Original Instructions
Topic Page
Important User Information 2
Environment and Enclosure 3
North American Hazardous Location Approval 4
European Hazardous Location Approval 5
Prevent Electrostatic Discharge 6
About the Power Supply 9
Install the Power Supply 10
Remove the Power Supply 10
Wire the Power Supply 11
Specifications 14
POINT I/O 24V DC Expansion Power Supply
SHOCK HAZARD: Labels may be on or inside the equipment (for example, drive or motor)
to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to
alert people that surfaces may reach dangerous temperatures.
IMPORTANT Identifies information that is critical for successful application and understanding of
the product.
ATTENTION: Read this document and the documents listed in the Additional
Resources section about installation, configuration, and operation of this
equipment before you install, configure, operate, or maintain this product. Users
are required to familiarize themselves with installation and wiring instructions in
addition to requirements of all applicable codes, laws, and standards.
Installation, adjustments, putting into service, use, assembly, disassembly, and
maintenance are required to be carried out by suitably trained personnel in
accordance with applicable code of practice. In case of malfunction or damage, no
attempts at repair should be made. The module should be returned to the
manufacturer for repair. Do not dismantle the module.
WARNING:
AVERTISSEMENT:
Explosion Hazard –
• Do not disconnect equipment Risque d’Explosion –
unless power has been removed • Couper le courant ou s'assurer que
l'environnement est classé non
or the area is known to be
nonhazardous. dangereux avant de débrancher
• Do not disconnect connections to l'équipement.
• Couper le courant ou s'assurer que
this equipment unless power has
l'environnement est classé non
been removed or the area is
dangereux avant de débrancher les
known to be nonhazardous.
connecteurs. Fixer tous les connecteurs
Secure any external connections
externes reliés à cet équipement à
that mate to this equipment by
using screws, sliding latches, l'aide de vis, loquets coulissants,
connecteurs filetés ou autres moyens
threaded connectors, or other
fournis avec ce produit.
means provided with this
• La substitution de composants peut
product.
rendre cet équipement inadapté à une
• Substitution of components may
impair suitability for Class I, utilisation en environnement de Classe
Division 2. I, Division 2.
WARNING:
• This equipment is not resistant to sunlight or other sources of UV radiation.
• This equipment shall be mounted in an ATEX/IECEx Zone 2 certified enclosure
with a minimum ingress protection rating of at least IP54 (in accordance with
EN/IEC 60079-15) and used in an environment of not more than Pollution
Degree 2 (as defined in EN/IEC 60664-1) when applied in Zone 2
environments. The enclosure must be accessible only by the use of a tool.
• This equipment shall be used within its specified ratings defined by
Rockwell Automation.
• Provision shall be made to prevent the rated voltage from being exceeded by
transient disturbances of more than 140% of the peak rated voltage when
applied in Zone 2 environments.
• The instructions in the user manual shall be observed.
• This equipment must be used only with ATEX certified
Rockwell Automation backplanes.
• Earthing is accomplished through mounting of modules on rail.
• Devices shall be used in an environment of not more than Pollution Degree 2.
ATTENTION:
• This product is grounded through the DIN rail to chassis ground. Use zinc
plated chromate-passivated steel DIN rail to assure proper grounding. The use
of other DIN rail materials (for example, aluminum or plastic) that can corrode,
oxidize, or are poor conductors, can result in improper or intermittent
grounding. Secure DIN rail to mounting surface approximately every 200 mm
(7.8 in.) and use end-anchors appropriately. Be sure to ground the DIN rail
properly. Refer to Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1, for more information.
• Do not remove or replace an Adapter Module while power is applied.
Interruption of the backplane can result in unintentional operation or
machine motion.
• Do not discard the end cap. Use this end cap to cover the exposed
interconnections on the last mounting base on the DIN rail. Failure to do so
could result in equipment damage or injury from electric shock.
• If this equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.
• Do not connect 120/240V AC power to this supply.
• Use the 1734-EP24DC and 1734-EP24DCK expansion power supply only with
POINT I/O™ adapters, such as the 1734-ADN DeviceNet adapter.
• To comply with the CE Low Voltage Directive (LVD), field power and all
connected I/O must be powered from a source compliant with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
• To comply with UL restrictions, field power and all connected devices must be
powered from a single source compliant with the following: Class 2.
WARNING: When you insert or remove the module while backplane power is on,
an electrical arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous before
proceeding. Repeated electrical arcing causes excessive wear to contacts on both
the module and its mating connector. Worn contacts may create electrical
resistance that can affect module operation.
At the end of its life, this equipment should be collected separately from any
unsorted municipal waste.
Interlocking
side pieces
43970
42511
1. Remove the module to the right of the power supply from its base unit.
2. Position the power supply vertically above the DIN rail.
3. Slide the power supply down allowing the interlocking side pieces to
engage the adjacent modules (both left and right sides).
4. Press firmly to seat the power supply on the DIN rail. The power supply
locking mechanism snaps into place.
5. Reinsert the module into the base next to the expansion power supply.
NC NC
WARNING: If you connect or disconnect wiring while the field-side power is on,
an electrical arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous
before proceeding.
12/24V DC Wiring
0 1
NC NC
Do not connect 120/240V AC 2 3
power to this supply. Chas Chas This supply will be
Gnd Gnd connected to the internal
4 5 field power bus.
12/24V DC C C
NC = No connection V DC
6 7
Chas Gnd = Chassis Ground V V
C= Common 43960
V = 12/24V DC
Adapter
Status
I I O O I I O
DeviceNet
Status
POINTBus
B B B B E E E
™ Status
1734-ADN
2 4C 2 4 1734-EP24DC
2 2 2
E E C C C
System System
Power Power
DeviceNet
DeviceNet Power
Power
0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1
Adapter
Status
I I O O I I O
DeviceNet
Status
POINTBus
B B B B E E E
™ Status
1734-ADN
2 4 2 4 1734-EP24DC
2 2 2
E E C C C
System System
Power Power
DeviceNet
DeviceNet Power
Power
0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1
12/24V DC
analog supply
12/24V DC
digital supply 1734adn4
Adapter
Status
I O I O I O O
DeviceNet
Status
PointBus
E E B B B B B
Status
1734-ADN
2 2 2 2 1734-EP24DC
2 2 4
C C E E E
System System
Power Power
DeviceNet
DeviceNet Power
Power
0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1
12V DC
supply
24V DC supply
1734adn4
Specifications
I/O module capacity 4...17 modules, depending on current rating of each module
24V DC nominal
Input voltage rating
10…28.8V DC range
Field side power requirements 24V DC (+20% = 28.8V DC max) @ 400 mA max
Output voltage will stay within specifications when input drops out for 10 ms @
Interruption
10V with maximum load.
General Specifications
Attribute Value
(1) Use this Conductor Category information for planning conductor routing as described in the appropriate System Level
Installation Manual. Also refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for
more information.
Environmental Specifications
Attribute Value
IEC6100-4-2:
ESD immunity 6 kV contact discharges
8 kV air discharges
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz
Radiated RF immunity 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
IEC 61000-4-4:
EFT/B immunity ±2 kV at 5 kHz on power ports
±2 kV at 5 kHz on signal ports
IEC 61000-4-5:
Surge transient immunity
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
IEC61000-4-6:
Conducted RF immunity
10V rms with 1 kHz sine-wave 80% AM from 150 kHz to 80 MHz
1.3
1.0
Current
Horizontal – 1 A @ (10...19.2V); 1.3 A @ (19.2...28.8)
0.5
Vertical – 1 A @ (10...28.8V)
10 19.2 28.8
Voltage 43971
Certifications
Certification (When Product
Value
Is Marked)(1)
UL Listed Industrial Control Equipment, certified for US and Canada.
See UL File E65584.
c-UL-us
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S.
and Canada. See UL File E194810.
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61326-1; Measurement/Control/Laboratory use, Industrial requirements
• EN 61000-6-2; Industrial Immunity
CE • EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2011/65/EU RoHS, compliant with:
• EN 50581; Technical documentation
Australian Radiocommunications Act, compliant with:
RCM AS/NZS CISPR 11; Industrial Emissions
European Union 2014/34/EU ATEX Directive, compliant with:
Ex • EN 60079-0:2012 + A11:2013; General Requirements
• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
• II 3G Ex nA IIC T4 Gc
• DEMKO04ATEX0330347X
Local Technical
Support Phone Locate the phone number for your country. http://www.rockwellautomation.com/
global/support/get-support-now.page
Numbers
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any
suggestions on how to improve this document, complete the How Are We Doing? form
at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-
du002_-en-e.pdf.
Notes:
Allen-Bradley, Rockwell Automation, POINT I/O, POINTBus, and Rockwell Software are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400