Professional Documents
Culture Documents
Vimalkumar B. Bilimoria
B.E., Pune University, India, 2005
PROJECT
MASTER OF SCIENCE
in
MECHANICAL ENGINEERING
at
FALL
2010
DESIGN OF SHELL AND TUBE HEAT EXCHANGER
USING SPECIFIED PRESSURE DROP
A Project
by
Vimalkumar B. Bilimoria
Approved by:
____________________________
Date
ii
Student: Vimalkumar B. Bilimoria
I certify that this student has met the requirements for format contained in the University format
manual, and that this project is suitable for shelving in the Library and credit is to be awarded for
the Project.
iii
Abstract
of
by
Vimalkumar B. Bilimoria
The pressure drops used in heat exchange of shell and tube type, the situations are particular and
put ahead of the design exercise. In such situations, it is very desirable to make full use of the
acceptable pressure drops in order to minimize the size of the heat exchanger. Heat exchanger
design is Complex due to large number of design variables like shell diameter, tube pitch, baffle
cut, tube diameter, baffle spacing, tube layout etc. in shell and tube type of heat exchanger. This
design method is a taking time and intervening procedure. This is mandatory to design thermal
and hydro mechanical procedure for this project performance. While fulfilling heat transfer
requirements, it has anticipated to estimate the minimum heat transfer area and resultant
minimum cost for a heat exchanger for given pressure drops. Effectiveness-NTU approach is the
way developed for the design of shell-and-tube heat exchanger. The total number of transmit
units, NTU, is scattered between shell and tube side. The methodology accounts for full use of
given pressure drops on both sides of exchanger to yield the smallest exchanger for a given duty.
_______________________
Date
iv
ACKNOWLEDGMENTS
It is my distinct honor and proud privilege to acknowledge with gratitude to keen interest taken
encouragement that made it possible to pursue and complete this project efficiently. Here I also
thank to the department of Mechanical Engineering and graduate coordinator Professor Kenneth
Finally I thank all the people who extended their support directly or indirectly to make this
project a complete success. In addition, it is a great pleasure to acknowledge the help of many
individuals without whom this project would not have been possible.
v
TABLE OF CONTENTS
Page
Acknowledgments................................................................................................................... v
List of Tables........................................................................................................................viii
List of Figures........................................................................................................................ ix
Chapter
1. INTRODUCTION .....................………………………………………………………… 1
2. LITERATURE REVIEW.................................................................................................. 3
vi
4.7 Tube Sheet............................................................................................................. 52
6.4 Conclusion................................................................................................................70
References............................................................................................................................. 72
vii
LIST OF TABLES
Page
9. Table 6.1 Shell and Tube Heat Exchanger Design Problem-Physical Properties.......64
10. Table 6.2 Shell and Tube Heat Exchanger Design Problem-Geometry.....................64
11. Table 6.3 Comparison of Shell and Tube Heat Exchanger Design-Geometry.......... 67
12. Table 6.4 Comparison of Shell and Tube Heat Exchanger Design-Performances.... 67
viii
LIST OF FIGURES
Page
4. Figure 3.1 Fixed Tube Sheet Shell and Tube Heat Exchanger.................................. 24
ix
1
Chapter 1
INTRODUCTION
Heat exchangers are devices in which heat is transfer from one fluid to another. The most
commonly used type of heat exchanger is a shell-and-tube heat exchanger. Shell-and-tube heat
exchangers are used extensively in engineering applications like power generations, refrigeration
and air-conditioning, petrochemical industries etc. These heat exchangers can be designed for
almost any capacity. The main purpose in the heat exchanger design is given task for heat transfer
The heat exchanger was introduced in the early 1900s to execute the needs in power
plants for large heat exchanger surfaces as condensers and feed water heaters capable of operating
under relatively high pressures. Both of these original applications of shell-and-tube heat
exchangers continued to be used; but the design have become highly sophisticated and
specialized, subject to various specific codes and practices. The broad industrial use of shell-and-
tube heat exchangers known today also started in the 1900s to accommodate the demands of
The steadily increasing use of shell-and-tube heat exchangers and greater demands on
accuracy of performance prediction for a growing variety of process conditions resulted in the
explosion of research activities. These included not only shell side flow but also, equally
The objective of the thesis is to formulate the design algorithm and optimization
required performance for fixed pressure drops. First step in the effective consideration of
factors, pressure drop of the stream and number of transfer units. The solution of this equation
The first chapter deals with the brief introduction of shell-and-tube heat exchangers. The
second chapter gives the development in the design methodology considering pressure drops as
constraint over the years for shell-and-tube heat exchangers. The third chapter gives the brief
outlines of various methods of design of shell-and-tube heat exchangers and constructional details
of various class of shell-and-tube heat exchanger. In the fourth chapter, the design procedure is
developing for a given heat exchanger specifications and pressure drops. In this design, both the
thermal and mechanical design is doing for a tube and shell exchanger. Various cost equations are
developing for tubes (including preparation and material), shell, nozzles, front and rear end heads,
baffles, and saddle of exchanger. The algorithm for exchanger with specified pressure drops is
present in the fifth chapter. In the sixth chapter, the heat exchanger design derived using the new
algorithm is comparing with the original one. The results and conclusion of the present work are
Chapter 2
LITERATURE REVIEW
Detailed design of shell-and-tube heat exchanger generally proceeds through the testing
of a range of potential exchanger geometries in order to find those that satisfy three major design
objectives:
The allowable pressure drops determine the operating cost of heat exchanger in
the process; they also determine the capital requirement of the installed heat exchanger
surface area.
drops during heat exchanger analysis. McAdams [1] was one of the earliest workers to
quantitatively demonstrate this. His analysis was simple and based on tubular heat exchanger.
By taking into account the cost of power and fixed cost of the exchanger, per unit heat
transferred, simple expressions for estimating the optimum mass velocities for both inside
tubes and outside tube fluids are developed. However, his equations are deriving on the basis
that each side of the exchanger can be treating independently of the other. It is assume that
the streams do not interact and the effect of opposing resistance is neglecting. This is an
erroneous assumption.
4
Jenssen [2] in an attempt to provide a quickly and general method for estimating
the economic power consumption in plate exchangers introduced the so-called ‘J’ parameter
(i.e. the specific pressure drop per heat transfer unit parameter). He produced graphs showing
economic optimum based on the assumption that the streams on the either side the exchanger
have the same flow rates and the same physical properties. The use of such graphs in design
only requires the knowledge of the ratio of the capital cost influence to the power cost
influence. The capital cost influence is given as the annual investment increment for added
unit heating surface area. The power cost influence is the annual unit power cost. One major
weakness in this work that has perhaps limited its practical application is the assumption that
the streams have identical fluid properties and identical geometries. These are highly limiting
assumptions. While the method may apply under restricted conditions to plate exchangers, its
Since the cost of heat exchanger, is usually a major item in the overall process,
the design of heat exchangers based on minimum total cost. The total annual heat exchanger
QΔ tC u
TC=AK F C Ao + + Aψ T h Δ tK T + Aψ S Δ tK S h
C pu ( ΔT 1− ΔT 2 +T 1−T 2 ) T 3. 5 S 4 .75
λF T ( ΔT 2 −ΔT 1 ) λ Dt 1
+
Q ln ( ΔT 2 −ΔT 1 )
−
( + + RF
A D ti hT hS ) (2.1)
Where
C Ao = Installed cost of heat exchanger per unit of outside heat transfer area
5
K S = Cost for supplying fluid through the shell side of the exchanger
λ= Lagrangian multiplier
ψ= Dimensional factors for evaluation of power loss per unit heat transfer coefficients
TC = Total cost
Sidney and Jones [3] have developed separate programs for the price optimum design of
shell-and-tube heat exchangers for four cases: (a) no phase change occurs, pumping costs of tube
side and shell side is given. Estimation of inside heat transfer coefficient is accomplished by
directly., (b) no change in phase and negligible costs on tube side: Under these conditions, the
6
outside heat transfer coefficient and the tube fluid velocity are fixed. Based on the assumptions
that
hT is constant and C is equal to zero. The optimum value of h S is determined by
T
differentiation of equation (2.1)., (c) no change in phase and negligible pumping costs on shell
side: Under these conditions, the outside heat transfer coefficient and shell side velocity are fixed.
Estimation film heat transfer coefficient on shell side is accomplished in a similar manner to that
used in case (b) but using a Nusselt type equation and the pressure drop equation for shell side,
phase on shell side: Under this condition, tube side power cost are significant but the
pressure drop and power costs for the fluid on the shell side are assumed to be zero and shell side
heat transfer coefficient is assumed to be constant. Optimum tube diameter is not obtained since
Steinmeyer [4, 5] has attempted to apply Jenssen’s [2] approach to shell-and-tube heat
exchangers. He produced separate relationships for shell side and tube side geometries. However,
in producing the relationships he, like McAdams [1], assumed that he could ignore the conditions
on the opposite side of the exchanger. Again, this assumption is incorrect and application on his
procedure can lead to serious errors. The result of McAdams [1], Jenssen [2] and Steinmeyer [4,
5] can be considered very useful. Their analysis on single heat exchanger at the optimum, the
annual power cost ranges from 20% to 50% of the heat exchanger cost. The lower value is valid
for non-viscous liquids and the higher value is valid for high viscosity liquids, with low viscosity
liquids and gases being in contact. This ratio can be used to warn (both the heat exchanger
designer and the process network designer), whether or not they are using reasonable coefficients.
7
Peter and Timmerhaus [6] recognized the importance of optimizing tube side pressure
drop; shell side pressure drop and heat transfer area simultaneously. Consequently, they produced
the most detailed and useful work to date on a single shell-and-tube heat exchanger optimization.
The problem with their method however, is that it is restricted to shell-and-tube heat exchangers
fitted with plain tube. Extension to other exchanger types requires new equations. No guidance is
given on how to generate these equations. Their results like all other previous authors are only
applicable to only pumped systems. Their method cannot be applied for shell-and-tube heat
Kovarik [7] has formulated the design procedure as the solution of five simultaneous
equations for a cross flow heat exchanger. The analysis of these equations yields general
properties of optimal cross flow heat exchanger. He has developed the optimization function,
1
J=
( C s +C p ) /Q (2.2)
Cs is the cost component related to the heat exchanger size, and Cp is the cost component related
to the pumping power. The position of the maximum J coincides with the minimum of the first
term in the denominator of the right hand side of the equation (2.2), and is independent of the
value of the energy cost factor. Therefore an optimal heat exchanger is optimal for any cost of
energy. A necessary condition for J to reach its maximum is the simultaneous vanishing of its
partial derivative with respect to all free variables. For any variable
X i , this means
∂Q ∂ ( TC )
( ∂ Xi
( TC ) −
∂ Xi ) 2
Q / ( TC ) =0
(2.3)
8
TC=C s +C p
(2.4)
X i ∂ ( TC )
Q i=
( TC ) ∂ X i (2.5)
Where
Qi is the logarithmic derivative of Q with respect to X i :
Xi ∂ Q
Q i=
Q ∂ Xi (2.7)
Qi is defined as the sensitivity of output to variable X i . The free variables can be flow
lengths and capacity rates. The model to be analyzed is a section that is rectangular and prismatic
in shape, consisting of passages bordered by heat transfer surfaces of known properties. In a cross
flow heat exchanger, the flow lengths are independent and the optimization scheme can be
applied with greater generality than with parallel flow and counter flow cases like shell-and-tube
heat exchanger.
Polley, Shahi and Nunez [8] have developed the rapid design algorithm for both shell-
and-tube exchanger and compact heat exchanger. They are based on full use of the allowable
pressure drops of both the streams being contacted. In case of shell-and-tube heat exchanger
algorithm, it is assuming that the best shell side performance can be gained by making baffle
window flow velocities and bundle cross flow velocities equal. This in turn leads to a ‘similarity
concept’ that can be used for the derivation of simple performance equation from of shell side
model. They have not shown theoretically that how much shell side performance is sensitive to
9
the window/cross flow area ratio. They have developed and shown how simple relationship
between fluid exchanger pressure drop, exchanger area and film heat transfer coefficient can be
used to rapidly design. For the tube side and shell side performance, the following relationships
exist:
3.5
ΔP T =K T Ahio (2.8)
ΔP S =( K 1 A + K 2 ) h 2S
(2.9)
The constants appearing in the above equations are complex functions involving shell geometry,
ideal friction factors and ideal heat transfer factors and are based on Delaware method. These two
Q=UAF T ΔT LM (2.10)
1 1 1
= + +R F
U h S hT (2.11)
The three simultaneous equations (2.8, 2.9 and 2.10) are then solved to yield exchanger area and
heat transfer coefficient for given pressure drop on both sides of shell-and-tube heat exchanger.
This in turn allows the calculation of velocities and shell diameter and baffle cut. The shell side
friction factor, heat transfer j factor, baffle cut and shell diameter are all set at standard initial
value. This allows the initial estimate of tube count and baffles spacing, and subsequently leakage
and bypass areas and correction factors to be made. From detailed geometry actual friction factors
and j factor are estimated and initial assumption are tested and updated if necessary. However, the
method is restricted. The first restriction is that the pressure drops referred to in the above
10
equations is that associated with the flow through the exchanger bundle. No account is taken of
any nozzle or header pressure drops. Allowance for these must be made ahead of design and
checked after design. This restriction is not considered here a serious impediment. The second
restriction is the use of the Kern’s correlations, which are generally considered too inaccurate for
use in modern exchanger design. In the derivation of relationship on shell side performance
When designing shell-and-tube heat exchangers, achieving the full use of the allowable
pressure drops from experience can be both difficult and dangerous. There is always the
possibility that it is not utilized properly. The allowable pressure drops of a stream will vary from
one system to another since it is dependent on the interaction between the streams. It will also
vary from one economic scenario to another. It is important that the full utilization of allowable
pressure drops be achieved for the streams in a shell-and-tube heat exchanger design as far as
possible. Furthermore, it is also important that once the allowable pressure drops of the stream
have been set, full advantage must be taken of them in order to obtain optimum heat exchanger
area in the design. Jegede and Polley [9] have considered the trade-offs involved in the optimum
design of shell-and-tube heat exchanger. They have shown how full use can be made of the
allowable pressure drops and shown how the optimum heat exchanger size can be determined.
The procedure is based on Kern’s correlations. For the tube side of the exchanger the pressure
drop relationship takes the form given by the equation (2.8). Similarly, for the shell side flow the
5. 1
ΔP S =K PS Ah S (2.12)
K T =K 1t ( Dti /4 V 0 Dt )( l/ K 2t )3 . 5
(2.13)
K 2t =0 .023 ( k / Dti ) Pr 0 . 33 ( ρD ti /μ ) 0. 8
(2.15)
K PS=K 1 S K 2S K 3 S (2.16)
3 . 81 1. 8
1 . 79 ( μ S / D e ) ρ
K 1 S=
2 ρD e (2.17)
K 3 S =0 . 36 ( k /D e ) Pr 0 .33 ( ρD e / μ S ) 0. 55
(2.19)
∆PT, ∆PS, Q and ∆TLM are specifying in the design requirements. Three equations (2.8, 2.10, and
2.12) with only three unknowns (hT, hS and A) are solved simultaneously and as such rapid
solution is possible. The procedure is independent of whether the streams involved are pumped
A general procedure for heat exchanger design has been presented in the Heat
exchanger Design Handbook (HEDH), but no precise criteria for determining the baffle spacing
has been offered, and the emphasis is only on its permissible range of application. Saffar-Avval
and Damangir [10] have established the optimization procedure to calculate the optimum baffle
spacing and the number of sealing strips for all types of shell-and-tube heat exchangers. Here the
J =W 1 A +W 2 W (2.20)
W1 is the heat transfer area weight factor, W2 is the pumping power weight factor, and W is power.
Cs Cp
W 1= W 2=
C s +C p ,
C s +C p (2.21)
well correlated with heat transfer area weight factor, W1. These results for each type of exchanger
( Dr / Dt )
Re S . Pr S . e =8. 89756+12 . 23475W 1 +6 . 24858 W 1 2
(2.22)
( Dr / Dt )
Re S . Pr S . e =6 . 48571+ 23. 67138 W 1 −6 .08711 W 1 2
(2.23)
( Dr / Dt )
Re S . Pr S . e =5. 98419+28 . 88928W 1−14 . 13602 W 1 2
(2.24)
.
M S Dt
Re S =
μS Sm
(2.25)
Where
S m is the cross flow area, given as:
13
Dt
[ (
S m=Lbc Lbb+ ( D S + Lbb + Dt ) 1−
Ltp )] (2.26)
Where
DS = Shell diameter
optimum baffle spacing. They have studied the effect of baffle spacing on heat transfer area and
pressure drops, and conclude that baffle spacing has a decisive effect on pumping power and
Poddar and Polley [11] present a new design heat exchanger through parameter plotting.
It can be used with any existing state-of-the-art exchanger-rating program. Rather than
systematically exploring the whole of the available exchanger sizes (diameters and tube length), it
determines the relationship between duty and tube length, pressure drop and tube length, etc. for a
range of diameters. This information is then used to clearly indicate the full range of geometries
14
that are suitable for a given duty and given constraints. Most state-of-the-art programs for the
performance. Virtually all of these programs will inform the user of the effective mean
temperature difference, the overall heat transfer coefficient, the tube side pressure drop and the
shell side pressure drop for a single baffle space. By running a rating program for a series of shell
diameters with a selected baffle configuration all of the performance information can be related to
shell diameter. The importance of maximum allowable pressure drop can be determined as
follows. First, allowance is made for exchanger nozzles. Normal design practice is to design the
exchanger nozzles such that they absorb just a small percentage of the total allowable value. So,
for each shell diameter studied, the tube side pressure drop is per unit length is determined. By
dividing the allowable tube side pressure drops by this value, the length of shell-and-tube heat
exchanger that coincides with the absorption of the allowable pressure drop is determined. The
relationship between shell diameter and the tube length for maximum pressure drops is shown in
Figure 2.1. Acceptable design lie above and to the left of this line; the design space has now been
reduced to EFIJH. The data generated on shell side pressure drop per unit length of exchanger can
be treated in exactly the same way. The result is also incorporated in Figure 2.1
15
Finally, the information on overall heat transfer coefficient and effective mean temperature
difference can be used to determine the area needed for the given duty as a function of shell
diameter. For each diameter, this can be related to tube length necessary for the heat transfer duty.
This relationship can now be placed on the plot. The result could be that shown in Figure 2.2.
Acceptable designs are those that are above and to the right of this line, the design space finally
reduced to MFKN. The procedure is a graphical technique and lays bare the influence of the
‘secondary constraints’ on design. This design procedure suffers from limitation like the one
some of the constraints are not considered (e.g., on shell side velocity). It cannot be readily
considered (e.g., on baffle spacing) in the approach proposed by authors, who plotted shell
diameter versus tube length. In addition, they did not establish any targets for minimum area and
cost.
Some designers have a conceptual problem in envisioning the cost of buying a heat
exchanger or the cost of paying the electricity to supply the pressure needed to overcome heat
exchanger pressure drop on the same basis as the lost value of unrecovered thermal energy
represented by the temperature driving force (∆T). To overcome these problems, Steinmeyer [12]
establishes the development of the optimum ∆T and ∆P relationships from a single turbulent
energy dissipation relationship, and the quantitative comparison of the relative “bills” of the three
components of heat exchanger costs. Also unique is the comparison of the conventional shell-
and-tube relationships to the prediction from energy dissipation. The most remarkable statement
he made in his paper is that at the optimum, the bill for pressure drop for the life of the heat
exchanger is one-third the life time bill for heat transfer area. The statement is known as the “one-
third rule”. The one-third rule provides a way of checking for proper allocation of pressure drop.
algebraic formulas for estimating the optimum heat exchanger area. The P1-P2 method is used in
the study, together with the well-known Effectiveness-NTU method, for thermo economic
analyses of three different unmixed type heat exchangers. Variable parameters used in
formulating the thermo economical optimum heat exchanger area are listed as: technical life of
the heat exchanger (N) , area dependent first cost of the heat exchanger (C s) , annual
interest rate (d ) , present net price rate of the energy (i) , annual energy price rate, annual
total heat transfer (Q) , overall heat transfer coefficient (U ) , maximum temperature
17
differential ( ΔT max) , and annual total operation time ( Δt ) . First of all for the C = 0 case, the
.
(
− MCp ) P2 C s
A opt =
U
min
ln
[ UP 1 C e ΔT max Δt ] (2.27)
N
1 1+i
If i≠d
P1= [ ][ ( ) ]
d−i
1−
1−i (2.28)
N
P1=
If i=d 1+i (2.29)
.
−N
P2 =1+ P 1 M −Rv ( 1+d ) (2.30)
P 2 C s A ( d−i )
N p=
ln 1−
[ 1+i
( )
.
C e M C p min ΔT max Δtε ]
ln ( 1+d ) (2.31)
P 2 ( 1+i ) C s A
N p=
.
(
Ce M C p ) min ΔT max Δt [ 1−e NTU (C−1) ] (2.32)
Similarly, the optimum heat exchanger area, Aopt, and the payback period can be
determined by using the same procedure for the parallel flow exchanger as:
.
(
− MCp ) P2 C s
A opt =
( 1+C ) U
min
ln
[ UP 1 C e ΔT max Δt ] (2.33)
If i≠d :
P2 C s A ( d−i )
N p=
ln 1−
[ 1+i
( )
.
εC e M C p min ΔT max Δt ]
ln ( ) 1+d (2.34)
If i=d :
( 1+i ) C s A ( 1+C )
N p=
.
( )
Ce mC p min ΔT max Δt [ 1−e− 1+C NTU ]
( )
(2.35)
Finally, for countercurrent heat exchanger, C = 1, case, the following are evaluated:
.
(
− MCp )
A opt =
U
min
[√
1−
P1 C e ΔT max ΔtU
P 2C s ]
(2.36)
If i≠d :
19
C s A ( d−i )( 1+NTU )
N p=
ln 1−
[ 1+i
.
( )
NTUC e m C p min ΔT max Δt ]
ln ( ) 1+d (2.37)
If i=d :
( 1+i ) C s A ( a+NTU )
N p=
.
( )
Ce m C p min ΔT max Δt . NTU (2.38)
Murlikrishna and Shenoy [14] have proposed a methodology that graphically defines the
space of all feasible designs. Given the large number of geometrical parameters, this space is
quite complex in nature. It is demonstrated that this complex space can be conveniently
represented on a two dimensional plot of shell side versus tubes side pressure drop. Equations are
derived for the various constraints and then plotted on the pressure drop diagram to define the
region of feasible design. The tube side pressure drop is given by:
L 1
ΔP T =K T 1 n ( 2+mt )
+KT 2
( D S−a ) ( DS −a )2 n
(2.35)
t 2+mt
K T 1=
2 K T ( N tp )
3+mt
(
( NS ) 4 M T ) ( bDt ) n ( 2+mt )
ρT μ mt π 2+mt D 5+mt
T ti (2.36)
20
.
20 ( N tp )3 ( NS ) M ( bDt )
2n
T2
K T 2=
ρT π 2 D 4
ti (2.37)
f T =K T Re
T mt (2.38)
L
ΔP S =K S1
R 3+ms D
bs S 4+2 ms (2.39)
.
2KSD ms −1 ( NS ) M
e S 2+ms
K S 1= 2+ms
μ ρS ( 1−D t / Ltp )
S ms (2.40)
f S =K S Re
Sms (2.41)
where typical values of KS and ms are 0.4475 and –0.19 respectively. In a manner analogous to
that used in deriving equations (2.35 and 2.39), the heat duty equation is rewritten below as
function of tube length, shell diameter and the baffle spacing to shell diameter ratio.
For
ReT ≤2100
D 1. 1 R L1/ 3 ( D S −a ) n/ 3
L ( D S −a )=K 2
[ S
K1
bs
0. 55
+
K3
+ K4
]
(2.42)
21
D 1 . 1 R 0. 55
[ ]
S bs 1
L ( DS −a )=K 2 + +K4
K1 D K6
K 5 1+
( L
ti 2/3
2/ 3 )( ( D S −a ) 2n/3
−125
) (2.43)
For
ReT > 10000
D 1. 1 R
0. 8 n
L ( D S −a )=K 2
[ S
K1
bs
0. 55
+
( D S −a )
K7
+ K4
] (2.44)
Where
.
0 . 36 k S D 0. 55 M
S 0 .55
K 1=
De
Pr 1/ 3 e
S μS ( ) ( 1−D t /Ltp )
0 .55
(2.45)
n
Q ( bD t )
K 2=
πD t ( NS ) F t ΔT LM (2.46)
. 1 /3
K 3=
1 . 86 k T
Pr 1/3
4 MT ( ) 1/3
( N tp) ( bDt )
n /3
Dt T
( πμT )1/3 (2.47)
22
Dt Dt
K 4 =R f +
2k
ln
D ti ( ) (2.48)
0. 116 k T
K 5= Pr
Dt T 1/3
(2.49)
. 2/3
K =
(4 M ) T
2/3
( N tp ) ( bDt )
2n /3
6 2/3
( πDti μ T ) (2.50)
. 0. 8
K 7=
0. 023 k T
Pr 1/3
( )
4 M T ( N tp ) ( bDt )
0. 8 0. 8 n
Dt T
( πDti μT )
0. 8
(2.51)
The tube side pressure drop relationship (equation 2.35), the shell side pressure drop
relationship (equation 2.39) and the heat duty relationship (equations 2.42, 2.43, and 2.44) form
freedom. The shaded region in Figure 2.3 defines the region of all possible design satisfying the
constraints. The methodology presented by them is equation based. If two of the five are
specified, then the remaining can be solved. Although every point in this feasible region
corresponds to a unique design that satisfies all the constraints, the designer may seek optimal
design, i.e., designs that meet certain objectives like minimum area or minimum cost. The
minimum area design will usually require the allowable pressure drops to be utilized to the
23
maximum extent, and the point can be readily located within the feasible region. The minimum
area design corresponds to minimum capital cost of the heat exchanger; but to minimize the total
annual cost, a simple techno-economic analysis is needed to determine the optimum pressure.
24
Figure 2.3 Region of Feasible Design on the Pressure Drop Diagram [14]
Literature has been reviewed for design of shell-and-tube heat exchangers where pressure
drop is considered as main constraint. All of the methods have some essential limitations, like use
of Kern’s correlation, less use of specified pressure drops. The methods discussed above proceeds
through the examination of the performance of a range of potential geometries. This leads to the
longer execution of program. To reduce the execution time, a quantitative relationship must be
Chapter 3
By far the most common type of heat exchangers to be encountered in the thermal
with numerous construction features and with differing materials for specific applications. This
chapter explains the basics of exchanger thermal design, covering such topics as: shell-and-tube
constructions.
It is essential for the designer to have a good knowledge of the mechanical features of
shell-and-tube heat exchangers and how they influence thermal design. The principal components
Shell
Shell cover
Tubes
Channel
Channel cover
Tube sheet
Baffles
Nozzles
26
Other components include tie-rods and spacers, pass partition plates, impingement
Plate, longitudinal baffles, sealing strips, supports, and foundation. The Tubular Exchanger
tube heat exchangers. A three-letter code has been used to designate the overall configurations.
The three important elements of any shell-and-tube heat exchangers are front head, the shell and
rear head design respectively. The Standards of Tubular Exchanger Manufacturers Association
(TEMA) [15] describes the various components of various class of shell-and-tube heat exchanger
in detail.
Figure 3.1-Fixed Tube Sheet Shell and Tube Heat Exchanger [15, 16]
27
Floatin-
g Tube
sheet
Relative cost 2 4 5 6 1 3
1=Least cost
Provision for Expansi Floating Floating Floating Individual Floatin-
ovable
Tubes Yes Yes Yes Yes Outside Yes
Mechanically
Cleanable
Shell side No Yes Yes Yes Yes Yes
Mechanically
Cleanable
28
sheet
Possible
Bundle No Yes Yes Yes Yes Yes
Replaceable
Gaskets
Possible Tube Any Any Any Any Any Even One or
Use of multiple tubes because of that is increasing the heat transfer area. Reason of
increasing heat transfer area is increase the velocity of fluid and lower effective ∆T.
There is different type of shell available, all shell are identified regarding the diameter
.Basically sizes of the shell are 8, 10, 12 inches. We find 2 inches of increment every step start
Tube size, which type of materials and array are primary criteria of designing of tube and
shell type of mat exchanger. After done this step hydraulic design will be done on automatically.
Small tube gives less cost with good thermal conductivity and Use of multiple tubes because of
that is increasing the heat transfer area. Reason of increasing heat transfer area is increase the
velocity of fluid and lower effective ∆T. It will create less shell area and size. Normally two
arrays are available, triangular array produces the more tube with lower cost for particular heat
29
transfer unit. We can control the pressure difference in square type of array so it is more
preferable rather than the triangular type of array. When the cleaning require because of
mechanical work, on that time square type of array are preferable. Wide pitch is used in this type
of array and 60o and 90o arrays have a tendency to create a channeled flow. So that way fluid have
a tendency to pass between two row of tube so there si not need to complete the full round of
flow. This is happen in each tube so it is big gain for evaporators and condensers for vapor
distributions.
With the close type of temperature, difference and tube side of pressure difference
generally start to design the heat exchanger with two or more tube passes. The way is to
established lot of heat exchanger with normal way. Front and rear end the pass particles are
installed in the tube side. For the multi-pass tube arrangement the stress are developed at high
joint. With the pressure and temperature difference, high tensile and compressive load located the
tube side.
First step in designing of heat exchanger, there is two way to design heat exchanger.
1. LMTD
2. NTU Method.
Q=UA 0 FT ΔT LM (3.1)
In terms of energy flow for heat exchanger, we can use this equation for hot fluid,
30
.
Q=−M C p ΔT h (3.2)
In terms of energy flow for heat exchanger, we can use this equation for cold fluid,
.
Q=M C p ΔT c (3.3)
Heat flows between the hot and cold streams due to the temperature difference across the
tube acting as a driving force. The difference will vary with axial location. Average temperature
or effective temperature difference for either parallel or counter flow may be written as:
ΔT 1 −ΔT 2
ΔT LM =LMTD=
ΔT 1
ln
( )
ΔT 2
(3.4)
Normal practice is to calculate the LMTD for counter flow and to apply a correction
ΔT LM =F T . ΔT LM ,CF (3.5)
31
The correction factors, FT, can be found theoretically and presented in analytical form. The
equation given below has been shown to be accurate for any arrangement having 2, 4, 6… 2n
√ R2+1
F1−2=
[ ]( )R−1
ln
1−P
1−PR
2/P−1−R+ √ R2 +1
ln
[ 2 /P−1−R−√ R 2 +1 ] (3.6)
T 1−T 2
R=
t 2−t 1 (3.7)
Provided that R≠1 in the case that R=1 , the effectiveness is given by:
P0
P=
N Shell −P0 . ( N Shell −1 )
(3.9)
t 2−t 1
P0 =
T 1 −t 1 (3.10)
P0 . R−1
X=
P 0−1
(3.11)
32
Gulyani and Mohanty [18] give alternate equations for the calculation of temperature correction
factors. They have derived linear equations for the same and established that the factor is below
NShell FT
Table 3.2 Linear Equations
1 1.208 G + 0.8037
for FT [18]
2 0.237 G + 0.961
3 0.1202 G + 0.9835
5 0.0429 G + 0.994
(3.12)
equation (3.1) has been used. This equation is simple and can be used when all the terminal
temperatures are known. The difficulty arises if the temperatures of the fluids leaving the
exchanger are not known. In such cases, it is preferably to utilize an altogether different method
defined as:
C S ( T Si −T So ) C T ( T To −T Ti )
ε= =
C min ( T Si −T Ti ) C min ( T Si −T Ti )
(3.13)
33
UA
The group
C min is called number of transfer units, NTU.
UA C min
ε =ε
( ,
C min Cmax )
(3.14)
C min CS CT
= or
Where C max CT CS (depending upon their relative magnitudes).
Kays and London [19] have given expressions for shell-and-tube heat exchangers. Some
[ ( √
1+exp −NTU 1+ 1+C )]
{
ε 1 =2 1+C min + 1+C √ min 2
[
1−exp −NTU ( 1+ √1+C )]
min
min
2
2 } (3.15)
−1
1−ε 1 C min 2 1−ε 1 C min 2
ε2=
[(
1−ε 1
−1
) ][( 1−ε 1 ) −C min
]
(3.16)
Flow across banks of tubes is, from both constructional and physical considerations, one
of the most effective means of heat transfer. However, it is recognized quite early that ideal tube
In 1951, Tinker presented what has become a classical paper on flow through the tube
bundles of shell-and-tube heat exchanger. He pointed out that a number of differing paths existed
for flow and argued that the assumption that all of the fluid passed through the whole of the
bundle was false. This was clearly demonstrated by his observations of the performance of
exchangers handling highly viscous oils. He then proceeded to propose a flow model based on
variety of flow paths cross flow, bundle bypass, tube-baffle leakage and shell-baffle leakage.
These paths are shown in Figure 3.6 and 3.7. This contribution became watershed in shell-and-
tube heat exchanger technology. Up until that, simple correlations, similar to those used for tubes,
had been produced and used for shell side performance. Following Tinker’s work researchers
concentrated on developing the sophisticated performance model for heat exchanger, which
Figure 3.2 Mechanical Clearances in Shell and Tube Heat Exchanger [8]
Figure 3.3 Flow Paths on Shell Side, A Cross Flow; B Window; C Shell-Baffle
Leakage; D Tube-Baffle Leakage; E Bundle Bypass [8]
35
directly the resulting hi and ∆Pi for derivations caused by the various split streams. The ideal tube
a3 b3
1 .33 a 1 .33 b
( ) ( )
a4 b4
j h =a 1 1+0 .14 Re Re 2 f =b1 1+0. 14 Re Re 2
Ltp / Dt L tp / Dt
And
(3.17)
For possible computer applications, a simple set of constants is given in [20] for the curve
.
hiS = jC p M Pr 2/3 (3.18)
h S =hiS j b j c j l j s j r
(3.19)
DS B
j c =1. 27−1. 44 ( −1
cos ( DS
D S −Lbb−Dt
1−
Bc
50 ( ))
−
( (
sin 2 cos−1
D S −Lbb−D t( )))
1− c
50
)
180 2π
( Lbb +0 . 5 Dt ) 100 N ss L pp
(
jb =exp −1 .25
Lbb Ltp , eff + ( D S −Lbb−D t )( L tp−D t )
1−
( √
50−Bc )) (3.21)
S sb
rs=
S sb + Stb (3.23)
S sb + Stb
rs=
Sm (3.24)
Where
S m is the cross flow area at the bundle centerline, is given by
D S −Lbb−Dt
[
S m=Lbc Lbb+
Ltp , eff
( Ltp −D t ) ] (3.25)
Bc
(
S sb =0. 00436 DS Lsb 360−2cos−1 1− [ ]) 50
(3.26)
S tb = { π4 [ ( D + L ) −D ]}( N )(1−F )
t tb
2
t2 tt w
(3.27)
0 .4
L Lbo
j s=
N b −1+ bi
Lbc ( ) ( ) +
Lbc
Lbi Lbo
N b−1+ +
Lbc Lbc (3.28)
jr is the correction factor for adverse temperature gradient, which is given as:
1 .51
j r =( j r )r =
Re S ≤20 N 0. 18
For c
(3.29)
20−ReS
For
20≤ReS ≤100 (
j r =( j r )r +
80 ) [( j r )r −1 ]
(3.30)
For
Re S ≥100 j r =1 (3.31)
Nc is the total number of tube rows crossed in the entire heat exchanger:
N c =( N tcc + N tcw )( N b −1 )
(3.32)
In addition, the shell side heat transfer coefficient is given by the following Nusselt
number correlation:
38
hS D e μ 0 . 14
kS
=0 .36 Re
S 0. 55 Pr S 1/3 ( )
μw
(3.33)
Equation (3.34) is given Kern and Krauss [21, 22]. Various correction factors for heat transfer
coefficient for shell side flow are calculated as per suggested in the Delaware method. The
For
ReT ≤2100
1/3
hT D ti D μ 0 . 14
kT (
=1. 86 ReT . PrT . ti
L )( ) μw
(3.34)
2/3
hT D ti D 0 . 14
kT
=0 .116 ( Re 2/3 −125 ) ( Pr T )1/ 3 1+ ti
T L ( ( ) )( ) μ
μw
(3.35)
For
ReT > 10000
hT D e μ 0 .14
kT
=0 .023 Re
T 0. 8
Pr
T 1 /3 ( )
μw
(3.36)
The shell side pressure drop [20] is calculated as a summation of the pressure drops for
the inlet and exit sections ( ΔP e ) , the internal cross flow sections ( ΔP c ) , and the window
sections ( ΔP w ) . For a shell-and-tube exchanger, the combined pressure drop is given as:
The zonal pressure drops are calculated from ideal pressure drop correlations and
correlation factors, which take account of bundle bypassing and leakage effects. The baffled cross
ΔP c=( N b −1 ) ΔP ci R b Rl
(3.38)
N tcw
ΔP e=2 ΔP ci R b 1+
( Nc ) (3.39)
ΔP w =N b ΔPwi Rl (3.40)
The correction factors for shell side pressure drop are given as:
[ (√
Rb =exp −3 . 7
Sb
Sm
1−
3 100 N ss L pp
50−Bc )] (3.43)
According to Kern and Krauss [22], the shell side pressure drop is given by the following
expression:
2 f S G 2 D S ( N b −1 ) ( NS )
S
ΔP S =
D e ρS ( μ / μ w )0 .14
(3.44)
f S =0 . 4475 Re
S−0 . 19
(3.45)
2fT G 2L ( N tp ) ( NS ) 1 . 25G 2 ( N tp ) ( NS )
T T
ΔP T = +
D ti ρT ( μ / μw )0 .14 ρT
(3.46)
The first term is due to friction and the second term is due to return losses. Most of the
pressure drop is due to surface friction inside the exchanger in an attempt to increase the heat
transfer. Therefore, only the straight tube pressure is considered. For smooth pipes, the
f T =K T Re
T −mt (3.47)
Note that
K T = 16, mt= = -1 for
ReT ≤2100 , whereas K T = 0.046, mt= -0.2
for
ReT >2100
The overall heat transfer coefficient (U) is related to individual heat transfer coefficient as:
41
1 1 1 Dt D t Dt
= + +
U h S hT Dti 2k T
ln
D ti
+ Rf
( ) (3.48)
It is essential that the designer of shell-and-tube heat exchangers becomes familiar with
the principles of the various correlations and methods in numerous publications, their advantages
and disadvantages, limitations and degrees of sophistication versus probable accuracy and other
related aspects. All the published methods can be logically divided into several groups:
1. The early developments based on flow over ideal tube banks or even single tubes.
2. The “integral” approach, which recognizes baffled cross flow modified by the presence
of window, but treats the problem on an overall basis without considerations of the
3. The “analytical” approach based on Tinker’s multistream model and his simplified
method.
4. The “stream analysis method”, which utilizes a rigorous reiterative approach based on
Tinker’s model.
5. The Delaware method, which uses the principles of the Tinker’s model but interprets
All of the methods suffer from essential drawbacks, which are given below:
1. All the “integral” methods such as Donohue and Kern cannot be recommended, as the
2. Although Tinker’s flow model is accepted as a valid basis, its full usefulness is idealized
in the rigorous iterative form. Even so, the crucial correlations of the flow resistance
3. Although the numerical method has promising future, it is difficult to apply to complex
cases and, for design purpose; it is not yet a substitute for the other methods listed.
4. The Delaware method appears to be the best available and the most suitable for design of
shell-and-tube exchangers. This method has a limitation that it does not allow for
In selecting the recommended method for the design of exchanger, the considerations
summarized above indicated that, of all the methods surveyed, the Delaware method is in
principle the most suitable on at the present. The method based on the principles of the Tinker’s
flow distribution model, and thus is more superior to “integral” methods. It should be clear,
however, that this no reiterative method cannot compete for accuracy with the complex stream
analysis-type methods.. Nevertheless, for a well-designed exchanger without any extremes, the
results are within respectable limits of accuracy. In this project, the Delaware method is used for
the forward calculations of heat transfer coefficients and pressure drops. This method has
Chapter 4
Typically, a designer chooses various geometrical parameters such as tube length, shell diameter
and baffle spacing based on experience to arrive at a possible design. If the design does not
satisfy the constraints, a new set of geometrical parameters must be chosen. Even if the
constraints are satisfied, the design may not be optimal. In this project, a methodology is
proposed that calculates the approximate free flow areas on tube and shell side for specified
pressure drops. Once these are obtained, geometrical dimensions can be tried to satisfy heat
transfer requirements.
The inputs specified for the design of heat exchangers consists of:
Process Data
Tube side ∆P
44
Shell side ∆P
Fouling resistances
Physical properties
Viscosity
Heat capacity
Thermal conductivity
Densities
pressure drops of the streams is specified. Utilization of pressure drop gives the heat exchanger
having minimum shell diameter. The pressure drop of one of the streams is given as:
G2 fL
ΔP=
2 ρD (4.1)
A cc
rh= L
A (4.2)
In alternate form, the characteristic length of heat exchanger may be defined as:
45
D
rh=
4 (4.3)
Combining equations (4.2 and 4.3), pressure drop of stream of heat exchanger becomes:
2
G fA
ΔP=
8 ρA cc
(4.4)
G=ρV (4.5)
.
M
G=
Or A cc (4.6)
V 2 ΔP 1 Acc
( )
2
=
ρ 4f A
(4.7)
η0 Ah
NTU =
C
(4.8)
h
St=
GC p (4.9)
Combining equations (4.2, 4.5, and 4.9), equation for number of transfer units of streams
becomes:
46
η0 A . St
NTU =
A cc (4.10)
Using equation (4.9) in equation (4.6), velocity of stream is given by the formula:
ΔP St 1
√
V = 2 η0
ρ 4 f NTU (4.11)
−2/3
St= j h ( Pr ) (4.12)
Putting equation (4.11) in equation (4.10), velocity of stream is then given by:
ΔP j h
√
V = 2 η0
1
ρ 4 f ( Pr )−2/3
1
NTU (4.13)
In equation (4.13), NTU denotes the number of transfer units of the stream. The total number of
transfer unit of shell-and-tube heat exchanger is calculated from equation (3.15 or 3.16).
Equations (3.15 and 3.16) are complex function of minimum heat capacity, effectiveness and
total number of transfer units NTU. Hence, NTU is calculated by using any root solving methods
like bisection method, false position method etc. Once total number of transfer units is available,
the NTU on shell side and tube side is calculated by distributing total number of transfer units in
1 1 1
= +
NTU C Shell C Tube
NTU Shell NTU Tube
C min C min (4.14)
47
jh
To calculate the velocity of fluid stream, value of f should be available from chart or from
correlations.
A cc
To determine the velocity and free flow area on shell side, the term A has to be
replaced as follows:
η0 AhS
NTU Shell = .
M Cp
(4.15)
The heat transfer coefficient of shell side is given by equation (3.34). Rearranging equation
0 . 36 C S μ −0. 14
h S=
S
.
Re 0 . 45 A cc ( )
( Pr )−2/3
μw
(4.16)
Putting equation (4.15) in equation (4.14), and rearranging, the number of transfer units on shell
side becomes:
−0 . 14
0. 36 A μ
NTU Shell =
Re 0 . 45 Acc
S
( Pr )−2/3
( )
μw
(4.17)
48
Or
A cc 1 μ −0 .14
A
=η0 jh Pr−2/3
( )
NTU Shell μ w
(4.18)
0 .36
jh=
Re 0. 45
Where S
(4.19)
Equations (3.45, 4.14 4.18, and 4.19) are used in equation (4.13) to determine the shell side
velocity. Once shell side velocity is available, the free flow area is computed. The free flow area
D s C' Lbs
A fS =
Ltp
(4.20)
The shell diameter is calculated from equation (4.20) for a standard tube diameter, baffle
jh
spacing, tube pitch, baffle cut and clearances and assumed f and Reynolds number. Tube
count
jh
is determined according to the formula given in HEDH. Alternatively, the value of f versus
Re S
jh
Figure 3.4 f versus Re for Shell Side Flow
A cc
To determine the velocity and free flow area on tube side, the term A has to be
replaced as follows:
For laminar flow, Reynolds number < 2100, (from equation (3.35)),
1/3
L
jh =1 .86
( )
D ti
Re1 /3
(4.21)
50
For the transition region, Reynolds number from 2100 to 10000, (from equation (3.36)),
2/3
L
j h =0 . 166 ( Re2/3 −125 ) 1+ ( ()) D (4.22)
For turbulent flow, Reynolds number > 10000, (from equation (3.37)),
0 .8
jh =0 . 023 Re (4.23)
The Colburn type of equation for tube side heat transfer coefficient is as:
−2/3
GC p μC p μ −0 .14
hT = j h
Re k ( ) ( ) μw
(4.24)
.
M
Replacing G by A cc in equation (4.23), heat transfer coefficient on tube side is given as:
.
−2/3
M C p μC p μ
−0. 14
hT = j h
A cc Re ( ) ( )
k μw
(4.25)
The total number of transfer units, NTU on tube side is given as:
η0 AhT
NTU Tube = .
MCp
(4.26)
Using equation (4.25) in equation (4.26), the total number of transfer units, NTU on tube side is
given as:
j A μ −0 . 14
NTU Tube =η0 h
ReT A cc
( Pr )−2/3
μw ( ) (4.27)
51
or
A cc Pr−2/3 1
=η0 j h φ−r
A Re NTU Tube (4.28)
Equations (3.47, 4.14 4.28, and 4.21 or 4.22 or 4.23) are used in equation (4.13) to determine the
tube side velocity. Once tube side velocity is available, the free flow area is computed. The free
.
M π
A fT = = D 2 ( NTP )( NS ) ( N tt )
ρt V t 4 ti (4.29)
jh
The second and third terms in equation (4.29) should be equal. f and Re is changed until
jh
these terms become equal with accuracy of 2 to 5 %. Alternatively, The value of f versus
ReT
jh
Figure 3.5 f versus Re for Tube Side Flow
The prediction about heat transfer and pressure drop optimization can be very complex –
with two layers of refinements and distinctions, often buried in complex code and sometimes
grossly misapplied. Several papers are present on the optimization heat exchanger. All authors are
succeeded in finding out the optimum pressure drops. In this case, the pressure drop is fixed.
Hence the costs due to process parameters are fixed. The cost associated with the surface is to be
minimized. For such situation, the minimum heat transfer area is the objective function of
optimization model.
53
Q
F=C s A=C s
U 0 F T ΔT LM (4.30)
Expressing objective function in the design parameters, the objective function becomes
optimization, and operating parameter optimization. For the former, the vector of the strategic
T T
X 1 =[ x 1 x2 x3 x4 x5 x 6 ] =[ Lto Bc DS Lbc Nb N tt ]
(4.32)
Lbch
B c=
Where DS (4.33)
Tube diameter is not included as an optimization variable because its value is generally
fixed ahead of actual design. Again, the tube pitch is not usually a design variable since it can be
fixed. Its common values range between 19.75 mm and 31.75 mm depending on the tube size.
T . T
X 2= x [ '
1
x
'
2
x
'
3
] =[ N P M ]
(4.36)
.
Where N , P , M are the rotary speed of power machinery, discharge pressure, and the flow
quantity of fluid respectively. The operating parameters are fixed for a fixed pressure drops.
exchanger:
gi ( X 1 )≥0
(4.37)
Lto Z oo DS
g1 = −2. 5 g2 = −1. 0 g3 = −1. 0
Ds Ds 40
DS 38 .1 DS
g4 =15− g5 = −1. 0 g6 = −1
Dt Dt Lbc
L bc 0. 5
g7 = −0 . 20 g8 = −1 . 0
DS Bc
0 .78 D
Bc otl 2 N tt
g9 = −1 g10= −N tt g11 = −1 .0
0 .10 C 1 L tp 7
55
Lbb
g15= −1 . 0
0 .022
0 . 075 jc 1. 3
g16= −1. 0 g17= −1. 0 g18= −1 .0
Lbb 0 .5 jc
jb 1. 3 js
g19= −1 . 0 g20= −1 .0 g21= −1 . 0
0 .3 jb 0 .5
1. 3 jl 0.8
g22= −1 .0 g23 = −1. 0 g24= −1. 0
js 0 .7 jl
h j ( X 1 )=0
(4.38)
Equations (3.20, 3.21, 3.22, 3.28, 3.29 or 3.30 or 3.31) are used for the calculation of
correction factors. Pressure drop in shell side is calculated as per equation (3.37) and pressure
drop in tube side is calculated as per equation (3.46). From the above equations, it is vivid that the
inequality and equality constraints. Hence, a multivariable search method is used for the
minimum area objective function. When the optimizing systems, where components are available
in finite steps of sizes, as in shell-and-tube heat exchangers, search methods are often superior to
Designers and fabricators of heat exchanger often treat thermal design and mechanical
design as two discrete and separable functions. The interaction between these two is essential in
some cases like thermal stresses in multiple passes fixed tube heat exchanger, effect of flexing of
tube sheets. Therefore, a designer alert to the mutual influence of these two designs and hence
In this report the thickness of tube sheet is calculated as per the TEMA [15]. Subjected to
requirements of the Code, the formulas and design criteria contained below are applicable with
limitations noted, when the following normal design conditions are met; size and pressure are
FG P
For bending
T=
2 S√
(4.39)
0 . 31 D L P
T=
D S ( )
For shear
(1− t
Ltp ) (4.40)
4A
DL = C = equivalent diameter of tube center limit perimeter
57
C = perimeter of tube layout measured stepwise in increments of one tube pitch from center to
The effective thickness of flat channel covers shall be the thickness measured at the
bottom of the pass partition groove minus tube side corrosion allowance in excess of the groove
depth. The required value shall be either that determined from the appropriate code formula or
1/3
G 4 hG A B G
[
T = 5 .7 P ( )
100
+2
√d B 100 ( )] (4.41)
Flanges and bolting for external joints shall be in accordance with design rules subjected
to the following limitations. The minimum permissible bolt diameter shall be 1.27 cm for
exchangers with shell diameter of 30.48 cm or less, and 1.58 cm for all other sizes. Maximum
2 D bo+ 6t cc
B max =
0.6 (4.42)
The segmental baffle and tube support plate are standard parts. Baffle has holes for tubes
of sizes depending upon the tube outer diameter and length of the tube as described in Table.
Similarly, baffle diameter and thickness are dependent on length and outer tube diameter and
internal shell diameter. They are selected using the Tables 4.1, 4.2 and 4.3.
1.219 < L < 1.524 0.356 < DSi < 0.711 9.52
Pricing of tube and shell heat exchanger is clearly not a precise matter. It depends, in part
on the costs of constructing the unit, but other factors may dominate. Prices will vary depending
on the average production backlog and general marketing conditions. However, statistical studies
are regularly done and reported in the engineering magazines. In the present project the costs are
taken as given by Crane [17]. Typical articles indicate that the price may be estimated using
The data included in this study-included carbon shells under 30 inches outside diameter.
In the absence of data for larger shell, these equations may be extrapolated to larger sizes. For
expansion joints it is recommended that the shell be priced as if an additional 5 Ft were added to
For 27.59 < P < 41.36 bar Cost = 6.72 L DS0.93 (4.44)
Tube costs are based on (a) the cost of the tubing itself, usually reported on a cost per
square foot of heat exchanger surface, and (b) the cost associated with preparing the tube sheets,
installing and rolling the tubes. These two factors may be estimated using the data below:
Tube OD, mm Rated pressure, bar Straight Tubes, $ / ft-Tubes U-Tubes, $ / ft-Tubes
<= 19.75 10.34 1.15 3.85
<= 19.75 20.68 1.30 4.15
<=19.75 27.59 1.40 4.50
> = 25.4 10.34 1.30 4.14
>= 25.4 20.68 1.45 4.50
>= 25.4 27.59 1.75 4.60
Table 4.4 Preparation Cost [17]
Note: This is an unusual procedure required only when fluids must absolute not leak. Normal cost
The total cost of preparing the opening, purchasing and welding the nozzles in place may
be estimated from the following equations. The data from which these fits were obtained were for
For 0 < P < 10.34 bar Cost = 118 – 4.33D + 2.46D2 (4.45)
For 10.34 < P < 20.68 bar Cost = 140 – 10D + 3.33D2 (4.46)
For 20.68 < P < 41.36 bar Cost = 119 – 2.5D + 3.75D2 (4.47)
The following equation has been fitted to estimate the costs of the front and rear end heads
construction costs.
The equations derived for shell-and-tube heat exchanger for given pressure drops are
used for thermal evaluation purposes. All the equations are used in design and optimization
algorithm in which heat exchanger geometrical dimensions are obtained from performance
specifications. Various cost equations are derived with the assumption that the market price of the
Chapter 5
Based on the design and optimization procedure formulated in chapter 4, design and optimization
algorithm is developed for shell-and-tube heat exchanger. A solution of core velocity equation is
The design process of shell-and-tube heat exchanger proceeds through the following
steps:
Process conditions (stream compositions, flow rates, temperatures, and pressures) must
be specified.
Required physical properties over the temperature and pressure ranges of interest must be
obtained.
A preliminary estimate of the size of the exchanger is made, using a heat transfer
A first design is chosen; complete in all details necessary to carry out the design
calculations.
The design chosen is now evaluated or rated, as to its ability to meet the process
specifications with respect to both heat duty and pressure drop. To do this, heat transfer
rate in shell-and-tube heat exchanger is calculated using equation (3.2 or 3.3). The
temperature correction factor should not be less than 0.75. If it is less than 0.75, the
number shell passes and tube passes are increased by 1 and 2 respectively. Effectiveness
is available, overall number of transfer units NTU is calculated from equations (3.15 or
3.16). Equations (3.15 and 3.16) are complex functions of minimum thermal heat
capacity and NTU. So, bisection method is used for the computation of NTU. The shell
side friction factor, heat transfer j factor and baffle cut are all set at standard initial
values. The core velocity equation (4.13) is used to find out the velocity on the shell side.
This shell side velocity is then used to compute free flow area. Once free flow area is
known, the shell diameter is known. The tube count gets fixed for a determined shell
diameter. The free flow area on tube side is also determined from core velocity equation.
This can be obtained by also tube count. These two free flow areas are matched. Once
this is achieved, the heat exchanger area, heat transfer coefficient on tube and shell side is
estimated and the initial assumptions are tested and updated if necessary. Once initial
66
assumptions and detailed geometry coincide, the design has been successfully
accomplished.
Based on this result a new configuration is chosen if necessary and the above step is
repeated. If the first design was inadequate to meet the required heat load, it is usually
necessary to increase the size of the exchanger, while still remaining within specified
pressure drops, tube length, shell diameter, etc. This will sometimes mean going to
multiple exchanger configurations. If the first design more than meets heat load
requirements or does not use the entire allowable pressure drop, a less expensive
Chapter 6
The pressure drop relationship, (equation 4.13), has been applied to develop a specific
relationship for a shell-and-tube heat exchanger based on the effectiveness-NTU approach. The
Bell’s Delaware design method is used for estimating various parameters. The actual heat transfer
coefficient is estimated and pressure drops are checked according to the HEDH method.
The flow rates, temperatures, allowable pressure drops, and physical properties of streams are
fixed. It is required to determine the optimum area and optimum cost of shell-and-tube heat
exchanger. A full specification of the design problem is given in Table 6.1 and Table 6.2.
Geometry Values
Tube OD (mm) 16
Tube ID (mm) 13.5
Tube layout (deg) 30
Tube pitch (mm) 20.8
Baffle-to-shell clearance (mm) 5.5
Tube-to-baffle clearance (mm) 0.5
Bundle-to-shell clearance (mm) 10
Table 6.2 Shell and Tube Exchanger Design Problem [8] – Geometry
The example used here is an adaptation of the one used by Polley, Panjeh Shahi and Nunez
[8] to demonstrate the inverse design methodology. The original example involved water on the
tube side of the exchanger with an assumed film heat transfer coefficient of 6000 W/m 2 K. The
fluid on shell side is viscous oil. The tube side and shell side pressure drops for this situation are
11.66 kPa and 13.7 kPa. These are the allowable P subsequently used in our design.
The design process of shell-and-tube heat exchanger proceeds through the following
steps:
68
Process conditions (stream compositions, flow rates, temperatures, and pressures) must
be specified.
Required physical properties over the temperature and pressure ranges of interest must be
obtained.
A preliminary estimate of the size of the exchanger is made, using a heat transfer
A first design is chosen; complete in all details necessary to carry out the design
calculations.
The design chosen is now evaluated or rated, as to its ability to meet the process
specifications with respect to both heat duty and pressure drop. To do this, heat transfer
rate in shell-and-tube heat exchanger is calculated using equation (3.2 or 3.3). The
temperature correction factor should not be less than 0.75. If it is less than 0.75, the
number shell passes and 1 and 2 increases tube passes respectively. Effectiveness of
available, overall number of transfer units NTU is calculated from equations (3.15 or
3.16). Equations (3.15 and 3.16) are complex functions of minimum thermal heat
capacity and NTU. So, bisection method is used for the computation of NTU. The shell
side friction factor, heat transfer j factor and baffle cut are all set at standard initial
values. The core velocity equation (4.13) is used to find out the velocity on the shell side.
This shell side velocity is then used to compute free flow area. Once free flow area is
known, the shell diameter is known. The tube count gets fixed for a determined shell
69
diameter. The free flow area on tube side is also determined from core velocity equation.
This can be obtained by also tube count. These two free flow areas are matched. Once
this is achieved, the heat exchanger area, heat transfer coefficient on tube and shell side is
estimated and the initial assumptions are tested and updated if necessary. Once initial
assumptions and detailed geometry coincide, the design has been successfully
accomplished.
Based on this result a new configuration is chosen if necessary and the above step is
repeated. If the first design was inadequate to meet the required heat load, it is usually
necessary to increase the size of the exchanger, while still remaining within specified
pressure drops, tube length, shell diameter, etc. This will sometimes mean going to
multiple exchanger configurations. If the first design more than meets heat load
requirements or does not use the entire allowable pressure drop, a less expensive
The final design should meet process requirements (within the allowable error limits) at
lowest cost. The lowest cost should include operation and maintenance costs and credit
for ability to meet long-term process changes as well as installed (capital) cost.
Exchangers should not be selected entirely on a lowest first cost basis, which frequently
The optimized heat exchanger design derived using the new algorithm is compared with
The new algorithm makes the full utilization of the available pressure drop and achieves
an overall heat transfer coefficient of 1149 W/m 2 K and the required area 49.39 m2 when 90 % of
total NTU is distributed between shell and 10 % of total NTU between tube sides. The original
design has an overall heat transfer coefficient of 971 W/m 2 K with a required area 58.9 m 2. Their
design procedure yields an overall heat transfer coefficient of 1088 W/m 2 K and a required area of
52.3 m2. Because of the way in which problem is set up, all the design makes full use of pressure
drop.
71
Program is run to evaluate the thickness of exchanger parts like tube sheet, baffle, shell
and tube. It is also possible to calculate the diameter and number of tie rods. Table 6.3 shows the
Area targeting in the previous section ensures exchanger of the smallest size with
minimum capital cost. However, the power cost and capital cost with pumping liquids and/or
compressing gases through an exchange often constitute a significant factor. However, in this
thesis, the problem is set up such that the cost associated with power and capital cost of
pumps/compressor is fixed. The only cost we look for here is the cost associated with the surface
area. The costs of various parts of exchanger for the outputs of the above problem are given
From cost analysis, the total cost of heat exchanger is $ 19319. This is the minimum
initial surface cost of a shell-and-tube heat exchanger. The minimum cost is found for the BEU
6.4 Conclusion
heat exchanger with a given pressure drops and provides targets for minimum area and
cost. In contrast to earlier approach, the methodology accounts for full use of given
pressure drops on both sides of exchanger to yield the smallest exchanger for a given
duty. For this, a quantitative relationship is developed that relates the pressure drop,
2. The methodology as presented in this work is based on Delaware method, which provides
good predictions for shell side flow. It has been shown that how the basic algorithm can
3. It must be emphasized heat exchanger had the potential danger of accepting a design that
satisfies the dirt factor and pressure drop constraints without thoroughly investigating
73
other options that may prove to be more promising. In contrast, in this work a rapid
4. Targeting for area and cost is vital and well-established step in the design of heat
exchanger networks by pinch technology. Targets present what is the best performance
that can be possibly achieved, before actually attempting to achieve it. The targets
proposed in this work allow the designer to determine the minimum area and cost (along
This is because vaporization and condensation processes in this type of heat exchangers are
often. However, the design method can also be used for two-phase heat transfer exchangers
like compact heat exchangers with some little modifications in core velocity equation.
Further research is needed before the approach can be extended to cover non-isothermal
phase changes.
74
REFERENCES
2. Jenssen, S.K., Heat exchanger optimization, Chemical Eng. Progress, 65(7), pp 59, 1969
3. Sidney, K., and Jones, P.R., Programs for the price optimum design of heat exchangers,
205, 1976.
5. Steinmeyer, D.E., Take your pick – capital or energy, CHEMTECH, March, 1982
6. Peter, M.S. and Timmerhaus, K.D., Plant design and economics for chemical engineers,
7. Kovarik, M., Optimal heat exchanger, Journal of Heat Transfer, Vol. 111, May, pp 287-
293, 1989
8. Polley, G.T., Panjeh Shahi, M.H. and Nunez, M.P., Rapid design algorithms for shell-
and-tube and compact heat exchangers, Trans IChemE, Vol. 69(A), November,pp 435-
444, 1991
75
9. Jegede, F.O. and Polley, G.T., Optimum heat exchanger design, Trans IChemE, Vol.
10. Saffar-Avval, M. and Damangir, E., A general correlation for determining optimum
baffle spacing for all types of shell-and-tube heat exchangers, International Journal of
11. Poddar, T.K. and Polley, G.T., Heat exchanger design through parameter plotting, Trans
12. Steinmeyer, D.E., Understanding ∆P and ∆T in turbulent flow heat exchangers, Chemical
13. Soylemez, M.S., On the optimum heat exchanger sizing for heat recovery, Energy
14. Murlikrishna, K. and Shenoy, U.V., Heat exchanger design targets for minimum area and
15. Bevevino, J.W., ET. al., Standards of tubular exchanger manufacturing association,
16. Mukherjee, R., Effectively design shell-and-tube heat exchangers, Chemical Engineering
17. Crane, R.A., Thermal Aspects of Heat Exchanger Design, University of South Florida,
18. Gulyani, B.B. and Mohanty, B., Estimating log mean temperature difference, Chemical
19. Sukhatme, S.P., Heat exchangers, A Text Book on Heat Transfer, University Press India
20. Taborek, J., Shell-and-tube heat exchangers, Heat Exchanger Data Handbook,
Hemisphere, 1983
21. Poddar, T.K. and Polley, G.T., Optimize shell-and-tube heat exchangers design,