For the safety of personnel performing maintenance operations on the recloser or connecting
equipment, all components should be electrically disconnected by means of a visible break and
securely grounded.
This product is intended to be operated and maintained by qualified persons thoroughly trained
and knowledgeable of the hazards involved. This publication is written only for such qualified
persons and is not intended to be substitute for adequate training and experience in the safety
procedures for this device.
Detailed descriptions of standard repair procedures, safety principles, and service operations
are not included. It is important to note that this document contains some warnings and cautions
against some specific service methods that could cause personal injury to service personnel, or
could-, damage equipment or render it unsafe. These warnings and cautions do not cover every
conceivable way in which service (whether or not recommended by SHINSUNG) may be done or
possible hazardous consequence of each conceivable way, nor could SHINSUNG investigate all
such ways. Anyone using service procedures or tools, whether or not recommended by
SHINSUNG, must satisfy himself thoroughly that neither personal safety nor equipment safety will
be jeopardized by the service method or tools selected.
All information contained in this manual is based on the latest product information available at
the time of printing. The right is reserved to make changes at any time without notice.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 2
Introduction
These instructions do not attempt to provide the user of this equipment with every possible
answer to questions which may occur in the application, operation and maintenance of the
product. Also, as improvements in parts and assemblies are made, some parts may differ in
appearance than depicted in illustrations; however, functionality will be equivalent.
Basically the SIREC vacuum reclosers and accessories are designed and constructed for
outdoor installation on the pole, and under the following conditions:
The components may vary and special protective treatment may be required where unusual
conditions are encountered:
-More high/low temperature,
-Dust and corrosive environment,
-Exposure to maritime, industrial and aggressive atmosphere.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 3
All SHINSUNG SIREC Reclosers carry out standard production (routine) tests in accordance
with the provisions of IEC 62271-111 in the factory prior to packing and shipping.
If damage is noticed when you receive products, call the carrier at once for inspection, and
request an inspection report. File a formal claim with the carrier, supported with the paid freight
bill, inspection report, and invoice. The local SHINSUNG sales representative or office should be
notified
.
(1) Check the position of the open-lock handle (green) whether it is set to the upper position as shown
below.
(2) To manual open operation, pull down the open-lock handle by hand or hook stick, and also
mechanically and electrically locked out not to close electrically.
☞ Manual open-lock handle can be operated in case the control is out of order even in energized power
line.
Open-Lock
[Original Position of manual open-lock Handle] [Manual Lock-Out Status for SIREC]
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 4
(3) To release the manual lockout, pull up the open-lock handle to return its original position for manual
close operation.
(1) In case of 27kV Recloser typed SIREC, pull up & down the close handle (red) for about 4-5 times until
close operation done by hand or hook stick.
(2) In case of 38kV Recloser typed SIREC-38, insert the steel rod into the closing port and turn it to the
clock wise.
Close Handle
☞ Manual close handle only available typed SIREC as an optional item is specially designed for manual
close operation in case the control is out of order, even in an energized power line(hot line status).
Notice
※ For the type SIREC-38, close operation shall be performed only when recloser is ‘de-
energized (electrically shut-off / on dead line)’ in order to avoid human danger from fault (over)
current from the live line.
Recloser On/Off operation status can be checked through on/off Indicator (ON: Red/OFF: Green),
which is directly connected to the main contact. The operation counter is at the bottom of recloser body as
indicated below;
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 5
On/Off Indicator
Operation
1. For long time storage, recloser set should be stored indoor in dry condition. Especially
Control Unit has to be protected from water in a rainy season.
2. If it is unavoidable to store them outdoors, they should be covered with waterproof material
and kept away as high as possible from the ground in order to minimize any humid penetration
from ground.
3. When "power-on" the Control Unit after long time storage, Make sure whether it is well dried
and dehumidified. Don't power-on before you are sure.
4. When the Control Cable or Power Cable is not connected at the Recloser and Control, please
attach the protective cap to the Connectors and Receptacles to prevent receptacles and
connectors from the water and humidity.
Please store the recloser with control box in a dry condition with proper humidity control to avoid
the malfunction from them.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 6
Site Procedure
Step 1. Required Tools preparation
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 7
Step 10. Remove the by-pass cable or open the by-pass switch
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 8
Step 3.2 Lifting and Mounting Recloser & External Transformer on the
Pole
For mounting on the pole, a four-point lifting is strongly recommended utilizing the Lifting Lugs in
upper side of the Recloser.
( Note 1) Take care during lifting to avoid damage to the bushings. The Recloser must not be
lifted or moved by the bushings. This may cause excessive stress on the bushings and result in
the broken bushings
( Note 2) Upon connecting the auxiliary power cable and external Potential Transformer (option),
In case the external transformer has double secondary voltage taps, do not use the higer voltage
tap, for instance, in case of 240V / 360V, 240V should input to Control Unit.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 9
[ Recloser Handling ]
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 10
The terminal lug as optional part shall be used for connection of the main circuit cable.
Depending on the type of terminals, the termination between bushing terminal and main cir
cuit cable(HV cable) shall be properly jointed recommended as below;
In case the bushing terminal is the bolted clamping type terminal, the copper or aluminum
cable shall be inserted into no. of the copper type sleeve below, apply grease compound and
compressed it tightened, and then no. of the copper type sleeve shall be connected to the
bushing bolted clamp terminal,
In case the bushing terminal is NEMA 2-hole type terminal, the copper or aluminum cable shall
be inserted into the NEMA two-hole terminal lug as below; application is the same as case 1
above.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 11
Before jointing HV cable termination, we recommend use/cover the bird guard caps(insulati
on cap) as an optional part on the connected terminals as below;
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 12
¶ The control hanger band is not included in the package due to the optional accessories.
Step 6. Earthing
The Recloser Tank shall always be earthed following
the local safety regulations. The earthing cable can be
connected to the earthing terminal at the upper (or
bottom) part of the Recloser with a clamp for M12 bolt.
The Diameter of the earthing terminal on the Recloser
and Control is Maximum 9 mm. The minimum diameter
of earth cable is over 2.6 mm. The Control Unit can
also be earthed by earthing terminal on the bottom part
of the control cabinet to the one earthing cable (T
Connection).
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 13
(Note) Earth Cable and Control Cable (including Power Cable) are recommended to be
minimum 20 cm apart from each other to prevent surge influence.
Notice
※ Check whether all cables are connected to the receptacle tightly to prevent dust or water
penetration
※ The external transformer for control power supply to control unit shall be connected using the
power cable .(External power transformer is an optional item)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 14
Step 9. Energizing
1. Check if Recloser’s position indicators are correct (Open state).
2. Check if the line (main circuit) cables are connected with sufficient clearances.
3. Check if Control Cables and Power Cable are connected normally.
4. Recloser’s position should be made to Close state.
5. Energize the Power Line by disconnecting the by-pass cable or opening the by-pass s
witch
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 15
※ Control cable can be available to disconnect while ACR is connecting to power line by CT
short device and VT open protection circuit.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 16
Overall Features
SHINSUNG polymer Recloser utilize vacuum interrupter as the interruption medium and solid dielectric
as the insulation medium. Also, VITR6 RTU based control is specially designed for self healing loop
system of radial and loop network.
The circuit breaker has 6 voltage sensors, 3 CT’s and sensitive zero phase current sensors, so even for
ungrounded system, it can detect very sensitive ground fault.
Unlike conventional recloser at loop scheme, it can isolate source and load side of faulted section
before tie switch close and it also has load encroachment algorithm, automatic setting group change
functions.
It also can make loop scheme with VIT sectionalizer or with VIT reclosing sectionalizer, so it can make
many sectionalizing points than conventional recloser loop scheme with low investment.
The VIT R6 control also has directional sensitive earth fault protection, random arc (HIF) protection and
open conductor fault protection features
Recloser is self contained circuit breaker which has CTs, voltage sensors, and all the protection relay
functions. It can be installed at substation, in the middle of network and it can reduce the outage area,
outage time.
If it is used with sectionalizer or reclosing sectionalizer, it can makes many sectionalizing points, so
easily fulfill the requirement of smallest outage area.
For radial line protection, it has phase, ground, directional SEF protection functions and specially it has
high impedance random arc fault protection and open conductor fault protection based on unbalance
current ratio element.
It also has sympathetic trip restraint feature because of delayed recovery voltage during source side
fault.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 17
Sequence coordination
Complex curve
Fault indicators
Measurement
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 18
The most important functions of VITR6 control is the enhanced loop operation capabilities. The VIT R6
control can isolate the source and load side of faulted section before tie switch close without using
communication.
It can make improved recloser loop scheme and also it can make many sectionalizing points using VIT
sectionalizer or VIT reclosing sectionalizer.
The VIT R6 control can isolate the source and load side even in open conductor fault situation. The
VIT R6 control can supply more current during loop operation without sacrificing sensitivity and security
through load encroachment algorithm and it can change the setting group automatically according to the
power direction.
Source and load side isolation of faulted section, so it eliminate the coordination problem and
unnecessary fault current impact to the healthy network during tie switch close.
The recloser can coordinate with 2 or 3 sectionalizer and can coordinate with infinite reclosing
sectionalizer even in loop scheme.
It has tie recloser functions and if the fault was at the zone of tie recloser, it goes to lockout without
attempting close into fault
During open conductor fault, it can isolate both side of open conductor.
It has load encroachment algorithm, so even the load current increased during loop operation, it
maintain sensitivity and security.
It has two setting groups and according to the power direction, it automatically changes.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 19
VITR6 is automatic circuit recloser control and feeder remote terminal unit (RTU) for distribution
automation application.
Main functions of VITR6 are 3-phase and ground protection, auto-reclosing and RTU functions for
remote operations of recloser. VITR6 is a fully digitalized and microprocessor-based control device, so the
customers can utilize this control for the powerful function of existing recloser and distribution automation
demand at present and in the future.
- Time Current Curve: 36 conventional curves, 5 US curves, 5 IEC curves, 4 user defined curves
- Complex curve
. Vertical multiplier
. Minimum response
Sequence coordination
Measurements
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 20
Active, reactive and apparent power for each phase and 3-phase
Power factor
Frequency
Control
Battery test
Status Monitoring
Contact inputs
- Battery status
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 21
Recording
Load profiling
Three (3) selectable setting groups ideal for loop scheme application.
MET Tester Compatibility: Since the main control cable of SIREC & VITR6 has the
same pin number as Cooper recloser, Cooper conventional control cable and MET
tester can be used at SIREC recloser and VITR6 control.
Dead Line Operation (option): Consisting of Battery, DC/DC converter and Capacitor,
it achieves dead line operability that is necessary for reconfiguration of the power
line during the line outages.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 22
Ratings
Operating Voltage
Features
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 23
Construction
4
1
2 5
6
3
1 Terminal
2 Vacuum Interrupter
3 Insulation Rod
4 Bird Guard Cap
5 HCEP Housing
6 Manual Close Handle (for applicable 27kV recloser type SIREC)*
7 Hook Stick- Operated manual trip and lockout control
8 Mechanical On/Off position indicator
* 38kV Recloser type SIREC-38 has a closing port instead of handle for manual close operation
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 24
7. Functional Description
The VIT recloser has all the conventional recloser functions, but also it has many enhanced functions
for self healing feeder automation system as follows;
Sensitive earth fault protection even for ungrounded system (sensitivity 100mA range)
- Automatic lockout of tie recloser if the fault is at the zone of tie recloser
- Can coordinate with sectionalizer and reclosing sectionalizer even in loop system, so more
sectionalizing points with better coordination than the conventional 5 recloser loop scheme.
- During open conductor fault, the source and load side of open conductor can be isolated.
Each shots can program the high current trip, and high current lockout.
If the fault is isolated or disappear before lockout, then the sequence will be reset
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 25
In case of VIT R6 control, the lockout state should be reset before closing.
If the control is reset, then it can close automatically if one side voltage is restored.
If there is fault after manual closing, then it will go to lockout after one trip. (one short to lockout feature)
The number of fast operation can be programmed within the total operation numbers. The remained
number of operation except fast operation from number of operations to lockout will be delay operation.
The fast curve will be used to save the fuse or to minimize the damage of the network.
Some fast curves are extremely fast, and in this case, it maybe can not survive during reclosing
sequence because of transformer magnetizing current. This may lead the downstream sectionalizer to trip
and lockout even during temporary fault. In this case, other fast curve which can survive should be chosen
or fast sequence only be permitted one times.
Minimum response time can be used for recloser to recloser fast curve coordination. The minimum
response time should be longer than 3cycles for series coordination
Sometimes, the series connected recloser can trip simultaneously, so for safety the number of
operations to lockout of upstream device will be more than the downstream device.
The VIT recloser has blocking timer for better series coordination. Once the recloser successfully closed,
then the blocking timer start and the fault pick up will be inhibited during blocking time.
For recloser to recloser coordination, the upstream recloser should be at the same delay sequence with
downstream recloser. If the fault is cleared by downstream recloser before fast curve timed out, then the
upstream recloser just advance sequence without tripping, so the delay sequence can be matched
together.
The cold load pick up functions will be sealed in when the recloser close after loss of load diversity.
Thermostatically controlled load loss load diversity after long outage, so when reenergizing the network,
there will be high cold load inrush current. The cold load pick up moves the fast curve to delay curve
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 26
and raise the minimum pick up current during the programmed time interval.
The recloser may mis trip during source side fault because of delayed recovery voltage after fault
clearing by the feeder circuit breaker. During fault, the system voltage will be dropped, and motor load
may nearly be stalled. Once the C.B of faulted feeder clears the fault, then the system voltage will be
recovered and during the time, the current will be increased and can trip recloser. The VIT R6 control
avoid sympathetic trip by desensitizing the pick up level during the time interval, if the voltage is down
without fault pick up.
Directional zero phase current ratio (I0/I1) can improve the sensitivity
In case of 3phase 3wire system, there is very small residual current during normal operation, so
very sensitive earth fault protection will be possible using I0 or △I0. The △I0 is the difference
between present residual current and the background residual current
Ungrounded system
Through software calibration technique even using 3CT’s for residual current detection, 100mA
range residual current can be detected.
High impedance fault has a tendency of small fault current, random arc, arc burst, high harmonic
contents. Conventional SEF protection can not cover random arc high impedance fault. The VIT R6
control can detect random arc, and the threshold level will be the same with sensitive earth fault current.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 27
The source side of open conductor fault can be detected through the unbalance current ratio (I2/I1) and
the load side of open conductor will be detected by the zero phase voltage ratio (V0/V1). To isolate the
both side of open conductor the source side will open after timing and the load side will detect loss of
voltage within the operation time window of upstream device, then it will open and lockout.
In R6 control, the load encroachment feature is applied to the protection algorithm in a slightly different
manner. There is not much high possibility in running the risk of miss tripping due to phase overcurrent
pickup set close to maximum load current in R6 control. There not also exists the probability for the load
encroachment feature to prevent miss tripping from occurring caused by overload condition in normal
load operation. This feature has an effect on the situation when the load condition of the distribution line,
on which the relay was placed, has been changed by not a certain fault but load switching due to switch
operation a kind of closing the normal open point. In this situation, the load current may be higher than
overcurrent pickup value so that the relay recognizes it as fault condition and goes into tripping state in
spite of the situation not being the fault state but being the increased load condition.
Load encroachment feature can prevent the relay from doing fault pickup by recognizing the high load
current beyond the normal overcurrent pickup by desensitizing the overcurrent pickup of the normal
load condition if the power factor of the load does not depart from the defined normal working range.
Load encroachment feature can also be used to regulate an operation of the sympathetic tripping
avoidance element. The sympathetic tripping avoidance element also desensitizes the overcurrent
pickup of the relay to prevent miss tripping from occurring owing to the fault of the other adjacent
sections. The unbalanced or high load conditions which occur during or immediately following out-of-
section fault may cause the relay to initiate a tripping operation as the load current is over the
overcurrent pickup threshold. It may be possible to prevent overcurrent pickup by raising the
overcurrent pickup threshold. In a certain case, however, the high load current may be in excess of the
highest desensitized overcurrent pickup and relay will pickup it as the fault current. In this situation, with
the help of load encroachment element that can identify if the power factor of the load does not deviate
from the defined normal working range, it is possible to prevent the relay from doing fault pickup by
recognizing the high load current beyond the highest desensitized overcurrent pickup of the sympathetic
tripping avoidance element as the non-faulted current.
Setting items
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 28
Setting Example
Figure 1. shows if the parameters above is applied and load zone is decided as figure 2.
Imaginary
LEPLAF=30º
LEPLAR=32º
LENLAR=35º
LENLAF=45º
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 29
And through the Overload and Load Encroachment Pickup current, Tripping Area(hatching Area) and Non-
Tripping Area(White area) are distinguished as the following Figure.
Imaginary
Tripping Area
LEPLAR=32º
LEPLAF=30º
Non-Tripping
Area
LEPC:500A
Real
OLPC:300A
LENLAR=35º
LENLAF=45º
Note: OLPC: Over-Load pickup current, LEPC: Load Encroachment Pickup current
The VIT R6 control has three setting group and it can be changed by manually or automatically.
The individual setting group can program the operation current, number of shot to lock out, power
direction, T-C-C and others.
For loop operation, setting groups can be changed automatically according to the condition and
can be reset automatically.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 30
SG1: setting group 1 is used for normal radial operation. The power direction should be set after
installation for directional protection. The setting group 1 can be changed to setting group 3
automatically if the load current continuously higher than the automatic setting group change level
and also if the load current reduced below the automatic change level, then setting group will be
reset from SG3 to SG1.
SG2: Setting group 2 is used for the reverse connected recloser during loop operation and
generally the operation current will be lower than SG1. The power direction should be set reverse
with SG1.If the load side voltage appear first after tie recloser close, then the setting group change
from SG1 to SG2. If the line is maintained and if the configuration be returned to normal state,
then the setting group will be change again from SG2 to SG1.
SG3: Setting group 3 is used for the recloser of healthy network and generally the operation
current will be higher than SG1 because it has to supply more currents during loop operation.
The VIT R6 control has load encroachment algorithm, so at the instant of tie closing, even the
load current increase than the operation current, it can avoid mis-tripping, if the load currents are
higher than change over current, the setting groups can be changed from SG1 to SG3
automatically. If the currents are reduced lower than change over current, the setting group will be
changed again from SG3 to SG1.
If many reclosers should be coordinated, even to use minimum response time, different number
of shots to lockout, still it is not easy to coordinate. The VIT R6 control has special fault block
functions, so once the reclosers are trip simultaneously, then the upstream recloser close
successfully without fault, then the fault block function will be engaged. So the downstream
recloser only response to the fault without additional simultaneous trip of upstream recloser.
The conventional recloser can not isolate load side of faulted section so when the tie recloser
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 31
close, there is coordination problems of many series connected protection device and can not
avoid unnecessary fault impact to the network because the fault still not isolated before tie switch
close. If the load side of fault can not be isolated, then the tie switch, mid point switch should be
circuit breaker, because during tie or mid point switch close, the fault should be cleared by the
switch. The VIT R6 control can isolate the load side of fault before tie switch close through the
voltage countings which same with the number of shots to lockout of the upstream device and if
there is no voltage restoration before tie switch close.
It monitor the operation of upstream device through the loss of voltage counting and voltage
restoration time.
If will open after one or two voltage counting, if it is set to two counts open, then during
temporary fault, it maintain close position.
If there is two count sectionalizer at the downstream, the voltage count should be one.
The control make voltage counts and check the reclosing interval of back up device through
voltage restoration. If the conditions are met and if the outage is extended, then the recloser
will be open and lockout before tie recloser close. If the conditions are not met and if the
outage is extended, then the recloser will be open, but it will close again when voltage is
restored through tie recloser close
Tie recloser has two setting group and if one side voltage is lost, the close timer will start and if both
side voltage is restored, the close timer will reset. The close timer can be programmed to start after
voltage counts, to avoid unnecessary automatic close during network maintenance.
Tie recloser monitor the both side upstream reclosers, and if the voltage counts, reclosing
interval condition are met and if the outage extended, then it will go to lockout, so it will not
close into faulted network.
The tie recloser will close after successful close timing and if there is still fault, then it will
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 32
open and lockout. If there is no fault, then it will recover to normal sequence according to the
stetting group.
The VIT sectionalizer can isolate the source side of fault through fault current countings, and it can
isolate the load side of fault through monitoring of upstream device. The recloser do the normal
sequential operations during downstream fault to coordinate sectionalizer and if the fault was the source
side of recloser it will open and lockout before tie recloser close. One count sectionalizer may not
recommended at the mid point because during the temporary fault, it can go to lockout. if the recloser is
set to 4shots lockout then it can coordinate with two sectionalizer (three counts sectionalizer, two counts
sectionalizer). If it coordinate with two counts sectionalizer, then the recloser should be set to one
voltage count open if the fault was at the source side.
VIT recloser and VIT sectionalizer scheme can make 5~8 sectionalizing points, (5recloser scheme can
make 3 sections), the coordination time is fast, the sectionalizer will not close into fault, so it is best
suited for urban network of solidly grounded system.
The VIT reclosing sectionalizer can make the self healing loop system with VIT recloser. The VIT
reclosing sectionalizer is different with sectionalizer, but it is best suited for long rural network of
impedance grounded system.
Close Timer
The close timer should be longer than the fault clearing time of back up C.B or recloser
After close, lockout timer will start and if the voltage lost again (Backup trip again because of
fault), then it will be open and lockout. If the lockout out timer (which is longer than back up
clearing time ) is successfully finished, then the blocking timer will start during total coordination
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 33
time (normally close time of tie switch) to prevent unnecessary current, voltage counting.
If the back up open again before close timer finished, it will go to lockout while maintain open
position
If the load side voltage is restored after tie switch close, it will change the setting group and will
close. If use the VIT recloser and VIT reclosing sectionalizer, then it can make infinite
sectionalizing points but compared with VIT sectionalizer scheme, the reclosing sectionalizer
open and close more times than sectionalizer, and it has a chance to close into fault during the
sequence. But if the system is resistance grounded or ungrounded, the damage from close into
fault will be very small, so it will be the best solution for long rural network with impedance
grounded system or ungrounded system.
7.15 Sensitive earth fault, high impedance fault and open conductor fault
The SEF, HIF and open conductor fault protection is the difficult challenge for the protection engineer.
The ground fault has a tendency to be high impedance because of asphalt, concrete pavement, but
many researches are focused to develop monitoring device at the substation. But detection of the small
earth fault at the substation has a limitation and also the isolation is very difficult because it means the
whole outage of the feeder. The best way is for recloser and sectionalizers have the protection functions
of SEF, HIF and open conductor, then it can have more sensitivity and can isolate the section, because
the outage is just at limited area. In the VIT self healing system, the sectionalizer can clear the ground
fault by itself up to maximum load current (630A) and during the open conductor fault, the both side of
broken conductor can be isolated without sequential operation of recloser.
The delay time of open conductor protection should be longer than any other protection element and if
the broken conductor make considerable unbalance current, then it can be isolated positively through
unbalance current ratio element I2/I1 or △I2/I1. But if broken conductor occurs at small branch line and
so there is no detectable unbalance current ratio, then it should be protected by SEF or HIF.
The 3 phase 3 wire system can realize sensitive earth fault protection, because the normal residual
current is very small. So, I0 or △I0 with directional protection can achieve SEF, HIF protection. The SEF
and HIF can use the same threshold level, but the HIF algorithm differs in the random arc phenomena
The 3 phase 4wire system is very difficult to get sensitive earth fault protection, because there is
phase to ground load during normal operation, and it makes zero phase current.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 34
To reduce the ground pickup lower than max. phase current, then it should use directional protection to
avoid mis-tripping during source side fault and to give more sensitivity, the zero phase current ratio
element I0/I1 or △I0/I1 are used in VIT recloser and VIT sectionalizer.
The radial network can use the VIT sectionalizer or VIT reclosing sectionalizer to clear directly the SEF,
HIF, open conductor fault, but in the loop network the SEF, HIF should be cleared by recloser through
sequential operation to isolate the both side of fault, but in case of open conductor, the recloser, LBS all
together can isolate the open conductor fault.
Under/Over voltage elements assert(trip or alarm) below or above under/over voltage preset value.
In case recloser is tripped, recloser will block the close operation under the out of preset value.
If the recloser is tripped by under/over voltage condition, single-shot reclosing function is activated after
voltage returns to normal. After reclosing, if the recloser is tripped again by under/over voltage condition
within preset reset time, recloser goes to lockout.
Under/Over frequency elements assert(trip or alarm) below or above under/over frequency preset value
in the presence of normal voltage (settable).
In case recloser is tripped, recloser will block (selectable) the close operation under the out of preset
value.
If the recloser is tripped by under/over frequency condition, single-shot reclosing function is activated
after frequency returns to normal. After reclosing, if the recloser is tripped again by under/over frequency
condition within preset reset time, recloser goes to lockout.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 35
8. Technical Data
Ratings
Environmental
Test Standards
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 36
Power Circuit
ANSI/IEEE C 37.90.1(1989)
IEEE C37.90.2(1995)
Opto-isolation : 2,000Vrms
Delay time setting (10~500ms) for each contact input to suppress bouncing
Signals
- Switch Locked
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 37
- Spare 3
- Recloser Trip
- Recloser Closing
- Battery Test
- Modem On/Off
- Spare 1
Max. current 10 A
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 38
Signals
- Ia : A-phase current
- Ib : B-phase current
- Ic : C-Phase current
- In : Neutral current
Signals
- Va : A-phase voltage
- Vb : B-phase voltage
- Vc : C-Phase voltage
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 39
- Vr : R-phase voltage
- Vs : S-phase voltage
- Vt : T-Phase voltage
8.3 Measurements
Current
RMS (A) & Phase angle (o) Ia, Ib, Ic, In, Ig
600~12,000A : ±3%
Voltage
RMS (V) & Phase angle (o) Va, Vb, Vc, Vr, Vs, Vt
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 40
Power
Accuracy ±1%
Power factor
Lead/lag display
Accuracy ±2%
Frequency
Accuracy ±0.02Hz
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 41
Energy
Accuracy ±2%
Harmonics
2nd ~ 8th harmonics RMS (A, kV) Ia, Ib, Ic, Va, Vb, Vc, Vr, Vs, Vt
Ia, Ib, Ic, Pa, Pb, Pc, P3ph, Qa, Qb, Qc, Q3ph
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 42
Va, Vb, Vc
8.4 Recording
- Resolution: 1ms
These event reports contain date, time, current, voltage, relay element, opto-isolated input, and
output contact information.
Up to fifty 20- cycle reports are stored in non-volatile memory. If more reports are triggered, th
e newest event report overwrites the oldest event report.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 43
These event reports contain date, time, fault current magnitude and shot count information
The control stores the latest 300 events of the fault events report in non-volatile memory. If the
report fills up, newer rows overwrite the oldest rows in the report.
The control adds lines in the SER report for a change of state of a programmable condition. The
SER lists data and time-stamped lines of information each time when a programmed condition changes
state. The control stores the latest 4000 lines of the SER report in non-volatile memory. If the report fills up,
newer rows overwrite the oldest rows in the report.
Load Profile time interval can be set to any one of 5, 10, 15, 30 and 60 minutes. And load profile can
be selected any of the following load profile items up to twenty. Load profile data can be stored for 110
days of 15 minutes, in case 20 items are fully activated.
8.4.3 Counters
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 44
8.5 Communications
Physical Layer
Class assignable for each object type. (single point, double points, measured point)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 45
Events display
Measurements display
HANDLE LOCK
Lockout information Load Side, Source Side, Bump Prevention, Loss of Voltage
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 46
Serial port
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 47
DSP
Remote communication
Self-diagnosis
Analog/Digital conversion
Memory
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 48
VITR6’s enclosure is constructed for normal operation under the high/low temperature and humid
environments by adopting duplicate external covers with air gap. Swing panel within enclosure will enhance
operational safety. No need to open swing door to operate/ manipulate VITR6. Behind swing panel
batteries, modem, analog modules and other parts are installed.
(CAUTION)
1) When mounting on electric pole, always utilize the lifting lugs and mounting accessories.
2) In connection of control and power cables, please make sure of correct insertion and
close adherence. Install the cable-fixing band at every 1 meter and reserve the enough curvature
radiuses to prevent direct load on the receptacles.
3) Grounding conductor of the enclosure should be fixed with some distance from the
control cable.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 49
Swing
Panel
Document
Door
Door S
Locking
Device Fuse for Outlet
NFB (No Fuse Breaker)
AC PowerOutlet
For Auxiliary AC Power
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 50
VITR6
Relay
Battery
Charger
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 51
9.2.1 Battery
There are two 12 Vdc sealed rechargeable batteries to back up external AC power loss and to supply
power of 24 Vdc. Battery condition can be checked by measuring battery voltage, charging current and
discharging current. A fully charged 18 Ah battery supplies the trip and control power for 10 to 24 hours
depending on ambient temperature and load. It takes approximately 24 hours to fully charge the battery
from a complete discharge state.
When battery capacity drops down to a threshold level voltage, 23V (temperature-compensated voltage
level), the VITR6 shifts to sleep mode.
It is normally expected 5 years of life span, but recommended to replace every 3 years according to the
operational environments. When replacing the batteries, be sure to confirm to the battery specifications.
(Caution) When testing the voltage of battery using voltage meter, be careful not to contact each
terminal and not to make it short-circuited.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 52
It is unnecessary to power on to LCD and other LED’s while the enclosure door is not opened for local
operation. The main control function module gets door status information from this switch. Therefore, when
the enclosure door is closed, VITR6 is designed to disconnect the power supply to LCD and LED’s to save
battery or external AC power. This status is also monitored remotely and can be used to acknowledge local
maintenance and for security purpose.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 53
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 54
On the panel, there are LED’s indicating Recloser’s status, functional buttons and LED’s, operational
buttons and LED’s, LCD manipulation buttons, and a RS232 port for maintenance.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 55
Display Part
LCD (liquid crystal display) : Shows the Status, Measurement, Settings and More
Operation Button : use 6 buttons (Up, Down, Left, Right, MENU/ESC, ENTER)
BATTERY TROUBLE
Battery test is done automatically every day(12:00 PM) or done manually by pressing BA
TTERY TEST button.
CONTROL ENABLED
Show the status of CPU. In normal state, green light blinks. If a problem occurs on the
CPU, stop blinking or light off.
HANDLE LOCK
AUX1
SEF/HIF: sensitive earth fault / High impedance fault overcurrent element trip.
BUMP PREVENTION
LED is lit when recloser is locked out at open state by bump prevention feature.
Loop mode has bump prevention feature. When the close timer is running, if the voltages
are alive from both source and load side, there should be prohibited the switch from bein
g closed to prevent unnecessary bumping between two networks by having the switch gon
e to lockout and getting the closer timer reset. If the condition that there exist voltages on
both sides is ended, the lockout state is automatically reset, the close timer starts again
and the switch is closed after close time ended.
LOSS OF VOLTAGE
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 56
Light is on when recloser is opened and locked out by loss of voltage lockout feature.
UVR: LED is lit when the recloser is opened and locked out through UVR feature. (under consi
deration)
OVR: LED is lit when the recloser is opened and locked out through OVR feature. (under consi
deration)
OPEN CONDUCTOR: LED is lit when the recloser is opened and locked out by open conducto
r fault protection feature.
SPARE1
Setting Group
The sticker was posted on the bottom of the control swing panel that describes the setting
group status according to the lamp on/off as below;
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 57
Setting value and status data & fault can be updated or recorded through LCD display and function keys
on Operation Control Panel. All the information is displayed on LCD in the tree view manner. The figure
following represents the main menu of Recloser. LCD Screen is to facilitate manual programming of control
unit and for viewing data such as settings, events, fault records and measurements. The LCD shall
preferably switch off when not in use and activated by pressing the appropriate key such as panel ON/OFF
switch. Default LCD screen display shall be selectable from PC.
In the right area of LCD (4 lines 20 characters), there are six(6) buttons for manipulating the LCD menus
and data input and output. These setting buttons have no relations with other buttons in the local front
panel such as REMOTE ENABLED pushbutton (Local/Remote) and BUTTON LOCK pushbutton
(Unlock/Lock). So even if Remote Button or Lock Button is activated (ON), you can still operate the setting
buttons. They have functions as below.
10.2.2 MENU/ESC
1. You can switch between main menu screen and initial mode screen.
2. You can return to higher category from a lower category in menu and initial mode.
3. You can cancel new setting value and return to the previous setting value.
10.2.3 ENTER
By this button,
1. You can move to a lower category from a category in any mode. When you are in the Initial Mode, by
pressing this button, you can move to sub-initial screen (Current & Voltage, Current & Voltage Angle,
Internal Power, MVA and MW & MVAR screen) from main Initial screen (Recloser Status and Current
& Voltage screen).
2. You can select a certain setting value you want to manage, where you can change the value with
pressing LEFT, RIGHT, UP, DOWN buttons.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 58
10.2.6 UP ARROW
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 59
10.3.1 CLOSE
Press this button when you close Recloser manually. Then red light is on to indicate that Recloser is
closed. Close action signal is transmitted to the main body of circuit breaker on pushing the CLOSE button
and fault detecting action is ready on completing the close action.
In case of manual close, cold load pickup action precedes the normal fault detection function if cold load
pickup scheme is enabled and if the load current is over the overcurrent pickup level, and unless the fault
current is detected the set sequences of phase/ground will be followed to prepare the basic operations.
With set a delay, the operator can push the CLOSE button and then keep a safe distance away from the
Recloser before the VITR6 transmits a close signal. With a set delay, light flashes on and off during the
delay time, indicating a pending close. This pending close can be aborted by pushing CLOSE again or by
pushing TRIP button. This delay setting is available through setting menu.
10.3.2 TRIP
Press this button to open the Recloser manually and take the control to the lockout state. Then green light
is on to indicate that Recloser is open. Open action signal is transmitted to the main body of circuit breaker
on pushing the TRIP button and fault detecting action is suppressed on completing the open action, then
the switch to be locked out. When the lock function is engaged, the TRIP operator control can still trip the
Recloser by TRIP free function. With set a delay, the operator can push TRIP button and then keep a safe
distance away from the Recloser before the VITR6 transmits a trip signal. With a set delay, lights flashes on
and off during the delay time, indicating a pending open. This pending open can be aborted by pushing
TRIP button again or by pressing CLOSE button. This delay setting is available through setting menu.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 60
These buttons are to enable or disable significant functions in running the Recloser. Press the buttons and
make the respective LEDs on to enable each function. These buttons are toggled between enable and
disable
PROTECTION ENABLED button is used to halt the fault detection operation temporarily. It enables or
disables phase fault detection and ground fault detection functions, simultaneously. PROTECTION
ENABLED operator control pushbutton is pressed and LED illuminates, protection enabled. Pushbutton is
pressed again and LED doesn’t illuminate, protection disabled.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 61
RECLOSE ENABLED button enables or disables the reclosing function. In disable mode, the Recloser is
locked out right after the 1st trip. RECLOSE ENABLED operator control pushbutton is pressed and LED
illuminates, auto reclosing enabled. Pushbutton is pressed again and LED doesn’t illuminate, auto reclosing
disabled.
GROUND ENABLED button enables or disables ground fault detection function only. GROUND
ENABLED operator control pushbutton is pressed and LED illuminates, ground enabled. Pushbutton is
pressed again and LED doesn’t illuminate, ground disabled.
SEF/HIF ENABLED button enables or disables sensitive earth fault / high impedance fault detection
function. SEF/HIF ENABLED operator control pushbutton is pressed and LED illuminates, SEF/HIF
enabled. Pushbutton is pressed again and LED doesn’t illuminate, SEF/HIF disabled.
To decide the control position to remote, push this button and make the LED on. REMOTE ENABLED
operator control pushbutton is pressed and LED illuminates, remote control enabled. Pushbutton is pressed
again and LED doesn’t illuminate, remote control disabled.
VITR6 carry out the close or trip action after set time. For example, if close and trip delay time is set
with10 seconds, and then VITR6 carry out the close or trip action after 10 seconds. Close or trip LED is
repeated blinking during the delay time.
This button is used to block closing of the Recloser locally or remotely while doing maintenance work or
repair work. HOT LINE TAG operator control pushbutton is pressed and LED illuminates, hot line tag set
and closing action is prohibited. Pushbutton is pressed again and LED doesn’t illuminate, hot line tag reset.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 62
Press this button for 3 seconds, if you use to radial normal close mode.
Press this button for 3 seconds, if you use to loop normal close mode.
Press this button for 3 seconds, if you use to loop normal open mode.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 63
Fault indicators show the fault information through the LED lamp. It has two kinds of reset mode; manual
and auto. Manual option retains the fault indication without
external command once a fault has been detected. In this
mode operators should do command action for reset,
locally manipulating the FI reset(Target Reset) button or
remotely sending a command, to extinguish these LED’s.
Manual FI mode is for the operator’s acknowledgement
purpose. On the other hand, auto option turns the lamp off
automatically after a fault on detecting the normal current.
These LEDs indicate on which state the Recloser operates. There are 3 states the Recloser operates and
the reclosing control is in one and only one of those 3
states at any time which are reset state and reclose cycle
state and lockout state. When in a given state, the
corresponding LED illuminates. Automatic reclose only
takes place when control is in the reclose cycle state.
10.6 Others
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 64
WAKE-UP: Wake up the VITR6 if Operation Control Panel is dark. The unit put itself to sleep after an
extended outage. After the unit wakes up, the
Panel illuminates. This button is also used to
turn on the VITR6 after the battery has been
installed by sealing the battery. The VITR6
wakes up automatically from an extended
outage when 220 VAC power returns to the unit.
LAMP TEST: Illuminate all front-panel LEDs for 3 seconds for LED test.
TARGET RESET: Clear trip-latched target fault indication LEDs (A, B, C, GROUND, SEF, FAST, HIGH,
DELAY, VOLTAGE)
Manual Mode is to check the battery by pressing the BATTERY TEST button on Panel.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 65
[Side of R6 Relay]
VOLT-IN: Measurement voltage input terminal, total 6 voltage (3 for source side, 3 for load side)
are input via voltage sensor. When the main circuit voltage is 13.2kV in connecting to the control, each
phase has about 0.85Vac.
CURR-IN: Measurement Current input terminal. Each phase has 1/1,000A that comes from the
main circuit.
DI_IN: It is a input terminal of the door open of the control box, recloser’s status(main circuit
close/open, manual handle lock), remote control command et.
AUX_TB: It is a auxiliary terminal block interconnecting to controller. It provides the input/output
terminal of modem power, Aux digital output contact.
DO: It is a output terminal of control Power(24~36dc), and close, Trip Sign
SM_IN : Connected with SMPS for charging. When inputting external power, SMPS supplies
36Vdc / 4A capacity to the control. It is used for battery charging, control power, and mode power. SMPS
has a wide input voltage range of 85V to 264Vac to provide stable power to the control under any external
power adverse conditions.
TR_IN: It is to connect the transformer for driving. When external power is input, Trans supplies
AC24V / 200VA power to the control. It is used only for driving and it is separated from the control power
and does not affect the control function. When both SM_IN and TR_IN are input with normal voltage,
control determines whether the external power is normal and the AC PWR lamp is turned on.
DCM: Output port for driving the magnetic actuator mechanism of reclosing body
Battery: Input terminal f the battery. After the checking the polarity, replace the battery or
maintenance.
Debug port(Rs-232/Male): It is a RS-232 serial port on the front panel to connect laptop computer
for local command, setting and configuration.
SCADA port(Rs-232/Male): It is a RS-232 serial port on the side of relay to connect the modem for
SCADA communication. If either port of Debug port or SCADA port fails, it can be used by changing each
other in the internal setting menu of LCD.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 66
485 port: It is a RS-485 port on the side of relay for connecting the modem with RS485 interface
for SCADA communication. The communication port setting is available via LCD display of the control front
panel.
- Ethernet: It is an Ethernet port on the side of relay for connecting the modem with RJ45 interface
for SCADA communication. The communication port setting is available via LCD display of the control front
panel.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 67
10.8 Others
- Communication cable inlet: A cable gland at the bottom of the control box is available for the channel of
the communication cable, which a cable grand has the protection of IP66 as following specification.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 68
10.8.3 Battery:
Two 12V batteries are connected in series for 24Vdc.
TYPE: Sealed lead-acid type
Standard: 12V/18Ah *2ea in series connection
Size(Based on 1 battery): (L)181*(W)76*(H)167
Weight(Based on 1 battery): 5.66Kg
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 69
[LRS-150-36]
Specification:
* Note the spec are applicable for the rating marked in red.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 70
The operating sequence is Remote Trip -> 79LO -> Remote Reset ->
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 71
※ Not required set PT ratio since the factory calibration was based on 33kV, which
can cover all of voltage ranges under 33kV class. This factor is only for manufacturer’s
reference value, not for customer.
Nominal voltage 6 – 63 kV 11
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 72
-. Set the control input AC voltage for control power supply (based on 100%).
Thermal use same method with thermal energy increase/decrease, Rolling use calculation by
5 minuts step counting
Stored Load Profile can be used for analysis by season and timeline
Instantaneous Ia, Ib, Ic, In, Va, Vb, Vc, Vr, Vs, Vt
Frequency
Can select storage periods by setting time, 95 days profile can be stored in case selecting
30 minutes
VITL6 control can store 20 cycles of fault wave when fault occurred. Can choose point of
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 73
For example if required for 10sec delay, set 500 at 50 Hz or 600 at 60Hz system
Must set as “AUTO” when operation mode Loop normal open, Loop normal close.
If the measured value after the battery test is below the dead voltage, it is a battery failure.
After the initial test according to the Start Hour, Start Minute,
the test is conducted at the time interval set in the Test Period.
Bat Drop Capacity / Dead Voltage 18 ~ 24 23.0V
-. In case of AC power loss, it is to protect the battery from the deep discharge. When it
goes below the setting value, the relay power is automatically cut off until AC power is
supplied
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 74
-. In a open status, it is to inhibit the close operation when the voltage angle difference of
source side and load side goes is out of setting range under the condition of the
between the high and low voltage range.
You can use the desired digital input point by changing the 6th trip and 7th close of the
internal terminal block of the control box to the SPARE setting.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 75
-. The time multiplier setting shifts a curve in time, by the set multiplier.
Fast- Phase
Fast-Ground
EM Reset Yes/No No
Fast-Negative
-. After the fault occurs, it is to choose the function of the returning time
Delay-Phase
of the relay where it is installed on the load side before trip operation.
Delay-Ground
Delay-Negative Time Add 0 ~ 60.00Cycle 0
-. The time adder setting adds a constant time to a curve.
Min.Resp. 0 ~ 1500Cycle 0
-. Curves can trip no faster than the Min. response time setting.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 76
-. In case SEF pickup is set, it will be tripped after the preset time.
Phase OFF, 1 ~ 5 2
Ground OFF, 1 ~ 5 2
-. After the fault occurs, when reclosing sequence, it operates as the fast curve according to
the preset count.
Phase OFF, 1 ~ 5 4
Ground OFF, 1 ~ 5 4
SEF OFF, 1 ~ 5 4
-. It goes to lockout when it reaches to the preset fault current count according to the
type of the fault pickups.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 77
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 78
Delay 0 ~ 999999.00Cycle 0
-. Condition: The recloser is open or Control is in the lockout state
or reclosing is disabled.
Loss Load Diversity In case of the condition above, the function of the loss load diversity
is activated for the preset time.
Note that the cold load pickup function is not applicable during the
time above.
Delay 0 ~ 999999.00Cycle OFF
Force Time -. Return back to the preset minimum pick-up current after close
operation.
Phase Yes/No No
Ground Yes/No No
SEF Yes/No No
Yes : If the cold load pickup scheme is active, the phase current
threshold for over current detection is forced back to the regular Min.
Restore Min. Trip
trip-phase level when the preceding Restore min. trips-time limit tines
out.
No : If the cold load pickup scheme is active, the phase current
threshold for overcurrent detection can only return back to its regular
Min.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 79
Precedence Yes/No No
Yes : If the ground fault current is above the Min. trip-ground level at the time of trip, the
operations to lockout follows Operations to lockout-ground.
if ground fault current is below the Min. trip-ground level and phase fault current is above the
Min. trip-phase level at the time of trip. the determination to go to lockout is controlled by
Operation to lockout-phase.
No : If ground fault current is above the min trip-ground level and phase fault current is below
the Min trip-phase level at the time of trip the determination to go to lockout is controlled by
Operations to lockout-ground.
If phase fault current is above the Min trip-phase at the time of trip, the determination to go to
lockout is controlled by Operations to lockout-phase.
Enabled Yes/No No
Po.Lo.Ang.For 0 ~ 90 20D
Ne.Lo.Ang.For 0 ~ (-)90 -56D
Po.Lo.Ang.Rev 0 ~ 90 54D
Ne.Lo.Ang.Rev 0 ~ (-)90 -21D
-. Refer to the clause 7.9 Load Encroachment Algorithm
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 80
Max.Torq-Ang 0 ~ 359 0
Ang Width 10 ~ (±)170 (±)90De
Enabled No/Forward/Reverse No
3V0 Pickup 2 ~ 100 10.0%
SEF
Max.Torq-Ang 0 ~ 359 0
Ang Width 10 ~ (±)170 (±)90De
Reverse power elements and directionally supervised over-current elements are employed.
The directional supervision of the phase overcurrent element is made up of two components.
One is the use of positive sequence voltage polarized phase elements to detect three phase
faults. The second is zero sequence voltage polarized directional element used to detect
unbalanced faults.
Following figure is a diagram of positive sequence element. For zero sequence element, it is similar to
this.
The settings such as MTA(Maximum Torque Angle), TAW(Torque Angle Width) are related closely to
the distribution system configuration and its grounding system. So it is hard to suggest guideline or
setting procedure.
1 Tuning works are necessary from site, because maximum torque angle is different according to
ground connection (un-ground, Peterson coli, high resistance ground).
2 Maximum torque angel is 135℃ at resistance ground, 180℃ at Peterson coil, 270℃ at un-ground.
3 If arc current is small and intermittent, must use HIF protection function because SEF protection
function is applied to continuous arc current.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 81
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 82
11.3.1 Count
Item Range Default
No Voltage Trip Cnt OFF, 1 ~ 2 1
VIT Recloser is will open when no-voltage count reaches to pre-set count(No Voltage Trip
Count) by sense the no-voltage(both side voltage is disappear). It is applied to Loop N.C mode
only.
Upstream Count OFF, 1 ~ 4 1
VIT Recloser is will goes to lockout when no-voltage count reaches to pre-set
count(Upstream Count) by sense the no-voltage(one of both side voltage). It is applied to Loop
N.C and N.O mode.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 83
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 84
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 85
-. According to the setting condition, it detects the unbalance and apply each function.
You can use the PC program by connecting to a PC through the corresponding port. Use
Speed as the same as PC program.
Protocol IEC101/IEC104 IEC101
-. It is to set the waiting time of the receiving/sending the data during SCADA
communication.
* DCD Timeout: Data Carrier Detect. If the modem send the carrier signal, it means it
* RTS Preamble: After sending the data from the controller, it is to set the waiting
* RTS Postamble: After completing the data from the controller, it is to maintain the
transmitting(RTS) time.
* CTS Checkout: It is the waiting time for modem’s CTS signal. The modem data
IP 192.168.010.095 0~255
RTU IP Address
SUB 255.255.255.000 0~255
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 86
-. Mode: For IEC60870-5-101, to set the unbalance and balance same as SCADA’s settings.
-. Size Address: Select the size of link address, and set it same as SCADA’s setting.
-. Confirm Timeout: To set the waiting time for the response,
-. Max Retiries: To set the re-try count when it has no response..
-. ASDU Size: To select the seize of the ASDU Address, and set it same as SCAD’s setting.
-. COT Size: To select the size of the cause of transmission, and set it same as SCADA’s setting
-. IOA size: To select the size of Information Object Address, and set it same as SCADA’s setting.
Sector ASDU Address 00003 0~65535
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 87
-. SBO Timeout: It is the Select Before Operation, which is to set the limit time for operate.
-. Event Mode: To select whether to save the latest data or the changed value .
-. Analog Input: Reserve the start address of Analog Input Point IOA
Time Setting
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 88
Level 2 Reading only Setting items but can write Config items “0000”
Level 3 Reading and writing for Setting items and Config items “0000”
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 89
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 90
APPENDIX 1: TC-Curves
100
CLEARING TIME
CURVE:A,B,C,D,E
CURVE SHOWN IS
THE 1.0×MULTIPLIER CURVE.
AVERAGE CLEARING TIME
VARIATIONS ±10% or 0.01 SECONDS
10
.
TIME(SECONDS)
0.1
D B
A
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 91
1000
CLEARING TIME
CURVE:K,L,M,N
CURVE SHOWN IS
THE 1.0×MULTIPLIER CURVE.
AVERAGE CLEARING TIME
VARIATIONS ±10% or 0.01 SECONDS
100
10
.
TIME(SECONDS)
N M
0.1
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 92
1000
CLEARING TIME
CURVE:P,R,T,V
CURVE SHOWN IS
THE 1.0×MULTIPLIER CURVE.
AVERAGE CLEARING TIME
VARIATIONS ±10% or 0.01 SECONDS
100
10
.
TIME(SECONDS)
1
V
T
0.1
R
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 93
1000
CLEARING TIME
CURVE:W,Y,Z
CURVE SHOWN IS
THE 1.0×MULTIPLIER CURVE.
AVERAGE CLEARING TIME
VARIATIONS ±10% or 0.01 SECONDS
100
10
.
TIME(SECONDS)
0.1
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 94
100
CLEARING TIME
CURVE:1,2,3,4,5
CURVE SHOWN IS
THE 1.0×MULTIPLIER CURVE.
AVERAGE CLEARING TIME
VARIATIONS ±10% or 0.01 SECONDS
10
TIME(SECONDS)
1 3
0.1
5
1
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 95
100
CLEARING TIME
CURVE:6,7,8,8*,9
CURVE SHOWN IS
THE 1.0×MULTIPLIER CURVE.
7 AVERAGE CLEARING TIME
VARIATIONS ±10% or 0.01 SECONDS
10
9
TIME(SECONDS)
8*
0.1
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 96
100
CLEARING TIME
CURVE:11,13,14,15,16,18
CURVE SHOWN IS
THE 1.0×MULTIPLIER CURVE.
AVERAGE CLEARING TIME
VARIATIONS ±10% or 0.01 SECONDS
10 11
TIME(SECONDS)
18
14
13
16
0.1
15
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 97
100
CLEARING
RECLOSERTIME
CLEARING TIME
CURVE:N1,N2,N3,N4
CURVE:A,B,C,D,E
CURVE SHOWN IS
THE 1.0×MULTIPLIER CURVE.
AVERAGE CLEARING TIME
VARIATIONS ±10% or 0.01 SECONDS
10
TIME(SECONDS)
N2 N3
N4
0.1
N1
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 98
US1
100
RESPONSE TIME
CURVE : US1
AVERAGE RESPONSE TIME
VARIATIONS ±10% or 0.01
SECONDS
10
15
10
TIME(SECONDS)
1
5
0.1 0.5
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 99
US2
1000
RESPONSE TIME
CURVE : US2
AVERAGE RESPONSE TIME
VARIATIONS ±10% or 0.01
SECONDS
100
10
TIME(SECONDS)
15
10
1 5
0.1 0.5
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 100
US3
1000
RESPONSE TIME
CURVE : US3
AVERAGE RESPONSE TIME
VARIATIONS ±10% or 0.01
SECONDS
100
10
TIME(SECONDS)
15
1
10
0.1 1
0.5
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 101
US4
1000
RESPONSE TIME
CURVE : US4
AVERAGE RESPONSE TIME
VARIATIONS ±10% or 0.01
SECONDS
100
10
TIME(SECONDS)
1
1
10
0.1
0.5
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 102
US5
100
RESPONSE TIME
CURVE : US5
AVERAGE RESPONSE TIME
VARIATIONS ±10% or 0.01
SECONDS
10
TIME(SECONDS)
1
1
10
0.1
0.5
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 103
IEC1
100
RESPONSE TIME
CURVE : IEC1
AVERAGE RESPONSE TIME
VARIATIONS ±10% or 0.01
SECONDS
10
1
TIME(SECONDS)
0.5
1
0.2
0.1
0.05
0.1
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 104
IEC2
1000
RESPONSE TIME
CURVE : IEC2
AVERAGE RESPONSE TIME
VARIATIONS ±10% or 0.01
SECONDS
100
10
TIME(SECONDS)
0.5
0.2
0.1
0.1
0.05
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 105
IEC3
1000
RESPONSE TIME
CURVE : IEC3
AVERAGE RESPONSE TIME
VARIATIONS ±10% or 0.01
SECONDS
100
10
TIME(SECONDS)
0.1 0.5
0.2
0.1
0.01 0.05
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 106
IEC4
10000
RESPONSE TIME
CURVE : IEC4
AVERAGE RESPONSE TIME
VARIATIONS ±10% or 0.01
SECONDS
1000
100
TIME(SECONDS)
10
0.5
0.2
1
0.1
0.05
0.1
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 107
IEC5
100
RESPONSE TIME
CURVE : IEC5
AVERAGE RESPONSE TIME
VARIATIONS ±10% or 0.01
SECONDS
10
TIME(SECONDS)
0.5
0.1
0.2
0.1
0.05
0.01
100 1000 10000
CURRENT(PERCENTAGE OF MINIMUM TRIP)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 108
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 109
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 110
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 111
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 112
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 113
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 114
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 115
Single Point
0 Remote Control Disable
1 Recloser Close Status
2 Recloser Open Status
3 Gas Pressure Low Alarm
4 Lockout after 4x Fail to Reclose
5 Fault Indicator Phaser R
6 Fault Indicator Phaser S
7 Fault Indicator Phaser T
8 Fault Indicator Phaser N
9 Fault Indicator SEF
10 Fault Over Current
11 Fault High Over Current
12 Fault Indicator Open Conductor
13 Recloser Handle Lock
14 AC Power Supply Failed Alarm
15 24VDC Battery Capacity Drop
16 24VDC Battery Fail
17 Door Switch Open
18 Hot Line Tag
19 Alternate Group Setting
20 Select Normal Group
21 Select Alternate Group 1
22 Select Alternate Group 2
23 Select Alternate Group 3
24 DI Spare 1(close)
25 DI Spare 2(trip)
26 Under Voltage
27 Over Voltage
28 Maintenance Alarm
29 Close Trip Fail(CB Fault)
30 Select Auto Group Change
31 79LO
32 79RS
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 116
Single Command
0 Recloser Open Command
1 Recloser Close Command
2 Target Reset Command
3 Hot Line Tag En/Dis Command
4 Protection En/Dis Command
5 Alternate Group Setting Command
6 Spare DO Command
7 Recloser En/Dis Command
8 Ground En/Dis Command
9 Radial Normal Close Command
10 Loop Normal Close Command
11 Loop Open Command
12 SEF/HIF En/Dis Command
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 117
Double Command
0 Recloser Open/Close Command
1 Target Reset Command
2 Hot Line Tag En/Dis Command
3 Protection En/Dis Command
4 Alternate Group Setting Command
5 Spare DO Command
6 Recloser En/Dis Command
7 Ground En/Dis Command
8 Radial Normal Close Command
9 Loop Normal Close Command
10 Loop Normal Open Command
11 SEF/HIF En/Dis Command
12 Close/Trip Delay Time En/Dis Command
13 ABC=>RST/RST=>ABC Power Flow Command
14 Sequence Reset Command
15 Battery test Command
16 Dummy CB1 Command
17 Dummy CB2 Command
18 Space
Analog Input
Measured Value
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 118
0 Voltage A
1 Voltage B
2 Voltage C
3 Voltage R
4 Voltage S
5 Voltage T
6 Voltage Average
7 Current A
8 Current B
9 Current C
10 Current N
11 Current Average
12 Fault Current A
13 Fault Current B
14 Fault Current C
15 Fault Current N
16 Voltage A Angle
17 Voltage B Angle
18 Voltage C Angle
19 Voltage R Angle
20 Voltage S Angle
21 Voltage T Angle
22 Current A Angle
23 Current B Angle
24 Current C Angle
25 Current N Angle
26 Power Factor A
27 Power Factor B
28 Power Factor C
29 Power Factor 3Phase
30 Zero Phase Current
31 Negative Phase Current
32 Positive Phase Current
33 Zero Phase Voltage
34 Negative Phase Voltage
35 Positive Phase Voltage
36 I0/V0 Angle
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 119
37 I1/V1 Angle
38 I2/V2 Angle
39 KW A
40 KW B
41 KW C
42 KW 3phase
43 KVA A
44 KVA B
45 KVA C
46 KVA 3phase
47 KVar A
48 KVar B
49 KVar C
50 KVar 3phase
51 Frequency A
52 Frequency B
53 Frequency C
54 Charger Voltage
55 Battery Voltage
56 Operation Voltage
57 External AC Voltage
58 Temperature
59 Recloser Operating Counter
60 Contact Wear A
61 Contact Wear B
62 Contact Wear C
63 Space
Double Point
0 Remote Control Disable
1 Recloser Open/Close Status
2 Gas Pressure Low Alarm
3 Lockout after 4x Fail to Reclose
4 Fault Indicator Phaser R
5 Fault Indicator Phaser S
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 120
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 121
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 122
Word Bit
No. Description
(Recloser)
19 HP HIF pickup
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 123
32 2XLD Forced lockout (when a voltage in 2 times of XLD time there is not)
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 124
48 51N1TCD Over current element torque control for delay curve (neutral)
49 51N1TCF Over current element torque control for fast curve (neutral)
56 51P1TCD Over current element torque control for delay curve (phase)
57 51P1TCF Over current element torque control for fast curve (phase)
Directional Block for Phase when directional blocking is applied and ACR
65 32PBLK
doesn’t trip if a fault occurs.
Directional Block for Ground when directional blocking is applied and ACR
66 32NBLK
doesn’t trip if a fault occurs.
Directional Block for SEF when directional blocking is applied and ACR
67 32SBLK
doesn’t trip if a fault occurs.
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 125
75 79LO1 Open command, manual trip, handle lock, trip fail, close fail lockout
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 126
99 CF Close failure
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 127
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 128
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 129
183 SV11T Cold load pickup natural reset time-out for SEF
189 SV7T Cold load pickup natural reset time-out for phase
191 SV9T Cold load pickup natural reset time-out for ground
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 130
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 131
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 132
SHINSUNG
Industrial Electric Co., Ltd.
Solid Dielectric Automatic Circuit Recloser 133
SHINSUNG
Industrial Electric Co., Ltd.